Mounting of Relay Metrosils Table 1 Identification of Metrosil Type for Relays on 1A CTs
The method of mounting Metrosil relay Maximum Internal Secondary Fault Current
units will depend on local conditions and Maximum Relay 50Arms
available space. To avoid overheating, Setting Voltage
the following general recommendations Vrms
Single Pole Relay Triple Pole Relay
may be of help:-
125
Multiple disc Metrosil units should be
mounted with the M12 stud and 175 600-A/S1/256 600-A/S3/I/802
brackets horizontal so that the 185
orientation of the discs is vertical
There should be approximately 40mm 300
600-A/S1/1088 600-A/S3/I/1195
clearance all round the Metrosil unit(s) 325
and live metalwork
Where many Metrosils are installed, 400 600-A/S1/6315 600-A/S3/I/6324
avoid locating them directly above
each other
Free airflow over the Metrosil must be
available
Table 2 Leakage Current, Protection Voltage and Short Time Currents for 1A Relay Metrosils
125 19
600-A/S1/256
175 73 405/495 1435 45 30 22 200
600-A/S3/I/802
185 90
600-A/S1/1088 300 30
810/990 2870 39 30 17 350
600-A/S3/I/1195 325 50
600-A/S1/6315
400 55 990/1210 3500* 46 26 19 425
600-A/S3/I/6324
*600A-A/S1/6315 will hold to 3400Vpk at peak of 46Arms and 3000Vpk at peak of 30Arms
All properties quoted in this table are typical values and do not constitute a specification
Metrosils for High Impedance Relays
July 2014 Page 3 of 4
Table 3 Identification of Metrosil Type for Relays on 5A CTs Definition of Metrosil nomenclature
Maximum Internal Secondary Fault Current Arms 600A reference to the disc diameter
Maximum Relay S1 single Metrosil disc units
Setting Voltage S2 2 Metrosil disc units
50 100 150
S3 3 Metrosil disc units
Vrms
I discs electrically insulated
200 600A/S1/1213 600A/S2/P/1217 600A/S3/P/1219 P discs connected in parallel
250 600A/S3/P/1220
600A/S1/1214 600A/S2/P/1215
275 600A/S3/P/1221
Table 4 Leakage Current, Protection Voltage and Short Time Currents for 5A Relay Metrosils
250 40
600A/S1/1214 670/800 2120 50 25 18 290
275 50
250 75
600-A/S2/P/1215 570/670 2120 90 50 35 290
275 100
All properties quoted in this table are typical values and do not constitute a specification