Professional Documents
Culture Documents
Design Tips
http://www.power-eng.com/articles/print/volume-120/issue-11/features/plant-instrument-air-system-
useful-design-tips.html
The equipment associated with the Instrument air system as used in the industry, generally consists
of an air compressor, air dryer and an air receiver fitted with a liquid drain trap. The instrument air
system is utilized by various plant instrumentation, some of which may have a critical role in plant
operation and safety. Therefore, the equipment should be properly sized and capable of producing
the required air quality.
This article provides an overview of some of the key points and calculations associated with the
instrument air system, which can assist the design engineer in his task.
1.Pressure Dew Point: "The pressure dew point as measured at the dryer
outlet shall be at least 10C (18F) below the minimum temperature to which
any part of the instrument air system is exposed. The pressure dew point
shall not exceed 4C (39F) at line pressure".
2.Particle Size: "A maximum 40 micrometer particle size in the instrument air
system is acceptable for a majority of pneumatic devices".
Consider ambient conditions of 14.7 psia, 68F and 40 percent Relative Humidity. The dew point can
be calculated as follows:
From steam tables 0.135 psia is the saturation vapor pressure at 43F, therefore normal dew point is
43F
Now consider the same case when dew point (that is, pressure dew point) is evaluated at a higher
pressure of 114.7 psia. In this case, the moisture vapor pressure evaluated above at 0.135 psia is
multiplied by the pressure ratio, giving 0.135 x 114.7/14.7= 1.053 psia. From steam tables, this is the
saturation pressure at approximately 104F.
Therefore the pressure dew point is 104F compared to normal dew point of 43F.
The dryers work by adsorbing moisture on desiccant material such as alumina, silica gel molecular
sieves. The desiccant material is contained in two packed towers which are alternately in service or
being regenerated. The regeneration can be achieved by different methods, such as, using a purge
of dry air from the operating tower or by using internal heaters or by an external heat source. Use of
purge of dry air is a simple process with the discharge air purged to the atmosphere. However, use
of purge air consumes about 15 to 20 percent of the compressed air capacity and is best utilized
when there is sufficient excess air capacity.
The capacity of air dryers as provided by the vendor is generally in terms of "inlet scfm" at a service
pressure of 100 psig and service temperature of 100F. At different service conditions, the inlet flow to
the dryer needs to be corrected by multiplying by the pressure correction factor and the temperature
correction factor.
If service pressure is higher than 100 psig (say 120 psig) the flow capacity of the dryer increases by
the pressure ratio (120+14.7)/(100+14.7)=1.17. On the other hand, if service temperature is higher
than 100F (say 115F), the flow capacity of the dryer decreases by the ratio of moisture saturation
vapor pressure ratio at 100F and 115F (that is, 0.9492 psia/1.4711 psia=0.64).
Based on above, the corrected flow to a dryer rated for inlet of 100 scfm (at 100 psig/100F) and
operating at 120 psig/115F, would be =100 x 1.17 x 0.64 = 75 scfm. Note that this is 25% less than
the rated value of 100 scfm.
For example, consider an end-user demanding 10 scfm of air with the understanding that standard
conditions are at 14.7 psia and 32F. Air density () at these condition of pressure and temperature is
=p/RT= 0.808 lbs/cu. ft. In other words the air demand is for 10 ft3/min *0.808 lbs/ft3= 8.08 lbs/min.
Now consider a reciprocating compressor supplying 10 scfm air at standard conditions of 14.5 psia,
68F. Air density () at these condition of pressure and temperature is =p/RT= 0.742 lbs/cu. ft. In
other words the air supply is providing 10 ft3/min *0.742 lbs/ft3= 7.42 lbs/min of air. This quantity of
air is only 92% of the air demand of 8.08 lbs/min and therefore does not meet the requirement of the
end user.
In case of a centrifugal compressor, the lower ambient pressure and higher ambient temperature at
suction conditions leads to lower discharge pressure.
Note that in some cases, compressor capacity is stated in terms of Free Air Delivery (FAD) which is
merely the discharge volumetric flow converted back to inlet conditions of the compressor.
For example, assume that the demand for compressed air requires 100 psig pressure in the air
receiver and the compressor is set to operate in a pressure band to load at 120 psig and unload at
130 psig. This means that in case the compressor is off-line, or if air demand increases, a storage
volume corresponding to air receiver pressure ranging from 120 psig to 100 psig is always available.
The air receiver volume can be calculated from the following equation which shows the time taken
for the air receiver to drop from the higher pressure point to the lower pressure point within the
operating pressure band:
t=V(p1-p2)/C*pa
Where,
t= time, mins
If air is supplied to the air receiver during the time interval being evaluated, then the value of C must
be reduced by the rate of air supplied.
Air Compressor:
There are three types of air compressors generally used in the industry. These are as follows:
1.Centrifugal Compressors
2.Reciprocating Compressors
The reciprocating compressors have effective multistep capacity control but has a high first cost with
special foundations for vibrations and needs routine maintenance.
The rotary screw compressor is popular in instrument air service since it is a compact package at a
relatively low first cost and provides oil-free air.
The balance line allows air which has entered the trap to be discharged back to the receiver. Without
the balance line, air binding can occur in the liquid trap.
The size of the liquid trap depends on the differential pressure across the trap and the required
discharge flow rate. The required discharge flow rate can be computed as follows:
Assume ambient air is at 14.5 psia, 70F and 70% relative humidity:
Now (0.022 moles/min) x 18 x (60/8.338) = 2.89 gallons per hour. This is the amount of water to be
discharged from the liquid trap at the bottom of the air receiver.
Conclusion:
The demand for compressed air may vary significantly at the plant. Therefore, the compressed air
system must be designed such that that all components in the system (compressor, air dryer, air
receiver and drain) are able to cope with the variation in demand. In this context, the design tips
provided in this paper may help the system designer.
Author