SUBSTATION NAME: 66 KV
TESTING OF CONTROL & RELAY PANEL
Panel Details:
Client : Honda Motorcycle & Scooter India Ltd
Designation : Non Directional Over current and Earth fault Relay.
RELAY TYPE : V57F-4AAA2BBA
Serial Number : EB164610011
Panel Name : BUSCOUPLER FEEDER
Aux. Volts : 110V DC
Nominal Current :1A
Settings:
CT Primary Current 1200 A
CT-Secondary Current 1A
1. MEASUREMENT:
Inject current in the relay as per the table below. Observe the reading on the relay display, in
primary values.
Phase Current Primary Current Displayed on Relay (Amp)
Injected (A) IL1 IL2 IL3 IN
L1-E 1 1198.00 0 0 1198.00
L2-E 1 0 1199.00 0 1199.00
L3-E 1 0 0 1198.00 1198.00
L1L2L3 1 1200.00 1200.00 1200.00 0
2. OVER CURRENT
IDMT CHARACTERISTCS(51) : SETTING CURRENT, I = 0.8 A, SETTING TIME, TMS = 0.05 s
TESTED BY M/S SREX WITNESSED BY M/S HONDA
3. EARTH FAULT :
B 1 0.043