Grid Solutions

Multilin D60
High-Speed Transmission Line Protection with Protection & Control
Single and Three-Pole Tripping Phase & Ground distance (5 zones) with
independent settings
The Multilin D60 is a high-end, cost-effective distance protection relay intended for protecting
Reverse power, out-of-step tripping and power
transmission lines and cables, providing reliable and secure operation even under the worst case power
swing blocking
system conditions. Part of the Universal Relay (UR) family, the D60 comes with a variety of versatile
features, truly integrating protection, monitoring, metering, communication and control in one easy- Line pickup, thermal protection, under/over
to-use device. frequency
Four-shot dual breaker autorecloser broken
conductor
Key Benefits
High-speed five zone quad or mho, phase and ground distance protection for greater system reliability
Reliable and secure protection on series compensated lines Advanced
Superior phase selection algorithm ensures secure high-speed single-pole tripping Communications
Supports multiple standard and customizable pilot schemes for fast fault clearance within the 3 independent Ethernet ports with IEEE 1588
protected zone support
Flexible programmable logic for building customized schemes Advanced IEC 61850 Edition 2 implementation
Simplified teleprotection interfaces with direct I/O communications hardware for transfer trip and and IEC 61850-9-2 process bus support
pilot-aided distance schemes Supported industry protocols: IEC 61850 Ed.2,
Embedded Synchrophasor measurement capabilities (per IEEE C37.118), eliminating the need for SFTP, MMS File Transfer Service, DNP 3.0,
dedicated PMUs and support for synchrophasor multi-cast (per IEC 61850-90-5) reducing bandwidth Modbus Serial/TCP, IEEE 1588, IEC608705104
and communications infrastructure costs and 103, PRP, SNTP, HTTP, TFTP
Advanced IEC 61850 Ed. 2 certified implementation, complete settings via SCL files and Direct I/O for secure, high-speed exchange of
IEC 61850-9-2 process bus solution enable resource and platform managing optimization and reduce data for DTT & pilot-aided schemes
cost of ownership
Routable GOOSE (R-GOOSE) enables GOOSE messages going beyond the substation, which enables
wide area protection and control applications Cyber Security
Increased network availability via failover time reduced to zero through IEC 62439-3 PRP support
CyberSentry provides high-end cyber security
aligned to industry standards and services
Advanced fault and disturbance recording, including internal relay operating signals, eliminating the
(NERC CIP, AAA, Radius, RBAC, Syslog)
need for external recording devices
Setting for security audit trails, tracking
Supports latest edition of waveform capture (COMTRADE 2013) simplifying fault records management
changes to D60 configurations

Applications
Overhead lines and underground cables of different voltage levels Monitoring & Metering
Single and dual-breaker circuits requiring single/three pole autoreclosing and independent Advanced recording capabilities with high-
synchrocheck capacity event recorder, configurable and
extended waveform capture and data logger
Circuits with in-zone power transformers and tapped transformer feeders
P & M class synchrophasors of voltage,
Secure application with Capacitively-Coupled Voltage Transformers (CCVTs)
current, and sequence components
Backup protection for generators, transformers and reactors
Supports IEEE C37.111-1999/2013, IEC 60255-
24 Ed 2.0 COMTRADE standard
D60 Line Distance Protection System

Protection & Control D60 - Protection, Metering, Monitoring and Control


As part of the UR family of Protection &
Control devices, the D60 offers a high degree
of modularity in its design and functionality,
providing superior performance while meeting
the toughest requirements of the marketplace.

Advanced protection and control features of this


relay includes:

Distance Protection
The core of the D60 relay is the distance function
providing a high degree of sensitivity and
selectivity for all types of faults. The distance
function comes with five zones of phase distance
and ground distance, providing the user maximum
flexibility to cater to different applications,
including primary line protection and backup
protection for busbars, generators, transformers
and reactors. The relay can be applied to power
The D60 is the single point for protection, control, metering, and monitoring in one integrated device that
systems with different earthing conditions, lines can be easily connected directly to HMI or SCADA monitoring and control systems.
with in-zone transformers or tapped transformer

Functional Block Diagram

52 52

CLOSE TRIP
Monitoring
59X 27X 81U/O 25

79 49 32S

50DD 50P 50_2 51P 51_2 50BF 21P 67P 67_2 68 78 50N 51N 67N/G 21G

59P
Data From/To Remote End Pilot FlexElement
TM

Metering Transducer
Inputs
(via Communications) Schemes
27P
50G 51G

52_2 59N

D60 Line Distance Protection System

ANSI Device Numbers & Functions


DEVICE DEVICE DEVICE


FUNCTION FUNCTION FUNCTION
NUMBER NUMBER NUMBER
21G Ground Distance 50P Phase Instantaneous Overcurrent 59_2 Negative Sequence Overvoltage
21P Phase Distance 50_2 Negative Sequence Instantaneous Overcurrent 67N Neutral Directional Overcurrent
25 Synchronism Check 51G Ground Time Overcurrent 67P Phase Directional Overcurrent
27P Phase Undervoltage 51N Neutral Time Overcurrent 67_2 Negative Sequence Directional Overcurrent
27X Auxiliary Undervoltage 51P Phase Time Overcurrent 68 Power Swing Blocking
32 Sensitive Reverse Power 51_2 Negative Sequence Time Overcurrent 78 Out-of-Step Tripping
49 Thermal Overload 52 AC Circuit Breaker 79 Automatic Recloser
50BF Breaker Failure 59C Compensated Overvoltage 81U/O Under/Over Frequency
50DD Current Disturbance Detector 59N Neutral Overvoltage ROCOF Rate of Change of Frequency
50G Ground Instantaneous Overcurrent 59P Phase Overvoltage
50N Neutral Instantaneous Overcurrent 59X Auxiliary Overvoltage

2 GEGridSolutions.com
D60 Line Distance Protection System

feeders, and overhead lines with series Load Encroachment operating characteristic. Negative sequence
compensation. Each zone element for the phase current supervisors provide extended selectivity
The load encroachment feature offers
and ground distance can be independently set as for detecting evolving faults that may appear as
discrimination between line loading conditions
quad or mho characteristics with the flexibility of a power swing event (faults with slow moving
and fault conditions, especially for long lines
designing different characteristic shapes to suit impedance locus).
under heavy loads, by supervising the distance
different power system conditions.
elements or any overcurrent element . This
Series Compensated Lines
The advanced comparator-based distance prevents unwanted tripping under heavy
elements provide the utmost security, sensitivity line load conditions and enables optimum D60 provides enhanced stability and security
and selectivity for different types of faults. Superior operation of the line, while meeting regulatory by employing an adaptive distance reach
digital filtering techniques provide secure and requirements for line loading. control to cope with the overreaching and
optimum reach accuracy even under worst case sub-synchronous oscillations when applied
CVT transients. Secure directional discrimination to, or in the vicinity of, series compensated
is achieved by using positive sequence lines. For directional integrity the relay uses
memory voltage polarization, providing reliable memory voltage polarization and a multi-input
directionality for worst case close-in faults. Dual comparator to deal with current inversion issues
distance algorithms deliver exceptional security in series compensated lines.
and speed performance to ensure average
Single-Pole Tripping
operating times of 1.5 cycles for 75% line reach
and SIR 30, and <2.5 cycles for 90% line reach and The D60 relay uses an advanced phase selection
SIR 60. The D60 employs a well-proven algorithm algorithm that provides fast and accurate fault
for phase selection, which provides faster, secure type identification even under weak in-feed
and reliable faulted phase identification for single- conditions. A convenient trip function is built-in
pole tripping and proper fault distance calculation to coordinate actions of the key elements of the
for a variety of power system conditions. An single-pole tripping package.
Distance relay quadrilateral characteristics
additional voltage monitoring function provides supervised by the load encroachment function.
extra security to the distance element, which can Communication Aided (Pilot) Schemes
be used to block the distance elements under D60 supports different teleprotection functions
voltage source fuse failure conditions. Fault Locator for fast fault clearance for any faults within the
protected line. The following types of pilot-aided
The integrated fault locator provides distance
schemes are available in the D60:
to fault in kilometers or miles. Parallel line
zero-sequence current compensation and Direct Underreach Transfer Trip (DUTT)
load current compensation enable the D60 to Permissive Underreach Transfer Trip (PUTT)
provide improved accuracy for fault distance
Two Permissive Overreach Transfer Trip
measurement.
(POTT)
Z3 Z1
Line Pickup (Switch-on-to Fault) Hybrid Permissive Overreach Transfer Trip
Z1 looking through a transformer. (HYB POTT): permissive echo and transient
The line pickup feature uses a combination of
blocking logic incorporated
undercurrent and undervoltage to identify a
line that has been de-energized (line end open). Directional Comparison Blocking Scheme
Three instantaneous overcurrent elements are (DCB)
used to identify a previously de-energized line Directional Comparison Unblocking Scheme
that has been closed on to a fault. (DCUB)
Customizable version of the POTT and DCB
Power Swing Detection schemes (POTT1 and DCB1)
Z3 Z1 Dynamic transients in the power system,
Z1 & Z3 looking through a transformer. due to short-circuits, circuit switching, or load
Undervoltage & Overvoltage Protection
unbalance changes, can travel across the power Long lines under lightly loaded or no-load
network as power swings that are characterized conditions may experience voltages exceeding
In-Zone Transformer Compensation
by fluctuating currents and voltages. This can the rated insulation voltage level. Use the
Phase distance protection in the D60 can be result in unwanted tripping since distance three phase overvoltage elements in the D60
used to detect faults through different types of elements can respond to these power swings as to detect and trip on this condition. A second
three-phase wye/delta transformers, allowing faults. The D60 power swing detection element compensated overvoltage element detects
the application of the D60 for backup protection provides both power swing blocking and out-of- overvoltage caused by breakers opening at the
on generators. VTs and CTs can be installed step tripping functions. The element measures remote end. The D60 also provides additional
independently of each other on either side of the positive sequence apparent impedance voltage functions, including neutral overvoltage,
the power transformer. The relay automatically and traces its locus with respect to either a negative sequence overvoltage and phase
compensates for transformer connections, to two or three-step user-selectable mho or quad undervoltage.
guarantee accurate reach for any type of fault.

GEGridSolutions.com 3
D60 Line Distance Protection System

Overcurrent Functions Breaker Failure Scalable Hardware


The D60 provides thermal overload, and time The D60 is able to provide fully independent The D60 is available with a multitude of I/O config-
and instantaneous overcurrent elements for breaker failure protection for the breakers urations to suit the most demanding application
phase, neutral, ground, negative sequence, associated to the line when connected to a needs. The expandable modular design allows for
phase and neutral directional. All of them can substation with a breaker-and-a-half or ring bus easy configuration and future upgrades.
run in parallel with distance elements or can be arrangement. The D60 provides the elements
Flexible, modular I/O covering a broad range
programmed to provide overcurrent protection to perform two independent breaker failure
of input signals and tripping schemes
under conditions when the distance element is functions.
blocked (example VT fuse failure). Types of digital outputs include trip-
rated Form-A and Solid State Relay (SSR)
Autorecloser IEC 61850 Process Bus mechanically latching, and Form-C outputs
The IEC 61850 Process Bus module is designed RTDs and DCmA inputs are available to
The D60 provides multi-shot autoreclosing (up
to interface with the Multilin HardFiber System, monitor equipment parameters, such as
to 4 shots) for single or three-pole autoreclose
allowing bi-directional IEC 61850 fiber optic temperature and pressure
on all types of faults with independently
communications. The HardFiber System is
programmable dead time for each shot .
Autoreclosing can be dynamically blocked
designed to integrate seamlessly with existing Monitoring and Metering
UR applications, including protection functions,
by user-programmable logic. Four different The D60 includes high accuracy metering and
FlexLogic, metering and communications.
autoreclose operation modes are available, recording for all AC signals. Voltage, current,
enabling users to select the reclosing mode to The Multilin HardFiber System offers the and power metering are built into the relay as a
suit specific applications. following benefits: standard feature. Current and voltage parameters
Communicates using open standard are available as total RMS magnitude, and as
Synchronism Check fundamental frequency magnitude and angle.
IEC 61850 messaging
The D60 provides ten synchrocheck elements that
Drastically reduces P&C design, installation Fault and Disturbance Recording
monitor voltage difference, phase angle difference
and testing labor by eliminating individual
and slip frequency taking the CB closing time into The advanced disturbance and event recording
copper terminations
account to ensure proper breaker closure as per features within the D60 can significantly reduce
user-defined settings. The D60 provides additional Integrates with existing D60s by replacing
the time needed for postmortem analysis
enhancements in synchronizing, by checking traditional CT/VT inputs with the IEC 61850
of power system events and the creation of
dead source conditions for synchronism bypass Process Bus module
regulatory reports. Recording functions include:
under these conditions. Does not introduce new cyber security
concerns Sequence of Event (SOE)
Multiple Breaker Configurations - 1024 time stamped events
Visit the HardFiber System product page on the
The D60 supports dual-breaker busbar GE Digital Energy website for more details. Oscillography
configurations, such as breaker-and-a-half or - Supports IEEE C37.111-1999/2013, IEC
60255-24 Ed 2.0 COMTRADE standard
ring bus arrangements, providing dual-breaker
autoreclose, dual synchrocheck elements, and
Advanced Automation - 64 digital & up to 40 analog channels
The D60 incorporates advanced automation - Events with up to 45s length
dual independent breaker failure elements.
The design provides secure operation during features including powerful FlexLogic Data Logger and Disturbance Recording
external faults with possible CT saturation. programmable logic, communication, and SCADA - 16 channels up to 1 sample/cycle/channel
capabilities that far surpass what is found in the Fault Reports
average line protection relay. The D60 integrates - Powerful summary report of pre-fault and
D60 Breaker-and-a-Half Configuration
seamlessly with other UR relays for complete fault values
system protection, including unit and auxiliary
The very high sampling rate and large amount
transformers, and balance of plant protection.
of storage space available for data recording
in the D60 can eliminate the need for installing
FlexLogic
costly stand-alone recording equipment.
FlexLogic is the powerful UR-platform
programming logic engine that provides the Advanced Device Health Diagnostics
ability to create customized protection and
The D60 performs comprehensive device health
control schemes, minimizing the need and
diagnostic tests at startup and continuously
associated costs of auxiliary components
during run-time to test its own major functions
and wiring. With 1024 lines of FlexLogic, the
and critical hardware. These diagnostic tests
D60 can be programmed to provide required
monitor for conditions that could impact security
tripping logic along with custom scheme logic
and availability of protection, and present device
for breaker control (including interlocking
status via SCADA communications and front
D60 supports breaker-and-a-half configuration. with external synchronizers), transfer tripping
panel display. Providing continuous monitoring
Two CTs can be brought in individually and schemes for remote breakers and dynamic
summed off at each terminal. and early detection of possible issues help
setting group changes.
improve system uptime.

4 GEGridSolutions.com
D60 Line Distance Protection System

Comprehensive device health diagnostic Settings Security & Device Status Reports
performed at startup
Monitors the CT/VT input circuitry to validate
the integrity of all signals

Cyber Security CyberSentry UR


CyberSentry UR enabled UR devices deliver full
cyber security features that help customers to
comply with NERC CIP and NIST IR 7628 cyber
security requirements. This software option
delivers the following core features:

AAA Server Support (Radius/LDAP)


Enables integration with centrally managed
authentication and accounting of all user
activities and uses modern industry best
practices and standards that meet and exceed
NERC CIP requirements for authentication and
password management.

Role Based Access Control (RBAC)


Efficiently administrate users and roles within
Track changes of settings to your D60 & view health and operating status by generating a report with the
UR devices. The new and advanced access click of a button.
functions allow users to configure up to five
roles for up to eight configurable users with
independent passwords. The standard Remote IEC 61850 Ed. 2 with 61850-9-2 and Multicast IEEE C37.118 synchrophasor
Authentication Dial In User Service (Radius) is 61850-90-5 support data between PMU and PDC devices using
used for authentication. DNP 3.0 (serial & TCP/IP) IEC91850-90-5

Ethernet Global Data (EGD) R-GOOSE enable customer to send GOOSE


Event Recorder (Syslog for SEM) messages beyond the substation, which
IEC 60870-5-103 and IEC 60870-5-104
Capture all cyber security related events within enables WAPC and more cost effective
Modbus RTU, Modbus TCP/IP communication architectures for wide area
a SOE element (login, logout, invalid password
HTTP, TFTP, SFTP and MMS file transfer applications
attempts, remote/local access, user in session,
settings change, FW update, etc), and then SNTP and IEEE 1588 for time synchronization
Direct I/O Messaging
serve and classify data by security level using PRP as per IEC 62439-3
Direct I/O allows for the sharing of high-speed
standard Syslog data format. This will enable
Supports Routable GOOSE (R-GOOSE) digital information between multiple UR
integration with established SEM (Security Event
relays via direct back-to-back connections or
Management) systems. IInteroperability with Embedded
multiplexed through a standard DS0 multiplexer
IEC61850 Edition 2
channel bank. Regardless of the connection
Communications The new IEC 61850 implementation in the UR method, direct I/O provides continuous real-time
Family positions GE as an industry leader in this channel monitoring that supplies diagnostics
The D60 provides for secure remote data and
standard. information on channel health. Direct I/O
engineering access, making it easy and flexible
to use and integrate into new and existing Implements Edition 2 of the standard across provides superior relay-to-relay communications
infrastructures. Fiber optic Ethernet provides the entire family of UR devices that can be used in advanced interlocking and
high-bandwidth communications allowing other special protection schemes.
Provides full relay setting management via
for low-latency controls and high-speed standard SCL files (ICD, CID and IID) Communication with up to 16 UR relays
file transfers of relay fault and event record in single or redundant rings rather than
Enables automated relay setting
information. The available three independent strictly limited to simplistic point-to-point
management using 3rd party tools through
Ethernet ports, redundant Ethernet option configurations between two devices
standard file transfer services (MMS and SFTP)
and the embedded managed Ethernet switch
Increases the number of Logical Devices and Connect to standard DS0 channel banks
provide the means to create fault tolerant through standard RS422, G.703 or
data mapped to them, GOOSE messages
communication architectures in an easy, cost- IEEEC37.94 interfaces or via direct fiber optic
from up to 64 remote devices, and reports
effective manner. The D60 supports the most connections
to support different organizational needs for
popular industry standard protocols enabling
data transfer and reduce dependency on No external or handheld tester required to
easy, direct integration into monitoring and
generic logical nodes provide channel diagnostic information
SCADA systems.
Configures GE Systems based on IEC 61850
using universal 3rd party tools

GEGridSolutions.com 5
D60 Line Distance Protection System

LAN Redundancy EnerVista Software Manuals


Substation LAN redundancy has been The EnerVista suite is an industry-leading set Application Notes
traditionally accomplished by reconfiguring of software programs that simplifies every Guideform Specifications
the active network topology in case of failure. aspect of using the D60 relay. The EnerVista Brochures
Regardless of the type of LAN architecture (tree, suite provides all the tools to monitor the status
mesh, etc), reconfiguring the active LAN requires Wiring Diagrams
of the protected asset, maintain the relay, and
time to switchover, during which the LAN is integrate information measured by the D60 into FAQs
unavailable. UR devices deliver redundancy as DCS or SCADA monitoring systems. Convenient Service Bulletins
specified by PRP-IEC 62439-3, which eliminates COMTRADE and SOE viewers are an integral part
the dependency on LAN reconfiguration and the of the UR setup software included with every UR Viewpoint Monitoring
associated switchover time. The UR becomes a relay, to carry out postmortem event analysis Viewpoint Monitoring is a simple-to-use and
dual attached node that transmits data packets and ensure proper protection system operation. full-featured monitoring and data recording
over both main and redundant networks software package for small systems. Viewpoint
simultaneously, so in case of failure, one of the EnerVista Launchpad Monitoring provides a complete HMI package
data packets will reach the receiving device with with the following functionality:
EnerVista Launchpad is a powerful software
no time delay.
package that provides users with all of the setup Plug-&-Play Device Monitoring
and support tools needed for configuring and
Multi-Language System Single-Line Monitoring & Control
maintaining Multilin products. The setup software
UR devices support multiple languages: English, within Launchpad allows for the configuration Annunciator Alarm Screens
French, Russian, Chinese, Turkish and German. of devices in real-time, by communicating Trending Reports
These language options are available on the using serial, Ethernet, or modem connections,
Automatic Event Retrieval
front panel, in the EnerVista setup software, and or offline by creating setting files to be sent to
in the product manuals. Easily switch between devices at a later time. Included in Launchpad is Automatic Waveform Retrieval
English and an additional language on the local a document archiving and management system
displays without uploading new firmware. that ensures critical documentation is up-to-
date and available when needed. Documents
made available include:

Power System Troubleshooting


The D60 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events.

Analyze transmission line faults using Graphically view zone settings for ground
system voltage, current and appropriate phase distance elements for the selected
pickup flags that are measured & Record the operation of the internal D60 elements and zones and the power swing detection
recorded up to 64samples/cycle. external connected devices with 1ms time-stamped element.
accuracy to identify the Sequence of Operation of station
devices during faults and disturbances.

6 GEGridSolutions.com
D60 Line Distance Protection System

Viewpoint UR Engineer Typical Wiring


Viewpoint UR Engineer is a set of powerful tools
that will allows the configuration and testing
A
of GE relays at a system level in an easy-to-
use graphical drag-and-drop environment .
B
52 52
C
Viewpoint UR Engineer provides the following
configuration and commissioning utilities: A B C

Graphical Logic Designer CURRENT


POLARIZATION
SOURCE

Graphical System Designer


Graphical Logic Monitor

F 1a

F 1b

F 2a

F 2b

F 3a

F 3b

F 4a

F 4b

F 5a

F 6a

F 7a

F 8a
F 1c

F 2c

F 3c

F 4c

F 5c

F 6c

F 7c

F 8c
Graphical System Monitor

VX
VB

VC
VA

VX
IG5

IG1

VB

VC
IG

VA
IA5

IA1

IB

IC
IA

IC5

IC1
IB5

IB1
Viewpoint Maintenance
Viewpoint Maintenance provides tools that H7a 6H I H1a TC 1
H7c H1 H1b
will create reports on the operating status of
V
H8a H1c
H8c I H2a

the relay, simplify the steps to download fault H7b H2 H2b


V
H2c
H8b SURGE
I H3a
and event data, and reduce the work required H3
V
H3b TC 2
H3c
for cyber security compliance audits. Tools Digital Energy H4
I H4a
H4b
V
Multilin
available in Viewpoint Maintenance include:
H4c
I H5a

D60
H5 H5b
V
H5c
Settings Security Audit Report D60-H07-HLH-F8L-H6H-M6K-P6C-U6D-W6A H6
I H6a
H6b
V
H6c
Device Health Report W5a 6A I W1a
W5c W1 W1b
V
W6a W1c
Single-Click Fault Data Retrieval W6c I W2a
W5b W2 W2b
V
W2c
W7a
EnerVista Integrator
W3a
W7c
W3 W3b
W8a
W3c
W8c
W4a
EnerVista Integrator is a toolkit that allows W7b
W8b SURGE
W4 W4b
W4c

seamless integration of Multilin devices into P1a

6C
P1 P1b

new or existing automation systems. Included in P1c


P2a
P2 P2b
EnerVista Integrator is: U1a P2c
6D

U1c P3a
U2a P3 P3b
OPC/DDE Server U2c
U1b
P3c
P4a
P4 P4b
U3a
Multilin Drivers U3c P4c
P5a
U4a
P5 P5b
U4c
Automatic Event Retrieval U3b P5c
P6a
U5a P6 P6b

Automatic Waveform Retrieval


U5c P6c
U6a P7a
U6c P7 P7b
U5b P7c
U7a P8a

User Interface
U7c P8 P8b
U8a P8c PERSONAL
COMPUTER
U8c
U7b
The D60 front panel provides extensive local U8b SURGE
M1a
6K

RS-232 1 M1b
HMI capabilities. The local display is used for B1b
CRITICAL DB-9
M1c
1

B1a M2a CONNECTOR CONNECTOR


FAILURE

monitoring, status messaging, fault diagnosis, B2b 2


(front) M2b 1 1 8
B3a M2c TXD 2 2 3 RXD
DC OUTPUT
B3b M3a
and device configuration. User-configurable RXD 3 3 2 TXD
B5b HI 3 M3b 4 4 20
CONTROL
B6b LO M3c 5 5 7 SGND
POWER SGND
messages that combine text with live data can be B6a
B8a SURGE 4
M4a
M4b
6
7
6
7
6
4
B8b
displayed when user-defined conditions are met.
FILTER M4c 8 8 5
M5a 9 9 22
* Optic
Fibre Tx1 10BaseFL
NORMAL
5 M5b
M5c
UR COMPUTER
Rx1

Tx2 10BaseFL COM M6a


ALTERNATE 6 M6b
Rx2 1
M6c
Shielded 10BaseT M7a
Remote 7 M7b
Device D1a
RS485 M7c
D2a
D3a com M8a
8 M8b
D4b
D4a IRIG-B M8c
Input
Co-axial BNC

IRIG-B
Co-axial BNC Output

837774A6.CDR
Minimum
X W V U T S R P N M L K J H G F D B
6 6 6 6 6 8 9 1
Inputs/ Inputs/ Inputs/ Inputs/
outputs outputs outputs outputs Inputs/ CT/VT CPU Power
* * * * outputs Supply
PROVIDED

This diagram is based on the following order code:


D60-H07-HLH-F8L-H6H-M6K-P6C-U6D-W6A .This diagram provides an
example of how the device is wired, not specifically how to wire the device.
Please refer to the Instruction Manual for additional details on wiring
based on various configurations.

GEGridSolutions.com 7
Ordering
D60 - * ** - H * * - F ** - H ** - M ** - P ** - U ** - W ** For Full Sized Horizontal Mount
Base Unit D60 Base Unit
CPU E RS485 & RS485 (IEC 61850 option not available)
J RS485 + multimode ST 100BaseFX
K RS485 + multimode ST Redundant 100BaseFX
N RS485 + 10/100 BaseT
T RS485 + three multimode SFP LC 100BaseFX. Req FW v7xx or higher
U RS485 + two multimode SFP LC 100BaseFX + one SFP RJ45 100BaseT.
Req FW v7xx or higher
V RS485 + three SFP RJ45 100BaseT. Req FW v7xx or higher
Software Options 00 No Software Options
(see note 1 below) 02 Breaker and Half
03 IEC 61850
05 Breaker and Half + IEC 61850
06 Phasor Measurement Unit (PMU)
07 IEC 61850 + Phasor Measurement Unit (PMU)
08 Breaker and Half + Phasor Measurement Unit (PMU)
09 Breaker and Half + IEC 61850 + Phasor Measurement Unit (PMU)
A0 CyberSentry UR Lvl 1. Req UR FW 7.xx or higher
B0 IEEE 1588. Req UR FW 7.xx or higher
C0 PRP
D0 IEEE 1588 + CyberSentry. Req UR FW 7.xx or higher
M0 IEC 61850 + PMU + 61850-90-5
Mount H Horizontal (19" rack) - Standard
A Horizontal (19" rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface F Vertical Front Panel with English Display
I Enhanced German Front Panel
J Enhanced German Front Panel with User-Programmable Pushbuttons
K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
W Enhanced Turkish Front Panel
Y Enhanced Turkish Front Panel with User-Programmable Pushbuttons
Power Supply H RH 125/250 V AC/DC w/ redundant 125/250 V AC/DC power supply
(see note 2 below) H 125/250 V AC/DC
CT/VT DSP 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8M 8M Sensitive Ground 4CT/4VT w/ enhanced diagnostics
IEC 61850 Process Bus 81 8 Port IEC 61850 Process Bus Module
Digital I/O XX XX XX XX XX No module
4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
Transducer I/O 5A 5A 5A 5A 5A 4 dcmA Inputs, 4 dcmA Outputs
5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 2B C37.94SM, 1300nm singlemode, ELED, 2 Channel singlemode
2I Channel 1 - IEEE C37.94, 820nm, multimode fiber, 64/128 kbps; Channel 2 -
1300 nm, singlemode, LASER
2J Channel 1 - IEEE C37.94, 820nm, multimode fiber, 64/128 kbps; Channel 2 - 1550
nm, singlemode, LASER
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, singlemode, ELED, 1 Channel
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, singlemode, ELED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
73 1550 nm, singlemode, LASER, 2 Channels
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel

Ordering Notes: 1. To view all the options available for D60, please visit GEs On-Line Store http://store.gedigitalenergy.com/viewprod.asp?model=D60
2. Redundant power supply only available in horizontal unit. If redundant is chosen, must be same type. Maximum 2 per chassis.

IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered


trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General
Electric Company.
GE reserves the right to make changes to specifications of products described at any time without
notice and without obligation to notify any person of such changes.
Copyright 2017, General Electric Company. GEA-12592I(E)