You are on page 1of 5

A Novel Phase Selection Method Based on Instantaneous Reactive

Power
Shuxin Luo, Xinzhou Dong, Shenxing Shi, Bin Wang
Department of Electrical Engineering, Tsinghua University, Beijing 100084, China

Keywords: Hilbert transform; Instantaneous reactive power; travelling wave to select the faulted phase, which is
Phase selection; UHV transmission lines; advantageous in identification speed, but is also defective in
its vulnerability to the wave reflection and refraction.
Abstract Moreover, in the cases of small fault initial angles, the
magnitude of travelling wave current is so faint that the
Travelling wave protection, which performs brilliantly with method cannot identify the fault type correctly. On the other
high operation speed, is perfectly feasible for ultra-high hand, transient energy is applied in phase selection to improve
voltage (UHV) transmission line protection. Since nearly 70% recognition performance. However, in some cases of three-
faults in UHV transmission lines are single-line to ground phase faults, this method may mistakenly classify them into
(SLG) faults, the cooperation of single phase tripping and two-phase faults. In addition, Reference [9] uses neutral
auto-reclosing is the most common and effective method to network to analyse fault high frequency noises and identify
isolate SLG faults and improve the stability of the power the faulted phase. This algorithm needs complicated
system. Among the techniques of single phase tripping, phase calculation and is not practical in relay device.
selection is an essential part for its contribution to select the
exact faulted phase. However, traditional phase selection In this paper, aiming at improving the accuracy and rapidity
algorithms do not work well with traveling wave protection of phase selection, a novel method based on instantaneous
due to their low recognition speed. In this regard, an reactive power is presented. The basic principles of
innovative phase selection method is presented in this paper. instantaneous reactive power are firstly introduced in Section
Firstly, reactive energies are proved to have significant 2. In Section 3, a phase selection method is proposed to
differences for healthy and faulted phase respectively. On this identify the fault type and the faulted phase, and the detailed
basics, instantaneous reactive power is adopted to construct algorithm is presented as well. Extensive simulations are
selection criterion to accelerate identification speed. Various carried out in Section 4 to verify the effectiveness of the
simulation results have been conducted to validate that the proposed method. Finally, conclusions are summarized in
proposed method is advantageous for travelling wave Section 5.
protection with rapid and accurate identification.
2 Basic principle
1 Introduction
With the rapid development of power systems, ultra-high 2.1 Fault characteristic
speed protection has been applied to isolate transmission line
faults as quickly as possible in order to ensure the security According to the superposition theorem, a faulted system can
and stability of the system. Travelling wave protection, one of be decomposed into normal operation network and fault
the most typical ultra-high speed protections, is widely component network. The fault components of voltage and
utilised in high voltage transmission lines [1-4]. Compared to current are calculated in (1).
traditional protection, travelling wave protection is attractive 'u (t ) u (t )  u (t  T )
not only for its high speed reaction, but also for its robustness (1)
'i(t ) i(t )  i(t  T )
to CT saturation and distributed capacitor current.
where T represents the power frequency period of voltage and
As SLG faults are the most common faults in UHV current.
transmission lines, single phase tripping is applied to isolate
SLG faults. Phase selection techniques are indispensable Figure 1 shows the fault component network in SLG fault
procedures for identifying the faulted phase. For travelling situation. Assume that the negative sequence impedance of
wave protection, it requires quick and accurate phase the transmission line is the same as the positive sequence
selection methods to cope with high action speed. However, impedance. From Figure 1, the results of Ia, Ib and Ic are
traditional phase selection methods, making use of power formulated in (2).
frequency component, is not feasible in travelling wave
protection due to its slow speed in faulted phase identification
[5, 6]. In this regard, several extended methods have been
investigated in the past decades. Reference [7] used initial

1
2.3 Definition of instantaneous reactive power
Zm M N Zn
C Ic The concept of instantaneous reactive power for sinusoidal
B Ib signals was first developed in [10]. It is used for reactive
Ia power calculation in reactive power compensation. Another
A F
definition of instantaneous reactive power is proposed in [11]
to be applied in non-sinusoidal signals, as shown in (9). The
UF voltage and current after faults contain steady sinusoidal
components and transient non-sinusoidal components as well.
Therefore, the instantaneous reactive power defined in (9) is
adopted in this study to deal with the transient non-sinusoidal
Figure 1: Fault component network in SLG fault situation
signals. It can be proved that the integration of instantaneous
reactive power in one cycle equals to the definition of
'I a I a 0  2 I a1 traditional reactive power [11, 12].
(2)
'I b 'I c I a 0  I a1 q(t ) u(t )iq (t ) u(t )Gqu(t ) (9)
Ia0 and Ia1 are expressed in (3). In (9), u(t ) is the Hilbert transform result of u(t). Gq is a
( L  x) Z 0  Z n U F ( L  x) Z1  Z n U F factor defined in (10), and iq(t) is the reactive component of
Ia0 , I a1 (3)
LZ 0  Z m  Z n Z LZ1  Z m  Z n Z current.
where Z is defined in (4).  u (t ), i (t ) !  u (t ), i (t ) !
Gq 2 2
(10)
( xZ1  Z m )[( L  x) Z1  Z n ] ( xZ 0  Z m )[( L  x) Z 0  Z n ] u(t ) u (t )
Z 2 
LZ1  Z m  Z n LZ 0  Z m  Z n For fault component network, the reactive energy is the
(4) integration of the fault component of the instantaneous
reactive power q(t), as shown in (11). Voltage and current
In the aforementioned formulas, Z1, Z0 depict the positive and
fault components u(t), i(t) are used to calculate q(t)
zero sequence impedance of the transmission line per unit of
according to (9). This result includes the reactive energy of
length. x is the fault distance and L is the total length of the
power frequency component, as well as the transient reactive
transmission line.
energy of high frequency component.
t
With the fact that Ia0 is approximately equal to Ia1, it can be 'Q(t ) 'q(W )dW (11)
concluded that Ia is much larger than Ib and Ic, as shown 0

in (5). Therefore, the reactive energy shown in (6) has the


same characteristic as the fault current. Similarly, the current 3 Proposed method
and reactive energy of the healthy phase in two-phase faults
are much smaller than the faulted phases. In three-phase faults,
as the system remains symmetrical, the currents and reactive 3.1 Algorithm
energies of three phases remain almost equal to each other.
The reactive energies of three phases Qa(t), Qb(t) and Qc(t)
'I a 'Ib 'I c (5) are calculated and sorted as Q (t), Q (t) and Q (t).
max mid min
These three indices have different performances in different
'Qa 'I a imag(Zm ) 'Qb 'Qc
2
(6) kinds of faults:

2.2 Hilbert transform 1) Single-line to ground fault - The faulted phase has the
maximum reactive energy and it is much greater than the
Hilbert transform, as defined in (7), is an all-pass filter which normal ones;
performs a -90 degree shift for the positive frequency 2) Two-phase fault - The reactive energies of the two faulted
component of the signal. phases are much greater than the healthy phase;
1 f x(W ) 1 3) Three-phase fault - The energies of three phases are
S
x(t ) dW x(t )* (7) almost the same as the system remains symmetrical.
f t W St
Therefore, the phase selection can be accomplished by the
In relay implement, Hilbert transform was discretized as filter following principle where kset1 and kset2 are the setting values.
h[n], as shown in (8). 'Qmax (t )
1) Single-line to ground fault: ! kset1 ;
0, for n even 'Qmid (t )

h[n] 2 (8) 'Qmid (t )
nS , for n odd 2) Two-phase fault: ! kset 2 ;
'Qmin (t )
3) Three-phase fault: all other results.

2
In order to improve the reliability of the algorithm, only when distributed capacitors in order to restrict over-voltage in the
the condition shown in (12) is satisfied, the method begins to transmission lines. In this model, the compensation factor is
carry out the fault type and fault phase. 35% in either side.
'Qmax (t ) ! Qset and t > 5ms (12) M N
L1 500km
Qset is set as the reactive energy produced by 10% variation of
voltage and current in half a period as shown in (13). S1 S
F1
Qset t 0.1U *0.1I *T / 2 0.065 MVar s (13) L2
S2
Load S3
In this study, Qset is set as 0.07 MVars and kset1, kset2 are set to
be 10. In order to improve the reliability of the method, only
if three consecutive calculated results satisfy the same Figure 3: Simulation model
principle, the fault type is decided and the faulted phase is
identified. 4.2 Different Fault types
Reactive energies during A-G fault, AC phase to ground fault
3.2 Flowchart
and ABC three phase fault are shown in Figure 4. More
The flowchart of the proposed phase selection method is results of different types of faults are shown in Table 1. The
shown in Figure 2. proposed method can identify the correct fault type and the
faulted phase in 5.2 ms. The response time is calculated from
Voltage and current the time when fault happened.
sampling data
0.5
Reactive energy

Fault 0
(MVARs)

happened?
-0.5
' Qa(t)
Yes -1 ' Qb(t)
' Qc(t)
t > 5ms -1.5
0 1 2 3 4 5 6 7 8
Time (ms)
Yes
(a) Phase A to ground fault
Calculate Qa(t), 1
Qb(t) and Qc(t)
Reactive energy

0
No
(MVARs)

-1
Yes Qmax (t)>Qset ' Qa(t)
-2 ' Qb(t)
' Qc(t)
-3
0 1 2 3 4 5 6 7 8
Qmax (t)/Qmid(t) No Qmid(t)/Qmin(t) No Time (ms)
>kset1 >kset2
(b) AC phase to ground fault
No Yes No Yes No 1
Reactive energy

0
(MVARs)

Consecutive three Consecutive three Consecutive three


points? points? points? -1
' Qa(t)
Yes Yes Yes -2 ' Qb(t)
' Qc(t)
-3
Single phase fault Two phase fault Three phase fault 0 1 2 3 4 5 6 7 8
Time (ms)
(c) ABC three-phase fault
End
Figure 4: Phase reactive energies during different kinds of
Figure 2: Flowchart of the proposed phase selection method faults ( *Note that Qb(t) and Qc(t) are almost the same in
(a). )
4 Simulations
Fault Qa(t) Qb(t) Qc(t) Response
types (MVars) (MVars) (MVars) time (ms)
4.1 Simulation model A-G -0.5025 -0.0062 -0.0062 5.2
B-G -1.61e-4 -0.1040 -1.54e-4 5.2
A simulation model recommended by the Chinese national C-G -0.0055 -0.0055 -0.1764 5.2
standard is built using EMTP/ATP, as shown in Figure 3 [13]. AB -0.3479 -0.3481 -1.47e-8 5.2
The frequency-dependent transmission line model is BC -3.02e-8 -0.1199 -0.1201 5.2
employed [14]. Shunt reactors are used to compensate the AC -0.4445 -8.53e-9 -0.4444 5.2

3
ABG -0.6829 -0.1825 -0.0033 5.2 the situation of close-up faults and long distance faults. In
BCG -0.0038 -0.1488 -0.1898 5.2 close-up fault situations, the method shows up a greater
ACG -0.6705 -9.71e-5 -0.3230 5.2 sensitivity due to the reactive power of the faulted phase is
ABC -0.8395 -0.1848 -0.2939 5.2 much larger than far-away faults.

Table 1: Results of different types of faults (Fault distance: Fault


Qa(t) Qb(t) Qc(t) Response
100 km) distance
(MVars) (MVars) (MVars) time (ms)
(km)
4.3 Influence of fault resistance 1 -3.3963 -0.0403 -0.0403 5.2
10 -2.4513 -0.0258 -0.0258 5.2
The influences of fault resistances are studied in this paper. 100 -0.5025 -0.0062 -0.0062 5.2
The simulation results are shown in Table 2 indicating that 200 -0.2411 -0.0081 -0.0082 5.2
the phase selection method is adaptive in high resistance fault 250 -0.2557 -0.0070 -0.0070 5.2
situation. With the increase of the resistance, the response 300 -0.2560 -0.0084 -0.0084 5.2
time becomes longer. When the fault resistance increases up 400 -0.2261 -0.0061 -0.0061 5.2
to 400 , the response time will be 6.9 ms. 499 -0.5708 -0.0555 -0.0555 5.2

Fault Table 4: Results of AG faults with different fault distances


Qa(t) Qb(t) Qc(t) Response
resistance
(MVars) (MVars) (MVars) time (ms)
()
5 Conclusions
0.1 -0.5025 -0.0062 -0.0062 5.2
1 -0.5018 -0.0062 -0.0062 5.2 This paper focuses on phase selection techniques for
10 -0.4849 -0.0056 -0.0056 5.2 travelling wave protection. The study first analyses the fault
20 -0.4539 -0.0050 -0.0050 5.2 component current in fault conditions, showing that the
50 -0.3497 -0.0038 -0.0038 5.2 reactive energies of healthy phases are much smaller than the
100 -0.2265 -0.0026 -0.0026 5.2 faulted phases, which is suitable to be a phase selection
200 -0.1136 -0.0014 -0.0014 5.2 criterion. On this basis, instantaneous reactive power based on
300 -0.0757 -9.40e-4 -9.39e-4 5.5 Hilbert transform, is adopted to construct a novel phase
400 -0.0772 -7.25e-4 -7.25e-4 6.9 selection method to identify the fault type and faulted phase.
The innovative method is accurate for significant differences
Table 2: Results of AG faults with different fault resistances of reactive energies in healthy and faulted phase, and it is also
(Fault distance: 100 km, fault type: AG) rapid in selection by using the instantaneous index instead of
frequency component as normal methods.
4.4 Influence of fault initial angle
Furthermore, various kinds of faults with different grounding
The influences of different fault initial angles are also resistances, fault initial angles and fault distances are
simulated. For the methods based on travelling wave, it is simulated to test the feasibility of the proposed algorithm.
non-effective in the case of fault occurred with zero voltage Simulation results show that the presented method is well
angle. Simulation results in Table 3 show that the proposed adaptive in diverse situations with brilliant speed. Compared
phase selection method can perform quickly and accurately in to the phase selection methods using travelling wave, this
the cases of small fault initial angles. method is irrespective of small fault initial angle. Meanwhile,
in the cases of close-up faults and high impedance faults, its
Fault performance is also satisfactory. As a result, it can be
Qa(t) Qb(t) Qc(t) Response
angle concluded that the reactive energy based method, which has
(MVars) (MVars) (MVars) time (ms)
(degree) great advantages in rapidly identifying the faulted phase by
0 -0.0987 -1.72e-4 -1.69e-4 5.2 using the instantaneous data, is feasible to be applied in
5 -0.1093 -1.65e-4 -1.63e-4 5.2 traveling wave protection.
10 -0.1240 -2.58e-4 -2.57e-4 5.2
20 -0.1629 -7.47e-4 -7.47e-4 5.2
30 -0.2459 -0.0019 -0.0019 5.2
Appendix
60 -0.4979 -0.0058 -0.0058 5.2 The line configuration is shown below:
90 -0.3861 -0.0078 -0.0079 5.2

Table 3: Results of AG faults with different fault initial angles

4.5 Influence of fault distance


Table 4 shows the results of AG faults with different fault
distances. It can be concluded that the method adapts well in

4
[4] X. Z. Dong, Y. Z. Ge, J. L. He. Surge impedance
relay. Power Delivery, IEEE Transactions on, 20, (2),
pp. 1247-1256, (2005).
[5] Z. Y. Xu, Q. X. Yang, W. S. Liu, et al. A sequence
fault phase selector for transmission line protective
relay, Proceedings of the Chinese Society for Electrical
Engineering, 17, (3), pp. 71-73, (1997).
[6] Q. Q. Xu, J. L. Suonan, G. B. Song, et al. A fault phase
selector for transmission line protective relaying using
current fault components. Automation of Electric
Power Systems, 27, (7), pp. 50-54, (2003).
[7] X. Z. Dong, W. Kong, T. Cui. Fault classification and
faulted-phase selection based on the initial current
traveling wave, Power Delivery, IEEE Transactions on,
24, (2), pp. 552-559, (2009).
[8] J. D. Duan, B. H. Zhang, Y. Zhou, et al. Transient-
based faulty phase selection in EHV transmission lines,
Proceedings of the Chinese Society for Electrical
Engineering, 26, (3), pp. 1-6, (2006).
[9] Z. Q. Bo, R. K. Aggarwal, A. T. Johns, et al. A new
approach to phase selection using fault generated high
Figure A1: Tower structure of 750 kV parallel transmission frequency noise and neural networks. Power Delivery,
lines IEEE Transactions on, 12, (1), pp. 106-115, (1997).
[10] H. Akagi, Y. Kanazawa, K. Fujita, et al. Generalized
Acknowledgements theory of instantaneous reactive power and its
application. Electrical Engineering in Japan, 103, (4),
This work was supported by the National Natural Science pp. 58-66, (1983).
Foundation of China (Grant 50937003, 51120175001, [11] Y. D. Xue, B. Y. Xu, Z. R. Feng. Average and
51107062). instantaneous reactive power of non-sinusoidal circuit
based on Hilbert transformation. Automation of Electric
References Power Systems, 28, (12), pp. 35-39, (2004).
[12] T. Cui, X. Z. Dong, Z. Q. Bo, et al. Hilbert-transform-
[1] M. Chamia, S. Liberman. Ultra high speed relay for based transient/intermittent earth fault detection in non-
EHV/UHV transmission lines -- Development, design effectively grounded distribution systems. Power
and application. Power Apparatus and Systems, IEEE Delivery, IEEE Transactions on, 26, (1), pp. 143-151,
Transactions on, 97, (6), pp. 2104-2116, (1978). (2011).
[2] H. W. Dommel, J. M. Michels. High speed relaying [13] DL/T 871-2004. The dynamic test of the power system
using traveling wave transient analysis. IEEE PES protective products. National Development and Reform
Winter Meeting, New York, NY, 1978. Commission, Peoples Republic of China. (2004).
[3] P. A. Crossley, P. G. Mclaren. Distance protection [14] J. R. Marti. Accurate modelling of frequency-
based on travelling waves. Power Apparatus and dependent transmission lines in electromagnetic
Systems, IEEE Transactions on, 102, (9), pp. 2971-2983, transient simulations. Power Apparatus and Systems,
(1983). IEEE Transactions on, 101, (1), pp. 147-157, (1982).

You might also like