Professional Documents
Culture Documents
3M - TP-SSTPL (300-T16)
Environment: Wind=15 mph, AAMT=41F, AAT=90F
Damper Summary
CAUTION: Damper Recommendation applies for specified ACA dampers only. If alternative type or
different manufacturer dampers are applied instead it is possible that damage will occur on the
conductor and/or the accessories.
Certain information such as the data, opinions or recommendations set forth herein given by ACA
representatives or by any software licensed by ACA, is intended solely as a general guide and only applies to
ACA products. Each installation of overhead electrical conductor, underground electrical conductor, and/or
conductor accessories involves special conditions creating problems that require individual solutions.
Therefore, the recipient of this information has the sole responsibility in connection with the use of the
information. ACA does not assume any liability in connection with such information.
Span Information Tensions Guard Total Dmpr Qty Protection Ranges (ft)
Item Ruling Max. # of Phase Level Level Level
Bundle Initial Final Type 1704-6 1704-9
(ft) (ft) Spans Circuit 0 1 2
225- 690-
1 138 1 2 3 2104 1646 NONE 0 0 0-225
690 690
295- 640-
2 128 1 2 3 1905 1441 NONE 0 0 0-295
640 640
220- 860-
223 1 2 3 2113 1670 NONE 12 0 0-220
860 1115
220- 855-
591 1 2 3 2120 1845 NONE 12 0 0-220
855 1710
215- 850-
226 1 2 3 2133 1692 NONE 12 0 0-215
850 1130
220- 860-
463 1 2 3 2113 1786 NONE 12 0 0-220
860 1720
215- 850-
810 1 2 3 2129 1925 NONE 12 0 0-215
850 1700
215- 850-
627 1 2 3 2127 1864 NONE 12 0 0-215
850 1700
Protection
Span Information Tensions Guard Total Dmpr Qty
Ranges (ft)
Item
Ruling Max. # of Phase Level Level Level
Bundle Initial Final Type 1704-6 1704-9
(ft) (ft) Spans Circuit 0 1 2
0- 325- 845-
656.3 778 4 2 3 2140 1890 AGS/54in 48 0
325 845 1690
1st Damper From
9 Suspension = 2 in
Damper(s) on Span Side: One from end of rods
2nd Damper = 21
in
0- 215- 850-
600 1 2 3 2127 1857 NONE 12 0
215 850 1700
0- 330- 850-
647.2 745 2 2 3 2132 1876 AGS/54in 24 0
330 850 1700
1st Damper From
11 Suspension = 2 in
Damper(s) on Span Side: One from end of rods
2nd Damper = 21
in
0- 325- 845-
879.7 1063 3 2 3 2140 1953 AGS/54in 48 0
325 845 1690
1st Damper From
Suspension = 2 in
12 Damper(s) from end of rods
on Span 1st Damper From
Side: Both Deadend = 28 in
2nd Damper = 22
in
0- 330- 855-
462.4 482 2 2 3 2118 1792 AGS/54in 24 0
330 855 1710
1st Damper From
13 Suspension = 2 in
Damper(s) on Span Side: One from end of rods
2nd Damper = 21
in
0- 330- 855-
563.3 607 3 2 3 2123 1836 AGS/54in 36 0
330 855 1710
1st Damper From
14 Suspension = 2 in
Damper(s) on Span Side: One from end of rods
2nd Damper = 21
in
Protection
Span Information Tensions Guard Total Dmpr Qty
Ranges (ft)
Item
Ruling Max. # of Phase Level Level Level
Bundle Initial Final Type 1704-6 1704-9
(ft) (ft) Spans Circuit 0 1 2
0- 330- 855-
585.6 705 5 2 3 2123 1848 AGS/54in 60 0
330 855 1710
1st Damper From
15 Suspension = 2 in
Damper(s) on Span Side: One from end of rods
2nd Damper = 21
in
0- 220- 855-
564 1 2 3 2123 1836 NONE 12 0
220 855 1710
0- 215- 850-
807 1 2 3 2129 1924 NONE 12 0
215 850 1700
0- 330- 850-
676.3 807 3 2 3 2133 1891 AGS/54in 36 0
330 850 1700
1st Damper From
18 Suspension = 2 in
Damper(s) on Span Side: One from end of rods
2nd Damper = 21
in
0- 220- 855-
604 1 2 3 2122 1852 NONE 12 0
220 855 1710
0- 220- 860-
499 1 2 3 2114 1802 NONE 12 0
220 860 1720
Protection
Span Information Tensions Guard Total Dmpr Qty
Ranges (ft)
Item
Ruling Max. # of Phase Level Level Level
Bundle Initial Final Type 1704-6 1704-9
(ft) (ft) Spans Circuit 0 1 2
0- 220- 855-
509 1 2 3 2119 1810 NONE 12 0
220 855 1710
0- 215- 850-
817 1 2 3 2133 1929 NONE 12 0
215 850 1700
0- 330- 850-
711.3 827 4 2 3 2131 1897 AGS/54in 48 0
330 850 1700
1st Damper From
23 Suspension = 2 in
Damper(s) on Span Side: One from end of rods
2nd Damper = 21
in
0- 330- 850-
723.1 745 2 2 3 2126 1895 AGS/54in 24 0
330 850 1700
1st Damper From
24 Suspension = 2 in
Damper(s) on Span Side: One from end of rods
2nd Damper = 21
in
0- 215- 850-
25 184 1 2 3 2128 1667 NONE 0 0
215 850 920
0- 225- 860-
236 1 2 3 2108 1673 NONE 12 0
225 860 1180
0- 225- 865-
27 194 1 2 3 2097 1648 NONE 0 0
225 865 970
0- 220- 850-
587 1 2 3 2126 1850 NONE 12 0
220 850 1700
Span Information Tensions Guard Total Dmpr Qty Protection Ranges (ft)
Item Ruling Max. # of Phase Level Level Level
Bundle Initial Final Type 1704-6 1704-9
(ft) (ft) Spans Circuit 0 1 2
220- 860-
262 1 2 3 2115 1696 NONE 12 0 0-220
860 1310
Notes: