You are on page 1of 3

C A P T U R I N G C O N D E N S AT E

O
ne way to reduce Section 314 of the International cooling. Some situations preclude
water use is by col- Plumbing Code (IPC) describes the use of condensate for cooling
lecting condensate, how cooling coil condensate must tower makeup, such as when chilled
which is produced by be conveyed to an approved place water is provided by a district energy
air-conditioning sys- ofdisposal. system or a local district cooling sys-
tems as they remove moisture from Appendix C of the IPC has been tem with satellite chillers.
Rainwater and condensate air during the cooling process. Two modified in the past several years to Although the authors are not
supplied by rooftop conden-
sate units are collected and ASHRAE standards address water allow for recycling of graywater, and aware of any systems currently
stored in two 8,600 gallon use within buildings and provide (or it is important to note that the defi- doing so, we envision a time when
tanks at the Sally Cheever Girl
Scout Leadership Center in
are considering providing) require- nition of graywater does not include collected condensate could be
San Antonio, Texas. ments for condensate collection.1 cooling coil condensate. If the con- fed into a reclaimed water utility.
Depending on the location of the densate were kept separate from Perhaps one day high performing
air-handling equipment with respect other graywater sources, it should buildings may even be able to sell
to the planned reuse location, it be allowable to use in the purposes that collected condensate to the
may be possible to directly drain described in this column. local municipality.
the condensate. Other situations (If the condensate is intended for
may require a separate small pump- flushing or irrigation purposes, it Condensate Collection

Brian Wilkie, San Antonio Water System


ing station. Regardless, disposing still may be advisable to follow the Scenarios

Capturing
condensate in the sanitary sewer requirements of the IPC Appendix C.) Two prime factors influence whether
has become outdated for a high per- Cooling towers are one of the bet- condensate collection should be
forming building. ter uses for condensate because they considered for a particular building
continually need makeup water due project: the local climate, and the
What to Do With to evaporation losses and the need building type and usage patterns.
Collected Condensate to manage the resulting buildup of While climate might seem obvious

Condensate
Several choices exist for using the dissolved solids. This evaporation at first, the actual amount of conden-
collected water. The best end use at typical design conditions is in the sate produced during the course of
depends on the particular building range of 0.02 to 0.03 gpm per ton of a cooling season for a given amount
and location. Ultimately, any water
use that displaces using potable
F I G U R E 1 C O N D E N S AT E C O L L E C T I O N P O T E N T I A L
water in the building is equal in
value to any other use. Collected
Gallons/CFM
water could be used in one or
more of the following common 01
B Y T O M L A W R E N C E , P H . D . , P. E . , M E M B E R A S H R A E ; A N D J A S O N P E R R Y , M E M B E R A S H R A E
applications:
Cooling tower makeup; 12

Toilet or urinal flushing; 24


Developed nations are realizing what has been common knowledge Makeup for water features; and
46
Landscape irrigation.
in developing nations: that water should be treated as a valuable Potentially, some confusion could 610

occur with a code officials inter- 1015


commodity. Supply (or lack of it) and demand influence the price of pretation on the use of condensate.
15+

water, but politics also play a role. Some within the green building 1. ASHRAE Standard 189.1-2009, Standard
for the Design of High Performance Green
Buildings Except Low-Rise Residential
circle now consider water concerns to be as important as energy. Buildings and proposed ASHRAE Standard Condensate collection potential varies by regional climates. The map represents the
191P, Standard for the Efficient Use of Water in potential amount of condensate that can be collected from each cfm of outdoor air over
Building, Site and Mechanical Systems. one year (8,760 hours).

56 HIGH P E R F O R M I N G B U I L D I N G S Fa l l 2 0 1 0 Fa l l 2 0 1 0 H I G H PERFORMING BUILDINGS 57


This article was published in High Performing Buildings, Fall 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc. Posted at www.hpbmagazine.org. This article may not be copied and/or distributed electronically or in paper form
without permission of ASHRAE. For more information about High Performing Buildings, visit www.hpbmagazine.org.
large number of hours per year, and of ASHRAE Standard 62.1-2010 by roughly the latent heat recovery
C O N D E N S AT E C O L L E C T I O N S Y S T E M S
may have a relatively good potential is one good source for design occu- effectiveness of the device.
for condensate collection. pant density levels. Systems serving
The type of building and occu- higher density spaces such as lecture Cost Factors for New
pancy patterns also greatly influence halls, lobbies, or special use spaces Construction
the amount of outdoor air required, such as a natatorium are good candi- The overall cost of a condensate

Marie Mize
and the duration of that air require- dates for consideration. collection system in new construc-
ment. A few areas of the U.S. are The authors are in the midst of a tion is largely dependent on the
Collected condensate can be used to operate obvious for consideration of conden- research project intended to provide end use and is difficult to general-
water features even during drought conditions.
sate collection. The southeastern guidance on the influence of climate ize: cooling tower makeup requires
U.S. definitely should, while the dry on the relative desirability of a con- little more than a run of pipe, while
of incoming outdoor ventilation air Great Basin region in the western densate collection system. Initial irrigation or toilet flushing involves
depends on the ambient humidity U.S. likely should not (unless local results of this study for the various cisterns, pumps, and some degree of
and on the number of hours per year circumstances warrant otherwise). regions of the United States are repre- filtration and treatment equipment.
that mechanical cooling is required. In the other, more marginal areas sented in Figure 1 (see p. 57), which One common factor is the need to
Some locations may have fairly high it depends on building occupancy, shows the potential amount of water Retrofitting a building for condensate col- The minimum cost of adding a dedi- convey water to the end use or stor-
lection often requires a collection basin cated drain for condensate collection
humidity levels, particularly at design type and outdoor air requirements. collected (in gallons) from one cfm of and sump pump, which add about $1,000 is approximately $5,000 for new age, which is likely to be at or below
cooling conditions, but only require a A building that requires a great deal outdoor air through the entire year. to the project cost. A meter to track the construction projects. ground level, from an air-handling
relatively small number of hours per of outdoor air, such as a laboratory The calculations are made based condensate collection costs about $500. unit that is preferably some height
year of mechanical cooling. Others building, may make condensate col- on the hourly TMY3 weather data above. Air-handling units that
may be in a relatively dry climate lection feasible and desirable in a for that locality and with a maxi- produce condensate typically are
but require mechanical cooling for a marginal climate location. Table 6-1 mum supply air humidity ratio of 0.008 pound water/pound air. This needed to include condensate collec- accompanied by drains that join the
supply air condition is representa- tion on a building project. Buildings buildings sanitary drain network, so
tive of a typical value of 56F and with dedicated outdoor air systems a separate drain system is required
about 85% relative humidity. This would have a better condensate to reuse the condensate.
study also is considering the eco- potential than a recirculating air The cost of doing this can be
nomics of water, and additional ini- system. On the other hand, systems considered the minimum added
tial results are discussed later. that include total energy recovery cost of condensate collection com-
Note that HVAC system type also (latent as well as sensible heat) will pared to a conventional building,
may influence the design work have a reduced condensate potential with extra costs for cisterns and

Brian Wilkie, San Antonio Water System

Collected rainwater and condensate are


used to irrigate landscaping at the Sally
Cheever Girl Scout Leadership Center in San
Antonio, Texas. Pumps inside the tanks pro-
vide adequate pressure for irrigation.

Fa l l 2 0 1 0 H I G H PERFORMING BUILDINGS 59
HPB.hotims.com/33325-13
labor, including a floor drain, fit- rainwater, a lower cost option might If it is in Athens, Ga., the Summary
tings, and miscellaneous costs, be to drain condensate from a pent- expected annual condensate pro- Incorporating condensate collection
the total installation cost for a house AHU into the roof drainage duction rate is about 13.3 gallons into new building designs is practi-
dedicated drain to the cooling tower system. However, one drawback per cfm of continuous outside air, cal in many areas and situations,
is about $5,000. No controls are to this for buildings with exterior so the approximate annual yield is and is becoming more of a societal

Brian Wilkie, San Antonio Water System


included in this amount, but typi- downspouts is that the condensate 667,000 gallons. The water cost rate imperative. Existing buildings can
cally may not be needed. cools the downspout and could is $0.0075 per gallon (water and be retrofitted for condensate collec-
Some situations (especially in the cause secondary condensate (or sewer cost combined), so the annual tion, but the building design or lay-
case of retrofits) call for a collec- son of condensate) to form on savings is $5,000, and the simple out may preclude successful imple-
tion basin and sump pump to get the outside drain surface. This can payback is one year. mentation in some situations. While
the condensate into a drain line, lead to accelerated corrosion of the The same building in San Diego many factors come into play, such as
in which case the budget should downspout and, in some cases, dis- would produce about half as much building type and climate, this is a
A rainwater and condensate collection sys- include an extra cost allocation of coloration or damage to the faade. condensate (7.3 gallons), but the simple technology to incorporate into
tem is among several sustainable designs approximately $1,000 (based on combined water/sewer cost is about an integrated building design.
incorporated in the Sally Cheever Girl Scout
Leadership Center. The building team also
ground-mounted cooling tower. Let us the authors experience with recent Economic Payback Example one-third higher than in Athens, so
preserved heritage trees and used exterior assume that the system requires 50 ft retrofit projects). While it is not Consider again the four-story build- the payback period is still only 1.3 ABOUT THE AUTHORS
metal panels with high recycled content. of vertical pipe from the penthouse to required, it is often desirable to ing with a $5,000 condensate col- years. However, placing the build-
Tom Lawrence, Ph.D., P.E., is public ser-
ground floor, and another 50 ft of pipe include a water meter to keep track lection system, and assume it is a ing in Phoenix would yield 135,500
vice associate, Faculty of Engineering,
other equipment to be determined to the sump of the cooling tower. of the condensate produced; this laboratory building that requires gallons per year and a simple pay- University of Georgia, in Athens, Ga.
by the end use. As an example, Using published construction cost requires an additional $500. 50,000 cfm of outside air con- back period of 5.5 years based on Jason Perry is a research engineer
consider a four-story building with data for materials (assuming 2 in. In buildings where condensate tinuously and does not have latent local water/sewer costs. in the Engineering Outreach Service,
University of Georgia, in Athens, Ga.
a penthouse air-handling unit and Schedule 40 steel drain pipe) and is to be collected and stored with energy recovery.

HPB.hotims.com/33325-12

HPB.hotims.com/33325-8

You might also like