Professional Documents
Culture Documents
4
DIVISION 23
HEATING VENTILLATION & AIR CONDITIONING (HVAC)
Item Description
HVAC SYSTEMS
Supply and installation of all the following HVAC System Works, including,
but not limited to, testing, balancing and commissioning, builder's works
(sleeves, opening, supports, accessories, etc.), reinforced concrete pads,
vibration isolation, blocking, seams, sealants, neoprene, gaskets, connection to
all other related project phases, operation and maintenance manuals, guarantee,
for all required system equipment and materials, as per contract documents,
drawings and specifications.
Chilled water pumps, complete with VFD and all accessories, gate valves,
strainer, pressure gauge, reinforced concrete base and vibration isolator as
detailed on drawings with all other related fittings and accessories
complete as required, as shown on the drawigns and as specified.
A Chilled water pump (Ref. CWP-5.1 & 5.2), 0.93 L/S capacity each, 175
KPA. approx. head, 1.50 KW power, END SUCTION type, complete with
all accessories as required, as shown on the drawings and as specified.
B Chilled water pump (Ref. CWP-13.1 & 13.2), 3.12 L/S capacity each, 175
KPA. approx. head, 1.50 KW power, END SUCTION type, complete with
all accessories as required, as shown on the drawings and as specified.
Item Description
Item Description
HVAC SYSTEMS
Chilled water pumps, complete with all accessories, gate valves, strainer,
pressure gauge, reinforced concrete base and vibration isolator as
detailed on drawings with all other related fittings and accessories
complete as required, as shown on the drawigns and as specified.
A Chilled water Make-up water pump (CH-PRP-01), 4.14 L/S capacity each,
670 KPA. approx. head, complete with all accessories as required, as
shown on the drawings and as specified.(Refer to item no B page: 1 in
Oncology Building)
Supply, Install of Air & dirt separator with pressure regulating valve assembly,
valves, air vent, drain, complete as specified and as shown in the
drawings.Included in the chilled water pipes accessories
EXPANSION TANKS
D ET-01 of Steel Pipes and chilled water fluid type (Mentioned in CUP Parking
Building)
SIDESTREAM FILTRATION
Item Description
E SFP-1, with flow 12.5 l/s and max. pressure 100 m (Mentioned in CUP
Parking Building)
Item Description
HVAC SYSTEMS
Item Description
Supply, install and test the following Chilled water system complete (but
not limited to) pipe markings, sleeves, openings, blocking seams, sealants
and base (if required) with all necessary valves, fittings, fixing accessories
complete as required, as shown in the drawings and as specified.
Chilled water pipes Black Steel Seamless (Schedule 40), complete with all
accessories as specified and as shown in the drawings.
1.A 15 mm diameter.
A 25 mm diameter.
B 40 mm diameter.
C 50 mm diameter.
D 65 mm diameter.
E 75 mm diameter.
F 100 mm diameter.
G 200 mmdiameter.
H 250 mm diameter.
Item Description
Item Description
HVAC SYSTEMS
Chilled water pipes Insulation (25 mm thick Rigid Fiber glass with
Aluminum Foil, 96 kg/cu.m) and 0.6 mm thick Aluminum Cladding for
exposed pipes and in plant rooms complete with all accessories as
specified and as shown in the drawings.
A 25 mm diameter.
B 40 mm diameter.
C 50 mm diameter.
D 65 mm diameter.
E 75 mm diameter.
E.1 80 mm diameter.
F 100 mm diameter.
G 200 mmdiameter.
H 250 mm diameter.
Item Description
Item Description
Energy Recovery Unit (Total Enthalpy) with Energy Recovery Wheel complete
with all accessories, reinforced concrete base, vibration isolators, condensate
drain pipe, controls and fittings, complete as required, as shown in the
drawings and as specified.
A Energy Recovery unit (Ref. ERU-1), 16,373 L/S at Supply side and 8,917 L/S
at Exhaust side each, complete with all accessories as required, as shown on
the drawings and as specified.
B Energy Recovery unit (Ref. ERU-2), 13,066 L/S at Supply side and 7,995 L/S
at Exhaust side each, complete with all accessories as required, as shown on
the drawings and as specified.
C Energy Recovery unit (Ref. ERU-3), 10,475 L/S at Supply side and 6,392 L/S
at Exhaust side each, complete with all accessories as required, as shown on
the drawings and as specified.
D Energy Recovery unit (ERU-1,2,3), 16,520 L/S Supply air flow and 847 Kw
Chilled water cooling coil capacity, complete with all accessories as required,
as shown on the drawings and as specified.(Refer to item no A page: 4 in
Oncology Building)
INERTIA FILTER
Supply, Install of Inertial Filter complete with all necessary accessories and
complete as specified and as shown in the drawings.(All air filters are included
in the HVAC equipments as per KFSH-1,schedule)
Item Description
Item Description
HVAC SYSTEMS
Supply, install and test the following modular type air handling units (ARI
rated units & UL listed motors) complete with all wiring, fittings, return
bell mouths, air filters, insulations, Gate valves, Pressure gauges,
Thermometers Butterfly valves, Modulating valves, Balancing valve ,
Automatic flow control valve, controls, thermostat, fixing accessories,
reinforced concrete base, vibration pads, condensate drain pipe, flexible
connections and all necessary accessories complete as specified and as
shown in the drawings.
A Ref. AHU-1-1 , total supply air 8972 L/S, total load on coil 54.6 KW.
B Ref. AHU-2-1 , total supply air 9469 L/S, total load on coil 149.4 KW.
C Ref. AHU-3-1 , total supply air 9469 L/S, total load on coil 149.4 KW.
D Ref. AHU-4-1 , total supply air 8826 L/S, total load on coil 117.7 KW.
E Ref. AHU-5-1 , total supply air 10231 L/S, total load on coil 157.4 KW.
F Ref. AHU-1-2 , total supply air 15318 L/S, total load on coil 211.0 KW.
G Ref. AHU-2-2 , total supply air 5923 L/S, total load on coil 89.1 KW.
H Ref. AHU-3-2 , total supply air 5923 L/S, total load on coil 86.1 KW.
J Ref. AHU-4-2 , total supply air 6083 L/S, total load on coil 66.9 KW.
Item Description
K Ref. AHU-5-2 , total supply air 6014 L/S, total load on coil 83.7 KW.
Item Description
HVAC SYSTEMS
A Ref. AHU-GL-1 , total supply air 7403 L/S, total load on coil 119.5 KW.
B Ref. AHU-GL-2 , total supply air 5913 L/S, total load on coil 89.0 KW.
C Ref. AHU-GL-3 , total supply air 5174 L/S, total load on coil 62.9 KW.
D Ref. AHU-B-1 , total supply air 6891 L/S, total load on coil 94.9 KW.
E Ref. AHU-B-2 , total supply air 6991 L/S, total load on coil 99.2 KW.
F Ref. AHU-P-1 , total supply air 6607 L/S, total load on coil 125.5 KW.
G Ref. AHU-P-2 , total supply air 6607 L/S, total load on coil 125.5 KW.
H Ref. AHUZ0.01-I, total supply air 7100 L/S, total load on coil 111 KW.
(Refer to item no D page: 5 in Medical Logestic Building)
J Ref. AHUZ1.01-I, total supply air 9450 L/S, total load on coil 150 KW.
(Mentioned in Oncology Building )
K Ref. AHUZ1.01-II, total supply air 7100 L/S, total load on coil 110 KW.
(Mentioned in Oncology Building )
L Ref. AHUZ1.01-III, total supply air 9450 L/S, total load on coil 150 KW.
(Mentioned in Oncology Building )
M Ref. AHUZ1.02-I, total supply air 9450 L/S, total load on coil 150 KW.
(Mentioned in Oncology Building )
Item Description
N Ref. AHUZ1.02-II, total supply air 9450 L/S, total load on coil 150 KW.
(Mentioned in Oncology Building )
Item Description
HVAC SYSTEMS
A Ref. AHUZ1.03-I, total supply air 9450 L/S, total load on coil 100 KW.
(Mentioned in Oncology Building )
B Ref. AHUZ1.03-II, total supply air 9450 L/S, total load on coil 118 KW.
(Mentioned in Oncology Building )
C Ref. AHUZ1.04-I, total supply air 9450 L/S, total load on coil 124 KW.
(Mentioned in Oncology Building )
D Ref. AHUZ1.05-I, total supply air 9450 L/S, total load on coil 114 KW.
(Mentioned in Oncology Building )
E Ref. AHUZ3.01-I, total supply air 9450 L/S, total load on coil 150 KW.
(Mentioned in Oncology Building )
F Ref. AHUZ3.01-II, total supply air 9450 L/S, total load on coil 150 KW.
(Mentioned in Oncology Building )
G Ref. AHUZ4.01-I, total supply air 11800 L/S, total load on coil 184 KW.
(Refer to item no E page: 5 in Oncology Building)
H Ref. AHUZ4.01-II, total supply air 11800 L/S, total load on coil 184 KW.
(Refer to item no E page: 5 in Oncology Building)
J Ref. AHUZ5.01-I, total supply air 11800 L/S, total load on coil 184 KW.
(Refer to item no E page: 5 in Oncology Building)
K Ref. AHUZ5.01-II, total supply air 11800 L/S, total load on coil 184 KW.
(Refer to item no E page: 5 in Oncology Building)
L Ref. AHUZ6.01-I, total supply air 11800 L/S, total load on coil 184 KW.
(Refer to item no E page: 5 in Oncology Building)
Item Description
M Ref. AHUZ6.01-II, total supply air 11800 L/S, total load on coil 184 KW.
(Refer to item no E page: 5 in Oncology Building)
SOUND ATTENUATORS
N Sound attenuator to maintain room noise level as required; with all accessories
complete as specified and as shown in the drawings.
Item Description
HVAC SYSTEM
Supply, install and test the following units (ARI rated units and UL listed
motors) complete with all wiring, insulation, valves, flat filter, flexible
connection, plenum box, motorized valves, controls, circuit breaker, space
thermostat, fixing accessories, vibration pads, condensate drain pipe etc., with
all necessary insulation, accessories complete as specified and as shown in
the drawings.
Item Description
Item Description
HVAC SYSTEM
J Type CRAC-1, total supply air 668 L/S, total load on coil 10.7 KW
Item Description
Item Description
HVAC SYSTEM
Condensate drain pipes (UPVC Class 4, with 9mm thick rubber insulation)
laid under tiles, above ceilings , walls, etc. from FCU/AHU complete as
specified and as shown in the drawings.
A Supply and install condensate drain pipes to the engineer approval where
needed and connect it to nearest floor drain Complete with Insulation Above
Tiles.
Item Description
Item Description
HVAC SYSTEM
Supply, install and test the following VAV units (ARI rated units and UL
listed motors) complete with accessories ( but not limited to) , all wiring,
insulation, valves, flow sensor, factory wired control voltage transformer,
factory mounted electric heating coil, automatic reset thermal cut-out, pressure
diffrential switch, electric switches for staging etc., with all necessary
insulation, accessories complete as specified and as shown in the drawings.
Item Description
Item Description
HVAC SYSTEM
Item Description
Item Description
HVAC SYSTEM
Supply, install and test the following VAV units (ARI rated units and UL
listed motors) complete with accessories ( but not limited to) all wiring,
insulation, valves, flow sensor, factory wired control voltage transformer,
factory mounted electric heating coil, automatic reset thermal cut-out, pressure
diffrential switch, electric switches for staging etc., with all necessary
insulation, accessories complete as specified and as shown in the drawings.
Item Description
Item Description
HVAC SYSTEM
Supply, install and test the following VAV units (ARI rated units and UL
listed motors) complete with accessories ( but not limited to), all wiring,
insulation, valves, flow sensor, factory wired control voltage transformer,
factory mounted electric heating coil, automatic reset thermal cut-out, pressure
diffrential switch, electric switches for staging etc., with all necessary
insulation, accessories complete as specified and as shown in the drawings.
Item Description
Item Description
HVAC SYSTEM
Supply, install and test the following SUPPLY AV units (ARI rated units
and UL listed motors) complete with accessories ( but not limited to)
Controller, all wiring, insulation, valves, flow sensor, factory wired control
voltage transformer, factory mounted electric heating coil, automatic reset
thermal cut-out, pressure differential switch, electric switches for staging etc.,
with all necessary insulation, accessories complete as specified and as
shown in the drawings.
Item Description
Item Description
HVAC SYSTEM
Supply, install and test the following RETURN AVEE units (ARI rated
units and UL listed motors) complete with accessories ( but not limited to)
Controller, all wiring, insulation, valves, flow sensor, factory wired control
voltage transformer, factory mounted electric heating coil, automatic reset
thermal cut-out, pressure differential switch, electric switches for staging etc.,
with all necessary insulation, accessories complete as specified and as
shown in the drawings.
Item Description
Item Description
HVAC SYSTEM
Supply, install and test the following EXHAUST AVE units (ARI rated
units and UL listed motors) complete with accessories ( but not limited to)
Controller, all wiring, insulation, valves, flow sensor, factory wired control
voltage transformer, factory mounted electric heating coil, automatic reset
thermal cut-out, pressure differential switch, electric switches for staging etc.,
with all necessary insulation, accessories complete as specified and as
shown in the drawings.
Item Description
Item Description
HVAC SYSTEM
RETURN FAN'S
Supply, Install and test the following Return Fans type Smoke Rated Fan
Complete with VFD (UL listed / FM approved), including flanges, support
framing, mounting bolts, isolating switches overload protection, back draft
damper and all necessary fixing accessories and connection complete as
required, as shown in the drawings and as specified.
L
Type Inline,REF AHUGL-1, 6574 L/S,995 Pa static pressure
M
Type Inline,REF AHUGL 2, 5101 L/S,995 Pa static pressure
N
Type Inline, REF AHU GL-3, 3156 L/S,995 Pa static pressure.
Item Description
Item Description
HVAC SYSTEM
D Type Inline, RF-AHUZ1.02-I, 9450 L/S, 750 Pa static pressure( Refer to item
no H page: 15 in Expansion Building)
H Type Inline, RF-AHUZ1.04-I, 9450 L/S, 750 Pa static pressure (Refer to item
no H page: 15 in Expansion Building)
Item Description
Item Description
HVAC SYSTEM
Item Description
Item Description
HVAC SYSTEM
SOUND ATTENUATORS
Sound attenuator fixed on supply, and return ducts for each AHU, and ERU to
maintain room noise level as required; with all accessories complete as
specified and as shown in the drawings, and Specs.
A Ref. S/A-S-1.1 and S/A-R-1.1, with 8972 L/S air supply (for AHU 1-1).
B Ref. S/A-S-2.1 and S/A-R-2.1, with 9469 L/S air supply (for AHU 2-1).
C Ref. S/A-S-3.1 and S/A-R-3.1, with 9469 L/S air supply (for AHU 3-1).
D Ref. S/A-S-4.1 and S/A-R-4.1, with 6036 L/S air supply (for AHU 4-1).
E Ref. S/A-S-5.1 and S/A-R-5.1, with 6135 L/S air supply (for AHU 5-1).
F Ref. S/A-S-1.2 and S/A-R-1.2, with 9211 L/S air supply (for AHU 1-2).
G Ref. S/A-S-2.2 and S/A-R-2.2, with 5923 L/S air supply (for AHU 2-2).
H Ref. S/A-S-3.2 and S/A-R-3.2, with 5923 L/S air supply (for AHU 3-2).
J Ref. S/A-S-4.2 and S/A-R-4.2, with 8774 L/S air supply (for AHU 4-2).
K Ref. S/A-S-5.2 and S/A-R-5.2, with 5994 L/S air supply (for AHU 5-2).
Item Description
Item Description
HVAC SYSTEM
A Ref. S/A-S-GL-1 and S/A-R-GL-1, with 7311 L/S air supply (for AHU GL-1).
B Ref. S/A-S-GL-2 and S/A-R-GL-2, with 7355 L/S air supply (for AHU GL-2).
C Ref. S/A-S-GL-3 and S/A-R-GL-3, with 5174 L/S air supply (for AHU GL-3).
D Ref. S/A-S-B-1 and S/A-R-B-1, with 6939 L/S air supply (for AHU B-1).
E Ref. S/A-S-B-2 and S/A-R-B-2, with 6992 L/S air supply (for AHU B-2).
F Ref. S/A-S-P-1 and S/A-R-P-1, with 6607 L/S air supply (for AHU P-1).
G Ref. S/A-S-P-2 and S/A-R-P-2, with 6607 L/S air supply (for AHU P-2).
Item Description
Item Description
HVAC SYSTEM
A Ref. SF-AHUZ0.01-I and RF-AHUZ0.01-I , with 7100 L/S air supply (for
AHUZ0.01-I).(Mentioned in Oncology Building)
B Ref. SF-AHUZ1.01-I and RF-AHUZ1.01-I , with 9450 L/S air supply (for
AHUZ1.01-I).(Mentioned in Oncology Building )
C Ref. SF-AHUZ1.01-II and RF-AHUZ1.01-II , with 7100 L/S air supply (for
AHUZ1.01-II).( Mentioned in Oncology Building )
D Ref. SF-AHUZ1.01-III and RF-AHUZ1.01-III, with 9450 L/S air supply (for
AHUZ1.01-III).(Mentioned in Oncology Building )
E Ref. SF-AHUZ1.02-I and RF-AHUZ1.02-I , with 9450 L/S air supply (for
AHUZ1.02-I).(Mentioned in Oncology Building )
F Ref. SF-AHUZ1.02-II and RF-AHUZ1.02-II, with 9450 L/S air supply (for
AHUZ1.02-II).(Mentioned in Oncology Building)
G Ref. SF-AHUZ1.03-I and RF-AHUZ1.03-I , with 9450 L/S air supply (for
AHUZ1.03-I).(Mentioned in Oncology Building )
H Ref. SF-AHUZ1.03-II and RF-AHUZ1.03-II , with 9450 L/S air supply (for
AHUZ1.03-II).(Mentioned in Oncology Building )
J Ref. SF-AHUZ1.04-I and RF-AHUZ1.04-I, with 9450 L/S air supply (for
AHUZ1.04-I).?(Mentioned in Oncology Building )
K Ref. SF-AHUZ1.05-I and RF-AHUZ1.05-I , with 9450 L/S air supply (for
AHUZ1.05-I).(Mentioned in Oncology Building )
Item Description
L Ref. SF-AHUZ3.01-I and RF-AHUZ3.01-I , with 9450 L/S air supply (for
AHUZ3.01-I).(Mentioned in Oncology Building)
M Ref. SF-AHUZ3.01-II and RF-AHUZ3.01-II, with 9450 L/S air supply (for
AHUZ3.01-II).(Mentioned in Oncology Building)
Item Description
HVAC SYSTEM
A Ref. SF-AHUZ4.01-I and RF-AHUZ4.01-I, with 11800 L/S air supply (for
AHUZ4.01-I).(Refer to item no F page: 28 in Expansion Building)
B Ref. SF-AHUZ4.01-II and RF-AHUZ4.01-II, with 11800 L/S air supply (for
AHUZ4.01-II).(Refer to item no F page: 28 in Expansion Building)
C Ref. SF-AHUZ5.01-I and RF-AHUZ5.01-I , with 11800 L/S air supply (for
AHUZ5.01-I).(Refer to item no F page: 28 in Expansion Building)
D Ref. SF-AHUZ5.01-II and RF-AHUZ5.01-II, with 11800 L/S air supply (for
AHUZ5.01-II).(Refer to item no F page: 28 in Expansion Building)
E Ref. SF-AHUZ6.01-I and RF-AHUZ6.01-I, with 11800 L/S air supply (for
AHUZ6.01-I).(Refer to item no F page: 28 in Expansion Building)
Item Description
Item Description
HVAC SYSTEM
PRESSURIZATION FAN'S
Supply, Install and test the following Pressurization Fans Inline type Complete
with VFD (UL listed / FM approved), including flanges, support framing,
mounting bolts, isolating switches overload protection, back draft damper
and all necessary fixing accessories and connection complete as required, as
shown in the drawings and as specified.
B.1
Type Inline,SPF-1, 8200 L/S, 250 Pa Total static pressure(Refer to item no A
page: 13 in Oncology Building)
B.2
Type Inline,SPF-2, 8200 L/S, 250 Pa Total static pressure(Refer to item no A
page: 13 in Oncology Building)
B.3
Type Inline,SPF-3, 7500 L/S, 250 Pa Total static pressure(Refer to item no A
page: 13 in Oncology Building)
Supply, Install and test the following Ventillation Exhaust Fans Inline &
Centrifugal type Complete with VFD (UL listed / FM approved), including
flanges, support framing, mounting bolts, isolating switches overload
protection, back draft damper and all necessary fixing accessories and
connection complete as required, as shown in the drawings and as
specified.
Item Description
Item Description
HVAC SYSTEM
A
Type Roof Top, EF-1, 400 L/S, 1000 Pa static pressure(Refer to item no D
page: 13 in Oncology Building)
B
Type Roof Top, EF-2, 3550 L/S, 1325 Pa static pressure(Refer to item no C
page: 13 in Oncology Building)
C
Type Roof Top, EF-3, 1400 L/S, 1325 Pa static pressure(Refer to item no C
page: 13 in Oncology Building)
Item Description
Item Description
HVAC SYSTEMS
Ductwork
C Stainless Steel exhaust air duct complete as required, as shown in the drawings
and as specified.
D Smoke exhaust air duct (2 hours fire rated) complete as required, as shown in
the drawings and as specified.
E Insulation (40mm thick fiber glass, 24 kg/m with aluminum foil) to indoor
supply, return, kitchen exhaust and fresh air ducts complete as required, as
shown in the drawings and as specified.
F Insulation (50mm thick fiber glass, 48 kg/m with aluminum foil) and
0.6mm thick aluminum cladding to duct work in mechanical room's with
all materials and accessories complete as required, as shown in the
drawings and as specified.
G Internal Acoustic duct lining (Hospital Grade), complete with glue and fixing
pins as required, as shown in the drawings and as specified.
H Fire rated cladding (2-hours) to smoke exhaust and make-up air duct works,
complete as required, as shown in the drawings and specified.
Item Description
J Fire rated paint to exhaust air ducts in parking areas, complete as required
as shown in the drawings and as specified.
K Allow for various sizes of Volume dampers, Smoke dampers Fire dampers and
Motorized dampers complete as specified and as shown in the drawings.
Item Description
HVAC SYSTEMS
Air Outlets
Grilles and Diffusers complete with opposed blade volume dampers and all
duct connections, flexible ducts with insulation and supports framing
complete as specified and as shown in the drawings.; color as selected by the
engineer.
Supply air linear diffuser including flexible duct with insulation complete as
specified and as shown in the drawings.
D Size, 1.0 m long,5 slots with plenum box (LD5 & LD7)
E.1 Size, 0.9 m long,2 slots with plenum box (LD2C), (Mentioned in Expansion
Building But with 1.0 m / 2 slots)
E.2 Size, 0.9 m long,3 slots with plenum box (LD3C), (Mentioned in Expansion
Building But with 1.0 m / 3 slots)
E.3 Size, 0.9 m long,4 slots with plenum box (LD4C), (Mentioned in Expansion
Building But with 1.0 m / 4 slots)
E.4 Size, 0.9 m long,5 slots with plenum box (LD5C) (Mentioned in Expansion
Building But with 1.0 m / 5 slots)
Return air linear diffuser including fixings and trims, complete as specified and
as shown in the drawings.
Item Description
Item Description
HVAC SYSTEMS
Item Description
Item Description
HVAC SYSTEMS
Item Description
Item Description
HVAC SYSTEMS
Fresh Air Louver including Plenium box with insulation complete as specified
and as shown in the drawings.
Item Description
Item Description
HVAC SYSTEMS
Item Description
Item Description
HVAC SYSTEMS
HEPA FILTER
Item Description
Item Description
HVAC SYSTEMS
AUTOMATIC CONTROL
Item Description
A Dedicated Special DDC for Air Valve Unit (Isolation Rooms) (Supplied by
the concerned specialist equipment provider).
B Dedicated General DDC for Switch Board ( SWBD ) (Size varies as per IO
point list)
C Dedicated General DDC for Fan (Size varies as per IO point list)
D Dedicated General DDC for Distribution Panel (DP) (Size varies as per IO
point list)
Item Description
Item Description
B Dedicated General DDC for Fans (Roof Top,) as per IO Points and
specifications
E Dedicated DDC for Lighting Control Panel ( LCP ) (Size varies as per IO point
list)
F IP Gateway/ Router
G BMS Work station with 32" LCD Screen and Event printer
Item Description
Item Description
Item Description
Item Description
Total Sum of
BILL No. 4
Carried to Summary