1 General
Test Universe 3.10 (build # 4743) is a major Test Universe release, compatible with Microsoft Windows 10
and focusing on the new IEC 61850 Client/Server module. It also offers many feature improvements and
resolves some problems. The new ISIO Connect module (included for free with Test Universe 3.10) is
intended for users extending the input/output scope of their test sets by using up to 3 ISIO 200 units with a
default configuration.
TU 3.10 can work with test files created with any previous Test Universe version, whereas files created with
TU 3.10 cannot be opened with older TU versions.
The major changes as compared with TU 3.01 are listed in alphabetical order of the components. Many
other minor improvements and bug fixes not mentioned here are also implemented.
Changes introduced with updates to the major version 3.10 are indicated with their build number. Changes
introduced with the most recent update (build # 4820) are shown in blue text.
The build number of your currently installed version is shown in a tooltip when hovering above the version
number (3.10) on the Test Universe start screen.
2 Global Features
2.8 #70848 (Build 4820): Firmware upgrade failed via USB connection
The upgrade of the CMC firmware could not be performed if the PC was connected to the CMC via USB.
This is fixed now.
4 Advanced Distance
4.2 #68913 (Build 4820): Problem with load current in Constant source
impedance mode
A Value out of range error was caused in this combination. This is fixed now.
5 Advanced TransPlay
6 Annunciation Checker
6.2 #56986: Copy/Paste between tables of the test module and Microsoft Excel
Copy/paste is supported in both directions. Make sure that you paste valid data and select a data table size
in Excel which corresponds with the table size in the test module for pasting.
7 Autoreclosure
8 CMC
The firmware update included with Test Universe 3.10 enhances the AuxDC behavior of the CMC test sets
for safety reasons:
8.1 #40683: The AuxDC LED will light up when any voltage >0V is output.
10 Differential
11 Hardware Configuration
11.2 #56977: Show connector, display name and connection terminal in report
This feature, per default shown in the Long Report setting, enhances the wiring documentation of the test.
For ease of report tailoring, two new context menu entries now allow to add all neutral terminals for
documentation and/or to remove all un-routed signals.
12.1 #69330 (Build 4820): Authentication mode always trying to use password
This happened even if none was selected. Fixed now.
12.2 #69920 (Build 4820): Display update problem when selecting a tab other than
Output and changing the static state
Fixed.
12.3 #69970 (Build 4820): Wrong assessment for values with unit frequency
The values were wrongly multiplied with the nominal frequency. Fixed now.
NOTE: Old test results cannot be corrected by this update. For a correct representation and assessment the
tests would need to be repeated after clearing the results.
12.5 #70838 (Build 4820): Wrong trigger condition for frequency values
E.g. 50 Hz was taken as 1000 Hz. Fixed now.
14 License Manager
15 Meter
16 Overcurrent
16.9 #68703 (Build 4820): Improper trip assessment with inverse trip contact logic
With the trip signal permanently active a `trip during prefault was indicated, ignoring the specified signal
inversion. This is fixed now.
17 PQ Signal Generator
17.2 #67019 (Build 4760): Interharmonics state: More than one interharmonic
If more than one interharmonic was defined then only the fundamental was generated. This is fixed now.
18.1 #56986: Copy/Paste between the fault state table of the test module and
Microsoft Excel
Copy/paste is supported in both directions. Make sure that you paste valid data and select a data table size
in Excel which corresponds with the table size in the test module for pasting.
18.2 #68035 (Build 4820): Activated binary outputs worked only for the first pulse
(fault state)
They should have been activated for all pulses. This is fixed now.
19 QuickCMC
19.3 #56986: Copy/Paste between tables of the test module and Microsoft Excel
Copy/paste is supported in both directions. Make sure that you paste valid data and select a data table size
in Excel which corresponds with the table size in the test module for pasting.
19.5 #66462 (Build 4820): Problems with horizontal scrolling of the test view
under Windows 10
Fixed.
20.2 #67753 / #68499 (Build 4820): The display of some linked values was not
immediately updated in test view and assessment view
When entering a LinkToXRIO link for a data field or changing the linked value in the Test Object the
displayed number was not adapted accordingly until e.g. a different data field was selected. This is fixed
now.
20.3 #68736: Problem with some assessments with virtual (GOOSE) inputs
The assessment regarding the timing of the virtual signals sometimes was not correct (buffer content order
not according to time stamping). This is fixed now.
21 State Sequencer
21.1 #56986: Copy/Paste between tables of the test module and Microsoft Excel
Copy/paste is supported in both directions. Make sure that you paste valid data and select a data table size
in Excel which corresponds with the table size in the test module for pasting.
23 Synchronizer
23.1 #67438(Build 4760): Problem when re-using certain files with test results
An issue has been fixed which caused the test module to not properly behave when executing a certain test
file, created with an older TU version, after clearing test results and starting the test.
25.3 #68798 (Build 4820): SVScout Help not showing from right-click option
Right-clicking on the SVScout entry on the TU Start screen should open the SVScout user manual. This is
working now.
26 TransPlay
26.1 #50315: Setting the time delay compensation via command line option
A defined time delay compensation is matching the characteristic of the CMC test sets. In case the output is
routed to third-party amplifiers via the low-level outputs this compensation should be deselected. You can
now deselect it also when launching TransPlay via command line for batch processing. The syntax is:
transplay.exe /bat /nodelaycomp
For further details see Test Universe Help, Starting TransPlay with Command Line Parameters.
27 TransView
When you are working with our products we want to provide you with the greatest
possible benefits. If you need any support, we are here to assist you!
At our technical support hotline, you can reach well-educated technicians for all of
your questions. Around the clock competent and free of charge.
Make use of our 24/7 technical support hotline:
Americas: +1 713 830-4660 or +1 800-OMICRON
Asia-Pacific: +852 3767 5500
Europe/Middle East/Africa: +43 59495 4444
Additionally, you can find our Service Center or Sales Partner closest to you at
www.omicronenergy.com.
Learn more about your product in one of the training courses offered by the
OMICRON Academy.
OMICRON electronics GmbH, Oberes Ried 1, 6833 Klaus, Austria, +43 59495
Page 12 of 12