Flkt Woods 8713 GB 2014.04 1 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
3. 4.
alt.
5. Dimensions
Dimensions in mm
Flkt Woods 8713 GB 2014.04 2 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Flkt Woods 8713 GB 2014.04 3 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Flkt Woods 8713 GB 2014.04 4 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Flkt Woods 8713 GB 2014.04 5 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Fan control
Fan control STRA-07 has a fan button. When you press
the button, a symbol is shown in the display for 10
seconds. During this time, it is possible to change the fan
speed using the INCREASE/DECREASE buttons. The
controller has the following positions:
It is possible to set different parameter values in a
Auto Automatic control of the fan
parameter menu in the display, using the buttons on
speed to maintain desired
the controller. You change parameter values with the
room temperature.
INCREASE and DECREASE buttons and confirm changes
0 Fan Off.
with the Occupancy button.
I Manual position with low
speed.
II Manual position with
medium speed.
III Manual position with high
speed.
In operating modes Off and Unoccupied, the fan is
stopped, regardless of the setting in the display.
Flkt Woods 8713 GB 2014.04 6 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Technical data
Inputs
External room sensor PT1000-sensor, 050C. Suitable sensor is Flkt Woods STRZ-05
Occupancy detector Closing potential-free contact. Suitable occupancy detector is Flkt Woods STRZ-09.
Condensation detector alt. window contact Flkt Woods condensation detector STRZ-16 alt. window contact STRZ-38 resp. potential-free contact
CO2 sensor STRZ-18, CO2 sensor with built-in relay. Active sensor is also possible to use.
Outputs
Fan control 3 outputs for speed I, II and III respectively, 24 V AC, max 0.5 A
Forced ventilation 24 V AC actuator, max 0.5 A
Valve actuator alt. thermal actuator 2 outputs
Valve actuator 010 V DC, max 5 mA
Thermal actuator 24 V AC, max 2.0 A
Control Heating or cooling
Actuator exercise FS = 23 hours interval
Terminal blocks So-called lift type for cable cross-section 2.1 mm2
Flkt Woods 8713 GB 2014.04 7 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Occupied
Operating mode Occupied means that the room is in
use and is therefore in a comfort mode. The controller
regulates the room temperature around a heating setpoint
and a cooling setpoint (FS heating setpoint=22C, cooling
setpoint=24C). The setpoints can also be adjusted +/- 3C
locally via the display, or via a central command.
Flkt Woods 8713 GB 2014.04 8 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
is connected.
When occupancy is indicated, the controller changes
operating mode to Bypass. If you want to be able to
enter the room temporarily without activating Bypass,
for example to pick something up, you can configure a
powerup delay. This means that Bypass is not activated
until the power-up delay has expired. The Bypass delay
can be set to a value between 0 and 60 minutes (FS=0
min).
In Bypass on presence, there is a switch-off timer, which
means that if there is no occupancy indication during this
time (FS=10 min), the controller will return to the preset
operating mode.
Heating/Cooling
Control states In control state Heating/Cooling, the controller functions
The controllers can be configured for different control as a heating controller when the room temperature
states/control sequences: is lower than the basic heating setpoint plus half the
neutral zone. The neutral zone is the difference in
Heating temperature between the heating setpoint and the cooling
Heating or cooling via the change-over function setpoint. When the room temperature exceeds this limit,
Heating/Heating the controller becomes a cooling controller. There is a
hysteresis of 0.1C when the controller changes from
Heating/Cooling heating to cooling controller and vice versa. When the
Heating/Cooling with VAV-control and forced supply controller is heating, it regulates according to the basic
air function heating setpoint plus the setpoint displacement, and
when it is cooling according to the basic cooling setpoint
Heating/Cooling with VAV-control
plus the setpoint adjustment.
Cooling
Flkt Woods 8713 GB 2014.04 9 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Actuator exercise
All actuators are exercised. The exercise takes place at
set intervals in hours (FS=23 hours interval). An opening
Cooling signal is sent to the actuator for as long time as the run
time has been configured. Then a closing signal is sent for
In control state Cooling, the unit is always a cooling as long time and the exercise is finished.
controller and controls according to the basic cooling
setpoint plus the setpoint displacement.
Cooling/Cooling
Split output signal
In control mode Cooling/Cooling, the controller always
functions as a cooling controller and controls according to
the basic cooling setpoint plus the setpoint displacement.
When the controller output signal reaches 50%, it is
divided between two actuators. 048% of the signal is
sent to actuator 1 and 52100% of the signal is sent to
actuator 2. See the figure below.
Actuators
STRA-07 can be used with two types of actuators:
Analogue 010 V actuators
Thermal actuators
The actuator type is set via the parameter menu in the
display.
Analogue actuators
The following output signals can be set for analogue
actuators:
010 V (FS)
210 V
102 V
100 V
Flkt Woods 8713 GB 2014.04 10 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Off/Unoccupied
In operating modes Off and Unoccupied, the fan is
stopped, regardless of the position of the fan switch or the
setting in the display, on condition that the temperature
is within the set temperature limits. If the temperature
is not within the set temperature limits, the fan will be
started in the corresponding Auto position, regardless of
the settings.
Flkt Woods 8713 GB 2014.04 11 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Frost protection
STRA has built-in frost protection, which is activated
when the controller is not in use. The frost protection
prevents the temperature from dropping below
8C. Return to normal fan speed and control occurs
automatically when the room temperature exceeds 8C.
Flkt Woods 8713 GB 2014.04 12 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Parameters
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter number Description Values Unit FS STRA-07
1 Occupied Heating Setpoint C 22
2 Occupied Cooling Setpoint C 24
3 Standby Neutral Zone C 3
4 Unoccupied Heating Setpoint C 15
5 Unoccupied Cooling Setpoint C 30
6 Frost protection Setpoint C 8
7 P-Band C 10
8 I-Time sec 300
9 Cooling Changeover difference temperature (Room C 3
and media)
10 Heating Changeover difference temperature (Room C 4
and media)
11 Heating/Cooling Functions 0=Heat, 3
1=Heat/Heat,
2=Heat or Cool via changeover,
3=Heat/Cool,
4=Heat/Cool with VAV and forced v'entilation,
5=Heat/Cool with VAV,
6=Cool,
7=Cool/Cool,
8=Heat/Cool with UO3,
9=Heat/Cool with Change-Over
12 Boost Mode Timer min 120
13 P.I.R Delay Off min 10
14 P.I.R Delay On min 0
15 Connected sensor on AI1 0=internal, 0
1=external,
2=Change over sensor
16 UI1 Signal 0 = Disabled, 2
1 = Change over sensor digital,
2 = Change over sensor analogue
17 Connected sensor DI1 Input 0=Disabled, 3
1=Window contact,
3=P.I.R,
4=Change over sensor
18 Connected sensor DI2 input 0=Disabled, 2
1=Window Contact,
2=Condensation Sensor,
4=Change over sensor
20 Function of UO1 Signal 0=None, 3
1=Thermal actuator heat,
2= None,
3=Heating actuator 0...10V,
4= None,
5=On/off actuator heat,
6= None
21 Function of UO2 Signal 0= None 4
1= None,
2=Thermal actuator Cool,
3= None,
4=Cooling actuator 010V,
5= None,
6=On/off actuator cool
Flkt Woods 8713 GB 2014.04 13 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Parameters
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter number Description Values Unit FS STRA-07
22 Function of UO3 Signal 0=None, 0
1=Forced Vent Digital,
2=Forced Vent 3 Step Analog,
3=None,
4=Ordinary Analog output,
5=None,
6=Control of EC-fan
24 U03 output in manual mode 0
28 Actuator type for UO3 0=0-10v, 0
1=2-10v,
2=10-2v,
3=10-0v
29 Heating Modulating Actuator Control 0=0-10v, 0
1=2-10v,
2=10-2v,
3=10-0v
30 Cooling Modulating Actuator Control 0=0-10v, 0
1=2-10v,
2=10-2v,
3=10-0v
31 Heating Thermal Actuator Time sec 60
32 Cooling Thermal Actuator Time sec 60
33 Travelling Time for Increase/Decrease Heating Valve 0 sec 120
(Not in use)
34 Travelling Time for Increase/Decrease Cooling Valve 0 sec 120
(Not in use)
35 Increase/Decrease NZ (Not in use) 0 % 2
36 Heating Valve Periodic Exercise Interval 0=inactive hours 23
37 Cooling Valve Periodic Exercise Interval 0=inactive hours 23
38 Hysteresis for the heating thermostat function C 2
39 Hysteresis for the cooling thermostat function C 2
40 The minimum heat output in heating mode % 0
41 Fan runs on low speed (Not in use) 0 0
42 Display View 0=Actual Temp Value, 0
1=Heating Setpoint,
2=Cooling Setpoint,
3=Average of Heating/Cooling,
4=Only Setpoint Displacement,
5=CO2,
6=Heating Setpoint + Setpoint Displacement,
7=Cooling Setpoint + Setpoint Displacement,
8=Average of Heating/Cooling Setpoints + Setpoint
Displacement,
9=Calculated Flow in L/S
43 Highest Setpoint Offset Increase C 3
44 Lowest Setpoint Offset Decrease C 3
45 Normal Mode Function 0=Off, 3
1=Unoccupied,
2=Stand-by,
3=Occupied
46 Energy Saving Mode Function 0=Off, 1
1=Unoccupied
47 BMS Operating Mode 0=Off, 5
1=Unoccupied,
2=Standby,
3=Occupied,
4=Not Used,
5=No Remote control
48 Minimum airflow on cooling UO2 in % of 0-10V. 20
Parameter is in use when cooling/heating mode with
VAV is selected.
49 Maximum airflow on cooling UO2 in % of 0-10V. 0
Parameter is in use when heating/cooling mode with
VAV is selected.
50 Fan Control 0=No control, 3
1=Heating,
2=Cooling,
3=Both
51 Fan Speed 1 Limit 0 % 5
52 Fan Speed 2 Limit 0 % 60
Flkt Woods 8713 GB 2014.04 14 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Parameters
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter number Description Values Unit FS STRA-07
53 Fan Speed 3 Limit 0 % 100
54 Fan Start/Stop Hyst 0 5
55 Fan Speeds 0 3
56 External Temperature Sensor Calibration Gain AI1 C 0
57 Sensor Calibration Gain UI1 C 0
58 Internal Temperature Sensor Calibration Gain C 0
59 Filter factor for AI temperature C 0.2
60 Normally open/Normally closed DI1 0 = For N/C-actuator, 0
1=For N/O-actuator
61 Normally open/Normally closed DI2 0=N/O, 1
1=N/C
62 Normally open/Normally closed UI1 0=N/O, 0
1=N/C
63 Heating Manual Override 0=, 2
1=Manual,
2=Auto
64 Cooling Manual Override 0=, 2
1=Manual,
2=Auto
65 Forced ventilation Manual Override 0=, 2
1=Manual,
2=Auto
66 Changeover Manual Override 0=Heating, 2
1=Cooling,
2=Auto
67 Manual Mode Heating Output % 0
68 Manual Mode Cooling Output % 0
69 Modbus Address
70 Modbus Parity 0=None, 2
1=Odd,
2=Even
71 Modbus Timeout millisecond 3
72 Modbus Response Delay Millisecond 5
73 Heating output 0 = For N/C-actuator, 0
1=For N/O-actuator
74 HMI Displacement View 0=The offset, 0 0
1=The active setpoint + offset,
2=The heating setpoint + offset,
3=The cooling setpoint + offset,
4=Occupied Heating Setpoint + Offset,
5=Occupied Cooling setpoint + Offset,
6=Occupied Average + Offset
75 Free Cooling 0=ON, 1=OFF N/A 0
76 Forced Ventilation control mode 0=No Action, 0
1=Forced on Heat/Cool output at 100%,
2=Forced on Cool output at 100%
77 P.I.R Activated Operation Mode 3=Occupied, 4
4=Bypass
78 The Controller PLA Address. Used in EXOline 0
79 The Controller ELA Address. Used in EXOline 0
80 Cool output 0=N/O, 1=N/C 0
81 AI2 Input 0=Disable, 0
5=CO2,
7=0-100% ,
8=Flow calculation,
9=0-10V
82 Flow at 0 volt on AI2 (Not in use) 0 l/s 0
83 Flow at 10 volt at AI2 (Not in use) 0 l/s 100
84 The minimum time the valve is open when the sec 60
calculation of change over is made
86 Alarm triggers when temperature falls below C 40
87 Alarm triggers when temperature raise above C 15
97 CO2 Level to Change to Boost Mode PPM 0
98 CO2 Level below "Boost Mode CO2 Start" value to PPM 0
start Boost Mode Timer countdown
100 AI CO2 Filter 0
104 CO2 Sensor PPM for 0v PPM 104
105 CO2 Sensor PPM for 10v PPM 0
Flkt Woods 8713 GB 2014.04 15 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.
Parameters
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter number Description Values Unit FS STRA-07
112 VAV CO2 Minimum Limit PPM 0
113 VAV CO2 Maximum Limit PPM 0
114 Port Mode 0=EXOline/Modbus, 0
1=BACnet
115 BACnet address Above 127 = Slave
116 BACnet device ID low 4 figures
117 BACnet device ID high 3 figures
118 BACnet Max Master 127
119 Com Speed 0=9600, 0
1=19200,
2=38400,
3=76800 (BACnet)
120 Reset com to factory default (Modbus 9K6, 8, N, 1) 0
121 The lowest output the fan will need to start (Not in 0 V 10
use)
122 The highest speed of the fan (Not in use) 0 V 100
125 The Model in Regin Range 1939 = STRA-07, Read Only 1939
1943 = STRA-04,
1945 = STRA-14
126 Major Version
127 Minor Version
128 Branch Version
129 Revision
Flkt Woods 8713 GB 2014.04 16 Specifications are subject of alteration without further notice.