You are on page 1of 2

St.

Petersburg Fire & Rescue


Prevention Division
400 Dr. Martin Luther King Jr. St. S
St. Petersburg, FL 33701-4472
Office 727 893-7064
Fax 727 892-5011

Occupant Name: The Attic Inspection Date: 6/30/2014


Address: 910 5 Avenue InspectionType: Reinspection

North
Contacts: -None- Inspected By: Ed Fishback
727-892-5320
Ed.Fishback@stpete.org
Occ. Sq. Ft.: 1200
Suite: B

Pass Fail N/A


FL NFPA 101 10
Floor 1
Chapter 6 Classification of
Occupancy and Hazard
Contents
6.1.14.1.4Occupancy The following accessory occupancies shall not be required to be separated from
Separation the primary occupancy as required in 6.1.14.4:
(1) A kitchen in an assembly occupancy does not constitute a mixed occupancy.
(2) Accessory uses in industrial and storage occupancies as otherwise provided
in 6.1.14.1.3(1)
(3) Rooms or spaces used for customary storage of nonhazardous materials in
assembly, business, educational, industrial, mercantile, hotel and dormitory, and
apartment occupancies which in aggregate do not exceed one-third of the major
floor area in which they are located. Protection from hazards shall be as
otherwise provided in the specific occupancy chapter.

ACTION REQUIRED: Provide proper seperation between occupancies.

LOCATION: The opening between the storage area and the assembly must have
rated doors installed.

Chapter 7 Means of

Egress
7.9.2.1Emergency Emergency illumination shall be provided for a minimum of 1 1/2 hours in the
Illumination event of failure of normal lighting. Emergency lighting facilities shall be arranged
to provide initial illumination that is not less than an average of 1 ft-candle (10.8
lux) and, at any point, not less than 0.1 ft-candle (1.1 lux), measured along the
path of egress at floor level. Illumination levels shall be permitted to decline to not
less than an average of 0.6 ft-candle (6.5 lux) and, at any point, not less than
0.06 ft candle (0.65 lux) at the end of 1 1/2 hours. A maximum-to-minimum
illumination uniformity ratio of 40 to 1 shall not be exceeded.

ACTION REQUIRED: Provide Emergency Lighting

LOCATION: Over 5th avenue entrance; In rear area; second floor walkway

Pass Fail N/A
FL NFPA 01 10
Floor 1
Chapter 11 Building

Services
11.1.10Open Electrical
Boxes
Image:checkmark.gif
Violation cleared on 6/30/2014

Inspector will return on or after 7/25/2014

Per City Ordinance 13-121 you will be billed for this inspection. The responsibility for compliance with all laws and
codes of the state of Florida and the City of St. Petersburg remains with the property owner and/or occupant. This
notice does not preclude future requirements for compliance.
Thank you for your cooperation in keeping your business and our community safe! If you have any questions, please
contact the Fire Prevention office at 727-893-7064.