Medium Voltage Distribution

WI
up to 52 kV
Gas-Insulated Switchgear with Vacuum Circuit-Breaker 1, 2 or 3-phase

System configuration
Conditions of Delivery
The General Conditions of Delivery as amended shall apply.

Illustrations
The illustrations are not binding
WI Contents

Overview............................................................................................................... 4
Features.......................................................................................................... 4

Product description............................................................................................. 5
Technical description....................................................................................... 5
Components of the switching unit................................................................... 6
Modular design................................................................................................ 7
Single busbar WIA up to 36 kV...................................................................... 7
Double busbar WIB up to 36 kV.................................................................... 7
Single busbar WIA 52 kV, 250 kV BIL........................................................... 8
Double busbar WIB 52 kV, 250 kV BILL........................................................ 8
Operator interfaces......................................................................................... 9
Switchgear panels......................................................................................... 10
Current/voltage transformers........................................................................ 11
Busbar modules............................................................................................ 13
Modules......................................................................................................... 15
Interlocks....................................................................................................... 16
Gas compartment monitoring WIA, WIB....................................................... 17
Gas-filled compartments of the WIA/ WIB.................................................... 18

Standards, regulations, provisions and standards....................................... 19


Type designation........................................................................................... 20
Applied norms............................................................................................... 21

Selection tables................................................................................................. 22
WIA/WIB 12 kV............................................................................................. 22
WIA/WIB 17 kV............................................................................................. 24
WIA/WIB 24 kV............................................................................................. 26
WIA/WIB 36 kV............................................................................................. 28
WIA/WIB 38 kV............................................................................................. 30
WIA/WIB 40.5 up to 52 kV............................................................................ 32
WIA/WIB 1 and 2-pole, for stationary railway traction power supply 50/60 hz......34

Range of products............................................................................................. 36
Single busbar panels WIA............................................................................. 36
Double busar panels WIB............................................................................. 37
Disconnector panel....................................................................................... 38
Bus section coupler / riser panel................................................................... 38
Bus section coupler, Bus coupler, metering panel........................................ 39

Cable connections............................................................................................. 40

Ecological considerations................................................................................ 43

Design data........................................................................................................ 44
Space requirements - dimensions and weights............................................ 44
Busbar connection with fully insulated conductor bars................................. 48

Shipping instructions........................................................................................ 50
Delievery, packaging..................................................................................... 50

WI EN 3
WI Overview

Features
The gas-insulated and metal-enclosed switchgear WI has been designed
for operation in power plants, transformer substations and industrial
networks.
The WI switchgear with vacuum circuit-breaker features maximum
availability, optimum operator safety and clear design using SF6 gas as
insulating medium. The switchgear units are insensitive to environmental
influences, such as humidity, dust and aggressive gases, and offer
complete operator safety. Their clear design facilitates operation.

Essential features
Parts under medium voltage in SF6 atmosphere
insensitive to air humidity, air pollution and foreign matter
High degree of operator safety
complete metal enclosure for all system components under medium
voltage
Compact and clear design
No mechanically moved parts in the busbar section
No problems with SF6 decomposition products
currents are switched in the vacuum interrupter chamber
Single busbar WIA up to 36 kV
Inert insulating gas SF6 protects the switchgear against fire
Three-pole enclosure of the functional compartments
negligible sheath currents
small number of static and dynamic seals
few gas compartments, pressure relief devices and gas monitoring
devices
easy access
moderate pressure increase in case of internal arcs
straightforward kinematics between drive and circuit-breaker or
three-position switch
Steel used as enclosure material
high pressure proofness
good screening effect against X rays
Optimum security of operation
complete interlocking system
separate actuators for isolation and earthing
automatic circuit-breaker ON or OFF operation in case of earthing at
the outgoing feeder
High capacity current and voltage transformer
Delivery of prefabricated switchgear panels to the construction site
Fully shrouded terminals
pluggable, fully insulated cable end boxes
Switchgear extension possible
on both sides
from single to double busbar system.

4 WI EN
WI Product description

Technical description
WI panels are suitable for configuring single or double busbar switchgear in
conjunction with indoor installation.
WI switchgear units are completely metal-enclosed. The busbar
compartment which accommodates fixed parts only is segregated gas-tight
from the flange-mounted switching unit. The switching unit comprises the
three-position switch with isolating and earthing functions and the vacuum
circuitbreaker; in case of double busbar systems, there are two three-
position switches with isolating and earthing functions and the vacuum
circuit-breaker.
The busbar compartment and the switching unit feature three-pole
enclosure. Single-pole enclosure is provided in the area of the toroidalcore
current transformers which are located in an easily accessible position
outside of the SF6 atmosphere. The compact design results in a very clear
Gas-insulated double busbar switchgear WIB switchgear arrangement with low space requirement; it has the advantage
Rated voltage up to 36 kV; rated peak withstand that a switching unit can be mounted or removed very quickly without the
current up to 100 kA; rated current up to 2500 A busbar requiring isolation from the power supply.
The panels are equipped with a low-voltage cabinet for the required
measuring and protection relays or the terminal strips. The high
performance of the instrument transformers installed means that not only
electronic but also conventional protection relays can be deployed.
Thanks to its design, this panel series permits straightforward extension of
an existing switchgear on both sides, and extension from single to double
busbar models.

WI EN 5
WI Product description (contd.)

Components of the switching unit


The circuit-breaker in question is a vacuum circuit-breaker. The switching
unit has been equipped, for its isolating and earthing functions, with a
three-position switch featuring the positions:
Disconnector ON (CLOSE)
Disconnector earthing switch OFF (TRIP)
Earthing switch ON (CLOSE)

Earthing
The metal-enclosed WI series switchgear is equipped with a separate
earthing line running along the length of the switchgear.

Wiring
Wiring is effected with flexible cables (HO7V-K) in the technically required
cross-sections.

Corrosion protection
If desired, the indoor panels WIA and WIB can be provided optionally with
enhanced corrosion protection. To ensure optimum switchgear protection,
the environmental installation conditions, such as wind-borne sand,
aggressive dust (to be defined as salt dust, coke dust, cement dust etc.),
vermin (termites), increased humidity levels, aggressive atmosphere (type
of chemicals and their concentration to be defined) must be specified.

Installation locations
The switchgear has been designed for installation in closed electrical
operating facilities.

Connection of cables and bars


The cables are connected by means of metal-enclosed connectors.
Switchgear units equipped with multiple connection tanks enable
connection of up to five 300 mm2 cables or two 1250 mm2 cables per
phase, depending on the insulation rating.
Alternatively, fully insulated busbar systems or SF6-insulated conductor
bars can be used.

Low voltage cabinet


The secondary devices for protection relay, control, measurement, billing
metering and other systems are installed in the low-voltage cabinet. The
low-voltage cabinet is separated systematically from the primary part, is
shock-proof and arc-resistant. It is an independent, closed low-voltage
compartment with mechanical and electrical interfaces to the vertical
section (screw-fastened plug-and-socket connector).
The clear separation between the rack and the low-voltage cabinet is a
particular advantage for the company operating the switchgear. Retrofitting
spare panels and conversion or replacement of complete low-voltage
cabinets (e.g. due to process changes) at a later date is also
straightforward. The panel remains completely enclosed even if the
low-voltage cabinet is not attached.
Optional inspection ports can be integrated in the torsion-resistant door of
the low-voltage cabinet, the door also being able to accommodate
measuring instruments, control elements and protection relays.

6 WI EN
WI Product description (contd.)

Modular design
A

Single busbar WIA up to 36 kV


A Tank with vacuum circuit-breaker and disconnector / earthing switch
B
C B Drive with control panel and pressure gauge for gas monitoring
C Tank with busbar
D Supporting structure with cable connection area
E Low voltage cabinet

Double busbar WIB up to 36 kV


A
A Tank with vacuum circuit-breaker and disconnector / earthing switch
B Drive with control panel and pressure gauge for gas monitoring

C2
C1 Tank with busbar 1
C2 Tank with busbar 2
D Supporting structure with cable connection area
E Low voltage cabinet
B

C1

WI EN 7
WI Product description (contd.)

A
Single busbar WIA 52 kV, 250 kV BIL
A Tank with vacuum circuit-breaker and disconnector / earthing switch
C B Drive with control panel and pressure gauge for gas monitoring
C Tank with busbar
B D Supporting structure with cable connection area
E Low voltage cabinet

Double busbar WIB 52 kV, 250 kV BILL


A Tank with vacuum circuit-breaker and disconnector / earthing switch
B Drive with control panel and pressure gauge for gas monitoring
C2
C1 Tank with busbar 1
A C2 Tank with busbar 2
D Supporting structure with cable connection area
C1 E Low voltage cabinet

8 WI EN
WI Product description (contd.)

Operator interfaces for WIA (single busbar)


and WIB (double busbar)
1 Button circuit-breaker ON
2 Button circuit-breaker OFF
1
9
3 Opening for charging the energy- storing device by means of a slide
2 4 Position indicator Energy-storing device (charged/released)
3
5 Circuit-breaker position indicator
10
11 6 Switch position indicator, disconnector (SS2)
18 12 7 Opening for operation of the disconnector (SS2)
SS1
4 8 Interrogating lever, disconnector
13
5
14
9 Earthing switch position indicator
16
10 Opening for operation of the earthing switch
11 Interrogating lever earthing switch
12 Switch position indicator, disconnector (SS1)
17
13 Opening for operation of the disconnector (SS1)
Operator interface, single busbar WIA
Operator interface, single busbar WIA 14 Interrogating lever, disconnector
15 Mechanical lock-out with cylinder lock
16 Rating plate
17 Insulating gas monitoring device
18 Operations counter

SS1: busbar 1 (corresponds to the lower busbar tank)


6
SS2: busbar 2 (corresponds to the upper busbar tank)
SS2
1 7
2
8
2 9
3 10
11
12
18 SS1
1
4 13
5 14

16

17 15

Operator interface, double busbar WIB


Operator interface, double busbar WIB

WI EN 9
WI Product description (contd.)

Switchgear panels
Single busbar Double busbar
Switchgear panel WIA up to 36 kV Switchgear panel WIB up to 36 kV
10
9

10
8

7 7
1

1
6 2
6
2

5
5
4

3 3
4

1 Drive mechanism 1 Drive mechanism


2 Vacuum circuit-breaker 2 Vacuum circuit-breaker
3 Low voltage cabinet 3 Low voltage cabinet
4 Cable end boxes 4 Cable end boxes
5 Current transformers 5 Current transformers
6 Busbar 6 Busbar I
7 Disconnector /earthing switch 7 Disconnector /earthing switch SSI
8 Pressure relief device 8 Busbar II
9 Disconnector /earthing switch SSII
10 Pressure relief device
Switchgear panel WIA up to 52 kV Switchgear panel WIB up to 52 kV
8 9 10

10

6
7

2
6

1
2

5
4
3 4

1 Drive mechanism 1 Drive mechanism


2 Vacuum circuit-breaker 2 Vacuum circuit-breaker
3 Low voltage cabinet 3 Low voltage cabinet
4 Cable end boxes 4 Cable end boxes
5 Current transformers 5 Current transformers
6 Busbar 6 Busbar I
7 Disconnector /earthing switch 7 Disconnector /earthing switch SSI
8 Pressure relief device 8 Busbar II
9 Disconnector /earthing switch SSII
10 Pressure relief device
10 WI EN
WI Product description (contd.)

Current/voltage transformers
Current transformers
The current transformers are designed as toroidal-core transformers and
are put onto the cable outgoing feeder areas with single-pole enclosure.
The current transformers in line with the busbar consist of identical units.
There, they are slipped onto the busbar areas which also feature singlepole
enclosure. The capacity of the current transformers is designed in such a
way that supply of conventional protective devices is also possible.
Up to 3 transformers (3 cores) can be accommodated per phase and
outgoing feeder. The transformers can also be exchanged subsequently.
Three current transformers (3 cores) per phase can also be installed in line
with the busbar, in order to measure its currents.
A special current transformer arrangement is the bus coupler panel within
one panel width. In the double busbar top attachment tank, one core of
Current transformer in line max. 80 mm height with an ID of 135 mm and an OD of 195 mm can be
with the busbar installed for each phase. The low voltage is led out via a max. 7-pole line
which is SF6 proof.

Dimensions
Outgoing feeder:
Transformer ID 185 mm
Transformer OD 275 mm
Max. stacking height 160 mm

In line with busbar:


Minimum ID 185 mm
Maximum OD 250 mm
Maximum stacking height for all
225 mm
cores incl. intermediate layer

Measurement Protection
/dyn (kA) 100
Ith (3sec) (kA) 40
Class 0.5 M 5 10 P 40 10 P 10
Core rating (VA) (VA) up to 15 up to 5 up to 30
Primary rated current (A) 150 up to 2500
Secondary rated current (A) 1 or 5

WI EN 11
WI Product description (contd.)

Voltage transformer
The conventional solution for the inductive voltage transformer is a
separate single-phase metalenclosed module which can be connected via
cable connectors almost anywhere in the busbar area and on the outgoing
feeder cable, and thus arranged in practically any location as required.
in the outgoing feeder area
Another design comprises metal-enclosed inductive voltage transformers
directly flangemounted to the outgoing feeder block, with the isolating /
earthing device mounted upstream. An externally operated isolating
feature prevents the voltage transformer from being endangered/ put at
risk during DC tests on the cable.

Voltage transformer on busbar

on the busbar
A separate metering panel with a set of inductive voltage transformers is
provided to this effect. Taking account of the high priority of the busbar, a
disconnector enables isolation of the transformer section. Both
disconnector and transformer are located in separate compartments.
Thus, any damage which might occur in the vicinity of the transformer
does not affect the isolating area or the busbar.

Performance characteristic

Ratings: up to 50 VA
Class: 0.5

Voltage transformer in outgoing feeder cable


(connection via multi-tank)

1 Multi-tank
2 Test cable connector

12 WI EN
WI Product description (contd.)

Busbar modules
Gas tank incl. installation parts
Busbar
Cover attachment on mounting flange with or without pressure relief.
All five busbar compartments require one pressure relief device. If it is not
possible to mount the device to the ends of the busbar tanks, e.g. if a tank
for voltage transformer connection or a busbar earthing switch is located
on the busbar end, or if the switchgear consists of over 10 panels, every
fifth panel is equipped with a pressure relief device on the mounting flange
Cover attachment on the stop flange of the left-hand and right-hand end
panel, with or without pressure relief, to connect metalenclosed voltage
transformers with cable connection to the front.
Gas lines incl. pressure gauges; preferably attached to the end panel.
(Only once for each gas compartment.)
Desiccant for 4 busbar tanks each, or for each gas compartment. (Cannot
be mounted on switchgear panels equipped with pressure relief device.)
Compensation element for busbar tanks. Required after 20 single busbar
panels, and after 10 double busbar panels.
Disconnector for bus sectionalizer
Earthing switch for bus sectionalizer to the left and right of the
disconnector

WI EN 13
WI Product description (contd.)

Accessories (for overall system)


SF6 gas for on-site assembly of the busbar sections
Special paint
Corrosion protection in case of extreme environmental conditions
Panel labeling according to specification
Operating elements, operating crank for vacuum circuit-breaker,
disconnector, earthing switch; for the busbar sections movable
segregating cover.
Star handle spanner
Hex. spanner
Castors
Transport cover for the busbar tanks (can be returned)
Jack rings
Integrated Voltage Detection System IVIS
Earthing and short-circuit device, 3-phase incl. operating rod
Cable dummy plug
Cable test socket on cable connector for cable measurement
Blanking caps for live cable connectors which have been withdrawn
always required
optional

Auxiliary equipment for transport only


Possible arrangement of the castors
1 Castors to be used
2 for movements in longitudinal direction
3 for transverse movements

14 WI EN
WI Product description (contd.)

Modules
The modules and attachments shown on this page apply to
outgoing feeder panels
incoming feeder panels
panels with circuit-breaker in case of coupler panels and bus
sectionalizers.
Switching device module
Gas tank incl. pressure relief device, gas lines and pressure gauge
Switching devices with three-position switch and vacuum circuit-breaker,
desiccant
Drive section module
Drive casing with drive mechanisms incl. interlocks
Attachment of drive casing on switching device module incl. connecting
parts
Attachments for the vacuum circuit-breaker
Motor drive mechanism to charge the energy-storing device
Auxiliary switch, 8, 12 or 16 contacts; 8 contact elements are required for
the basic circuitry (material: silver [normal], gold, silver-palladium)
Passing contact for pulse contact time stretching (contacts normal or
gold-plated)
Push switch actuated by energystoring device. (Push switches for basic
circuitry included in basic design)
Push switch, actuated by ON-OFF pushbutton. (The basic design
includes 1 push switch for each)
Shunt closing release, 1 ea.
Shunt opening release, 1 or 2 ea. with or without auxiliary spring energy
store
Secondary release, 1 or 2 ea., or in case of design without undervoltage
release: 3 ea.
Undervoltage release, with or without time delay
Blocking coil on ON pushbutton. Always required on coupler switch in
case of bus section coupler and bus coupler, consisting of 2 panels
(switchgear panel + bus riser panel)
Blocking coil on OFF pushbutton. Always required on coupler switch in
case of bus section coupler and bus coupler, consisting of 1 or 2 panel(s)
(switchgear panel + bus riser panel)
Mechanical lock-out with lock (for vacuum circuit-breaker and three-
position switch)
Counter
Attachments for three-position switch
Motor-drive mechanism. In case of single busbar: 1 motor-drive
mechanism each for isolating and earthing movements. In case of double
busbar: 1 motor-drive mechanism for the isolating movement of busbar 1,
busbar 2 and earthing movement of busbars 1+2. The vacuum
circuitbreaker s ON button features a mechanical lock-out.
An auxiliary switch, 2-20 contact elements each, for disconnecting and
earthing movement. (Material: silver (normal), gold, silverpalladium)
Interlocking solenoid. Single busbar: only in circuit-breaker panel of
coupler and in bus riser panel of bus sectionalizer. Generally required in
case of double busbar. If the interlocking solenoids are not installed in
case of remote control (motor-drive mechanism) of the three-position
switch, the local actuation is not locked. In this case, mechanical lock-
outs (locks) are required on the ON button of the vacuum ircuit-breaker
and on the threeposition switch.
always required
optional

WI EN 15
WI Product description (contd.)

Interlocks
Actuation of the three-position switch and the continuous mechanical
interlock between circuitbreaker and three-position switch are designed in
such a way that the operator can proceed as usual. This means separate,
completely interlocked actuation for the switching procedures Establishing
isolating distance and Earthing. For the earthing procedure, which is only
possible with the three-position switch in isolated position, the circuit-breaker
switched off and the circuit-breaker energy-storing device pre-charged, the
circuitbreaker is connected positively after the contact blades have
beeninserted into the earthing contacts, and protected against immediate
mechanical or electrical switching OFF. Vice versa, on de-earthing, the
circuit-breaker is first switched off positively before the isolating distance to
the earthing contacts established. The interlocks ensure that each
switching operation is always performed completely. Thus, once the
switching operation has commenced, the motion cannot be reversed, if
applicable, and the operating lever cannot be removed before it reaches its
end position.
The description only refers to the single busbar. In the case of double
busbars, some of the internal interlocking functions of the panel, as well as
all inter-panel interlocking functions are performed by electro-mechanical
interlocks (blocking coil).
The following interlocking functions are provided:
Disconnector does not switch ON while the circuit-breaker or the earthing
switch are ON
None of the disconnectors switches OFF while the circuit-breaker or the
earthing switch are ON
Circuit-breaker only switches ON with the disconnector in its end position
No earthing with disconnector engaged
No earthing with circuit-breaker ON
No earthing without circuit-breaker being in ready-to-operate condition
Automatic connection of circuitbreaker during earthing
Automatic disconnection of circuit- breaker during de-earthing
The following has been ensured:
The operating crank cannot be removed from the disconnector or
earthing switch before it has reached its end positions completely
The circuit-breaker cannot be actuated while a switching operation is
being performed on the disconnector or earthing switch
The circuit-breaker cannot be switched off with the three-position switch
in earthing position
All interlocks act partly mechanically and partly electrically
An operating crank can only be inserted on the disconnector or earthing
switch once the insertion opening has been released via a manual
interrogation system.
All interlocks also effective when the three-position switch is
motor-actuated.

16 WI EN
WI Product description (contd.)

Gas compartment monitoring


Single busbar WIA with bus section coupler

Gas-tight electrical
bushing
1 Gas-filled busbar compartments
2 Gas-filled circuit-br eaker compartments Check valve
Gas connector socket (disposal valve)
Pressure gauge

Gas compartment monitoring


Double busbar WIB with bus coupler

Gas-tight electrical
bushing
1 Gas-filled busbar2 compartments
2 Gas-filled busbar1 compartments Double check valve
3 Gas-filled circuit-br eaker compartments Gas connector socket (disposal valve)
Pressure gauge

WI EN 17
WI Product description (contd.)

Gas-filled compartments of the WIA/B series panels

WIA up to 40.5 kV, WIB up to 40.5 kV,


single busbar double busbar

WIA up to 52 kV, WIB up to 52 kV,


single busbar double busbar

WIA up to 36 kV, WIB up to 36 kV,


single busbar double busbar
Gas-filled
circuit-breaker compartment

busbar 1 compartment

busbar 2 compartment

18 WI EN
WI Standards
Regulations, provisions and standards

WI series switchgear units are


metal enclosed
SF6 insulated
prefabricated and type-tested
tested for internal faults

Ambient and operating conditions


WI switchgear units are to be operated under normal operating conditions
according to the specifications EN 60694 or the IEC publication 60694
(new: IEC 62271-1).
Operation under conditions other than these is only admissible upon
consultation with and with the consent of the manufacturer.

Degrees of protection against foreign


objects and accidental contact

Main electric circuits IP 65


Drives IP 2X, IP 5X1)
Low-voltage cabinets and cable connection IP 3X, IP 5X1)
compartments (operators side with cable
compartment cover and side panels)
1)
Optional

Other ambient temperatures


The rated (normal) currents IN specified in the selection tables refer to a
maximum ambient switchgear temperature of 40 C.
In case of different maximum ambient temperatures T of the switchgear,
between +25 C and +55 C, the appropriate normal current INT can be
determined from the following formula:

105 - T
At 25 0 C T < 40 0C INT = IN
65

105 - T
At 40 0 C < T 55 0C INT = IN 0.7
65

Ambient conditions
Temperature class "Minus 25 indoors 1)
Min./max. ambient temperature C -51) / 40 2)
Average value over 24 hours (max.) C 35 3)
Maximum installation altitude above sea m 1000 4)
level
Insulating gas
Type Sulphur hexafluoride (SF6)
Design pressure pre at 20 C MPa 0.03 - 0.05
1)
Optional: minus 25 indoors
2)
Optional up to 55 C in case of reduction of normal currents
3)
Optional up to 40 C in case of reduction of normal currents
4)
Higher installation altitudes possible on request

WI EN 19
WI Standards
Regulations, provisions and standards
(contd.)

Type designation
The type designation of the type-tested, prefabricated panels contains information about their design, rated voltage, insulation
level, panel width and panel height.
Example:
Prefabricated, type-tested WI
series panel with single busbar, for indoor installation, version A
Rated peak withstand current 100 kA
Rated voltage 12 kV; insulation level acc. to list 2
Panel width: 600 mm, panel height: 2100 mm
Type designation: WI A 10 / 12-2 / 621
Type designation Explanation
Series WI . . . /..- . Fully insulated (SF6) switchgear panels, primarily for distribution
substations, for very stringent requirements
Version A Single busbar, indoors
B Double busbar, indoors

8 Rated peak withstand current 80 kA


10 100 kA
Rated voltage / 12-2 upper rated voltage 12 kV
/ 17-2 17.5 kV
/ 24-2 24 kV
/ 36-2 36 kV
/ 38-2 38 kV
/ 40.5-2 40.5 kV
/ 52-2 52 kV
Dimension code WI A up to 40.5 kV / 621 Panel width 600 mm Panel height 2100 mm
WI A up to 52 kV / 626 600 mm 2664 mm
WI B up to 40.5 kV / 627 600 mm 2750 mm
WI B up to 52 kV / 633 600 mm 3314 mm

20 WI EN
WI Standards
Regulations, provisions and standards
(contd.)

Applied norms
WI switchgear units meet the following standards and regulations:

Designation IEC standard IEC classes EN standard


Switchgear IEC 62271-200 Category for operating EN 62271-200
IEC 60694 availability: EN 60694
LSC 2A (new EN 62271-1)
(new IEC 62271-1)
Partition class
(compartmentalization class): PM
Behaviour in case of internal faults IEC 60298 EN 60298
Circuit-breaker IEC 62271-100 M2, E1, C1 EN 62271-100
Earthing switch IEC 62271-102 E2 EN 62271-102
Three position disconnector IEC 62271-102 M1 EN 62271-102
Current transformers IEC 60044-1 EN 60044-1
Inductive voltage transformers IEC 60044-2 EN 60044-2
Voltage detection systems IEC 61243-5
Protection against accidental contact, IEC 60529 EN 60529
foreign objects and water
Erection HD 637 S1
Operation of electrical equipment EN 50110

WI EN 21
WI Selection tables

WIA/WIB 12 kV
Rated insulation level

Rated peak withstand current


Ratings of isolating distance

Percentage value of the DC


Rated short-circuit breaking
equal to rated short-circuit
3)

Rated short-time current


Type
Rated lightning impulse

Rated power frequency

Rated (normal) current


withstand voltage

withstand voltage

Rated frequency
Design pressure

making current
Pr at 20 0C 5)
Rated voltage
Panel width

component
current
1s 3s
mm kV kV kV kV/kV bar Hz A kA kA kA kA %
WIA 8/12-2/621 0.8 630 80 31.5 20 31.5
WIA 8/12-2/621 0.8 1250 80 31.5 31.5 31.5
WIA 8/12-2/621 600 12 75 28 85/32 0.8 50/60 1600 80 31.5 31.5 31.5 38
WIA 8/12-2/621 1.3 2000 80 31.5 31.5 31.5
WIA 8/12-2/621 1.3 25001) 80 31.5 31.5 31.5
WIB 8/12-2/627 0.8 630 80 31.5 20 31.5
WIB 8/12-2/627 0.8 1250 80 31.5 31.5 31.5
WIB 8/12-2/627 600 12 75 28 85/32 0.8 50/60 1600 80 31.5 31.5 31.5 38
WIB 8/12-2/627 1.3 2000 80 31.5 31.5 31.5
WIB 8/12-2/627 1.3 25002) 80 31.5 31.5 31.5
WIA 10/12-2/621 0.8 1250 100 40 40 40
WIA 10/12-2/621 0.8 1600 100 40 40 40
600 12 75 28 85/32 50/60 38
WIA 10/12-2/621 1.3 2000 100 40 40 40
WIA 10/12-2/621 1.3 25001) 100 40 40 40
WIB 10/12-2/627 0.8 1250 100 40 40 40
WIB 10/12-2/627 0.8 1600 100 40 40 40
600 12 75 28 85/32 50/60 38
WIB 10/12-2/627 1.3 2000 100 40 40 40
WIB 10/12-2/627 1.3 25002) 100 40 40 40

LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O
1)
with cooling gas tank, panel height 2750 mm
2)
with motor-actuated fan
3)
possible limits and components fitted, refer to project planning documents WI no. 49 542
4)
adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
5)
minimum service pressure 0.3 bar at a filling pressure of 0.8 bar; 0.7 bar at a filling pressure of 1.3 bar

22 WI EN
WI Selection tables (contd.)

Rated operating Number of operating Operating times Command times


sequence cycles without with release with release
overhaul
25 W 160 W 160 W 25 W 160 W 160 W
mecha- electrical

and earthing switch with motordrive


nical

Operating time for disconnector


under out-of-phase conditions

Charging time for motor drive


O - 3 min - CO - 3 min - CO

O - 0.3 s - CO - 3 min - CO

with rated (normal) current


O - 0.3 s - CO - 15 s - CO

Rated breaking current


Cable breaking current

Small indirect currents

with rated short-circuit

mechanism, 160 W
Arc duration (max.)
4)

4)
breaking current

4)
CO - 15 s - CO

Opening time

Opening time

Closing time

mechanism
LS,
TS,

Off

Off

On
E
On Off
A A kA ms ms ms ms ms ms ms s s
8 10000
8 1000
25 10 1000 10000 100 45-65 33-50 40-70 12 50 20 20 12 18


8 10000
8 1000
25 10 1000 10000 100 45-65 33-50 40-70 12 50 20 20 12 18


10 10000
10 1000
25 10 10000 100 45-65 33-50 40-70 12 50 20 20 12 18
10 1000
10
10 10000
10 1000
25 10 10000 100 45-65 33-50 40-70 12 50 20 20 12 18
10 1000
10

WI EN 23
WI Selection tables (contd.)

WIA/WIB 17 kV
Rated insulation level

Rated peak withstand current


Ratings of isolating distance

Percentage value of the DC


Rated short-circuit breaking
equal to rated short-circuit
3)
Type

Rated short-time current


Rated lightning impulse

Rated power frequency

Rated (normal) current


withstand voltage

withstand voltage

Rated frequency
Design pressure

making current
Rated voltage

Pr at 20 0 C 5)
Panel width

component
current
1s 3s
mm kV kV kV kV/kV bar Hz A kA kA kA kA %
WIA 8/17-2/621 0.8 630 80 31.5 20 31.5
WIA 8/17-2/621 0.8 1250 80 31.5 31.5 31.5
WIA 8/17-2/621 600 17.5 95 38 110/45 0.8 50/60 1600 80 31.5 31.5 31.5 38
WIA 8/17-2/621 1.3 2000 80 31.5 31.5 31.5
WIA 8/17-2/621 1.3 25001) 80 31.5 31.5 31.5
WIB 8/17-2/627 0.8 630 80 31.5 20 31.5
WIB 8/17-2/627 0.8 1250 80 31.5 31.5 31.5
WIB 8/17-2/627 600 17.5 95 38 110/45 0.8 50/60 1600 80 31.5 31.5 31.5 38
WIB 8/17-2/627 1.3 2000 80 31.5 31.5 31.5
WIB 8/17-2/627 1.3 25002) 80 31.5 31.5 31.5
WIA 10/17-2/621 0.8 1250 100 40 40 40
WIA 10/17-2/621 0.8 1600 100 40 40 40
600 17.5 95 38 110/45 50/60 38
WIA 10/17-2/621 1.3 2000 100 40 40 40
WIA 10/17-2/621 1.3 25001) 100 40 40 40
WIB 10/17-2/627 0.8 1250 100 40 40 40
WIB 10/17-2/627 0.8 1600 100 40 40 40
600 17.5 95 38 110/45 50/60 38
WIB 10/17-2/627 1.3 2000 100 40 40 40
WIB 10/17-2/627 1.3 25002) 100 40 40 40

LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O

1)
with cooling gas tank, panel height 2750 mm
2)
with motor-actuated fan
3)
possible limits and components fitted, refer to project planning documents WI no. 49 542
4)
adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
5)
minimum service pressure 0.3 bar at a filling pressure of 0.8 bar; 0.7 bar at a filling pressure of 1.3 bar

24 WI EN
WI Selection tables (contd.)

Rated operating Number of operating Operating times Command times


sequence cycles without
overhaul with release with release
mech. electrical 25 W 160 W 160 W 25 W 160 W 160 W

and earthing switch with motor -


Operating time for disconnector
under out-of-phase conditions

Charging time for motor drive


O - 3 min - CO - 3 min - CO

O - 0.3 s - CO - 3 min - CO

with rated (normal) current


O - 0.3 s - CO - 15 s - CO

drive mechanism, 160 W


Rated breaking current
Cable breaking current

Small indirect currents

with rated short-circuit

Arc duration (max.)


breaking current

4)

4)
CO - 15 s - CO

4)
Opening time

Opening time

Closing time

mechanism
LS,
TS,

On
Off

Off
E
On Off
A A kA ms ms ms ms ms ms ms s s
8 10000
8 1000
25 10 8 1000 10000 100 45-65 33-50 40-70 14 50 20 20 12 18
8
8
8 10000
8 1000
25 10 8 1000 10000 100 45-65 33-50 40-70 14 50 20 20 12 18
8
8
10 10000
10 1000
25 10 10000 100 45-65 33-50 40-70 14 50 20 20 12 18
10 1000
10
10 10000
10 1000
25 10 10000 100 45-65 33-50 40-70 14 50 20 20 12 18
10 1000
10

WI EN 25
WI Selection tables (contd.)

WIA/WIB 24 kV
Rated insulation level

Rated peak withstand current


Ratings of isolating distance

Percentage value of the DC


Rated short-circuit breaking
equal to rated short-circuit
3)
Type

Rated short-time current


Rated lightning impulse

Rated power frequency

Rated (normal) current


withstand voltage

withstand voltage

Rated frequency
Design pressure

making current
Rated voltage

Pr at 20 0C 5)
Panel width

component
current
1s 3s
mm kV kV kV kV/kV bar Hz A kA kA kA kA %
WIA 8/24-2/621 0.8 630 80 31.5 20 31.5
WIA 8/24-2/621 0.8 1250 80 31.5 31.5 31.5
WIA 8/24-2/621 600 24 125 50 145/60 0.8 50/60 1600 80 31.5 31.5 31.5 38
WIA 8/24-2/621 1.3 2000 80 31.5 31.5 31.5
WIA 8/24-2/621 1.3 25001) 80 31.5 31.5 31.5
WIB 8/24-2/627 0.8 630 80 31.5 20 31.5
WIB 8/24-2/627 0.8 1250 80 31.5 31.5 31.5
WIB 8/24-2/627 600 24 125 50 145/60 0.8 50/60 1600 80 31.5 31.5 31.5 38
WIB 8/24-2/627 1.3 2000 80 31.5 31.5 31.5
WIB 8/24-2/627 1.3 25002) 80 31.5 31.5 31.5
WIA 10/24-2/621 0.8 1250 100 40 40 40
WIA 10/24-2/621 0.8 1600 100 40 40 40
600 24 125 50 145/60 50/60 38
WIA 10/24-2/621 1.3 2000 100 40 40 40
WIA 10/24-2/621 1.3 25001) 100 40 40 40
WIB 10/24-2/627 0.8 1250 100 40 40 40
WIB 10/24-2/627 0.8 1600 100 40 40 40
600 24 125 50 145/60 50/60 38
WIB 10/24-2/627 1.3 2000 100 40 40 40
WIB 10/24-2/627 1.3 25002) 100 40 40 40

LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O

1)
with cooling gas tank, panel height 2750 mm
2)
with motor-actuated fan
3)
possible limits and components fitted, refer to project planning documents WI no. 49 542
4)
adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
5)
minimum service pressure 0.3 bar at a filling pressure of 0.8 bar; 0.7 bar at a filling pressure of 1.3 bar

26 WI EN
WI Selection tables (contd.)

Rated operating Number of operating Operating times Command times


sequence cycles without
overhaul with release with release
mech. electrical 25 W 160 W 160 W 25 W 160 W 160 W

Operating time for disconnector


and earthing switch with motor -
under out-of-phase conditions

Charging time for motor drive


O - 3 min - CO - 3 min - CO

O - 0.3 s - CO - 3 min - CO

with rated (normal) current


O - 0.3 s - CO - 15 s - CO

drive mechanism, 160 W


Rated breaking current
Cable breaking current

Small indirect currents

with rated short-circuit

Arc duration (max.)


breaking current

4)

4)
CO - 15 s - CO

4)
Opening time

Opening time

Closing time

mechanism
LS,
TS,

On
Off

Off
E
On Off
A A kA ms ms ms ms ms ms ms s s
8 10000
8 1000
31.5 10 8 1000 10000 100 45-65 33-50 40-70 14 50 20 20 12 18
8
8
8 10000
8 1000
31.5 10 8 1000 10000 100 45-65 33-50 40-70 14 50 20 20 12 18
8
8
10000
1000
31.5 10 10000 100 45-65 33-50 40-70 14 50 20 20 12 18
1000
-
10000
1000
31.5 10 10000 100 45-65 33-50 40-70 14 50 20 20 12 18
1000

WI EN 27
WI Selection tables (contd.)

WIA/WIB 36 kV
Rated insulation level

Rated peak withstand current


Ratings of isolating distance

Percentage value of the DC


Rated short-circuit breaking
equal to rated short-circuit
3)
Type

Rated short-time current


Rated lightning impulse

Rated power frequency

Rated (normal) current


withstand voltage

withstand voltage

Design pressure

Rated frequency

making current
Rated voltage

Pr at 20 0C 5)
Panel width

component
current
1s 3s
mm kV kV kV kV/kV bar Hz A kA kA kA kA %
WIA 6/36-2/621 1.3 630 63 25 20 25 42
WIA 6/36-2/621 1.3 1250 63 25 25 25 42
WIA 6/36-2/621 600 36 170 70 195/80 1.3 50 1600 63 25 25 25 42
WIA 6/36-2/621 1.3 2000 63 25 25 25 42
1)
WIA 6/36-2/621 1.3 2500 63 25 25 25 42
WIB 6/36-2/627 1.3 630 63 25 20 25 42
WIB 6/36-2/627 1.3 1250 63 25 25 25 42
WIB 6/36-2/627 600 36 170 70 195/80 1.3 50 1600 63 25 25 25 42
WIB 6/36-2/627 1.3 2000 63 25 25 25 42
WIB 6/36-2/627 1.3 25002) 63 25 25 25 42
WIA 10/36-2/621 1.3 1250 100 40 40 40 31
WIA 10/36-2/621 1.3 1600 100 40 40 40 31
600 36 170 70 195/80 50/60
WIA 10/36-2/621 1.3 2000 100 40 40 40 31
1.3 1)
WIA 10/36-2/621 2500 100 40 40 40 31
WIB 10/36-2/627 1.3 1250 100 40 40 40 31
WIB 10/36-2/627 1.3 1600 100 40 40 40 31
600 36 170 70 195/80 50/60
WIB 10/36-2/627 1.3 2000 100 40 40 40 31
WIB 10/36-2/627 1.3 25002) 100 40 40 40 31

LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O

1)
with cooling gas tank, panel height 2750 mm
2)
with motor-actuated fan
3)
possible limits and components fitted, refer to project planning documents WI no. 49 542
4)
adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
5)
minimum service pressure 0.7 bar

28 WI EN
WI Selection tables (contd.)

Rated operating Number of operating Operating times Command times


sequence cycles without
overhaul with release with release
mech. electrical 25 W 160 W 160 W 25 W 160 W 160 W

and earthing switch with motor -


Operating time for disconnector
under out-of-phase conditions

Charging time for motor drive


O - 3 min - CO - 3 min - CO

O - 0.3 s - CO - 3 min - CO

with rated (normal) current


O - 0.3 s - CO - 15 s - CO

drive mechanism, 160 W


Rated breaking current
Cable breaking current

Small indirect currents

with rated short-circuit

Arc duration (max.)


breaking current

4)

4)
CO - 15 s - CO

4)
Opening time

Opening time

Closing time

mechanism
LS,
TS,

On
Off

Off
E
On Off
A A kA ms ms ms ms ms ms ms s s
6.3 10000
6.3 1000
50 10 6.3 1000 10000 100 43-65 29-50 40-65 14 50 20 20 12 18
6.3
6.3
6.3 10000
6.3 1000
50 10 6.3 1000 10000 100 43-65 29-50 40-65 14 50 20 20 12 18
6.3
6.3
6.3 10000
6.3 1000
50 10 10000 100 43-65 40-65 14 50 20 12 18
6.3 1000
6.3
6.3 10000
6.3 1000
50 10 10000 100 43-65 40-65 14 50 20 12 18
6.3 1000
6.3

WI EN 29
WI Selection tables (contd.)

WIA/WIB 38 kV
Rated insulation level

Rated peak withstand current


Ratings of isolating distance

Percentage value of the DC


Rated short-circuit breaking
equal to rated short-circuit
Type

3)

Rated short-time current


Rated lightning impulse

Rated power frequency

Rated (normal) current


withstand voltage

withstand voltage

Rated frequency
Design pressure

making current
Rated voltage

Pr at 20 0C 5)
Panel width

component
current
1s 3s
mm kV kV kV kV/kV bar Hz A kA kA kA kA %
WIA 8/38-2/621 1.45 630 80 31.5 20 31.5 31
WIA 8/38-2/621 1.45 1250 80 31.5 31.5 31.5 31
WIA 8/38-2/621 600 38 200 80 220/90 1.45 50/60 1600 80 31.5 31.5 31.5 31
WIA 8/38-2/621 1.45 2000 80 31.5 31.5 31.5 31
1)
WIA 8/38-2/621 1.45 2500 80 31.5 31.5 31.5 31
WIB 8/38-2/627 1.45 630 80 31.5 31.5 31.5 31
WIB 8/38-2/627 1.45 1250 80 31.5 31.5 31.5 31
WIB 8/38-2/627 600 38 200 80 220/90 1.45 50/60 1600 80 31.5 31.5 31.5 31
WIB 8/38-2/627 1.45 2000 80 31.5 31.5 31.5 31
WIB 8/38-2/627 1.45 25002) 80 31.5 31.5 31.5 31
WIA 8/40.5-2/621 1.45 1250 80 31.5 31.5 31.5 31
WIA 8/40.5-2/621 185 215/90 1.45 1600 80 31.5 31.5 31.5 31
600 40.5 85 50
WIA 8/40.5-2/621 (200) (220/90) 1.45 2000 80 31.5 31.5 31.5 31
1.45 1)
WIA 8/40.5-2/621 2500 80 31.5 31.5 31.5 31
WIB 8/40.5-2/627 1.45 1250 80 31.5 31.5 31.5 31
WIB 8/40.5-2/627 185 215/90 1.45 1600 80 31.5 31.5 31.5 31
600 40.5 85 50
WIB 8/40.5-2/627 (200) (220/90) 1.45 2000 80 31.5 31.5 31.5 31
WIB 8/40.5-2/627 1.45 25002) 80 31.5 31.5 31.5 31

LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O

1)
with cooling gas tank, panel height 2750 mm
2)
with motor-actuated fan
3)
for possible limit values and components fitted, refer to the project planning documents WI no. 49 542
4)
adm. tolerance range, is not a manufacturing tolerance, for the current value of a specimen, refer to the routine test report
5)
minimum service pressure at 20 C = 1.0 bar (overpressure)

30 WI EN
WI Selection tables (contd.)

Rated operating Number of operating Operating times Command times


sequence cycles without
overhaul with release with release
mech. electrical 25 W 160 W 160 W 25 W 160 W 160 W

and earthing switch with motor -


Operating time for disconnector
under out-of-phase conditions

Charging time for motor drive


O - 3 min - CO - 3 min - CO

O - 0.3 s - CO - 3 min - CO

with rated (normal) current


O - 0.3 s - CO - 15 s - CO

drive mechanism, 160 W


Rated breaking current
Cable breaking current

Small indirect currents

with rated short-circuit

Arc duration (max.)


breaking current

4)

4)
CO - 15 s - CO

4)
Opening time

Opening time

Closing time

mechanism
LS,
TS,

On
Off

Off
E
On Off
A A kA ms ms ms ms ms ms ms s s
10000
1000
50 10 1000 10000 100 43-65 40-65 14 50 20 12 18


10000
1000
50 10 1000 10000 100 43-65 40-65 14 50 20 12 18


10000
1000
50 10 10000 100 43-65 40-65 14 50 20 12 18
1000

10000
1000
50 10 10000 100 43-65 40-65 14 50 20 12 18
1000

WI EN 31
WI Selection tables (contd.)

WIA/WIB 40.5 up to 52 kV
2 vacuum interrupter chambers per conductor
Rated insulation level

Rated peak withstand current


Ratings of isolating distance

Percentage value of the DC


Rated short-circuit breaking
equal to rated short-circuit
Type

3)

Rated short-time current


Rated lightning impulse

Rated power frequency

Rated (normal) current


withstand voltage

withstand voltage

Rated frequency
Design pressure

making current
Rated voltage

Pr at 20 0C 5)
Panel width

component
current
1s 3s
mm kV kV kV kV/kV bar Hz A kA kA kA kA %
WIA 10/40.5-2/626 1.45 1250 100 40 40 40
600 40.5 200 80 220/90 50 26
WIA 10/40.5-2/626 1.45 25001) 100 40 40 40

WIB 10/40.5-2/633 220/90 1.45 1250 100 40 40 40


600 40.5 200 80 50 26
WIB 10/40.5-2/633 1.45 2)
2500 100 40 40 40

WIA 8/52-2/626 52 250 290/110 2.2 1250 82 31.5 31.5 31.5


600 95 50/60 26
WIA 8/52-2/626 (60) (110) 2.2 25001) 82 31.5 31.5 31.5

WIB 8/52-2/633 52 250 290/110 2.2 1250 82 31.5 31.5 31.5


600 95 50/60 26
WIB 8/52-2/633 (60) (110) 2.2 25002) 82 31.5 31.5 31.5

LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O

1)
with cooling gas tank, panel height 3314 mm and with motor-actuated fans
2)
with motor-actuated fan
3)
possible limits and components fitted, refer to project planning documents WI no. 49 542
4)
adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
5)
minimum service pressure at 20 C: 0.1 bar at a filling pressure of 1.45 bar; 1.8 bar at a filling pressure of 2.2 bar

32 WI EN








WI

O - 3 min - CO - 3 min - CO

WI EN
O - 0.3 s - CO - 3 min - CO

sequence
CO - 15 s - CO

Rated operating
O - 0.3 s - CO - 15 s - CO

50
50
50
50
Cable breaking current

A
Small indirect currents

Rated breaking current

kA
under out-of-phase conditions

E
LS,
TS,

1000
1000
1000
1000
1000
1000
1000
1000
mech.

10000
10000

10000
10000
with rated (normal) current

10000
10000
10000
10000
overhaul
cycles without

electrical

with rated short-circuit


Number of operating

100
100
100
100
breaking current

4)

ms
Opening time

50-80
25 W

50-80
50-80
50-80
4)



ms
Opening time


with release

4)
ms

Closing time

40-65
40-65

40-65
40-65
Operating times

160 W 160 W

14
14

14
14
Arc duration (max.)
ms

50

50
50
50

Off
ms
Selection tables (contd.)

Off
ms
On
with release
Command times

Off

On
ms

20
20
20

20
25 W 160 W 160 W

Charging time for motor drive


s

12
12
12
12

mechanism
Operating time for disconnector
s

and earthing switch with motor -


18
18
18
18

drive mechanism, 160 W

33
WI Selection tables (contd.)

WIA/WIB 1 and 2-POLE, for stationary railway traction power supply 50/60 Hz
with 2 vacuum interrupter chambers per conductor
Rated insulation level

equal to rated short-circuit ma-


Rated peak withstand current
Ratings of isolating distance

Rated short-circuit breaking

Percentage value of the DC


Rated voltage UNM acc. to

Type

Rated short-time current


Rated (normal) curren 3)
Rated voltage U acc. to

Rated lightning impulse

Rated power frequency


withstand voltage

withstand voltage

Design pressur e

Rated frequency
Pr bei 20 0C 5)

king current
Panel width

component
EN 50 124

EN 60 694

current
1s 3s
mm kV kV kV kV kV/kV bar Hz A kA kA kA kA %
WIA 6/55-S/626 1250 65 25 25
600 27.5 52 250 95 290/110 2.2 50/60 26
WIA 6/55-S/626 2000 65 25 25

WIA 6/55-T/626 1250 65 25 25


600 27.5 52 250 95 290/110 2.2 50/60 26
WIA 6/55-T/626 2000 65 25 25

WIA-Z 600 17.5 36 170 70 195/110 2.2 16 2/3 1250 80 31.5 31.5 46

LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O
S = 1-pole
T = 2-pole

3)
without cooling gas tank and heat sink
4)
adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
5)
minimum service pressure at 20 C 1.8 bar

34 WI EN




WI

O - 3 min - CO - 3 min - CO

WI EN




O - 0.3 s - CO - 3 min - CO




sequence
CO - 15 s - CO

Rated operating
O - 0.3 s - CO - 15 s - CO

50
50
50
Cable breaking current

A
Small indirect currents

Rated breaking current

kA

12.5
12.5
under out-of-phase conditions

E
LS,
TS,

1000
1000
1000
1000
1000
1000
mech.

10000
10000
with rated (normal) current
haul

10000 10000
10000
10000
electrical

with rated short-circuit


Number of operating

100
100
100
cycles without over -

breaking current

4)

ms
Opening time
25 W

50-80
50-80
4)


ms
Opening time

25-35
with release

4)
ms

Closing time
40-50

40-50
40-50
Operating times

160 W 160 W

14

14
Arc duration (max.)
ms

6-68
50

50

Off
ms
Selection tables (contd.)

20

Off
ms
On
with release
Command time

Off

20
20
20

On
ms
25 W 160 W 160 W

Charging time for motor drive


s

12

12
12

mechanism
Operating time for disconnector
s

and earthing switch with motor -


18
18
18

drive mechanism, 160 W

35
WI Range of products

Single busbar panels


Circuit-breaker panel
With inner cone-type cable connection for
rated voltage up to 52 kV
rated short-circuit breaking current up to 40 kA
rated busbar and outgoing feeder (normal) currents up to 2500 A

Disconnector panel
With inner cone-type cable connection for
rated voltage up to 52 kV
rated short-time current up to 40 kA
rated busbar and outgoing feeder (normal) currents up to 2500 A

Bus section coupler


for
rated voltage up to 52 kV
rated short-circuit breaking current up to 40 kA
rated busbar (normal) currents up to 2500 A

Circuit-breaker panel Bus section coupler


(Inner cone-type cable connection)

Busbar attachments

Panel connection
Panel attachment
connection
variants
1)

Voltage Current Current


transformer, transformer transformer
pluggable
Plug-in cable
single

or Plug-in cable or Plug-in cable


single, double
Terminal type 3
1) 1)
if a surge arrester is used,
the number of cables is
or Voltage or Plug-in cable reduced by one
transformer, triple
pluggable 1)

1)

or Surge or Plug-in cable


arrester, quadruple
pluggable
1)

and Busbar or Busbar Surge


current with solid arrester,
transformer insulation pluggable

1)
not possible in case of 52 kV

36 WI EN
WI Range of products (contd.)

Double busar panels


Circuit-breaker panel
With inner cone-type cable connection for
rated voltage up to 52 kV
rated short-circuit breaking current up to 40 kA
rated busbar and outgoing feeder (normal) currents up to 2500 A
Bus section coupler
(Circuit-breaker panel and bus riser panel)
With inner cone-type cable connection for
rated voltage up to 52 kV
rated short-circuit breaking current up to 40 kA
rated busbar and outgoing feeder (normal) current up to 2500 A
Bus section coupler
for
rated voltage up to 52 kV
rated short-circuit breaking current up to 40 kA
rated busbar (normal) current up to 2500 A

Bus coupler (transverse)


for
rated voltage up to 52 kV
rated short-circuit breaking current up to 40 kA
rated busbar (normal) current up to 2500 A

Metering panel
for
rated voltage up to 36 kV
rated busbar (normal) current up to 2500 A
Circuit-breaker panel
(Inner cone-type cable connection)

Busbar attachments
SS2
SS1

Panel connection
attachment

variants
1)

Voltage Current
transformer, transformer
pluggable

Plug-in cable
single

or Plug-in cable or Plug-in cable


single, double
Terminal type3

1) 1) if a surge arrester is used,


the number of cables is
or Voltage or Plug-in cable reduced by one
transformer, triple
pluggable 1)

1)

or Surge or Plug-in cable


arrester, quadruple
pluggable

1)

and Busbar or Busbar Surge


current with solid arrester,
transformer insulation pluggable

1)
not possible in case of 52 kV
WI EN 37
WI Range of products (contd.)

Disconnector panel Bus section coupler / riser panel


(Inner cone-type cable connection)

SS2 SS2
SS1 SS1

Panel
connection Panel connection
attachment attachment

1) 1)

Panel Panel
Voltage connection Voltage Current
connection transformer, transformer, transformer
variants variants
pluggable pluggable

Plug-in cable Plug-in cable


single single

Plug-in cable or Plug-in cable


or double
double

1) 1) if a surge arrester is used, 1) 1) if a surge arrester is used,


the number of cables is the number of cables is
reduced by one Plug-in cable reduced by one
or Plug-in cable or
triple triple

1) 1)

Plug-in cable or Plug-in cable


or quadruple
quadruple

1) 1)

Busbar Surge or Busbar Surge


or with solid
with solid arrester, arrester,
insulation pluggable insulation pluggable

1)
not possible in case of 52 kV

38 WI EN
WI Range of products (contd.)

Bus section coupler Bus coupler up to 2500 A 1) Disconnector/earthing


switch in line with busbar

SS2 SS2 SS2


SS1 SS1 SS1

Current Current
transformer transformer

Bus coupler
up to 2000 A
(1 panel width) 1)

SS2
SS1

Current
transformer

only up to 40.5 kV
1)

Abbreviations
SS1 = Busbar 1
SS2 = Busbar 2

WI EN 39
WI Cable connections

Cable connections in outgoing feeder block


The medium-voltage cables are connected to the switchgear panels via
metal-enclosed inner cone-type plug-in terminations. The panels are
equipped with inner cone-type appliance couplers according to EN 50 181.
The manufacturers specifications of the regarding selection and assembly
of the plug-in terminations must be adhered to. This does not only apply to
the selection of size, but also to all electrical rated data, in line with the
switchgears data.
It is essential that all appliance couplers which are not equipped with
plug-in terminations are terminated correctly using voltage-proof and fully
shrouded insulating terminals/ dummy plugs.
To this effect, the inner cone-type cable plug-in terminations for attachment
to WI require capacitive decoupling. The coupling electrodes for the
capacitive voltage detection system are an integral part of the appliance
couplers installed in the switchgear panel.

Cable connections in outgoing feeder

3 phase switchgear 1 phase switchgear 2 phase switchgear


panels panels panels

Inner cone acc. to EN 50181


Terminal types:
size 1 630 A
size 2 800 A
size 3 (up to 40.5 kV) 1250 A
size 3 (> 40.5 up to 52 kV) 1250 A
size 4 2500 A

Single / double busbar Single cable, 3-phase, without


outgoing voltage transformer
12-36 kV 38-40.5 kV
1x size 1
1x size 2
1x size 3
1x size 4

Size 4 with supporting structure increased in height

Single busbar Railway traction power supply with 2 vacuum


interrupter chambers per phase
1-pole L1 2-pole L1, L3
Single cable connection 1x size 3/S

40 WI EN
WI Cable connections (contd.)

Single / double busbar with 1 vacuum interrupter chamber


per conductor/phase
Multi-cable, 3-phase, without outgoing
voltage transformer
12 kV - 36 kV 38 kV - 40.5 kV
2 x size 1
3 x size 1
2 x size 2
3 x size 2
4 x size 2
2 x size 3
3 x size 3
Multi-cable connection 4 x size 3
1 x size 1 + 2 x size 3
1 x size 2 + 2 x size 3

Single / double busbar with 2 vacuum interrupter chambers


per conductor/phase
Single- and multi-cable, 3-phase, without outgoing voltage transformer
40.5 kV 52 kV
BIL 200 kV BIL 250 kV
1 x size 3
1 x size 3/S
2 x size 3
2 x size 3/S
3 x size 3
3 x size 3/S

Single busbar for stationary railway traction power supply


with 2 vacuum interrupter chambers per conductor/phase
Multiple cable without voltage transformer
1-phase L1 2-phase L1 + L3
2 x size 3/S
3 x size 3/S
4 x size 3/S
5 x size 3/S

WI EN 41
WI Cable connections (contd.)

Single / double busbar with 1 vacuum interrupter chamber


per conductor/phase
Multi-cable, 3-phase with 3 outgoing
voltage transformers
12 kV - 36 kV 38 kV - 40.5 kV
1 x size 2
3 x size 2
4 x size 2
1 x size 3
2 x size 3
3 x size 3
4 x size 3
1 x size 2 + 1 x size 3
Multi-cable connection with voltage
transformer in outgoing feeder 1 x size 2 + 2 x size 3
1 x size 2 + 3 x size 3
1 x size 2 + 4 x size 3
1 x size 1 + 3 x size 3

Single / double busbar with 2 vacuum interrupter chambers


per conductor/phase
Multi-cable, 3-phase, with 1 outgoing voltage transformer (1-phase in L2)
40.5 kV 52 kV
BIL 200 kV BIL 250 kV
1 x size 3
1 x size 3/S
2 x size 3
3 x size 3/S
possible up to rated (normal) current in outgoing feeder of max. 1600 A

Single busbar for stationary railway traction power supply


with 2 vacuum interrupter chambers per conductor/phase
Multi-cable with 1 or 2 voltage transformers
2-phase L1 + L3
1-phase Voltage Voltage transformers
L1 transformers L1 + L3
L3
1 x size 3/S
2 x size 3/S
3 x size 3/S
4 x size 3/S

42 WI EN
WI Ecological considerations

A WI switchgear satisfies to a high degree ecological requirements in view


of environmental protection thanks to
optimization of material and energy consumption during manufacture
compliance with all ecological requirements during its service life
the use of recyclable materials for efficient disposal at the end of its
service life.
Our design directives regarding environmentally compatible design specify
the use of materials which are easily recyclable and can be disassembled.
The metals which make up approx. 90 % of the switchgear are easily
recyclable. At the end of their service life, they are recycled 100 % in the
form of homogenous materials.
Plastics can also be recycled. Thermosetting i.e. non-melting plastics
can be comminuted and reused as fillers in other plastic components;
thermoplastic - i.e. melting - materials can be recycled in the form of
homogenous material. This means that the material is conserved, melted
down and used for the construction of new durable parts.
To ensure efficient and environmentally compatible disassembly and
assignment of materials by the responsible disposal experts, the
switchgears plastic components have been identified accordingly.
Moreover, material and utilization data sheets are available to provide the
customer with an over- view about the materials used. Equally, the disposal
company is provided with important information regarding the recycling process.
Thus, the materials used for our products can be reused 100 %.
This represents a major contribution towards saving primary energy and
material resources.
All materials were selected and developed so that e.g. in case of fire within
buildings, affected switchgear only have a minor influence on the fire load
(heat development, pollutants in the emissions).
Another important ecological aspect is the longevity of our products (min.
30 to 40 years), which is an extremely long service life compared to other
capital goods. Furthermore, the switchgear units have been designed so as
to require little maintenance which would in turn use up energy and material,
and so as to enable straightforward replacement of part components, e.g. if
new controllers have been developed on the market (upgrading).
In our gas-insulated switchgear WI, the majority of the switchgear panel
has been sealed hermetically in an insulating inert gas (sulphur
hexafluoride SF6 which is neither reactive nor toxic). Thus, all
environmental influences reducing the service life are shut out. The special
characteristics of the insulating gas also enable an overall size reduction by
approx. 50 percent versus switchgear designed without insulating gas with
comparable technical properties. This again saves a lot of material and
energy required for material production. The portion of insulating gas used
for WI switchgear amounts to approx. 0.5 percent by weight. Once the
switchgears service life has elapsed, the gas is extracted completely via
the disposal valve provided serially in each gas-filled, cladded
compartment, and then recycled. The gas suppliers have developed an
efficient recycling concept to this effect.
During normal operation, the gas need not be replenished during the entire
service life of the switchgear. The switchgear is a hermetically sealed
pressure system acc. to IEC 60694 (IEC 62271-1).
Average material distribution in gas-insulated
switchgear units

Materials Wt. %
Metals Steel 7
Copper 6.5
Aluminium, brass 2
Plastics Thermosetting plastics 7
Thermo-plastics 2
Elastomers 0.5
Electronics Plastics 0.5
Metals 1
Insulating gas Sulphur hexafluoride 0.5

WI EN 43
WI Design data
Space requirements - dimensions and
weights

>500
>500
WIA up to 40.5 kV WIA up to 52 kV

>500

2400
>500

2964
>1500 1)

>1000

>1000
>1500 1)

View
view
>500

>500

>1500 1)
>500

Topview
Top view

1692
70 70 280 70
Spacer bars 673
600
460
70

Flooringducts
Flooring ducts

1)
smaller gap on request

Weights:
WIA up to 40.5 kV approx. 1000 kg
WIA 52 kV approx. 1350 kg

44 WI EN
WI Design data
Space requirements - dimensions and
weights (contd.)

WIA up to 52 kV

>500
WIA up to 52 kV

>500
WIA up to 40.5 kV

>500
2400

>500 >500

2964
>1500 1)
>1000

>1000
>1500 1)

View
view
>500

>500

>500
>1500 1)
>500

Top view

1692
70 70 280 70
Spacer bars 673
600
460
70

Flooring ducts

1)
smaller gap on request
Weights:
WIA up to 40.5 kV max. 1000 kg
WIA 52 kV approx. 1350 kg

WI EN 45
WI Design data
Space requirements - dimensions and
weights (contd.)

WIB up to 40.5 kV

WIB bis 52 kV

>500
WIB bis 40,5 kV
>500

3614
>500
3050

>500 >500

>1500 1)
>1000

>1000
>1500 1)

view
View
>500

>500

1)
>500
>1500
>500

Top view

1692
70 70 280
Spacer bars 673
70
600
460

1)
smaller gap on request
70

Weights:
WIB up to 40.5 kV approx. 1300 kg
WIB 52 kV approx. 1700 kg
Flooring ducts

46 WI EN
WI Design data
Space requirements - dimensions and
weights (contd.)

WIB up to 52 kV

>500
WIB up to 40.5 kV WIB up to 52 kV

>500
3050

3614
>500

>500

>1500 1)
>1000

>1000

>1500 1)

view
View
>500

>500

>1500 1)
>500

Top view
Top view

1692
70 70 280
Spacer bars 673
70
600
460
70

1)
smaller gap on request
Weights:
WIB up to 40.5 kV approx. 900 - 1000 kg
WIB 52 kV approx. 1100 - 1500 Kg
Flooring ducts
Flooring ducts

WI EN 47
WI Design data
Space requirements - dimensions and
weights (contd.)

Busbar connection with fully insulated conductor bars

Direct transfer line. Phase exchange in terminal tank


Direct transfer line. Phase exchange in terminal tank

48 WI EN
WI Design data
Space requirements - dimensions and
weights (contd.)

Transfer
Transfer line
line at bottom.
at the the bottom.
Phase Phase exchange
exchange required inrequired in transfer line
transfer line

Transferline
Transfer line
toptop
andand bottom
bottom by of
by means means of supplementary
supplementary gas tank gas tank

Direct transfer
Direct line.line.
transfer Phase exchange
Phase in terminal
exchange tank
in terminal tank

WI EN 49
WI Shipping instructions

Transporting the switchgear unit


When transporting the switchgear unit, it is important to ensure that the
transport units do not slip or tilt (if necessary, nail transport pallet down to
the loading surface). Reuse the original packaging to store parts which
have been unpacked for inspection.

Packaging of the switchgear


If packed for truck transport, the switchgear unit is delivered on a pallet
with PE protective film.
For sea-worthy transport, the units are packed in sealed aluminium film
with desiccant and in a closed case with tightly closed wooden base.
In case of air transport, the switchgear unit is packed in a wooden crate
with closed wooden base and with a blister IPE film as dust protection or
in a wooden case, also with closed wooden base.

Transport to the site of installation


Store under conditions admissible for switchgear operation. Avoid
condensation.
During transport to the site of installation, remember that the main weight is
located in the top area of the switchgear top-heavy.
Transport using a forklift truck: Only transport the switchgear on a pallet.
Attention top-heavy!
Transport without pallet: The crane mounting harness must be hooked into
the jack rings of the switchgear.

50 WI EN
Appendices Notes

WI EN 51
2011 Schneider Electric - All rights reserved

Schneider Electric As standards, specifications and designs change from time to time, please ask for
35, rue Joseph Monier confirmation of the information given in this publication.
CS 30323
This document has been printed
92506 Rueil-Malmaison Cedex, France
on ecological paper
RCS Nanterre 954 503 439 Publishing: Schneider Electric
Capital social 896 313 776 Design: Schneider Electric
www.schneider-electric.com Printing:
WI EN 02-2011