Canute LLP

How to calculate a re sprinkler system


Category: Hydraulic calculation for re protection engineers (/Table/Support/Hydraulic-calculation-for-re-protection-engineers/)

The long way- by hand


In this article, will demonstrate some of the basics for carrying out re sprinkler calculations by the long hand method with just the aid of a scientic calculator or our own hydraulic calculator - Hcal2
(/products/hcalc.html) which you can freely download from our website.

We will for this example use simple three sprinklers and three pipes which would of course be part of a much larger re sprinkler system. These basic procedures can also be used for calculating many other types of
systems such as re hydrant, hose reel or the discharge from a water cannon or monitor we can also use the same principal for almost all other water-based re protection systems if we have a k-factor for the
output device (re sprinkler, water mist nozzle and so on).

In this example, will we use a very simple system with just three sprinklers and three pipes this is often called a range pipe or branch pipe, which is part of a larger tree system. A tree system is end feed, that is water
is only fed from one direction as opposed to a grid or loop system when water may arrive at the sprinkler head from more than one direction.

Below is a diagram of the three sprinklers and three pipes which we will calculate. We have dimensioned the pipe lengths and given each junction point a unique node reference number which we use throughout the
calculations.

For each pipe, we need to know the pipe length, internal diameter (ID) of the pipe and the pipe material so we can determine the pipes c-factor, the table below summarises the pipe data which we will need for the
calculation for this example:

Node Ref Pipe Size ID (mm) Length (m) C-factor

130-120 27.30 3.20 120

120-110 27.30 3.20 120

110-100 36.00 3.20 120

We will also we will need some additional information such as the type sprinkler head, the area each head is covering, the design density for each sprinkler head in the system.

For this example, we will use the following design parameters:

design density: 7.50 mm/min


sprinkler head: K-factor of 70 with a minimum pressure 0.5 bar
head area: 10.20 m2

In this example, we have kept it very simple and used the same sprinkler head for all three sprinklers but this may not always be the case so again it way be useful to summarises the information in a table such as
this:

Node Ref Design Density Sprinkler k-factor Sprinkler minimum Head area (m2)
(mm/min) pressure (Bar)

130 7.50 70 0.5 10.20

120 7.50 70 0.5 10.20

110 7.5 70 0.5 10.20

The rst step is to calculate the minimum ow which will be required at the most remote sprinkler which in this case is at node [130], this is a two-step process as will need to calculate the minimum ow required to
satisfy the 7.50 mm/min design density and then nd the ow rate from the sprinkler given the sprinklers minimum pressure requirement, whichever is the greater ow will become our initial ow from the rst
sprinkler at node [130].

We will rst calculate the ow given the design density of 7.50 mm/min and the area the head is covering, we do this by multiplying the design density (/support-topmenu/support-basichydraulics/54-design-
density.html) by the head area:

Equation 1:

q1 = (design density) x (area per sprinkler)

In this example, this gives:

q1 = 7.50 mm/min x 10.20 m2 = 76.50 L/min

The second step is to calculate the minimum ow from the sprinkler given the K-Factor and the minimum head pressure by using the standard K-Factor formula (/support-topmenu/support-
basichydraulics/27-k-factor-formula.html):
Equation 2:

q = kp0.5

Where

p = the required pressure


q = the required ow from the rst sprinkler
k = the discharge coecient of the sprinkler (k-factor)

In this example, this gives:

q = 70 x 0.50.5 = 49.50 L/min

By comparing the two calculations above we can see that the minimum ow required from the sprinkler head will be 76.50 L/min as this is the highest ow rate from the two calculations and is required to meet the
7.50 mm/min design density. We can also see that the minimum sprinkler pressure of 0.5 bar is not sucient to produce the require ow rate so the next step will be to determine what pressure will be required to
produce the require ow of 76.50 L/min at the rst sprinkler head at node [130] we can do this by using equation 3.

Equation 3

p = (q/k)2

In the example, this gives:

p = (76.50 / 70)0.5 = 1.194 bar

We have now determined the minimum pressure and ow for the rst sprinkler at node [130] which will be 76.50 L/min @ 1.19 bar the next step is to calculate the pressure drop in the pipe between node [130] and
[120] and for this we will use the Hazen-Williams pressure loss formula (/support-topmenu/support-basichydraulics/26-the-hazen-williams-formula-for-use-in-re-sprinkler-systems.html).

Equation 4

Where

p = pressure loss in bar per meter


Q = ow through the pipe in L/min
C = friction loss coecient
d = internal diameter of the pipe in mm

We know that the ow rate from the sprinkler at node [130] is 76.50 L/min and this will be the ow rate in the rst pipe between nodes [130]-[120]. As the pipe has an internal diameter of 27.30 mm and has a C value
of 120 this will give us:

The pressure loss in the rst pipe is 0.027 Bar/m and the total pressure loss in the pipe is 0.086 bar.

We now need to add the pressure loss in the pipe to the start pressure at the sprinkler head at node [130] which was 1.19 bar to nd to pressure at node [120] and at the seconded sprinkler head at node [120] this
gives us 1.194 + 0.086 = 1.28 bar.

The next step is to nd the ow from the seconded sprinkler head at node [120] to do this we will use the K-Factor formula

Equation 5

This gives 70 x 1.2800.5 = 79.20 L/min from the sprinkler head at node [120] which we now add to the ow in the rst pipe node [130]-[120] to nd the total ow in the second pipe [120]-[110] to nd the total ow in
the seconded pipe which is 155.70 L/min.

Having found the total ow in the seconded pipe [120]-[110] we can now nd the pressure loss in, to do this we will use the Hazen-Williams pressure loss, formula 4 which we used above this gives us:
We now add the pressure loss 0.317 bar to the pressure at node [120] to nd the pressure at node [110] this give us: 0.317 + 1.280 = 1.597 bar

We now need to nd the ow from the sprinkler at node [110] we do this by using the k-factor given in equation 5 as we now know the pressure at node [110] is 1.597 bar, this gives 70 x 1.5970.5 = 88.50 L/min from
the sprinkler head at node [110]. We now add this ow to the ow in the seconded pipe [120]-[110] to nd the total ow in the third pipe [110]-[100] which will give us the ow of 244.20 L/min.

The last step is to nd the pressure loss in the third pipe [110]-[100] and again we will use Hazen-Williams pressure loss formula given is formula 4 above. However, the last pipe has an internal diameter of 36.0 mm
so this gives us:

We now add the pressure loss in this pipe to the pressure at node [110] to nd the pressure at node [100] this will be 0.189 + 1.597 = 1.786 bar. We have now complete the calculation for all three sprinkler heads and
have found the source pressure and ow required for this system is:

244.20 L/min @ 1.786 Bar

This pressure and ow is offer referred to as the source requirement for the system and is the minimum pressure and ow required for the system for it to be able to provide the required design density (in this
example 7.50 mm/min) at the most remote head [MRH] at node [130].

You should also be able to see that only the Most Remote Head has the minimum requirement of 7.50 mm/min design density and all the other sprinklers will have a higher pressure as they are hydraulically closer to
the water source so they will have a higher pressure and will discharge more water through the sprinkler this can be seen in the table below:

Node Ref min Design Density Pressure Flow from sprinkler Head Area Actual
(mm/min) (Bar) (L/min) (m2) Design Density

130 [MRH] 7.50 1.194 76.50 10.20 7.50

120 7.50 1.280 79.20 10.20 7.76

130 7.50 1.597 88.50 10.20 8.68

Sprinkler calculation step by step

1. Calculate minimum ow from the MRH with the sprinkler minimum pressure and k-factor
2. Calculate the minimum ow given the system design density and sprinkler head area.
3. If the calculation in step 2 is the highest ow demand, then calculate the required head pressure otherwise we can use the minimum sprinkler pressure in step 1.
4. Calculate the pressure loss in the pipe.
5. Add the head pressure to the pressure loss in step 4 to determine the pressure at the next sprinkler.
6. Use the k-factor formula to determine the ow from the sprinkler head.
7. Repeat step 4 to 6 until you do not have any more sprinklers or pipes

Next (/Hydraulic-calculation-for-re-protection-engineers/reynolds-number.html)
More Hydraulics calculations articles
If you have enjoyed the Basic Hydraulics calculations articles in this section then you may be interested in becoming a Registered User as this will open up additional articles and tutorials which will be of interest
to anyone if re protection engineering. The additional articles provide more basics hydraulics and advanced hydraulic calculation techniques which are used in re protection engineering.