Professional Documents
Culture Documents
1 Application and features Protection devices for electrical systems minimize fault
2 Design damages, assist in maintaining power system stability
3 Working Principle and help to limit supply interruptions to remaining
3.1 Operating principle of the differential consumers.
protection
3.2 Working principle of the C.T. saturation Differential protection for generators, based on the
detector SAT well-known Merz-Price circulating current principle,
3.3 Block diagram which compares currents in two measuring points, e.g.
4 Operation and settings the current to the star point of a generator with the cur-
4.1 Parameter setting rent to the busbar, is a fast and selective form of pro-
4.2 Setting of the pickup value for the differential tection. Faults lying within the protected zone are
current ld1 fine tripping characteristic cleared very rapidly, thus limiting fault damage.
5 Relay testing and commissioning
5.1 Connection of the auxiliary voltage Types of faults occuring within the protected zone re-
5.2 Checking the set values quiring immediate tripping and isolation of the genera-
5.3 Secondary injection test tors are:
5.3.1 Test equipment
5.3.2 Checking of the pickup and dropout value faults between statorwindings
5.3.3 Checking the trip delay stator earth faults
5.4 Primary injection test ground faults and faults between phases outside the
5.5 Adjustment of the interposing C.T.s generator but within the protected zone, e.g. at the
5.6 Maintenance generator terminals or on the external connections.
5.7 Function test
6 Technical Data An extremely important feature of any generator differ-
6.1 Relay case ential protection is that it should remain absolutely sta-
6.2 Technical Data ble (i.e. no tripping command) for faults or any other
7 Orderform transient phenomena outside the protected zone.
2 TD_XD1-G_01.04_GB
The relay XD1-T of the PROFESSIONAL LINE has the fol- Extended version (type suffix SAT)
lowing special features:
Ability to recognize saturation of the main current
Fault indication via LEDs transformers
Extremely wide operating ranges of the supply volt- Extremely stable even during saturation of current
age by universal wide-range power supply transformers
Very fine graded wide setting ranges Current transformer burden and class requirements
Extremely short response time are low
Compact design by SMD-technology Additional printed circuits for recognition of satu-
Static, three-phase differential protection relay rated C.T.s can be added at a later stage, e.g. as
Dual slope percentage bias restraint characteristic the power system develops and fault levels increase
with adjustable bias setting
Electronical storage for indication of the faulty phase
Applicable for 45 to 65 Hz Further features of the unit XD1-G:
Burden < 0.05 VA at rated current High reliability and easy-to-service arrangement
Setting ranges: Plug in design makes it possible to simplify extension
Differential current: of the basic unit
5 to 42.5 % IN in 15 steps LED indication of operating conditions
Bias slope:
10 % of actual current (fixed)
Isolation between all independent inputs
High electromagnetic compatibility
The use of precision components guarantees high
accuracy
Permissible temperature range:
-20C to +70C
According to the requirements of VDE 0435,
part 303 and IEC 255
TD_XD1-G_01.04_GB 3
2 Design
4 TD_XD1-G_01.04_GB
3 Working Principle
The fundamental operating principle of generator dif- With many transformer differential protection systems,
ferential protection is based on a comparison of the relay instability may cause to trip if the main current
current to the star point with the current to the busbar. transformers saturate. In the transient condition of satu-
For an ideal generator the currents entering and leav- ration the C.T.s on both ends of the protected zones
ing the generator must be equal. Or according to do not produce the correct secondary current accord-
Kirchhoff's first law "the vector sum of currents entering ing to the primary current. The differential relay meas-
and leaving any point must be zero". If the sum Id of ures a differential current on the secondary C.T. side
currents is not zero, an internal fault is indicated. which is not present on the primary side. Hence a
false tripping might occure.
The basic equipment of relay XD1-G recognizes these Such transient phenomena causing C.T. saturation
differential currents Id and the relay gives the tripping may occur due to:
command according to the precision measuring char- Heavy through faults (external short circuit)
acteristic (see Tripping characteristics). Starting of big motors
Magnetizing inrush currents of transformers
To explain the function at XD1-G the working principle
is shown in figure 3.1. The figure 3.2 explains the saturation of the C.T. core
due to a short circuit current. In the instant of a short
circuit often a DC-component is present in the current.
Protected Zone The high primary current induces a flux in the C.T.
core, reaching the saturation level. The iron-core re-
Iin Iout tains the high flux level even after the primary current
Generator falls to zero. In the time periods of saturation the C.T.
does not transform the primary current to the secondary
I1 I2 side but the secondary current equals zero.
Differential relay
Current
comparision
Id
Biasing circuit
Is
Us
Ud Tripping
characteristic
Trip
TD_XD1-G_01.04_GB 5
Dissimilar saturation in any differential scheme will Fig. 3.3 shows the two secondary currents in the in-
produce operating current. stant of an heavy external fault, with current i1 sup-
posed to C.T. saturation, current i2 without C.T. satura-
Figure 3.3 shows the differential measurement on the tion.
example of extremly dissimilar saturation of C.T.s in a The differential current id represents the measured dif-
differential scheme. Fig. 3.3 shows the secondary cur- ferential current, which is an operating current. As this
rent due to C.T. saturation during an transformer fault differential current is caused by an external fault and
(internal fault). The differential current id represents the dissimilar saturation of the two C.T.s, the differential re-
fault current. The differential relay must trip instan- lay should not trip.
tanously.
The wave forms for the differential current Id for internal and external faults are seen to be different for the cases
considered.
t t
id id id=i2-i1
id=i2-i1
t t
Figure 3.3: Current comparison with C.T.s saturated by DC offset in fault current wave form
6 TD_XD1-G_01.04_GB
The saturation detector SAT analyses the differential
current of each phase separately. The SAT module dif-
ferentiates the differential current and detects:
TD_XD1-G_01.04_GB 7
3.3 Block diagram
8 TD_XD1-G_01.04_GB
4 Operation and settings
LEDs
For adjustment of the unit the transparent cover has to LED ON is used for display of the readiness for ser-
be opened as illustrated. Do not use force! The trans- vice (at applied auxiliary voltage Uv). LEDs L1, L2, L3
parent cover has two inserts for labels. and TRIP are provided for fault indication. LED 2 in-
dicates changeover to the coarse measuring element
(only with an additional SAT module).
Potentiometer
TD_XD1-G_01.04_GB 9
4.1 Parameter setting 4.2 Setting of the pickup value for
the differential current ld1 fine
tripping characteristic
For each phase the relay calculates the differential cur- The pickup value of the fine tripping characteristic can
rent Id and the stabilizing current IS. The differential cur- be adjusted in the lower section by means of the step
rent Id is the vector difference between star point and switch Id1 in the range from 5 - 42.5 %. (Scale 2.5 %).
outgoing currents. The value of differential current at
which the relay responds is dependent on the stabiliz- Example:
ing current, as shown in fig. 5 "Tripping characteristic". Adjustment of the characteristic is shown on the
IN is relay rated current (1 A or 5 A) and the two quan- following diagram:
tities Id/IN and IS/IN are scaled in multiples of rated cur-
rent.
The basic version of the relay is equipped with the
"fine" tripping characteristic only. The differential cur-
rent Id is adjustable from 5 % to 42.5 % of rated cur- TRIPPING
rent. With the extended version SAT the tripping char-
acteristic can be automatically switched from the se- Id/IN
lected "fine" to the fixed "coarse" characteristic. 10%
The biased slope characteristic (right and upper part of 100
the characteristic) prevents incorrect operation of the
relay at through faults. The lower section of the charac-
teristic shows the minimum differential current required
to operate the relay with zero or low levels of stabiliz- Setting Id1 = 20%
ing current.
10-1
Bias characteristic setting (fixed)
(related to stabilizing current IS)
Id2 % = Id/IS = 10 %
NO TRIPPING
Differential current settings 10-2
(related to relay rated current IN) 10-1 100 IS/IN 101
Id2 % = Id/IS = 60 %
For differential currents up to rated current the time Figure 4.4: Adjustment of step switch
delay is 100 ms.
For differential currents greater than rated current the
relay trips instantaneously (approx. 40 ms).
10 TD_XD1-G_01.04_GB
5 Relay testing and 5.3.2 Checking of the pickup and
commissioning dropout value
NOTE!
Before this test is initiated by means of secondary cur-
rent, it must be ensured that the relay cannot cause
any switching actions in the system (shut-down risk).
TD_XD1-G_01.04_GB 11
5.5 Adjustment of the interposing
C.T.s
12 TD_XD1-G_01.04_GB
5.6 Maintenance
Attention!
Disconnect all leads for adjusting the interposing C.T.s
and perform the following function test:
TD_XD1-G_01.04_GB 13
6 Technical Data
Relay XD1-G is designed to be fastened onto a DIN-rail acc. to DIN EN 50022, the same as all units of the
PROFESSIONAL LINE.
The front plate of the relay is protected with a sealable transparent cover (IP40).
Connection terminals
2
The connection of up to a maximum 2 x 2.5 mm cross-section conductors is possible. For this the transparent
cover of the unit has to be removed (see para. 3).
14 TD_XD1-G_01.04_GB
6.2 Technical Data
Measuring input
Rated data:
Rated current 1A/5A
Rated frequency fN: 50 - 60 Hz
Power consumption
in current circuit: at IN = 1 A < 0.1 VA
at IN = 5 A < 0.5 VA
Auxiliary voltage
General data
Output relays
Max. rated making current: 64 A (VDE 0435/0972 and IEC 65/VDE 0860/8.86)
Making current: min. 20 A (16 ms)
6
Mechanical life span: 30 x 10 operating cycles
5
Electrical life span: 2 x 10 operating cycles at 220 V AC / 6 A
Contact material: silver cadmium oxide (AgCdO)
TD_XD1-G_01.04_GB 15
System data
Mechanical tests:
Shock: class 1 as per DIN IEC 255 part 21-2
Vibration: class 1 as per DIN IEC 255 part 21-1
16 TD_XD1-G_01.04_GB
Tripping characteristics
60%
Id/IN
10%
Coarse measuring characteristic
Setting Id1 = 100%
100
10-1
Setting Id1 = 5%
10-2
10-1 100 IS/IN 101
t [ms]
100
80
60
40
20
0
0 1 2 3 4 5 6
Id/IN
TD_XD1-G_01.04_GB 17
Accuracy details
Idtrip Idset
for IS < IN: e= 100 %
IN
Idtrip Idset
for IS IN: e= 100 %
IS
If the operating temperature or frequency are outside the ranges quote, additional errors are:
Temperature range
-20C...70C: eadd < 2,5 %
Frequency range
45 Hz...66 Hz: eadd = 1 %
7 Orderform
18 TD_XD1-G_01.04_GB
Setting-list XD1-G
Setting of parameters
Default Actual
Function Unit settings settings
Id1 Differential current % In 5
TD_XD1-G_01.04_GB 19
Woodward SEG GmbH & Co. KG
Krefelder Weg 47 D 47906 Kempen (Germany)
Postfach 10 07 55 (P.O.Box) D 47884 Kempen (Germany)
Phone: +49 (0) 21 52 145 1
Internet
Homepage http://www.woodward-seg.com
Documentation http://doc.seg-pp.com
Sales
Phone: +49 (0) 21 52 145 635 Telefax: +49 (0) 21 52 145 354
e-mail: kemp.electronics@woodward.com
Service
Phone: +49 (0) 21 52 145 614 Telefax: +49 (0) 21 52 145 455
e-mail: kemp.pd@woodward.com