You are on page 1of 10

Dangerous magnetic field exposure near transformer

substation in the building


electrical-engineering-portal.com /magnetic-field-exposure-transformer-substation

Google+ 5/5/2017
Magnetic flux density in the apartment
Transformer substations located close to the living areas could induce high long-term exposures to extremely
low frequency magnetic fields of nearby inhabitants. Some of the researches have shown increased risk to
childhood leukemia associated with the long term exposure to the elevated levels of magnetic fields.

With the increasing public interest, prudent avoidance and good practice it is becoming more and more important to
minimize the exposure of the nearby inhabitants.

Dangerous magnetic field exposure near transformer substation in the building (photo credit: Edvard Csanyi)

The most cost efficient way of achieving this goal is to include the magnetic field mitigation in the
early stage of the planning and construction/reconstruction process of each transformer
substation.

Using numerical modeling we studied different variants of reconstruction of a typical transformer substation located
in the basement of a block of flats with a living room located right above the transformer. To obtain a comprehensive
snapshot of current situation before the reconstruction we performed detailed spot and 24-hour measurements of
magnetic flux densities.
1/10
Based on the results of the numerical modeling we proposed the optimum and cost effective reconstruction plan.

After the reconstruction, numerical results were evaluated by the comparison of the numerical results with the results
of the measurements after the reconstruction and numerically predicted 10-fold reduction factor of the highest
values of the magnetic field was confirmed.

Contents:

Introduction
Materials and methods

Situation
Measurements
Numerical calculations

Results

Results of spot measurements


Results of continuous 24-hour measurements
Numerical modeling
Spot measurements after the reconstruction

Discussion and conclusions

Introduction

International Agency for Research on Cancer included extremely low frequency (ELF) magnetic field among the
possibly carcinogenic factors for humans [1].

This decision is based on the results of two studies [2, 3], which showed that elevated 24 hours averaged values of
ELF magnetic field (<0.3-0.4 T) do increase the risk of childhood leukemia but the biological mechanisms of this
risk remain un-known [1, 4, 5, 6].

Transformer substations (TS) located in the basement of the buildings where apartments are located next or above
the TS are without doubts important sources of ELF magnetic fields inside nearby apartments. In a study carried out
in Finland [7] they found that in more than 70 % of the apartments above TS the daily average value of the
magnetic flux density exceeds 0.4 T, whereas in higher stories this was true only for 6.7 % apartments.

Minimization of the magnetic field is possible either by moving all the parts with high currents away from the
apartments, by changing the geometry of the conductors, especially the low voltage (LV) busbar, by replacing
components of the TS (with components with lower emissions) and finally it is possible to shield the nearby
apartments with materials with either high permeability or high conductivity.

Go back to contents

Materials and methods

2/10
Situation

Typical TS with nominal power 630 kVA, nominal voltage 10/0.4 kV is located in the basement of the residential
apartment building. In the first room there is transformer (Figure 1) whereas in the second one both 20 kV and low
voltage switchgear is located.

We were contacted by the owner of the apartment above the TS to estimate the field levels inside the apartment.
First measurements shoved magnetic flux density up to values of 15 T inside the apartment above the TS .

Go back to
contents

Measurements

Magnetic field is
linearly correlated
to the actual
current load, but
this can vary during
the day depending
on the present use.

To obtain the
detailed snapshot
of the magnetic
field in the
apartment above
the TS it is
therefore not
enough to make
only spot
measurements,
but also 24-hour
measurements to
evaluate the time
variability of the Figure 1: Transformer located in the right room of the transformer substation

magnetic field
and determine worst case condition.

For spot measurements we have used Wandel & Goltermann EM field analyzer EFA-3 with the B field probe. For
24-hour measurements we have used automatic measurement station PMM 8055 which measures the magnetic
flux density continuously 24 hours per day.

It consists of measurement probe for ELF magnetic flux density HP-051, control unit with the GSM modem to send
the measurements from the measurement station to the server connected to the internet, housing with solar cells
and accumulator. After the data are automatically transferred to the server, they could be viewed by everyone
3/10
through an internet application.

According to the Slovenian legislation and the international standards (IEC 61786) the magnetic flux density is
measured at the height of 1 or 1.5 m above the ground. But in the apartment, it is not uncommon that the
children have their beds on the floor or do they play on the floor and with measurements 1 m above the ground the
exposure would be greatly underestimated.

Therefore all the measurements spot and continuous 24-hour were taken at the height of 0.2 m
above the ground.

Go back to contents

Numerical calculations

We used program package


Narda EFC-400EP for
numerical modeling of the
magnetic flux density in the
vicinity of the TS. It is based on
segmentation method where
each conductor is presented
with finite segments.

Corresponding material and


electromagnetic characteristics
are assigned to all the segments
and the resulting magnetic field
is the sum of the contributions of
all the segments.

Go back to contents
Wandel & Goltermann EM field analyzer EFA-3

Results

Results of spot measurements

Spot measurements were carried out on the 22 of October 2008 between the 10.30 and 11.30. Measurements were
taken on 15 locations inside the TS as well as on 17 locations in the apartment above the TS . Measurement
results in the apartment together with the locations are shown in Table 1. Based on the data from electric distribution
company the value of the current in the LV busbar during measurements was 100 A.

Table 1 Measured values of magnetic flux density in apartment above TS

Go back to contents
4/10
Results of continuous 24-hour measurements

Table 1 Measured values of magnetic flux density in apartment above TS

Continuous 24-hour measurements were carried out first time between the beginning of December 2007 and the
end of January 2008 and second time between the beginning of spot measurements (22 October 2008) and 6
December 2008.

The highest measured magnetic flux density was 15.6 T with the highest 24-hour average of 9.4 T. Based on
the results of continuous measurements we estimated the real worst case load of the TS.

During spot measurements the current in the LV busbar was 100 A. A nominal load with the current 909 A
represents the worst case condition where such conditions in real situations are very unlikely. Based on the results
of continuous measurements we estimated that in real worst case condition the current in the LV busbar is 200
A.

Go back to contents

Numerical modeling

To verify our numerical model of the TS we compared measured and calculated results under the same load
conditions at the same locations (Table 2) and it could be seen that both values agree well. Small differences are
possible due to different factors (simplification of the model, changes of the load of the TS).

We made separate calculations for different parts of TS to evaluate which parts are the most critical and identified
5/10
LV busbar, which is fixed on the ceiling of the TS and therefore the distance between the LV busbar and the floor of
the above apartment is only 0.5 m. Other important sources are also switchgear and transformer.

Based on this findings we numerically analyzed the re-construction of the TS with following modifications:

1. Removing LV busbar, new LV busbar located under the floor of the TS;
2. Change of the switchgear, since it is already old, with a new, which should be as low as possible;
3. Proper design and realizations of all the busbars in the TS (all cables close together and arranged in the
triangle, as short busbars as possible, especially parts of them which are higher than the floor of the TS).
4. We propose transformer to remain, since it was replaced few years ago.

Table 2 Comparison of measured and calculated magnetic flux density inside the apartment above the TS

Table 2 Comparison of measured and calculated magnetic flux density inside the apartment above the TS

From the results in Table 3 and Figure 2 to 5 we can see that the reconstruction will lower the maximum value
of the magnetic flux density for about 10 times.

Table 3 Comparison of the maximum calculated values of the magnetic flux density before the reconstruction and after it

Magnetic flux density before and after reconstruction

Results of the numerical calculation of the magnetic flux density in the apartment at the height of 0.2 m above the
floor before (left) and after the reconstruction (right). The current in the LV busbar is 100 A.

Results of the numerical calculation of the magnetic flux density in the apartment at the height of 0.2 m above the
floor before (left) and after the reconstruction (right). The current in the LV busbar is 909 A.

MAGNETIC FIELD OF TRANSFORMER SUBSTATIONS

Results of the numerical calculation of the magnetic flux density in vertical plane through LV busbar before (left) and
after the reconstruction (right). The current in the LV busbar is 100 A.

Results of the numerical calculation of the magnetic flux density in vertical plane through LV busbar before (left) and
after the reconstruction (right). The current in the LV busbar is 909 A.

6/10
Go back to contents

Spot measurements after the reconstruction

To verify the findings of the numerical calculations measured the magnetic flux density after the reconstruction on
the same locations as before the reconstruction (Figure 2). During the measurements after the reconstruction, the
current load was slightly higher current: before it was about 100 A, after it was about 160 A .

Figure 2: Results of the numerical calculation of the magnetic flux density in the apartment at the height of 0.2 m above the floor before (left) and after the
reconstruction (right). The current in the LV busbar is 100 A.

In Table 4 where the values of the magnetic flux density are given for the measurements before the reconstruction
(second column) and after it (third column). The ratio between both measurements showing the reduction of the
magnetic field in the apartment above TS, given in the fourth column, therefore slightly underestimate the
effectiveness of the reconstruction, as the current load was 1.6 times higher during the measurements after the
reconstruction.

Table 4 Measured magnetic flux density in the apartment above the TS


7/10
Go back to contents

Discussion and conclusions

Figure 3 Results of the numerical calculation of the magnetic flux density in the apartment at the height of 0.2 m above the floor before (left) and after the
reconstruction (right). The current in the LV busbar is 909 A.

We analyzed the magnetic field in the apartment above the TS before the reconstruction. With numerical
calculations the reconstruction was optimized in terms of cost effectiveness and the goal to reduce the levels of
the magnetic field in the apartment above the TS.

In spite of the fact that the increase of the costs of the reconstruction was minimal and the realization of the
proposed solution was not problematic, it still reduced the exposure of the people living in the apartment for a
factor of 10.

To further lower the magnetic field in the apartment it will be necessary to either change the transformer with a one
with reduced magnetic field emissions or to use shielding materials for ELF magnetic field. Shielding materials are
either good conductors (aluminium or copper plates) or have high permeability.
8/10
With shielding materials it is possible to reduce the magnetic field for a factor of 5 or even more, but these
solutions are associated with much higher costs compared to the proposed one.

Go back to contents

Authors: BLAZ VALIC and PETER GAJSEK (INSTITUTE OF NON-IONIZING RADIATION, POHORSKEGA
BATALJONA 215, 1000 LJUBLJANA, SLOVENIA)

References:

1. IARC. (2002) Non-ionizing radiation, Part 1: Static and extremely low-frequency (ELF) electric and magnetic
fields. IARC Monogr Eval Carcinog Risks Hum 80:1395. Lyon, France

Figure 4 Results of the numerical calculation of the magnetic flux density in vertical plane through LV busbar before (left) and after the reconstruction (right).
The current in the LV busbar is 100 A.

Figure 5 Results of the numerical calculation of the magnetic flux density in vertical plane through LV busbar before (left) and after the reconstruction (right).
The current in the LV busbar is 909 A.

2. Ahlbom A, Day N, Feychting M et. al. (2000) A pooled analysis of magnetic fields and childhood leukaemia. Br
J Cancer 83:692698

9/10
3. Greenland S, Sheppard AR, Kaune WT et. al. (2000) A pooled analysis of magnetic fields, wire codes, and
childhood leukemia. Childhood Leukemia-EMF Study Group. Epidemiology 11: 624634
4. Kheifets L, Repacholi M, Saunders R et. al. (2005) The sensitivity of children to electromagnetic fields.

Table 4 Measured magnetic flux density in the apartment above the TS

Pediatrics 116:303313
5. Swanson J, Kheifets L (2006) Biophysical mechanisms and the weight of evidence for EMF. Radiat Res
165:470478
6. Schuz J (2007) Implications on protection guidelines from epidemiologic studies on magnetic fields and the
risk of childhood leukemia. Health Phys 92:642-648
7. Ilonen K, Markkanen A, Mezei G et. al. (2008) Indoor Transformer Stations as Predictors of Residential ELF
Magnetic Field Exposure. Bioelectromagnetics: 29: 213-218

10/10

You might also like