N Series

SINGLE PHASE CAST RESIN TRANSFORMER FOR CONTROL, ISOLATION AND SAFETY

Ratings 25 5000 VA
Voltage Primary 230 / 400 / 460 V
range Secondary 6 / 12 V 12 / 24 V 24 / 48 V 115 / 230 V

Voltage selection by means of metal connection bridges, offering the full rated power at any
selected combination of input and output voltages.

Applications
Control Transformer: Transformer able to supply a high instantaneous power without voltage drop at the output. Very
suitable for interlocking contactors, relays and electro valves, as well as adaptation of the mains voltage to the
necessary supply voltage of the loads.

Isolation Transformer: Transformer with secondary voltage > 50 V, with double or reinforced isolation between primary and
secondary. Its construction provides an excellent degree of attenuation of electrical distortions. Recommended for:
- Electronic equipment, PLCs and automation systems.
- Auxiliary elements in electrical panels.
- Linear and switching power supplies.
Eliminates the risk of human accidents in case of unipolar contacts.

Safety Transformer: Transformer with secondary voltage < 50 V, with double or reinforced isolation between primary
and secondary. Eliminates any risk of human accidents in case of unipolar or bipolar contacts.

Standards
IEC 61558 / EN 61558 / UNE-EN 61558 (certified)................................................................... Control, Isolation and Safety
UL 506 ....................................................................................................................................... Control, Isolation and Safety
IEC 60742 / EN 60742 / UNE-EN 60742 (certified) ................................................................................ Isolation and Safety
IEC 60989 / EN 60989 / UNE-EN 60989 ................................................................................................................... Control

Characteristics

Frequency ............................................................................................................................................................ 50 - 60 Hz
Protection degree ..................................................................................................................................................... IP - 205
Ambient temperature ( ta ) ................................................................. + 45 C (IEC 61558, UL 506, IEC 60742, IEC 60989)
+ 25 C (IEC 60742, IEC 60989)
Humidity (without condensation ) ............................................................................................................................ < 95 %
Safety class ...................................... .......................................................................................................................... Class I
Installation .................................................................................................................................................................. Indoor
Operation ............................................................................................................................................................ Continuous
Test voltages :
- between Primary and Secondary ..................................................................................................................... 4600 V
- between Primary and Earth .............................................................................................................................. 3200 V
- between Secondary an earth ........................................................................................................................... 2500 V
Voltage drop at nominal power .................................................................................................................................... < 5 %
External covering ......................................................................................................................................................... Resin
Isolation .............................................................................................................................................. Class B-130 C ( IEC )
Class 105 ( UL )
Windings ................................................................................................................... Copper HC-200 C (double enamelled)
Refrigeration ................................................................................................................................................. (AN) Natural Air
Terminals ............................................................................................................................. Screws with supporting washers
Earthing ................................................................................................................................ connection on transformer base

1
N Series
SINGLE PHASE CAST RESIN TRANSFORMER FOR CONTROL, ISOLATION AND SAFETY

Cast Resin construction: robust and resistant casting system, suitable for application in humid, marine and corrosive environments as well as
under unfavourable vibration conditions.
Fast mounting system: support for mounting on DIN rail 35 x 7,5 mm (EN 50022) on transformers up to 100 VA, simplifying mounting in
electrical panels and cabinets.
Separation of connections: by means of isolating resin partitions.
Protection of connection terminals: by means of polycarbonate cover ( V-2 according to UL94 ) avoiding accidental electrical contacts.

Dimensions
Maximum
Overall Mounting
Reference weight
A B C D E
mm mm kg
N 25 50 97 74 80 34 6 0 76
N 40 50 97 84 80 34 6 0,95
N 63 75 96 85 80 56 6 1,3
N 100 75 96 100 80 56 6 1,8
N 160 84 102 110 86 65 6 2,7
N 200 96 112 106 96 77 6 3,2
N 250 96 112 116 96 77 6 3,7
N 315 108 122 125 106 89 6 4,7
N 400 108 122 135 106 89 6 5,4
N 500 126 145 147 125 102 7 7,1
N 630 126 145 167 125 102 7 9,1
N 1000 150 165 180 145 125 7 13,3
N 1600 150 165 210 145 125 7 16,9
N 2000 195 198 228 178 173 7 25,3
N 2500 195 198 248 178 173 7 30,5
N 3150 195 198 268 178 173 7 35,8
N 4000 240 235 280 212 218 7 47,7
N 5000 240 235 300 212 218 7 55

Rating Short circuit Short circuit


No load No load Efficiency
Instantaneous losses voltage Maximum
voltage losses (100C)
Reference power cos = (100C) (100C) conductor
ta = + 25 C ta = + 45 C 0,5 size
Vo Po PK ( * ) (*) UK ( * )
2
VA VA VA % W W % % mm
N 25 25 20 43 10 34 39 77 4 15 5 6
N 40 40 25 66 10 4.9 5.0 80.2 12.3 6
N 63 63 40 117 10 4.5 10.7 80.6 16.8 6
N 100 100 63 174 8 6.8 11.0 84.9 11.3 6
N 160 160 100 373 7.2 9.5 16.1 86.2 9.6 6
N 200 200 160 494 6.4 8.8 19.1 87.8 8.4 6
N 250 250 200 607 5.6 11 21.2 88.6 7.7 6
N 315 315 250 967 4.8 10.9 22.4 90.4 6.5 6
N 400 400 315 1.256 4 12.9 24.2 91.5 5.9 6
N 500 500 400 1.613 3.2 13.9 27.3 92.4 5.1 16
N 630 630 500 2.440 2.8 19.7 25.4 93.3 4.0 16
N 1000 1.000 630 3.967 2.6 18.8 37.7 94.4 3.8 16
N 1600 1.600 1.000 5.436 2.5 26.5 55.6 95.0 3.6 16
N 2000 2.000 1.600 6.576 2.4 38.9 57.0 95.4 3.2 16
N 2500 2.500 2.000 9.509 2.4 47.2 63.2 95.8 2.7 16
N 3150 3.150 2.500 13.711 2.3 56 65.9 96.3 2.3 16
N 4000 4.000 3.150 13.444 2.3 63.5 84.7 96.4 2.6 16
N 5000 5.000 4.000 15.125 2.2 76.9 96.0 96.7 2.5 16
( * ) the indicated values correspond to the power at ta = +25 C. For +45 C a correction has to be applied by multiplication with 0.63 of the PK and with 0.8 of the UK.

2
N Series
SINGLE PHASE CAST RESIN TRANSFORMER FOR CONTROL, ISOLATION AND SAFETY

References of standard transformers

Rating Secondary voltage


Primary voltage
ta = + 25 C ta = + 45 C 6 / 12 V 12 / 24 V 24 / 48 V 115 / 230 V
VA VA V References
25 20 230 / 400 NA 25 NB25 NC25 ND25
40 25 230 / 400 NA 40 NB40 NC40 ND40
63 40 230 / 400 NA 63 NB63 NC63 ND63
100 63 230 / 400 NA100 NB100 NC100 ND100
160 100 230 / 400 NA160 NB160 NC160 ND160
200 160 230 / 400 / 460 NA200 NB200 NC200 ND200
250 200 230 / 400 / 460 NB250 NC250 ND250
315 250 230 / 400 / 460 NB315 NC315 ND315
400 315 230 / 400 / 460 NB400 NC400 ND400
500 400 230 / 400 / 460 NB500 NC500 ND500
630 500 230 / 400 / 460 NC630 ND630
1.000 630 230 / 400 / 460 NC1000 ND1000
1.600 1.000 230 / 400 / 460 NC1600 ND1600
2.000 1.600 230 / 400 / 460 NC2000 ND2000
2.500 2.000 230 / 400 / 460 NC2500 ND2500
3.150 2.500 230 / 400 / 460 ND3150
4.000 3.150 230 / 400 / 460 ND4000
5.000 4.000 230 / 400 / 460 ND5000

Ordering special transformers


The N series transformers are available in special executions, with special voltages, special power ratings, distribution of power ratings,
regulations , electrostatic screens , etc . When ordering, specify the characteristics different from the standard ones and following reference:

Reference NS

Voltage selection system

Example:

To select a supply voltage


400 V, place the metal bridge
between terminal 2 - 3 and
connect the supply cables to
terminals 1 and 5.

In case the transformer is a


NA , and bridges are placed
between terminals 6 - 7 and
between terminals 8 - 9, an
output voltage of 6 V ( V21 ) is
obtained between terminals 7
Reference V21 V22 and 8.
NA 6V 12 V
NB 12 V 24 V The connection bridges for the voltage
NC 24 V 48 V selection are delivered with each
ND 115 V 230 V transformer.
3
N Series
SINGLE PHASE CAST RESIN TRANSFORMER FOR CONTROL, ISOLATION AND SAFETY

Protection type and rating

A ) Protection at the primary side of the transformer :

The supply circuit of the transformer should only be protected against short circuits, by means by a protection with rating of at least 2
times the nominal current of the transformer due to the inrush current of the transformer (about 20 times I nominal during 10 ms) .

PRIMARY
230 V 400 V 460 V
Reference
Rating Type Rating Type Rating Type
N 25 0 25 T 0 125 T -- --
N 40 0.40 T 0.20 T -- --
N 63 0.63 T 0.315 T -- --
N 100 1 T 0.50 T -- --
N 160 1.6 D , aM 1 D , aM -- --
N 200 2 D , aM 1 D , aM 1 D , aM
N 250 2.5 D , aM 1.25 D , aM 1.25 D , aM
N 315 3.15 D , aM 1.6 D , aM 1.6 D , aM
N 400 4 D , aM 2 D , aM 2 D , aM
N 500 5 D , aM 2.5 D , aM 2.5 D , aM
N 630 6 D , aM 3.15 D , aM 3.15 D , aM
N 1000 10 D , aM 5 D , aM 5 D , aM
N 1600 16 D , aM 8 D , aM 8 D , aM
N 2000 20 D , aM 10 D , aM 10 D , aM
N 2500 25 D , aM 12.5 D , aM 12.5 D , aM
N 3150 32 D , aM 16 D , aM 16 D , aM T : T type, temporised fuse
N 4000 40 D , aM 20 D , aM 20 D , aM aM : aM type fuse
N 5000 50 D , aM 25 D , aM 25 D , aM D : magnetic circuit breaker, curve D

B ) Protection at the secondary side of the transformer :

The secondary side of the transformer should be protected against overloads, by means of a protection rated equal or inferior to the
secondary current of the transformer.

SECONDARY
6V 12 V 24 V 48 V 115 V 230 V
Reference
Rating Type Rating Type Rating Type Rating Type Rating Type Rating Type
N 25 4 gG C 2 gG C 1 gG C 0 50 T 0 20 T 0 10 T
N 40 6 gG , C 3.15 gG , C 1.6 gG , C 0.80 T 0.315 T 0.16 T
N 63 10 gG , C 5 gG , C 2.5 gG , C 1.25 gG , C 0.50 T 0.25 T
N 100 16 gG , C 8 gG , C 4 gG , C 2 gG , C 0.80 T 0.40 T
N 160 25 gG , C 12.5 gG , C 6 gG , C 3.15 gG , C 1.25 gG , C 0.63 T
N 200 32 gG , C 16 gG , C 8 gG , C 4 gG , C 1.6 gG , C 0.80 T
N 250 -- -- 20 gG , C 10 gG , C 5 gG , C 2 gG , C 1 gG , C
N 315 -- -- 25 gG , C 12.5 gG , C 6 gG , C 2.5 gG , C 1.25 gG , C
N 400 -- -- 32 gG , C 16 gG , C 8 gG , C 3.15 gG , C 1.6 gG , C
N 500 -- -- 40 gG , C 20 gG , C 10 gG , C 4 gG , C 2 gG , C
N 630 -- -- -- -- 25 gG , C 12.5 gG , C 5 gG , C 2.5 gG , C
N 1000 -- -- -- -- 40 gG , C 20 gG , C 8 gG , C 4 gG , C
N 1600 -- -- -- -- 63 gG , C 32 gG , C 12.5 gG , C 6 gG , C
N 2000 -- -- -- -- 80 gG , C 40 gG , C 16 gG , C 8 gG , C
N 2500 -- -- -- -- 100 gG , C 50 gG , C 20 gG , C 10 gG , C
N 3150 -- -- -- -- -- -- -- -- 25 gG , C 12.5 gG , C
N 4000 -- -- -- -- -- -- -- -- 32 gG , C 16 gG , C
N 5000 -- -- -- -- -- -- -- -- 40 gG , C 20 gG , C

T : T type temporised fuse


gG : gl gG type fuse
C : magnetic circuit breaker curve C
4
N Series
SINGLE PHASE CAST RESIN TRANSFORMER FOR CONTROL, ISOLATION AND SAFETY

Determination of a control transformer

For calculation and selection of a transformer to be used for control and interlocking, following data is necessary:

1_ VA maint. The sum of the maintenance power ratings of all elements: contactors, relays, electro valves, signal lights, etc...
2_ VA conn. The maximum sum of the connection power ratings of the elements that trip simultaneously during switching
operations.
3_ cos maint. and conn. of each of the elements of the switching sequence.

A ) Calculation for transformer selection, example:

In the example, the maintenance power rating is the sum of the total VA maint. of the three contactors and the maximum sum of the
connection power ratings is occurring when during a switching operation the biggest contactor trips.

Main data:
Maintenance During connection
Number of contactors VA maint. cos maint. VA conn. cos conn.
2 10 0,28 68 0,8
1 62 0,25 860 0,41
Consider cos = 0,5 when not known
Calculation:

VA total = VA maint. + VA conn.


VA total = (10+10+62) + 860 = 942 VA Instantaneous power

W total = [VA maint. x cos maint.] + [VA conn. x cos conn.]


W total = [ (10x0,28) + (10x0,28) + (62x0,25) ] + (860x0,41) = 373,7 W

cos = W total / VA total


cos = 373,7 / 942 = 0,40 cos (when not coinciding, use the one immediate superior)

B ) Using the table for transformer selection:

In line cos (0,40), look for the instantaneous power value equal or immediate superior to the calculated total instantaneous power (1138
VA) in order to obtain the transformer reference. In case of the example, the reference of the transformer to be used is N 315. Check that the
transformer power rating is superior to the VA maint. of the contactors, signal lights and other elements to be supplied by the transformer.

cos Instantaneous Power (VA)


0,9 35 55 85 106 231 304 369 581 751 963 1447 2345 4112 5290 7947 11663 12670 13750
0,8 37 58 90 115 251 330 401 630 813 1042 1563 2531 4158 5238 7769 11388 11921 14235
0,7 39 61 94 132 286 377 460 726 939 1205 1814 2944 4562 5661 8330 12100 12410 14622
0,6 41 63 105 146 316 417 508 803 1038 1331 2003 3244 4736 5783 8417 12253 12191 14892
0,5 43 66 117 174 373 494 607 967 1256 1613 2440 3967 5436 6576 9509 13711 13444 15125
0,4 46 71 130 202 434 576 711 1138 1481 1903 2888 4708 6065 7192 10276 14756 14152 15817
0,3 50 80 140 235 502 668 829 1333 1736 2232 3399 5550 6612 7695 10876 15613 14578 16026
0,2 57 98 173 291 615 823 1033 1681 2204 2840 4353 7160 7974 9115 12770 18127 16632 18264
N 315

N 1000

N 1600

N 2000

N 2500

N 3150

N 4000

N 5000
N 100

N 160

N 200

N 250

N 400

N 500

N 630

Transformer
N 25

N 40

N 63

reference

You might also like