You are on page 1of 1

NOTES:

NOTES CONT'D: 1. FOR GENERAL NOTES, SYMBOLS AND DETAILS SEE DRAWING
A10-A-PID-VA-449162-001 THRU A10-A-PID-VA-449165-005.
A29-U-0001 23. THE BLIND FLANGE WILL BE STORED SOMEWHERE DURING NORMAL 2. SEE PIPING UNDERGROUND AND PAVING LAYOUTS FOR DETAILS
OPERATION, IT WILL BE INSTALLED ONLY IN LIFT STATION MAINTENANCE OF GRAVITY DRAINAGE COLLECTION SYSTEM (A29-S-UTI-VA-209626-001).
SANITARY LIFT STATION 10 TO PLUG INLET OPENING TO LIFT STATION. 3. PUMP SHALL BE NON-CLOG TYPE, SUBMERSIBLE, GRINDER TYPE
SPECIFICALLY DESIGNED FOR PUMPING SEWAGE.
SIZE (LxWxH): 2.0 m x 2.0 m x 3.2 m NOTE 19 4. LIFT STATION SHALL BE EQUIPPED WITH PERMANENT GUIDE
WORKING CAP: 1.0 m^3 RAILS FOR REMOVING THE PUMP.
INSULATION: NI 5. ACTIVATED CARBON PASSIVE ODOUR CONTROL UNIT.
MOC: CONCRETE 6. AN AUDIO VISUAL DEVICE (A LIGHT) SHALL BE INSTALLED AT
TRIM: NOTE 22 THE LIFT STATION FOR EXTERNAL OBSERVATION.
7. DELETED.
8. EMERGENCY PUMP CONNECTION.
9. MINIMUM GOOSENECK VENT HEIGHT 3,000MM ABOVE HP LIFTSTATION
DECK LEVEL. AND MINIMUM SIZE OF 3 INCHES.
10. DUTY PUMP WILL START ON HIGH LIQUID LEVEL AND STOP ON LOW
LIQUID LEVEL. IF THE LIQUID LEVEL UPTO HIGH HIGH LEVEL OR DOWN
TO LOW LOW LEVEL, ALARM WILL BE ACTUATED. STANDBY PUMP WILL
ONLY TO BE STARTED ON HIGH HIGH HIGH LIQUID LEVEL AND STOPPED
ON LOW LIQUID LEVEL.
11. HATCH FOR MAINTENANCE ACCESS FOR PUMPS, VALVES, AND
VACUUM TRUCK CONNECTION.
12. GREASE TRAPS SHALL BE PROVIDED UPSTREAM AT THE SOURCE
(WITHIN THE BUILDING) FOR STREAMS FROM A COMMUNAL KITCHEN.
13. DELETED.
14. DELETED.
15. LOCATE LOCAL INDICATORS AT GRADE LEVEL.
A29
16. PUMP HAS PROVISIONS FOR REMOTE START FROM DCS.
FI 17. DELETED.
18. ALL INSTRUMENT TAG NUMBER SHALL BE PREFIXED BY THE PLANT NO. A29.
0763 L 19. THE SIZE OF SANITARY LIFT STATION 10 SHALL BE CONFIRMED AFTER
RECEIVE VENDOR INFORMATION.
20. DELETED.
A29 FF SP 21. THE LIQUID LEVEL SETTED NEED TO BE CONFIRMED AFTER RECEIVE
FT A29
A
A51 VENDOR INFORMATION. LIQUID LEVEL IS DETERMINED ACCORDING TO THE
0073 SANITARY STATION BUTTOM 97.00 m FOR DATUM PLANES.
0763 BL
2-1/2" 22. TRIM: C1 12FE0U9
AG UG IP-GUT-GP-4093 A29-U-0001
D1,D2 12CS3U4
A29-3"-SWS-00002-12CS3U4 A29-3"-SWS-00005-12FE0U9 A51-3"-SWS-00012-12FE0U9
M A51-442844-053 LEGEND
NOTE 8 NI (38 C) 0 mm NI (38 C) 0 mm NI (38 C) 0 mm
SANITARY PIPING MATERIAL INSTRUMENT DEFINITION & SYMBOLS SAES-J-004
A29-3"-SWS-00001-12CS3U4 A29 12CS3U4 12FE0U9(CS) 12FE0U9 (CS) 12FE0U9 WASTEWATER SPECIFICATION SAES-L-105
AC/AFO -AIR TO CLOSE/ VE -VIBRATION ELEMENT
FE HEADER AIR FAILURE OPEN VS -VIBRATION SWITCH
NI (38 C) 0 mm AC/AFS -AIR TO CLOSE/AIR
0763 PROCESS LINE VT -VIBRATION TRANSMITTER
FAILURE STEADY XL -PILOT LIGHT
INSTRUMENT AO/AFC -AIR TO OPEN/ (NOT FOR MOTOR)
AIR LINE AIR FAILURE CLOSE XS -LIMIT SWITCH
AO/AFS -AIR TO OPEN/AIR ZV -SAFETY SHUTDOWN VALVE
INSTRUMENT
FAILURE STEADY
ELECTRICAL LINE DATA LOGGER POINT
AOV -AIR OPERATED VALVE
1" 1" F-FLOW P-PRESS.

INPUTS
AT -ANALYZER TRANSMITTER
L-LEVEL T-TEMP.
DT -DENSITY TRANSMITTER

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
X-MISC. A-ALARM
REDUCER ESD -EMER. SHUTDOWN SYSTEM
LOCAL PANEL
FC - FLOW CONTROLLER
SPECTACLE MOUNTED INSTR.
FV -FLOW CONTROL VALVE
PLATE-OPEN FCV -FLOW CONTROL VALVE
A29 A29 FF A29 A29 FF BOARD MOUNTED
PI PT 3" PI PT 3" (SELF-ACTUATED) INSTRUMENT
SPECTACLE FE -FLOW ELEMENT
0761 0761 0762 0762 PLATE-CLOSED FG -FLOW SIGHT GLASS
R/G
STATUS LIGHTS
GATE VALVE FHV -FLOW MANUAL CONT. VALVE XL R=RED, G=GREEN
FHTD -FLOW MANUAL TRANSDUCER PILOT LIGHT (DO NOT
A29 GLOBE VALVE FIC -FLOW INDICATOR CONTROLLER USE FOR MOTOR STATUS)
LI FM -FLOW METER
CHECK VALVE
RO -RESTRICTION ORIFICE MOTOR STATUS
0761 PILOT LIGHT
PLUG VALVE FQI -FLOW TOTALIZER INDICATOR
FR -FLOW RECORDER
BALL VALVE ML LOCAL MOUNTED
NOTE 16 NOTE 16 FT -FLOW TRANSMITTER INSTRUMENT
A29 HHH A29 A29
DOUBLE DISC FY -FLOW RELAY
UC HS HS GATE VALVE HIC -HAND INDICATOR CONTROLLER
MOUNTED BEHIND
ANGLE VALVE HS -HAND SWITCH LOCAL PANEL
0761 LL 0762D 0763D LA -LEVEL ALARM
LV -LEVEL CONTROL VALVE
PRESS. RELIEF VALVE RACK MOUNTED
LCV -LEVEL CONTROL VALVE (OR BACK OF PANEL)
(SELF-ACTUATED)
LG -LEVEL GAUGE GLASS ELECTRICAL
LIC -LEVEL INDICATOR CONTROLLER SUPPLY REQUIRED
VACUUM RELIEF VALVE -LEVEL INDICATOR
LI
LR -LEVEL RECORDER INSTRUMENT
LS -LEVEL SWITCH AIR SUPPLY REQUIRED
M MOTOR OPERATED
LT -LEVEL TRANSMITTER
VALVE H
LTD -LEVEL TRANSDUCER HIGH LOW
SP SEE DETAIL 6 SEE DETAIL 6 ML -MOTOR STATUS LIGHT L
P MOV -MOTOR OPERATED VALVE
A 0071
A51 A29 PISTON OPERATED NA -ANNUNCIATOR TWO PEN RECORDER
VALVE PB -PUSHBUTTON
BL I TO SAFE
IP-GPB-S-N781 PC -PRESSURE CONTROLLER FF
UG AG LOCATION NOTE 9 CONTROL VALVE PV -PRESS. CONTROL VALVE FOUNDATION
PCV -PRESS. CONTROL VALVE FIELDBUS INSTRUMENT
A51- -SWS-XXXXX-12FE0U9 A29-3"-SWS-00010-12FE0U9 A29-3"-SWS-00010-12FE0U9 (SELF ACTUATED)
P
BALL TYPE PDC -PRESS. DIFF. CONTROLLER DISTRIBUTED CONTROL/SHARED
NI (38 C) 0 mm NI (38 C) 0 mm HC (38 C) 40 mm CONTROL VALVE PDI -PRESS. DIFF. INDICATOR DISPLAY SYMBOLS
SANITARY NOTE 5

A29-2"-SWS-00003-12CS3U4

A29-2"-SWS-00004-12CS3U4
WITH POSITIONER PDIC -PRESSURE DIFFERENTIAL
WASTEWATER FROM INDICATOR CONTROLLER
(DCS) DISTRIBUTED CONTROL
S SYSTEM, OPERATOR ACCESSIBLE
EPC 5 SOLENOID VALVE PDIS -PRESSURE DIFFERENTIAL IN CONTROL ROOM
INDICATOR SWITCH (DCS) DISTRIBUTED CONTROL
A29

LI HHH PDT -PRESS. DIFF. TRANSMITTER


VALVE NORMALLY SYSTEM, OPERATOR INACCESSIBLE
PDTD -PRESS. DIFF. TRANSDUCER IN CONTROL ROOM
0760 LL CLOSED
PG -PRESSURE GAGE

NI (38 C) 0 mm

NI (38 C) 0 mm
PI (DCS) DISTRIBUTED CONTROL
-PRESSURE INDICATOR
SYSTEM, OPERATOR INACCESSIBLE
A29-4"-VG- -12CG0U

PIC -PRESS. INDICATOR CONTROLLER


IN FIELD
NOTE 15 NOTE 15 2"
PR -PRESSURE RECORDER
2" PS -PRESSURE SWITCH
A29 FF A29 FF A29 FF PT -PRESSURE TRANSMITTER DISTRIBUTED CONTROL
LT LT LT NC NC PX -PRESSURE POINT INTERCONNECTING LOGIC
0760 0761A 0761B PY -PRESS. COMPUTATION MOD. CONTROLLER WITH BINARY
GWR GWR GWR PZV -PRESSURE RELIEF VALVE OR SEQUENTIAL FUNCTIONS
RTD -RESIST. TEMP. DETECTOR
(PLC) PROGRAMMABLE LOGIC
RS

RS
MH SI -SPEED INDICATOR
CONTROLLER, NORMALLY
NOTE 11 NOTE 11 SS -SPEED SWITCH INACCESSIBLE OR BEHIND THE
EL. 100000.00 TC -TEMP. CONTROLLER PANEL DEVICE OR FUNCTIONS

I L3 L1 L2 V1 R1 2" D1 H1 M1 R2 2" D2 H2 TV -TEMP. CONTROL VALVE (PLC) PROGRAMMABLE LOGIC


4" 4" 4" 4" 3" HOLD 24" 3" HOLD TCV -TEMP. CONTROL VALVE CONTROLLER FUNCTION,
(SELF-ACTUATED) CAN BE NORMALLY
A29-2"-SWS-00008-12FE0U9

A29-2"-SWS-00009-12FE0U9
A29-3"-SWS-00007-12FE0U9

A29-3"-SWS-00006-12FE0U9
TE -TEMP. ELEMENT DISPLAYED ON CRT
NI (38 C) 0 mm

TSO -TIGHT SHUT OFF TG -THERMOMETER LOCAL DCS OR AUXILIARY


S.C. - SAMPLE CONN. THS -TEMP. HAND SWITCH DCS LOCATION NORMALLY
NI (38 C) 0 mm

NI (38 C) 0 mm

NI (38 C) 0 mm

NI (38 C) 0 mm
TI -TEMP. INDICATOR ACCESSIBLE TO OPERATOR
S -DRAIN TO
TR -TEMP. RECORDER
PRESSURE SEWER
HHHLL=1000.0 mm TS -TEMP. SWITCH
(PLC) PROGRAMMABLE LOGIC
CONTROLLER I/O POINT
HHLL=900.0 mm OWS -OILY WATER SEWER TT -TEMP. TRANSMITTER NORMALLY INACCESSIBLE
HLL=800.0 mm
LLL=500.0 mm M M D -DRAIN TTD -TEMP. TRANSDUCER BY OPERATOR
V -VENT TW -THERMOWELL
NOTE 23 LLLL=400.0 mm
NOTE 2
NOTE 21
FROM GRAVITY REFERENCE DRAWINGS
SANITARY UNDERGROUND
BELOW GRADE
C1
A29-U-0001
A29-U-0001 LETTER IDENTIFICATION OF LINES AE-036204
COLLECTION SYSTEM GRAVITY FLOW 8"
PIPING SYMBOLS AB-036227
NOTE 3 NOTE 3 EQUIPMENT SYMBOLS AB-036305
MANHOLE 0.1% A29-G-0001A A29-G-0001B
SLOPE A29-G-0001A A29-G-0001B INSTRUMENT SYMBOLS AC-036950
PIPING LAYOUT INDEX
PLOT PLAN
PROCESS FLOW DIAGRAM
HYDROSTATIC TEST DIAGRAM
DRAWING CONTROL FOR J.O.
INSTRUMENT INSTALLATION SCHEDULES
Jazan - \A29\A29\VA-718610-001.pid - 8/29/2016 4:26:47 PM - [JE07]

A29-G-0001A / B
SANITARY LIFT PUMP 10 REVISION VALIDATION
CAPACITY: 7.6 m^3/hr THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
HEAD: 48.5 m REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
S.G.: 0.990
DRIVER POWER: 17.20 kW 10-01525-0004-029
MOC: HFB1
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
TRIM: 12CS3U4 (DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE
Y.GAO B.ANDERS
06/29/16 06/29/16

REV.NO. DATE REVISION DESCRIPTION


00 06/29/16 ISSUED FOR CONSTRUCTION

JOB ORDER/EWO NO.


THIS REVISION IS NOT TO BE USED FOR
10-01525-0004 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY


DRAWING TYPE
PIPING & INSTRUMENTATION DIAGRAM PID
SANITARY LIFT STATION 10
ELECTRICAL POWER DISTRIBUTION & INT
JAZAN SAUDI ARABIA
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

A29 A VA-718610 001 00


Saudi Aramco 5994 ENG. (09/03)

RESTRICTED SMART CADD-05