Professional Documents
Culture Documents
SM15A
Mini Rail &
Surface Mount
Features Applications
Hydraulic-magnetic technology Mining, heavy industrial and commercial applications
100% rating capability, independent of ambient temperature requiring high sensitivity earth leakage protection from
VC 8035 compliant electrical shock and fire hazards
AS/NZS 3111 and AS/NZS 3190 compliant Telecom / datacom equipment
Immune to pulsating DC load current Lighting control
Operating Voltage 110 and 240 V AC UPS equipment
Ratings 10 to 100 A Alternative energy equipment
Earth Leakage sensitivity 30 mA, 50 mA, 100 mA, 250 mA, Mobile power generation equipment
375 mA, 500 mA, 1000 mA Railway signalling equipment
Single pole plus switched neutral earth leakage protection
Precision tripping characteristics
Reset immediately after overload
Suitable to use for electrical isolation
Medium
S Current Sensitivity Voltage No special
Requirement Type M 1 pole + N Overload No auxiliary delay
Frame rating 100 A 100 mA 240 V AC termination
curve 2
100000
1500
OPERATING
CHARACTERISTICS
10000
CURVE 2
1000
100
Tripping Time (Seconds)
10
0.1
Maximum
0.01
Minimum
0.001
1000
100
105
1500
2000
2500
3000
4000
5000
130
150
200
300
400
500
% Rated Current
* The published time delay curves are generated at 30oC ambient temperature with the Circuit Breaker mounted in the up-right position. The must hold, must trip and instantaneous
trip current values are not affected by temperature, although delay time for the other operating current values may have to be adjusted using the temperature compensation curve which
is available on request.