OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

OMICRON PTL

Protection Test Template PTT

Feeder Protection

AREVA P132 P139

User Manual

V1.000

OMICRON electronics GmbH 1/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

Contents

1 General information ..................................................................................................................................3


2 Quick start information.............................................................................................................................4
3 Using the template ....................................................................................................................................5
3.1 Test Object ...........................................................................................................................................5
3.2 Hardware Configuration .......................................................................................................................5
4 Requirements ............................................................................................................................................8
5 Functional range .......................................................................................................................................8
6 Not supported functions ..........................................................................................................................8
7 OMICRON philosophy...............................................................................................................................9
8 Template structure ....................................................................................................................................9
8.1 Wiring test .......................................................................................................................................... 10
8.2 Initial test ........................................................................................................................................... 10
8.3 Pick-up and drop-off of the phase overcurrent .................................................................................. 10
8.4 Overcurrent trip time tests ................................................................................................................. 11
8.5 Trip/warning time of the thermal overload ......................................................................................... 11
8.6 Pick-up and drop-off of the residual overcurrent protection .............................................................. 12
8.7 Residual protection trip times ............................................................................................................ 12
8.8 Pick-up and drop-off of the negative sequence protection ................................................................ 12
8.9 Trip time of the negative sequence protection .................................................................................. 12
8.10 Directional tests ............................................................................................................................... 12
8.11 CB trip time ...................................................................................................................................... 13

OMICRON electronics GmbH 2/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

1 General information
The P132 P139 feeder protection test template is used for testing protection functions of the AREVA P132
and P139 relays dedicated to feeders. This template comprehends various modules for testing the most
important protection functions. It is designed and configured for use with the AREVA P132 P139 XRIO
converter which is included in this template. For more information about the converter, see the user
manual of the AREVA P132 P139 XRIO Converter.

Note: The template is designed and built for the applications of the Test Universe 2.30 software or higher.

The template has been tested on following relay:


AREVA P1323394540NU00G0A
Ser No. 3286650/11/08

Annotations:
Although this template is developed particularly for the relays specified above, it can also be used
for testing similar protection relays of the P132 or P139 line.
The OMICRON PTTs are designed for an experienced OMICRON user. The use of the Test
Universe software, the XRIO technology with LinkToXRIO should be familiar (see
http://www.omicron.at/products/training/ for training information).

OMICRON electronics GmbH 3/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

2 Quick start information


To test with the P132 P139 feeder protection template:
1. Double click the file AREVA P132 P139.occ to start the template-based procedure.
2. Open the global test object.
3. Load (Import) the latest XRIO converter version for the P132 P139.
4. Enter your relay settings, and then click OK.

Figure 1: Relay settings in the XRIO converter

5. Open the Hardware Configuration and enter all necessary information for:
a. General
b. Analog Outputs
c. Binary / Analog Inputs
d. Binary Outputs
e. DC Analog Inputs
6. Follow the wiring instructions.
7. Start testing.
8. Evaluate and archive the results.

OMICRON electronics GmbH 4/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

3 Using the template


The P132 P139 feeder protection test template is divided into three object groups: test object, hardware
configuration and the list of OMICRON test modules used for testing the following relay's protection
functions:
DTOC (definite time overcurrent)
IDMT1 (inverse time overcurrent)
IDMT2 (inverse time overcurrent)
SCDD (short circuit direction determination)
THERM (thermal overload protection)

3.1 Test Object


The test object already contains the AREVA P132 P139 XRIO converter which includes all setting
parameters of the modeled P132 P139 protection functions. The setting parameters are built as an image
of the MiCOM S1 Studio software.

Note: The XRIO converter doesnt support the Operating curves type IDG.

For more information, see the AREVA P132 P139 XRIO converter user manual.

3.2 Hardware Configuration


The hardware configuration offers various configuration options for voltage and current outputs. For
testing the AREVA P132 P139 relay with the P132 P139 feeder protection test template, the standard
configuration as shown in the following figure is required.

OMICRON electronics GmbH 5/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

Figure 2: Configuration of the voltage and current outputs

Note: If higher currents are needed for testing (e.g. relays with Inom = 5 A), the current output
configuration can be adapted.

In the Analog Outputs dialog box, the voltage and current outputs have to be routed to the name
variables. The figure 3 shows the Analog Outputs configuration.

Figure 3: Analog Outputs configuration

The current output A is used for the phase currents (IA, IB and IC). Only the first channel from the current
output B is used for the IN CT (residual overcurrent).

The following figure shows the Binary / Analog Inputs configuration.

OMICRON electronics GmbH 6/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

Figure 4: Binary / Analog Inputs configuration

Note: The binary inputs are preset to potential free. Change these predefined settings to the values
needed at the test site.

Route the signals configured in the Binary / Analog Inputs dialog as shown in the next figure:

Note: The circuit breaker auxiliary contact (52a) is required for the trip test with the circuit breaker. If the
circuit breaker auxiliary contact cannot be connected to the binary input, the trip test with the circuit
breaker cannot be performed.

Connection for
AREVA
P132 or P139
X041-1
X041-2
X041-3
X041-4

X041-5
X041-6
X042-2/4/6
X042-3
X042-5
X042-1

CB Aux.(52a)
Thermal Warning
General Start
General Trip
X042-7

X042-8

Figure 5: Connecting the CMC 356 to the P132 or P139 relay

OMICRON electronics GmbH 7/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

4 Requirements
To use this template, you must have a valid test license for the OMICRON Test Universe 2.30 or higher
and the following test modules:
Control Center
Quick CMC
Ramping
State Sequencer
Overcurrent

To use this template, a CMC with six current outputs is necessary. The development tests were
performed with a CMC256plus.

5 Functional range
The test modules are grouped according to the tested protection function. The P132 P139 feeder
protection test template includes OMICRON test modules for the following tests:
Pick-up and drop-off of:
o Phase overcurrent protection
o Calculated residual overcurrent protection
o Measured residual overcurrent protection
o Negative sequence overcurrent protection
Trip time of:
o Phase overcurrent protection forward and reverse
o Calculated residual overcurrent protection forward and reverse
o Measured residual overcurrent protection forward and reverse
o Negative sequence overcurrent protection
o Thermal overload protection
Directional element test of :
o Phase overcurrent protection forward and reverse
o Calculated residual protection forward and reverse
o Measured residual overcurrent protection forward and reverse
Trip time with circuit breaker contacts

The test modules are activated and deactivated automatically according to the corresponding protection
function status in the test object.

6 Not supported functions


The following functions of the P132 P139 relay are not supported by the P132 P139 feeder protection test
template:
SOTF (switch on to fault)
ARC (auto-reclosure)
TGFD (transient ground fault detection)
GFDSS (ground fault direction determination using steady state values)
MP (motor protection)
V<> (under and overvoltage)
f<> (under and overfrequency)
P<> (power directional protection)

OMICRON electronics GmbH 8/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

CBF (circuit breaker failure)


I2>

The P132 P139 feeder protection test template can be extended by the user to allow testing the protection
functions currently not supported. It is possible to add any test module to the existing templates. The
additional test modules will not affect the template. The LinkToXRIO option can also be used to activate or
deactivate automatically the new test module.

7 OMICRON philosophy
The P132 P139 feeder protection test template includes the pick-up and trip time value tests which are
performed in a standardized way. For the pick-up and drop-off value test, the setting value is evaluated by
a ramp increasing the variable under test until the pick-up value is reached. The test of drop-off values is
done in a similar way by decreasing the tested value until the drop-off value is reached.
Trip times are tested by simulating a fault which exceeds the pick-up value and the specific tolerances.
This results in a trip command of the tested protection function. The time between the simulation of the
fault and the reception of the trip signal is measured and evaluated.

Note: Do not only rely on the automatic assessment of test points in the test modules. Check the
plausibility of all test results manually to gain maximum security that all test results are reliable.

8 Template structure
The structure of the P132 P139 feeder protection test template is shown below.

Figure 6: P132 P139 feeder protection test template

Note: For the trip time tests using the OMICRON Overcurrent module:
a. Test shots are previously defined. Check if these points are suitable and adapt them manually
if necessary;
b. In the Fault tab, Fault Settings area, the Absolute max. time is preset to 1.0ks in case the first
stage is an Inverse curve. If testing with bigger trip times is required, remove the LinkToXRIO
and adjust this value. In case all the stages are definite time ones, the Absolute max. time will
be set automatically.

OMICRON electronics GmbH 9/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

8.1 Wiring test


The wiring test is used to check the connections between the CMC test set and the relay. Therefore the
OMICRON QuickCMC test module is used to inject voltage and current values. The values of voltage and
current can be freely defined by the user. If all connections are correct, the same values can be read out
of the relay and the test can be manually assessed.

Please note that the values of the residual current and voltage are scaled with the phase CT and phase
VT ratios.

The test has to be started by pressing the F5-Button and after reading the values out of the relay this
button has to be pressed again. By using the F10-Button the test can be rated as "passed" or "failed". You
have to leave the QuickCMC module by hand to return to the OCC-file.

8.2 Initial test


The initial test is used to check whether the relay trips when a fault condition occurs. The OMICRON State
Sequencer test module is used for this test. A fault simulating an asymmetrical high current condition and
an asymmetrical voltage condition should cause tripping of basic protection functions in the relay.

8.3 Pick-up and drop-off of the phase overcurrent


For testing the pick-up and drop-off values, the OMICRON Ramping test module is used. This module
allows testing the pick-up and drop-off of the overcurrent stage with the lowest pick-up value. The lowest
pick-up value is taken from the all set phase overcurrent stages.

Figure 7: Pick-up and drop-off phase overcurrent ramps

OMICRON electronics GmbH 10/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

8.4 Overcurrent trip time tests


For testing the trip times of overcurrent stages, the OMICRON Overcurrent test module is used. The test
is performed with a three-phase fault The resulting characteristic for all overcurrent stages in each
direction is drawn and the test shots are set at 1.1 IPickup for all active stages and additionally at
0.9 IPickup for stages 2 and 3. The trip time for each test point is measured and evaluated. The test
points can be adapted if necessary.
If a phase overcurrent stage is active in the non-directional mode, it will be visible in both the forward and
reverse test modules. However, if all stages are selected as non-directional, only the forward test module
is activated
Note: Only one of the stages can have an inverse definite minimum time (IDMT) characteristic. The other
two stages must have a definite time characteristic.
Note: The thermal overload protection may interfere overcurrent trip time tests. To avoid interferences,
this function needs to be blocked before running the test.

Figure 8: Trip time test for phase overcurrent stages

8.5 Trip/warning time of the thermal overload


The thermal overload function of the relay is tested with the OMICRON Overcurrent test module by
simulating a symmetrical load. The test shot is set to 1.6Iref. The test shot can be adjusted manually if
required. Please mind the Start factor (072.180) when placing your shots.
The thermal memory of the function should be reset before beginning of the test. For detailed information,
see the relay documentation.

Note: If one of the thermal overload stages tests are not required or cannot be tested (e.g. the warning
signal is not available) remove the link and uncheck the test module.
Note: The phase overcurrent protection stages may interfere with this test. To avoid any interference, the
overcurrent function needs to be blocked.

OMICRON electronics GmbH 11/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

8.6 Pick-up and drop-off of the residual overcurrent protection


For testing the pick-up and drop-off values, the OMICRON Ramping test module is used. The lowest pick-
up value of stages set forward, reverse or no directional is tested. Current magnitude is ramped until pick-
up is reached and the type of injection is dependent on the method of evaluation of residual current:
IN calculated - current is injected to relays phase CT inputs as 3I0 condition.
IN measured current is injected to relay neutral CT input.

8.7 Residual protection trip times


For testing the trip time of the directional/non-directional residual overcurrent stages, the OMICRON
Overcurrent test module is used. Tests for elements using measured and calculated neutral current
evaluation are divided into modules, covering forward overcurrent stages and reverse stages with
separate modules activated depending on the type of neutral voltage evaluation. The residual test voltage
and the current angle are automatically calculated and linked in both test modules.

If a residual overcurrent stage is active in the non-directional mode, it will be visible in both the forward
and reverse test modules. However, if all stages are selected as non-directional, only the forward test
module is activated.
The resulting characteristic for all active stages for each operating mode and direction is drawn and the
test shots are set at 1.1 IPickup for all active stages and additionally at 0.9 IPickup for stages 2 and 3.
The trip time for each test point is measured and evaluated. Test points can be adapted if necessary.

Note: Only one of the stages in each direction can have an inverse definite minimum time (IDMT)
characteristic. The others must have a definite time characteristic.

8.8 Pick-up and drop-off of the negative sequence protection


For testing the pick-up and drop-off values of the negative sequence protection, the OMICRON Ramping
test module is used. The lowest pick-up value of negative sequence overcurrent stages is being tested.
For these tests an anti-symmetrical three-phase fault and two ramp states are generated. The pick-up
value is tested with the first ramp, the drop-off value with the second ramp.

8.9 Trip time of the negative sequence protection


The trip times of the two negative sequence stages are tested with the OMICRON Overcurrent test
module. The resulting characteristic for all active negative sequence overcurrent stages is drawn and the
test shots are set at 1.1 IPickup for all active stages and additionally at 0.9 IPickup for stages 2 and 3.
The trip time for each test point is measured and evaluated. Test points can be adapted if necessary.

Note: Only one of the stages can have an inverse definite minimum time (IDMT) characteristic. The other
stage must have a definite time characteristic.

8.10 Directional tests


The directional minimum and maximum angles are tested with the OMICRON Ramping test module. The
directional angle is tested with two ramp states per test module. The first ramp state tests the minimum
directional angle and the second ramp state tests the maximum directional angle. An intermediate state is
introduced between the two ramps to reset the pick-up signal. The relay characteristic angle (RCA) is
calculated from the maximum and the minimum directional angles and evaluated by the test module.

OMICRON electronics GmbH 12/13


OMICRON PTL AREVA P132 P139 Feeder Protection Test Template User Manual

1
er 90
B ord CA -
. R
dir ngle
A
reverse

Uo (reference)
forward

2
er 90
ord CA +
Io (at char angle)
. B R
dir ngle
A

Figure 9: Directional maximum and minimum reverse angles (Phase angle mode)

8.11 CB trip time


For testing the trip time with circuit breaker contacts, the OMICRON State Sequencer test module is
used. This test is divided into three sequencer states: pre-fault, fault and post-fault. In the fault state, a
three-phase overcurrent condition is simulated in forward direction (Ifault = 2Ipickup). The time between the
trip command and the time when the circuit breaker is opened is evaluated.

Note: The auxiliary circuit breaker contacts (52a) should be wired to the binary input of the CMC during
this test.

OMICRON electronics GmbH 13/13