You are on page 1of 22

SPEC FOR DATA

INTRODUCTION:

1. Interfacing all DVRs from different locations to LAN/PIN to view all


respective units through PIN PCs over the LAN.
2. Supply and implementation of all other associated hardware, software
and licenses for DVRs and 43 existing client PIN machines and 7 new
clients.
3. Maintenance of the system.

1.Standard Specification
A. Scope
B. Bids
C. Design & Construction
D. General Requirement
E. Nameplate
F. Service
G. Inspection and Testing (FAT)
H. Site Acceptance Test
I. Warranty
J. Annual Maintenance Contract (AMC)
K. Mandatory spares
L. Test tools
M. Rejection
2.Job Specification
1. Application
2. System Description
3. Vendors scope of supply (Bill of Materials)
4. Camera location
5. Summary of CCTV system
3.Data Sheet
1. Camera Station
2. Positioning Device, Pan and Tilt unit
3. Digital Video Recorder (DVR)
4. Client Machine
5. Command Receiver

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 1 of


SPEC FOR DATA

6. Video Amplifier
7. Cables and Miscellaneous
4.Drawings
1. Drawing No.1
2. Drawing No.2
3. Drawing No.3
4. Drawing No.4
5. Drawing No.5

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 2 of


SPEC FOR DATA

STANDARD SPECIFICATION FOR CLOSE CIRCUIT


TELEVISION (CCTV) FOR PLANT SURVEILLANCE

GENERAL

A. Scope

1. This Specification, together with the data sheets attached herewith,


covers the requirements for the Design, Materials supply, Nameplate
marking, Testing, Inspection, Shipping, Installation and Commissioning
of the Close Circuit Television (CCTV).

2. The related Standards referred to herein and mentioned below shall be of


the latest edition prior to the date of purchasers enquiry.

IS-2147 Degree of Protection provided by Enclosures for low


Voltage Switchgear and Control Gears.
IS-2148 Flame proof Enclosures for Electrical Apparatus.
IEC-529 Classification of degree of protection provided by
Enclosures.
IEC-79 Electrical Apparatus for Explosive Gas Atmospheres.
DIN 50049 Document on Material Testing
ANSI/ ASME American National Standards Institute / American
Society of Mechanical Engineers.
B1.20.1 Pipe Threads.

3. In the event of any conflict between this specification, data sheets, related
standards, codes etc, the vendor should refer the matter to the purchaser
for clarification and only after obtaining the same should proceed with
the manufacture of the items in question.

4. Purchasers data sheets indicate the minimum requirements of Camera,


Lens, Digital Video Recorder (DVR), Pan & Tilt unit, Monitoring unit
etc. However, this does not absolve the vendor of the responsibility for
proper selection with respect to the following:

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 3 of


SPEC FOR DATA

a) Selection of lens focal length, camera resolution, monitor resolution,


controllability limits of pan and tilt mechanism etc for proper
monitoring.
b) Selection of compatible camera, controls unit and monitor for the
special application.

B. Bids

1. Vendors quotation shall include a detailed specification sheet for each


item providing all the details regarding type, construction, power supply
requirements, etc., of a Close Circuit Television System and its
accessories.

2. Following data MUST be furnished by vendor in their offer:

a) Maximum and minimum viewable distance.


b) Maximum tilt or pan angle possible.
c) Voltage and frequency variation.
d) Pan and tilt speed.
e) Interconnecting cable specifications.

3. Vendor shall provide detailed dimensional and sectional drawings


including mounting details for all the units offered. All dimensions shall
be in millimeters.

4. The offer shall also include a blockdiagram showing all units with
model numbers and interconnecting cabling with size and type indicated.

5. Vendor shall furnish certificate for weatherproof housing for offered


system from statutory authority along with the offer.

6. Vendor shall furnish a list summing up all the deviations, if any, from the
purchasers data sheets. Also vendor should provide reasons for these
deviations wherever possible.

7. Vendor shall enclose catalogues giving detailed technical specifications


and their technical information for the items covered in the bid.

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 4 of


SPEC FOR DATA

8. Vendors quotation, catalogues, drawings and maintenance manuals shall


be in English.

9. Vendor shall also quote for the following: -

a) 10% Mandatory hardware spares (Minimum one item each type as


offered for this tender). The mandatory spares shall include Camera,
Zoom lens, Pan and tilt unit, DVR, Client Machine, Command
receiver, Video Amplifier.
b) Commissioning tools and special tools like digital Multi meter (4
nos.), earth megger, line tester, electrical portable hand drilling
machine, Crimping Tools and Maintenance tool kits, tool box (4
nos.) having screw driver set, spanners and allen key , etc.
c) Annual Maintenance Contract (AMC) for three years (year wise
break-up required), which will be used after expiring the warranty
period. Vendor has to depute engineer for preventive maintenance
(four visits per annum) for preventive maintenance. Further vendor
shall quote rate for emergency visit on Man-day basis for emergency
problems. Based on the actual duration, payment will be made.
CPCL will maintain spares as per vendor recommendation.

C. Design & Construction

1. Power Supply

The control system, monitors, camera video recorders and other critical
components of the CCTV system shall be connected to the plants
Power Supply system: 110V AC +or- 10%, (50 Hz + or - 3Hz).

2. Degree of protection

The minimum enclosure protection degree for the system components shall
be in accordance with IEC 529 as follows.
- Outdoor IP 65 minimum
- Indoor GENERAL PURPOSE.
- Panels with open door IP20 (Live parts shielded)

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 5 of


SPEC FOR DATA

1. Control panels monitors and all peripherals will be installed in air-


conditioned rooms. Cameras will be installed outdoors where conditions
apply as per site and utility data. Integrated camera with Pan and Tilt unit
will not be accepted.

2. The flame protection type of the electrical materials shall be in


accordance with the area classification and conform to IS: 5571. When
certain materials require to be of a particular type of protection, this will
be specified in the requisition.

3. Zone classification, gas group and temperature class shall comply with
the requisition.

4. All materials installed inside a hazardous area shall have a certificate of


conformity or a declaration of compliance issued by the appropriate
authority.

D. General Requirements

1. The system shall include all hardware, wiring, cabinets, materials and
application software for fully functional system as defined in the
requisition.

2. Components shall be of industrial quality. Consumer electronics is not


allowed.

Camera & Lens : As per data sheet


Camera housing : As per data sheet
Pan & Tilt unit : As per data sheet
Receiver Driver Unit : As per data sheet
Digital Video Recorder (DVR) : As per data sheet
Client Machines : As per data sheet
Cable : As per data sheet

F. Service

1. Training

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 6 of


SPEC FOR DATA

Supplier is required to provide training on system operation and


maintenance for 3 engineers and 6 Technicians at owners site. Vendor shall
provide necessary training manual and instruction manual.

2. Installation and Commissioning

Supplier is required to install and commission the total system as per the
technical specification and the drawing 1,2 3,4 and 5. Cable laying is also in
the vendor scope. Owner shall provide cable tray and assistance to open and
close cable trench. Vendor has to lay all the cable from the field to control
room and within control room. The routine of the cable will be discussed
during detailed engineering.

G. Inspection and Testing

1. Vendor shall submit the following test certificates and test reports for
purchasers review:
a. Performance test report.
b. Certificates form a statutory body for Weather Proof (IP 65)
enclosures.
c. Dimensional drawing.
d. System architecture

2. Factory Acceptance Test (FAT)

Vendor shall test and demonstrate integrity of the system hardware and
software at vendors site. No material or equipment shall be transported until
all required tests are successfully completed and certified 'Ready for
Shipment' by the owner deputed officials. Factory Acceptance Test shall be
carried out in the presence of the Owner. Vendor shall furnish standard FAT
procedure at least four weeks in advance for owner comments and
acceptance. Vendor shall intimate exact date of FAT at least two weeks in
advance.

Following tests/checks shall be carried out as a minimum.

a. Physical dimensional checks and workmanship

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 7 of


SPEC FOR DATA

b. Performance testing of all individual system and integrated system.


c. Review of all certificates and test reports as indicated in this
specification.

H. Site Acceptance Test

The following site acceptance will be carried out as a minimum:

a. System Architecture Performance


b. Functional test of all individual and integrated components of the
system.

Note: The detailed Site Acceptance procedure will be provided during the
detailed engineering of the system.

K. Mandatory Spares

L. Test tools

Vendor shall supply 5 nos. of digital Multimeters (3 1/2 digit) of reputed


make. Vendor shall supply 5 nos. of portable tool kit consisting of all types
of screwdrivers, spanners, crimping tools, tester etc.

M. Rejection

Vendor shall make his offer in detail with respect to every item of the
purchasers specification. Any other not confirming fully to this shall be
summarily rejected.

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 8 of


SPEC FOR DATA

Summary of Job:

- Design , Engineering
- Manufacture
- Testing( Factory Acceptance Test and Site Acceptance Test)
- Supply
- Installation
- Commissioning
- Training
- Documentation
- Warranty

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 9 of


SPEC FOR DATA

1. Vendors Scope of Supply (Bill of Materials)

Hardware:

-
- .

Software:

Digital Video Recorder (DVR) software (Server Software) as per


attached technical specification with necessary license for each control
room system as per drawings (drawing no. 1,2,3,4 and 5)
Client software to interact with all the proposed DVRs simultaneously
with necessary license for 50 users (existing and proposed clients) as per
attached technical specification. Client software shall be Web enabled.

4.
Note: Cable tray wherever required, will be provided by CPCL. Trench
opening and closing will be carried out by CPCL. Single power source in
each control room will be provided by CPCL. Vendor shall carry out power
distribution within the system.

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 10 of


SPEC FOR DATA

DATA SHEET
Camera Station (CS)

The CS shall be composed of video camera, lens, Pan and Tilt, Command
receiver, interconnection cables and accessories. All to be included in the
scope of supply. Each CS shall only have one interconnection cable in order
to lower the installation cost and increase operation safety. There shall be no
outside cabling between field cable junction box, pan and tilt unit and
camera housing.

Camera Function

- To capture and transmit images from plant


- Automatic control of image brightness (Electronic shutter)
- Automatic control of lens iris
- Day and night Operation

Technical requirements

Type : Hi sensitivity and Hi Resolution


(Day and Night Operation)
Day / Night change mode : I R filter
Image : COLOR
Output video signal : 1.0 V Peak to Peak, 75 Ohms
Lens format : 1/2 interlined CCD
Scanning Elements : (H: 768 X V: 494)
Scanning system : PAL standard
Minimum illumination
@ f/1.2 / 30IRE : 0.04 lux
Autoelectronic Shutter : 1/60 Fixed or 1/60-100,000
seconds linear
Back light compensation : Required
Controls : Zoom, focus, Iris
Temperature range : 0 to 50 0C
Video output : 1V peak to peak composite
Negative sync
Camera identification : yes
TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 11 of
SPEC FOR DATA

Area Classification : Weather proof IP 65

Lens type

Lens focal length : 8 to 80 mm


Zoom range : 10 X
Zoom control : Motorised
Focus control : Motorised
Iris Control : Automatic
Present function : Required
Mounting accessories : Required
Min. object distance : Vendor to specify
Max. object distance : Vendor to specify
Angle of installation : To match installation
Angular field view : Vendor to specify
Warm up time : 1 second
Scan system : PAL standard
Area Classification : Weather proof IP 65
Protection degree : IP 65,
View window material : Tempered glass
Materials, Accessories and
screws material : Vendor to specify
Finish : Electro polished
Cabling (fixed housing) : One multicable preferred
Cabling (housing w/pan and tilt): Internal, through pan/ tilt assembly

General

IP Protection rating : IP 65
Power supply : From Control unit or PDB
Sunshield : Required
Fasteners : Stainless steel
Utility requirement : Vendor to indicate
Cable entry : NPTF with double compression
Ex- proof cable gland
Camera Make and Model no. : By vendor
Dimension : By vendor

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 12 of


SPEC FOR DATA

Positioning device, Pan and Tilt unit

Function

The positioning device (pan and tilt) shall be able to position the camera
horizontally and vertically the camera. Movement of the device shall be
smooth. The pan and tilt unit shall be one device only with no external
cabling.

The pan and tilt unit shall comply with following:

Pan range : 0 degree to 350 degrees


Tilt range : + / - 90 degrees
Dimensions : By supplier (in order to comply with
camera and camera housing )
Torque : By supplier (in order to comply with
camera and camera weight)
Electrical connections : One connector only, through integrated
junction box
Stops : Externally adjustable
Speed ( no load ) : Pan 6 degrees / second and
Tilt 3 degrees / second
Preset Function : Required
Loading : Suitable for camera and camera housing
Temperature : 0 to 50 Deg. C
Area Classification : Weather proof
Protection degree : IP 65
Power Consumption : Vendor to specify
Finish : Electro polished

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 13 of


SPEC FOR DATA

Digital Video Recorder (DVR)- Server Machine Specification

DVR type shall be TRIPLEX (Simultaneously Record, Playback, live and


playback view, LAN Access)
It shall be capable to connect 16-camera input and one Analog Video
output, one SVGA Video output and one LAN Video output (TCP/IP) set
as a minimum.
The recording speed shall be minimum 100 frames per second.
It shall have a dedicated keyboard to create configuration.
It shall have a dedicated monitor (21 SVGA) to view locally.
It shall be possible to assign password for atleast three levels to set
priority.
It shall have Alarm protection, Motion Detection, Telemetry control.
It shall be possible to assign Camera Title (16 alphanumeric characters
per camera)
It shall have network interface by RJ 45 (10/100 Base-T) connection.
It shall have data ports for RS422 / RS485 interface.
The internal Hard Disk (HDD) shall have minimum 1 T Byte (1000 GB)
capacity.
OS and application Software shall be up-gradable and it should not be
embedded type.
All necessary hardware and software shall be provided to access this
DVR from any of the existing maximum 50 client machines over CPCL
LAN.
The client software should be Web enabled.

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 14 of


SPEC FOR DATA

Power Supply

110 V AC; 50Hz

Vendor to distribute the power from the remote control unit to all units of
CCTV system. The purchaser shall provide power supply at a single point
only (one feeder) for each configuration drawing and further distribution to
the system is in vendors scope.

Model No. : By vendor

Video Signal Amplifier ( If required )

Function : To ensure crisp & clean images for


Monitoring.
Area Classification : IP 65
Mounting Accessories : Required

Cables

Purpose: All interconnection cables between cameras, monitors, power


supply and control cables for all the vendor supplied equipments including
all the connectors etc. vendor shall use cable tray and clamp for proper
dressing of the cable and termination.

Quantity: As required (Refer drawing 1,2 3,4 and 5 for distances)

Type: *

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 15 of


SPEC FOR DATA

Cable parameters: *Note-2

Cable size: *Note-2

Make: *

Notes:
1. '*': Information to be provided by vendor.
2. Cable parameters shall be decided by the vendor based on the distances
specified for each unit for proper operation of the system.
3. In case of any accessory like relays box/ repeaters etc. required, due to
distance limitation, same shall be offered by vendor.

Minimum Technical requirements for multicable (outdoors)

Flame retardant to : IEC332.1 and 3


UL Standard : 1729
Oil Resistant : System 518
Strain relief : Braided
Ambient temperature : - 40 to + 80 0C
Oil and Mud resistant : Yes
Nominal Breaking : More than 1400kg.
Screen : 0.15mm copper braid

Power wire

Thickness : 4 x 2.5 mm2,


Conductor : 50 x 0.25 mm tinned copper
Insulation : FRLS
Screen : Wrapped with Aluminized Polyester

Cabinet

Cabinet included in this scope of supply, shall be able to support the power
supply and applicable termination hardware. The cabinet access for cable
connections or maintenance shall be frontal or rear end. Cable entry into the
cabinet is from the bottom as standard.

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 16 of


SPEC FOR DATA

Scope

All cables as indicated above shall be provided by Vendor. All individual


type cables shall be supplied in single run. Intermediate flame-proof junction
boxes/ connector shall be provided, if required.

Laying of all the cables is in vendor scope. Cable tray will be provided by
the owner and wherever cable trench is to be open, owner shall provide
assistance to open and close cable trenches. Sine cable trenches already
available in the area, there will not be any requirement to dig the cable
trenches.

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 17 of


SPEC FOR DATA

(DRAWING No.-1)

DHDS CONTROL ROOM


DHDS-1
1000 M

DHDS-2
1000 M DIGITAL VIDEO
RECORDER
WITH POWER SUPPLY
LEB
200 M

BHS
200 M

CAMERAS
Client Machines
For Camera
Operation
DVR Monitor

LAN OUTPUT
(TCP/IP)
Switcher unit
(CPCL SCOPE)

UTP Cables

Note: Vendor shall supply MONITORS and console to house these monitors. The
CONSOLE shall be placed in the control room and it shall be designed aesthetically in
order to match with DCS panels.

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 18 of


SPEC FOR DATA

(DRAWING No.-2)

COGEN CONTROL ROOM

200 M

DEARATOR
DIGITAL VIDEO
150 M RECORDER
WITH POWER
SUPPLY
POWER HOUSE

300 M

OLD PROJECT SITE


CAMERAS

DVR Monitor
Client Machine
For Camera
LAN OUTPUT
Operation
(TCP/IP)
Switcher unit
(CPCL SCOPE)

UTP Cables

Note: Vendor shall supply MONITORS and console to house these monitors. The
CONSOLE shall be placed in the control room and it shall be designed aesthetically in
order to match with DCS panels.
TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 19 of
SPEC FOR DATA

(DRAWING No.-3)

OLD POWER HOUSE CONTROL ROOM

DM PLANT

300 M

DIGITAL VIDEO
RECORDER
GT WITH POWER
CONTROL
ROOM
SUPPLY
600 M

CAMERAS

Client Machines
For Camera
Operation
DVR Monitor

LAN OUTPUT
(TCP/IP)
Switcher unit
(CPCL SCOPE)
UTP Cables

Note: Vendor shall supply MONITORS and console to house these monitors. The
CONSOLE shall be placed in the control room and it shall be designed aesthetically in
order to match with DCS panels.
TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 20 of
SPEC FOR DATA

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 21 of


SPEC FOR DATA

TECHNICAL SPECIFICATION FOR CCTV SYSTEM Page 22 of

You might also like