M60-RTU Display for Modbus RTU


Display for Modbus RTU protocol with 6 digits and 14mm digit height in
red or green color. Standard 96x48mm (1/8 DIN) size, for panel mount.
Configurable 16bit or 32bit registers. Reading range from 999999 to
-199999. Decimal point. Two configurable working modes with different
alarm controls: Full slave and Process slave. Watchdog function, Bus
activity function, Fast access menu, On power up function. Universal
high and low AC and DC power options. Optional retransmission and
control modules with relays, analog outputs and serial outputs.

Technical specifications
Digits 6 Order reference
Reading 999999/-199999 (with 32bit registers)
32767/-32767 (with 16bit registers) Model Power Option1 Option2 Option3 Others
Decimal point X.X.X.X.X.X
Led color red or green M60 - RTU - H - - - -
Digit height 14 mm
Protocol Modbus RTU -H (85-265Vac/dc) - R1 (1 relay) - NBT (no keypad)
Bus RS-485 -L (11/60Vdc, - AO (analog output) - 65 (front IP65)
Function Modbus RTU slave 24Vac, 48Vac) - RTU (Modbus RTU) - G (green led)
Speed from 38.400bps to 600bps (19.200bps by default) - S4 (RS-485)
Data format 8n1, 8e1, 8o1, 8n2 - S2 (RS-232)
Address 1 to 247 - (empty)
Bus terminators not included
Watchdog configurable from 1 to 120 seconds
* Relays R1 with contacts (NC / NO / Common), max. 250Vac 8A
Functions supported 6 - Write single register * Special options with 4 and 6 relays.
16 - Write multiple registers
3 - Read registers * Analog outputs and serial outputs, isolated.
5 - Write single coil
15 - Write multiple coils
1 - Read coils
Power H
Power L
85 to 265Vac/dc (isolated 2500Veff)
11 to 60Vdc and 24/48Vac (isolated 1500Veff) Functions included
Retransmission and control options relays, analog output, serial communications, ...
Consumption <1.5W (meter only) Full slave / Process slave Full slave allows for remote control of the alarms
by writing to registers or coils. Process slave allows
<4.0W (meter with options)
for local control of alarms, based on local alarm con-
Protection IP54 standard (optional IP65)
figuration and actual display value.
Connections plug-in screw terminal
Weight <150grams Watchdog function generates error after predefined time without com-
Mounting panel munication with the master. Alarm can be linked to
Front size 96x48mm the watchdog function.
Panel cut-out 92x44mm Bus activity function detects electrical activity on the bus. Useful for
Deep 91mm (including terminals) troubleshooting.
Operating temperature 0 to 50C
Fast access menu specific menu entries can be associated to key UP

Dimensions and connections (5), such as display address, or alarm setpoints.


On power-up function configurable delay at start-up, and configurable
state of alarms at start-up.
Brightness 5 levels of brightness intensity.

48mm Password blocks access to configuration menu.

Option1 Option2
91mm 96mm
(including terminals)
Option3

Detail of the plug-in screw


terminal. The instrument is
provided will all male and
+ h
GN
A D
B

-N
Ea tra

Ph
eu
rt l

female terminals needed.


as
e

FEMA ELECTRNICA, S.A. Manufacturing for Industrial Automation . www.fema.es . info@fema.es


Altimira 14, P.I. Santiga . E08210 Barber del Valls . Barcelona . Spain . T. +34 93.729.6004 . F. +34 93.729.6003
www.fema.es Series M
MANUFACTURING FOR INDUSTRIAL AUTOMATION
PANEL METERS . SIGNAL CONVERTERS . LARGE DISPLAYS

Application example Other options and accessories


Factory signals are concentrated into a PLC who receives and manages factory pro- Options for M Series of instruments and mounting accessories for 96x48mm hous-
cesses. Critical information can be numerically communicated to local operators via ings of M Series.
Modbus RTU repeaters M60-RTU. Local displayed values are of valuable help to the
operator, who can review in a single and fast visual check the main critical param-
eters of the system.

Modbus RTU

NBT - Without front keypad WME - Wall mount housing

Relay1

Relay2
G - Green leds DRA - DIN rail mount adapter

Alarms example
Process alarms with one setpoint, configurable deactivation hysteresis, indepen-
dent activation and deactivation delays.
Reading

65 - IP65 front sealing THM - Benchtop housing


setpoint
hysteresis

Time

on Maximum type alarm, with no


hysteresis and no delays
off
Time KIP - Protector IP65 KA96 - 96x96mm adapter

on Maximum type alarm, with


hysteresis and delays
off
activation deactivation Time

on
delay delay

Minimum type alarm, with


Web documentation
no hysteresis and no delays
off M60-RTU users manual www.fema.es/docs/3690_M60-RTU_manual_i.pdf
Time
M60-RTU datasheet www.fema.es/docs/3691_M60-RTU_datasheet_i.pdf

Double setpoint alarms


Process alarms with double setpoint, configurable as maximum or minimum, allow
to create activation or deactivation windows.. Reading distances
Reading
Reading distances and series of product for panel meters with digit height starting
at 10mm and up to 100mm.
Setpoint 2

Setpoint 1
Digit height (mm)
Reading distance 4m 5m 8m 20m 40m
Time
Series L35 Series M Series K BDF-24 BDF-44
Minimum type alarm, with Series S
on double setpoint, with no
Doc.3691r01

hysteresis and no delays


off
Time

FEMA ELECTRNICA, S.A. Manufacturing for Industrial Automation . www.fema.es . info@fema.es


Altimira 14, P.I. Santiga . E08210 Barber del Valls . Barcelona . Spain . T. +34 93.729.6004 . F. +34 93.729.6003