You are on page 1of 4

Hydronic Accessories

Hydraulic Separator
Tacos Hydro-Sep Hydraulic Separators are compact economical units that allow fast
and efficient installation of primary/secondary piping for many different boilers. Installing
this unique Hydraulic Separator offers the additional advantages of assisting in the
removal of unwanted air and dirt particles, preventing their damaging affects on system
components. It is especially suitable for todays smaller boilers that tend to have a much
higher flow resistance.

Taco Catalog #100-76 Effective Date: 10/05/09


Supersedes: 5/30/09 Printed in USA
Applications

Hydraulic Separators save


The Taco Hydro-Sep is the ideal tasks the flow rates of these differ- If this decoupler is installed correct-
piping companion for todays wide- ent circuits must be independent ly then the flow in one circuit does
spread usage of Primary Secondary of each other, i.e., the flow in one not affect the flow in the other cir-
piping. By installing the efficient and circuit must not affect the flow in cuit. The flow in each circuit is only
compact Taco Hydro-Sep piping another circuit. This is known as a function of the pump head in its
errors can be prevented, installation decoupling or hydraulic separation. circuit. This flow is not influenced by
time reduced and valuable mechan- the pumps in the opposing circuit
To decouple or hydraulically sepa-
ical room space saved. On systems being in series with the pumps in
rate one circuit from another, an
using boilers with higher pressure its circuit.
area of very low pressure drop
drops the Hydraulic Separator
must be created in the common There are 3 combinations of flow
allows for the possible use of
piping between the two circuits. and temperature possible with
smaller zone circulators because it
This pipe is sometimes referred Tacos Hydraulic Separator depending
is not required to overcome the
to as the decoupler or hydraulic on the relationship of the primary
additional head loss associated with
separator. This decoupler must be and secondary flow rates.
the boiler. At the same time the
as short (tee to tee) as possible to
boiler pump can maintain constant Figure 2 shows the relationship
insure that the path of least resis-
flow through the boiler. with the primary (Q primary) and
tance for the flow of water of one
secondary (Q secondary) flows
Primary Secondary circuit is through the decoupler
equal.
Pumping and not through the opposing con-
nected circuit. In this instance the secondary cir-
Primary secondary pumping is used
cuit supply temperature is equal
extensively in HVAC systems to This decoupler or common pipe is
to the primary circuit supply tem-
hydraulically isolate different circuits shown in Figure 1 in red.
perature. For example a building
in the same hydronic system.

This can be useful to save energy


by shutting off or reducing the Decoupler
speed of pumps in areas of the sys-
tem with no or low loads. This can Secondary
Circuit
also be useful to increase comfort
by supplying areas of a system with Secondary 2 Tees
Circuit Pump
different water temperatures or dif-
ferent flow rates.

To successfully accomplish these Primary Decoupler (in red)


Circuit as short as possible

Figure 1
Applications

e energy and system wear.


Figure 4 shows the relationship if
the primary flow (Q primary) is
Primary Secondary Primary Secondary
less than the secondary flow (Q
secondary).
Q1 Q2 Q1 Q2
In this instance the secondary cir- T1 T2
T1 T2
cuit supply temperature is less than
Q1 =Q4 Q2 =Q3 Q1 =Q4 Q2 =Q3
the primary circuit temperature.
T4 T3 T4 T3
For example a building secondary
Q4 Q3 Q4 Q3
circuit supply water temperature
will be lower than a boiler and
higher then the chiller primary cir-
cuit supply water temperature. This Q Primary < Q Secondary
Q Primary = Q Secondary is because some of the secondary (Q3 Q1) T3 + (Q1) T1
flow mixes with the primary flow T2 =
Q3
and dilutes the supply water tem-
Figure 2 Figure 4
perature to the secondary circuit.
secondary circuit supply water This can cause system performance
temperature will be the same as a problems, especially in chilled water
boiler or chiller primary circuit sup- Primary Secondary systems, since the building second-
ply water temperature. ary supply water temperature
Q1 Q2 cannot be maintained at the chiller
Figure 3 shows the relationship if
T1 T2 primary supply water temperature.
the primary flow (Q primary) is
greater than the secondary flow Q1 =Q4 Q2 =Q3 This can result from staging off of
(Q secondary). T4 T3 multiple boiler or chillers while
Q4 Q3 maintaining a constant volume
In this instance the secondary cir-
building secondary circuit flow rate.
cuit supply temperature is the same
as the primary circuit temperature. This application can also be used
For example a building secondary Q Primary > Q Secondary for low mass boilers that have flow
circuit supply water temperature (Q1 Q2) T1 + (Q3) T3 limits below the building secondary
T4 =
will be the same as a boiler or Q1 flow rate. In this application system
chiller primary circuit supply water water is bypassed around the boiler
temperature. Figure 3 to limit the boiler flow to manufac-
turers maximum flows.
Submittal Data # 101-137 Effective: 10/05/09
Submittal Data Information Supersedes: 05/30/09
Hydro-Sep
Features
Small space saving design
Rugged all copper construction
B

Suitable for use with oxygenated


water heating systems A J

F
Blow down port for sediment removal K

High quality, industry standard


automatic Taco Hy-Vent D J

Wall mounting brackets G

Materials of Construction E

Body .................................. Copper C

Drain valve body.............. Brass


Air vent body.................... Brass Model Number HSEP100-1 Model Number HSEP125-1
Engineered plastics A 18-1/8 21-1/8
BUNA N B 15-1/2 22-3/16
Teflon C 3-1/2 4
D 1.124 - 1.127 OD x .050 Wall 1.375 - 1.377 OD x .055 Wall
Specifications E 9-1/16 10-9/16
F 12-1/4 13-1/4
Connections...................... 1 and 1-1/4
Copper Sweat G 3 4
H 4-1/2 5-1/2
Max. Flow........................... 1 (11 GPM) J 1-1/4 2-3/4
1-1/4 (15 GPM) K 3 4
Media.................................. Water or Glycol Dimensions provided for reference only and are subject to change
up to 50%
Max. Pressure .................. 350 PSIG
Max. Temperature............. 240 F

Pressure/Temperature Chart Typical Installation


PRESSURE / TEMPERATURE RATINGS
TACO
350 4900 SERIES
AIR SEPARATOR
325
TACO Zone 1 Zone 2 Zone 3
300 CIRCULATOR
275
250
TACO ZONE ZONE ZONE
225
PSIG

CIRCULATOR VALVE VALVE VALVE


200
EXPANSION
175 TANK
150
125
100 HYDRO-SEP

75 BOILER
100 125 150 175 200 225 250
TEMPERATURE F

Taco Inc., 1160 Cranston Street. Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com

You might also like