Earth Leakage Relay

Seiko Zero-phase sequence


current transformer

CE

TIFIE
ER D
C


M
MAN

TE
S

G
A

SY
EM

QUALITY SYSTEM
ENT
SEIKO CE

051
Control & Electronics
J Q A - 2 0 6 2
EC99J1124

ISO9001 ISO14001
Seiko GD-B Earth Leakage Relay
High-speed operation, exposed type

Features
Reference Standard IEC60755-1983
Low cost

Compact
Small design means it fits easily into control centers,
control boards and even machinery.

Switchable voltage and current sensitivity


Circuit voltage can be changed easily by just changing the terminal connections.
Current sensitivity can be changed quickly by changing the connecting bar
(excluding 30-mA unit).

Two output contact systems


In addition to standard output connection it can also be used for applications
like alarms and remote display.

Robust enough to withstand surge currents without misoperation

Indicator lamps let you check operation at a glance

With terminal cover

1
Dimensional drawings M3.5 terminal screw (copper-zinc plate)
Operation indicator
Reset switch
Test switch 38 2-4.6mm dia. Holes
Case (polycarbonate, black)
(for M4)

80
94

41 74
84
51
Terminal cover (polycarbonate, clear)

Voltage terminal connection


P3
P2 Internal connection diagram
Operation
V
V

indicator
P1 Leakage relay
Test switch
ZCT Reset switch

Current sensitivity select connection

k C1
k Connect bar between k and n for
200, 500 and 1000 mA a1
ZCT n n
Connect between l and n for b1 Output
100, 200 and 500 mA contacts
C2
No bar on 30 mA model Current P3 a2
Select bar sensitivity Control
select bar P2
supply P1
AC 100 or
200 V
Caution: Factory setting is between k and n.
Adjust as needed.

Specifications
Model GD-B03T GD-B12T GD-B25T GD-B510T Operating temperature (C) -20 to +60 (average ambient 50C max.)
Rated current sensitivity (mA) 30 100/200 200/500 500/1000 Operating humidity (%) Relative 45 to 85 (no condensation)
Rated current threshold (mA) 50% min of rated current sensitivity Usage voltage range (%) 80 to 110
Rated control voltage (AC-V) 100, 110/200, 220 Operation indicator Red LED
Rated frequency (Hz) 50, 60 Leakage detection Electronic current operation
Power consumption (W) 2 max. Recovery Manual
Operating time (sec) 0.1 max. Weight (kg) 0.25
Output contacts 1a+1c
Applicable ZCT GDZ-16 to 80, GDZM-16 to 107.
Load
Voltage Resistive load (COS1) Inductive load (COS0.4) For GD-B03T use GDZ-16 to
Output contact ratings 40 and GDZM 16 to 42.
AC125V 5A 3A
AC250V 5A 2A

2
Seiko GD-C Earth Leakage Relay
Multi-function, exposed type
Features
Reference Standard IEC60755-1983
Rational wiring layout
Connecting wires can be run in either of two
directions to fit available space, providing
expanded freedom in layout.

Selectable control voltage,


current sensitivity and operating time
Change operating characteristics quickly to
match changes in specifications or installation.

Two output contact systems


In addition to standard output connection it
can also be used for applications like alarms
and remote display.

Robust enough to withstand surge


currents without misoperation

Indicator lamps let you check


operation at a glance

Operation speed Can be fitted with terminal covers


select switch
Terminal covers are available as optional parts.
Operation
indicator Single cover: GDTC-C
Cover set: GD-C-C
Test switch

Can be mounted on DIN rails


Reset switch
DIN rail mounting fittings are available as
optional parts.
Sensitivity
current select DIN rail fittings: GDAP-C
switch

N.P

DIN rail

Leakage relay set type: GDC D

Insert a C here to indicate terminal covers.

3
Dimensional drawings M3.5 terminal screw (copper-zinc plate)

99
38 96
25 8

75
85

2-4.5mm dia. Holes


Case (polycarbonate, black)
(for M4)
Terminal (tin plate) Terminal cover (polycarbonate, clear)
(option)

Internal connection diagram


Operation time select
Control supply
max. (50-60 Hz)
0.1S 0.3S
Output contact
Operation
speed select
switch

Adjust as required. Operation Sensitivity


current select
(0.3 sec) indicator switch

Sensitivity current select Reset switch Test switch


100
30 200 Output
500 contact
1000
mA

Use a flat-blade screwdriver to


adjust as required. (30mA)

Specifications
Model GD-C Operating temperature (C) -20 to +60 (average ambient 50C max.)
Rated current sensitivity (mA) 30/100/200/500/1000 (selectable) Operating humidity (%) Relative 45 to 85 (no condensation)
Rated current threshold (mA) 50% min of rated current sensitivity Usage voltage range (%) 80 to 110
Rated control voltage (AC-V) 100, 110/200, 220 Operation indicator Red LED
Rated frequency (Hz) 50, 60 Leakage detection Electronic current operation
Power consumption (W) 2 max. Recovery Manual
Operating time (sec) 0.1 max. (high-speed)/0.3 (delay): (selectable) Weight (kg) 0.25
Output contacts 1a+1c GDZM-16 to 107
Load Applicable ZCT For 30-mA current sensitivity,
Voltage Resistive load (COS1) Inductive load (COS0.4) use GDZM-16 to 42.
Output contact ratings AC125V 5A 3A
See page 12 for explanation of model types.
AC250V 5A 2A

4
Seiko GD-D (embedded type) Earth Leakage Relay

Front Rear

Specifications

Current sensitivity
Selectable to 100, 200, 500 or 1000 mA with a rotary switch.

Operating time
Selectable to 0.3, 0.5, 1 or 2 s with a rotary switch.

Power indicator
Green LED provided to show when power is supplied from board.

Terminal cover
Clear terminal cover mounted. Holes for tightening
terminal screws are designed to protect fingers.

5
Features
Reference Standard IEC60755-1983
Wide range of supply voltages
Can be used at AC 120 and 240 V as well,
making it perfect for use outside Japan.

Manual or automatic recovery (switchable)


Switchable selection of push button manual recovery or
automatic recovery after leakage current is resolved.

DIN size
Board footprint is DIN size, 48 x 96 mm, for easy board
standardization.

One-touch mounting
Quick mounting by just snapping into place on the board.
No screws are needed, only a square hole, reducing construction time and
labor requirements.
Time and labor are further reduced because no screw tightening is needed.

Quick-release terminals
Terminal screws cannot fall out, reducing connection time and labor requirements.


Dimensional drawings
One-touch panel mechanism
(applicable panel thickness 1 to 3.2 mm) Rear case
Operating information (polycarbonate, black)
48
12 65
Sensitivity current
Power indicator select switch
(green)
Leakage Operating time
indicator (red) select switch

Manual/automatic
recovery select switch
Test switch

91
Reset switch
96

Ratings

Front case
(polycarbonate,
black)

Movable protective cover M3.5 screw (quick-release type)


(polycarbonate, clear) (copper-zinc plating)
45 +0.8
0

92 +0.8
0

44

Rear cover Mounting hole dimensions


(polycarbonate, clear)
A view Terminal labels

Specifications
Model GD-D Operating temperature (C) -20 to +60 (average ambient 50C max.)
Rated current sensitivity (mA) 100/200/500/1000 (selectable) Operating humidity (%) Relative 45 to 85 (no condensation)
Rated current threshold (mA) 50% min of rated current sensitivity Usage voltage range (%) 80 to 110
Rated control voltage (AC-V) 100, 120/200, 240 Operation indicator Red LED
Rated frequency (Hz) 50, 60 Power indicator Green LED
Power consumption (W) 2 max. Leakage detection Electronic current operation
Operating time (sec) 0.3/0.5/1/2 (selectable) Recovery Manual or automatic (switchable)

Output contacts 1a+1c Weight (kg) 0.25


Load Applicable ZCT GDZM-16 to 107
Voltage Resistive load (COS1) Inductive load (COS0.4)

Output contact ratings AC125V 5A 3A


AC250V 5A 2A

7
Installation locations for ground short protector
An earth leakage breaker or earth leakage relay can be used with a breaker (line breaker, sole-
noid breaker, etc.) as a ground short protector. With an earth leakage relay board area can be
used effectively.
Quick reference chart for ground short protector installation locations Installation required Not required Not applicable
Voltage to ground 150 V max. Over 150 V
Law 200V
Installed equipment and environment Operating voltage 60 V max. 100V 3W 200V 415V

Where possibility of 1. Sites exposed to water


Electrical facility technical standards (Article 15)
Electrical facility technical standards (interpretations)
cases (Article 40)
Equipment with metal external

contact by human be- 2. Sites exposed to high humidity


ings exists 3. Dry sites
4. Equipment installed in generating plants, substations, breaker stations or similar sites
5. For equipment covered under and fitted with ELB, and power feed reinforced
6. Where ground resistance is 3 max.
7. For equipment covered under with double-insulated construction
8. Non-grounded circuit using isolation transformer
9. Equipment covered with insulating material such as rubber, synthetic resin, etc.
10 Equipment connected to secondary side of inductive motor
11 Electric welding machines, electric furnaces, electric boilers, electrolysis tanks, etc.
12 Low-voltage lines connected to super-high or high voltage lines through transformers (excluding at generating plants and substations) (Article 40)
13 2 kW or larger equipment in residential sites, connected to circuits with over 150 V to ground (Article 162)
14 Equipment in gunpowder storage facilities (Article 195)
15 Thermocouple systems such as floor heating (Article 228)
16 Electrically-heated floors (Article 230)
17 Underwater lighting for pools, etc (Article 234)
(30 V max.X)

18 Cabtyre cables in aboveground installation (Article 147)


19 Sites where ground construction is difficult (Articles 19, 29)
20 Temporary wiring embedded in concrete (Article 242)
21 Sites damp with water or other highly conductive liquids
safety regulations
Labor health and
(Articles 333, 334)
motorized equipment
Movable and transportable


22 Installations over conductive surfaces such as steel plate, steel beams, workbenches, etc. (50 V max.X)

23 Sites other than 21 and 22 above


24 Ungrounded circuits using isolation transformers
25 Uses on isolation benches
26 For equipment covered under with double-insulated construction
27 Where workers may contact insulated wires or moving wires (Article 336)
(50 V max.X)

Note: For details refer to the official documentation.


Representation connection diagrams
1. When used in conjunction with line breaker 3. When used as leakage alarm
(Power (Power
supply) supply)
Remote power
supply can also
be provided for
alarm display
Note:
For automatic reset,
connect control sup-
ply to MCCB load
side (will not dis-
play leakage).

(Load) (Load)

2. When used as solenoid breaker 4. Zero-phase sequence current transformer thru-conductors


(Power
supply) Single-phase Single-phase 3-line Triple-phase
2-line Triple-phase 3-line 4-line
1 2 1 2 3 1 2 3N
Off
On

(Load)

8
Zero-phase sequence
Seiko GDZM current transformer

Can be used together with GD-B, GD-C or GD-D relays.

Models with terminals Models with leads

GDZM16BT GDZM16B

GDZM30AT GDZM30A

GDZM42AT GDZM42A

GDZM65AT GDZM65A

GDZM80AT GDZM80A

GDZM107AT

9
Dimensional drawings
Models with terminals Models with leads
60 60

50 50

2 5-mm dia. Holes (for M4) 2 5-mm dia. Holes (for M4)
18

When terminal
cover used 42 M3.5 screw 42 18

16
16

49.5
46

46
22

22
0.5 mm2 lead, length 700, black
GDZM-16BT GDZM-16B
40

50

40

50
F

E
Mounting hole (for M5) 6 Mounting hole (for M5)
6
G F

B
When terminal B
cover used M3.5 screw

A A
E
D

D
C

C
0.5 mm2 lead,
length 700, black

Model A B C D E F G Model A B C D E F

GDZM-30AT 30 66.5 34 71.5 73 23 40 GDZM-30A 30 66.5 34 71.5 23 40


GDZM-42AT 42 79.5 40.5 86.5 88 23 65 GDZM-42A 42 79.5 40.5 86.5 23 65
GDZM-65AT 65 106 53.5 108 110 24 65 GDZM-65A 65 106 53.5 108 24 65

GDZM-30AT,42AT,65AT GDZM-30A,42A,65A

M3.5 screw
27
40
50

27
40
50

6 6
100 Mounting hole (for M5) 100 Mounting hole (for M5)

126 126
When terminal
cover used
149.5
148

148

80
64.5

64.5

0.5 mm2 lead,


length 700, black

GDZM-80AT GDZM-80A

10
Dimensional drawings

Models with terminals M3.5 screw


(copper-nickel plate)
M6 mounting hole

76.5
62
130
175

46
Case SPCC
36.4
Terminal cover (option) Terminal strip (caution electrocoat) 30

Insulating tube (hard PVC)

210
209
194

10
7

GDZM-107AT

Nominal cross-sectional area of thru-conductor


Model Hole dia. Rated 600 V vinyl insulated wire (IV) 600V flame-retardant Polyflex wire (600V MLFC)
current
2 wires 3 wires 4 wires 6 wires 2 wires 3 wires 4 wires 6 wires

GDZM-16BT, GDZM-16B 16 50A 14mm2 8mm2 8mm2 14mm2 8mm2 8mm2


GDZM-30AT, GDZM-30A 30 150A 60mm2 50mm2 38mm2 60mm2 38mm2 30mm2
GDZM-42AT, GDZM-42A 42 250A 125mm2 125mm2 100mm2 100mm2 80mm2 60mm2
2 2 2
GDZM-65AT, GDZM-65A 65 500A 400mm 325mm 250mm 250mm 250mm 150mm2
2 2

GDZM-80AT, GDZM-80A 80 800A 500mm2 500mm2 400mm2 325mm2 325mm2 250mm2


GDZM-107AT 107 1600A 500mm 500mm 500mm 500mm 325mm2 325mm2 325mm2 325mm2
2 2 2 2

Note: Wire dimensions as per Hitachi Cable standards.

11
List of Seiko Electric earth leakage relays and zero-phase sequence current transformers
GD-B earth leakage relays
Model Specification
GD-B03T AC 100, 110/200, 220 V, sensitivity current 30 mA
GD-B12T AC 100, 110/200, 220 V, sensitivity current 100/200 mA
GD-B25T AC 100, 110/200, 220 V, sensitivity current 200/500 mA
GD-B510T AC 100, 110/200, 220 V, sensitivity current 500/1000 mA

GD-C earth leakage relays


Model Specification
AC 100, 110/200, 220 V, operating time 0.1 max/0.3 s,
GD-C
Sensitivity Current 30/100/200/500/1000 mA, manual reset
GD-CA Automatic reset
GD-CS1 Operating time 0.2/0.5 s
GD-CAS1 Automatic reset, operating time 0.2/0.5 s
GD-CS2K1 Sensitivity current 30/100/300/500/1000mA Operating time 0.1/0.2 s
GD-CAS2K1 Automatic reset, Sensitivity current 30/100/300/500/1000mA operating time 0.1/0.2 s
GD-CK2 Sensitivity current 30/40/50/100/1000 mA
GD-CV1 AC 120/240 V
GD-CE Electrical external reset (resettable via external contact)
Only specifications different from GD-C shown.
When optional terminal cover installed, a C suffix is added.
When DIN rail fittings used, a "D" suffix is added.

GD-C options
Model Specification
GDTC-C Terminal cover (single unit)
GDAP-C DIN rail mount fittings (single unit)

GD-D earth leakage relay


Model Specification
AC 100, 120/200, 240 V, operating time 0.3/0.5/1/2 s,
GD-D
sensitivity current 100/200/500/1000 mA
AC 100, 120/200, 240 V, operating time 0.3/0.5/1/2 s,
GD-DK2
sensitivity current 50/100/200/500 mA

GDZM zero-phase sequence current transformer


Model Specification
GDZM-16BT With terminals, thru-hole diameter 16 mm, rated current 50 A
GDZM-30AT With terminals, thru-hole diameter 30 mm, rated current 150 A
GDZM-42AT With terminals, thru-hole diameter 42 mm, rated current 250 A
GDZM-65AT With terminals, thru-hole diameter 65 mm, rated current 500 A
GDZM-80AT With terminals, thru-hole diameter 80 mm, rated current 800 A
GDZM-107AT With terminals, thru-hole diameter 107 mm, rated current 1600 A
GDZM-16B With leads, thru-hole diameter 16 mm, rated current 50 A
GDZM-30A With leads, thru-hole diameter 30 mm, rated current 150 A
GDZM-42A With leads, thru-hole diameter 42 mm, rated current 250 A
GDZM-65A With leads, thru-hole diameter 65 mm, rated current 500 A
GDZM-80A With leads, thru-hole diameter 80 mm, rated current 800 A
When optional terminal cover installed, a C suffix is added.

12
Handling precautions
Do not disassemble earth leakage relays or zero-phase sequence current trans-
formers.
Never test to confirm electrical shock safety with your hand or other part of
your body.
It is impossible to prevent electrical shocks between wires.
When measuring circuit insulation resistance or dielectric strength it is impossi-
ble to measure between wires, so always disconnect the leakage relay first.
There are no problems, however, between chargers and ground.
Do not test dielectric strength between control supply terminals or between ter-
minals for input from the ZCT. This could damage the leakage detect circuit.
Where there are excessive branches or where line length is excessive, a high-
sensitivity relay on the main circuit could result in false triggers by weighted
leakage. Select an appropriate current sensitivity.

Precautions in use
Always prepare mounting holes to specified dimensions and mount securely.
Connection terminal torque is 0.7 to 1.0 N m. Excess torque will damage termi-
nals.
Do not mount in sites subject to excessive heat.
Do not mount in sites subject to excessive vibration or impact.
Do not mount in sits subject to corrosive or flammable gas, ash, steam or salt,
or subject to water or oil spray.
Do not run dedicated ground lines through zero-phase sequence current trans-
formers
Always run the common wire for single-phase 3-line and triple-phase 4-line sys-
tems through the ZCT.
The straight portion of the thru-conductor should be as long as possible to en-
sure ZCT balancing.
Thru-conductors should be bundled with cable ties to prevent damage from
electromagnetic repulsion in the event of shorts.
Connection between earth leakage relay and ZCT should be with twisted wire to
avoid induction effects.
Earth leakage relays and ZCT should be at least 10 cm distant from trunks carry-
ing several thousand A or more, to avoid external magnetic field effects.
Load equipment should be grounded in accordance with local law and regula-
tion.

Maintenance inspection items


Always check operation with the test button prior to use. Press the test button
long enough to operate.
Check operation with the test button periodically, about once a month.
If the leakage relay activates, inspect the circuit and rectify the problem, then
turn power back on.

13