Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

include oil temperature indicator

2 winding temperature indicator

tap position indicator

AVR relay

it have Without M2.

TRANSFORMERS
Date..// Contractor signature Rev. 0

Page 1 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

GUARANTEE SCHEDULES

Date..// Contractor signature Rev. 0

Page 2 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project


GUARANTEE SCHEDULES

TABLE OF CONTENTS

ITEM DESCRIPTION

G2 Name of manufacturers, place of manufacture, testing & inspection and standard specification

G3 Bushing

G4 Power Transformers

G5 On-load Tap-changer

G-6 Fire Fighting System (N.A)

Date..// Contractor signature Rev. 0

Page 3 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

Date..// Contractor signature Rev. 0

Page 4 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 2]

Names of Manufacturers, Places of Manufacture, Testing & Inspection and Standard Specifications

Place of Place of
ITEM Names of Manufacturers Standard
Testing & Inspection
Manufacture

Main transformer TBEA China China IEC Standard

On-load tap-changer MR Germany MR, Germany IEC Standard

Bushing (primary) TBEA China China IEC Standard

Bushing (secondary) TBEA China China IEC Standard

Bushing (tertiary) TBEANanjing Zhida Electric Co., Ltd. China China IEC Standard

Oil Nynas Sweden Sweden IEC Standard

Core steel Baoshan iron and steelBaosteel China China IEC Standard

Winding copper Goldcup electrical apparatuscable China China IEC Standard

Voltage Regulator MR Germany MR, Germany IEC Standard

Date..// Contractor signature Rev. 0

Page 5 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

Date..// Contractor signature Rev. 0

Page 6 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 3]
Bushings

Transformer
Nominal Voltage - kV
Unit
Neutral terminal Line terminal Description
66 220 11 66 220

IEC Standard IEC Standard IEC Standard IEC Standard IEC Standard Standard and relevant publication 1.

TBEA TBEA TBEA Nanjing Zhida TBEA TBEA Name of Manufacturer 2.

Place of Manufacture 3.

China China China China China - Country 3.1.

Shenyang Shenyang Shenyang Nanjing Shenyang Shenyang - City 3.2.


BRDLW-
BRDLW- BFW-24/4000(BW- BRDLW- (BRDLW-252/1250)
72.5/2500BLW-3
126/6302500 24/4000) 72.5/20002500 2500
Type reference 4.
6/1250)

Date..// Contractor signature Rev. 0

Page 7 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

Classification 5.

OIP OIP OIP OIP - Major insulation 5.1.

Oil Oil Oil Oil Oil - Filling insulation 5.2.

Ratings: 6.
3672.5 126 1224 72.5 252 kV - Nominal voltage 6.1.

- Standard insulation level : 6.2.


170 550 75 325 1050 kV * dry lightning impulse 6.2.1.
* power -frequency
77155 255 35 155 505 accepted kV 6.2.2.
dry

Date..// Contractor signature Rev. 0

Page 8 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 3]
Bushings

Transformer
Unit Nominal Voltage - kV
Neutral terminal Line terminal Description
66 220 11 66 220
140 230 28 140 460 kV * power - frequency wet 6.2.3.
20002500 12502500 4000 20002500 12502500 A - Rated current 6.3.
50 63 100 50 63 kA - Rated thermal current 6.4.
1 1 1 1 1 Sec - Duration of thermal current 6.5.
125 158 250 125 158 kA - Rated dynamic current 6.6.
- Total cross-section corresponding to Ir
500 250 1600 800 500 mm2 6.7.
(St).
- Equivalent cross-section taking account of
625 310 2000 1000 625 mm2 6.8.
skin effect (Se).
N.A N.A N.A N.A N.A kg/m3 - Rated density of insulating gas 6.9.
Date..// Contractor signature Rev. 0

Page 9 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project


3150 4000
3150 3150 3150 N - Cantilever withstand load 6.10.
accepted accepted
200 350 N.A 200 350 F - Maximum value of test tap capacitance 6.11.
- Dielectric dissipation factor (tan )
0.1 0.1 N.A 0.1 0.1 % 6.12.
increase bet. 1.05 Um/ 3 & Um
N.A N.A N.A N.A N.A % - Leakage rate of gas / year 6.13.
10 10 10 10 PC - Partial discharge (at Um) 6.14.

SCHEDULE [G 3]
Bushings

Transformer
Unit Nominal Voltage - kV
Neutral terminal
Line terminal Description
66 220 11 66 220

Date..// Contractor signature Rev. 0

Page 10 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

Operating conditions 7.
Um Um Um Um 0.8Um kV - Temporary over voltage 7.1.
O
58 58 58 58 58 C - Temperature rise 7.2.
N.A N.A N.A N.A N.A M Pa - Max. operating pressure 7.3.
O
<30 <30 <30 <30 <30 - Angle of mounting 7.4.
2248
4305 385 accepted 2310 8593 mm - Minimum creepage distance 7.5.
accepted

Design: 8.
72.5 accepted 126 12 accepted24 72.5 252 KV - Rated voltage 8.1
Envelope Envelope Envelope Envelope
with oil with oil Tight by seals with oil with oil - Insulating envelope type 8.2.
conservator conservator conservator conservator
180 190 30 180 600 Kg - Weight of bushing. 8.3.

Date..// Contractor signature Rev. 0

Page 11 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 4]
Power Transformers

175 MVA Rated Power - MVA


220/66/11 kV Unit
Description

IEC Standard Standard and relevant publication 1.


TBEA
Name of manufacturer 2.

Place of manufacturer : 3.

China - Country 3.1

Hengyang / Changzhou - City 3.2


175 MVA/220 kV, three phase, oil immersed, core type, air cooling,
ONTC, with stability winding transformer, SF SZ-175-175000/220 Type reference 4.

YNyn0d11 Vector group 5.


220/72.5/12 KV Rated voltage ratio at no-load, principal tapping 6.
175/175/63 MVA Rated power 7.

Date..// Contractor signature Rev. 0

Page 12 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

A Rated primary current 8.

417.5 - Extreme plus tapping 8.1

459.3 - Principal tapping 8.2

510.3 - Extreme minus tapping 8.3

SCHEDULE [G 4]

Power Transformers

175 MVA Rated Power - MVA


Unit
220/66/11 kV
Description

1393.6 A Rated secondary current at main tapping. 9.


28873031 A Rated tertiary current 10.
A/mm2 Current density at principal tapping 11.

Date..// Contractor signature Rev. 0

Page 13 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

- At rated load current : 11.1

2.5 * Primary 11.1.1

2.5 * Secondary 11.1.2

2.5 * Tertiary 11.1.3

- At short-circuit (J) : 11.2

23.1 * Primary 11.2.1

21.5 * Secondary 11.2.2


74.6 * Tertiary 11.2.3

Date..// Contractor signature Rev. 0

Page 14 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 4]
Power Transformers

175 MVA Rated Power - MVA


Unit
220/66/11 kV
Description

KV Rated primary voltage at no load : 12

242 - Extreme plus tapping 12.1

220 - Principal tapping 12.2

198 - Extreme minus tapping 12.3


1.6 Tesla Flux density at rated voltage and main tapping 13.
72.5 KV Rated secondary voltage at no-load 14.
Date..// Contractor signature Rev. 0

Page 15 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project


12 KV Rated tertiary voltage at no-load 15.
220/66/11 KV Rated voltage ratio at full load, PF 0.8 and principal tapping 16.
Voltage drop with load at full load between
% 17.
primary & secondary
1.1 confirmed - Unity 17.1

8.5confirmed - 0.8 PF 17.2


0.9 A No load primary current at main tapping 18

SCHEDULE [G 4]
Power Transformers

175 MVA Unit Rated Power - MVA


220/66/11 kV Description

MVA Rated output with : 19

105 MVA - Natural cooling 19.1


Date..// Contractor signature Rev. 0

Page 16 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

140 MVA - One group of cooling fans in operation 19.2

175 MVA - Two group of cooling fans in operation 19.3

Permissible duration of over load without exceeding


20.
the specified temp. rises, at extreme minus tapping:

hr -10% overload starting from : 20.1

24.33 * full load 20.1.1

4.84.67 * full load 20.1.2

6.95.17 * full load 20.1.3

8.95.83 * full load 20.1.4

Date..// Contractor signature Rev. 0

Page 17 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 4 ]
Power Transformers

175 MVA
Unit Rated Power - MVA
220/66/11 kV Description

min -25% overload starting from : 20.2

80200 * full load 20.2.1

115220 * full load 20.2.2

150250 * full load 20.2.3

190280 * full load 20.2.4

min -50% overload starting from : 20.3


Date..// Contractor signature Rev. 0

Page 18 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

5015 * full load 20.3.1

7019 * full load 20.3.2

11025 * full load 20.3.3

15032 * full load 20.3.4

SCHEDULE [G 4 ]
Power Transformers

175 MVA
Unit Rated Power - MVA
220/66/11 kV Description

min 75% overload starting from : 20.4

Date..// Contractor signature Rev. 0

Page 19 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

207 * full load 20.4.1

5010 * full load 20.4.2

6514 * full load 20.4.3

11017 * full load 20.4.4

min 100% overload starting from : 20.5

155 * full load 20.5.1

306 * full load 20.5.2

408 * full load 20.5.3

5510 * full load 20.5.4

Date..// Contractor signature Rev. 0

Page 20 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 4 ]
Power Transformers

175 MVA
Unit Rated Power - MVA
220/66/11 kV Description

Ohm Resistance per phase at 95oC: 21.

Approx. 0.35 - Primary winding. 21.1.

Approx.0.026 - Secondary winding. 21.2.

Approx.0.005 - Tertiary winding. 21.3.


Based on 175 MVA % Impedance voltage at rated current, main tapping and 95 oC 22.

Date..// Contractor signature Rev. 0

Page 21 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

based on 175 MVA:

14 - Primary to secondary. 22.1.

24 - Primary to tertiary. 22.2.

8 - Secondary to tertiary. 22.3.

% Zero sequence impedance per phase


12.3 23.
(primary / secondary)

Date..// Contractor signature Rev. 0

Page 22 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 4 ]
Power Transformers

175 MVA
Unit Rated Power - MVA
220/66/11 kV Description

kW Load losses at 95 OC, full load (ONAF) and principal 24.


tapping at unity PF.
480 - Primary to secondary to tertiary. 24.1.

480 - Primary to secondary. 24.2.

130, based on 63 MVA - Primary to tertiary. 24.3.

124, based on 63 MVA - Secondary to tertiary. 24.4.


90 kW No-load losses at rated voltage and main tapping. 25.
10.2 kW Fans power consumption. 26.
Date..// Contractor signature Rev. 0

Page 23 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

% Efficiency at : 27.

99.61%/99.52% - 125% full-load at 0.8/ unity PF. 27.1.

99.67%/99.59 - 100% full-load at 0.8/ unity PF. 27.2.

99.72%/99.65% - 75% full-load at 0.8/ unity PF. 27.3.

SCHEDULE [G 4]
Power Transformers

175 MVA
Unit Rated Power - MVA
220/66/11 kV Description

99.76%/99.70% - 50% full-load at 0.8/ unity PF. 27.4.

99.72%/99.65% - 25% full-load at 0.8/ unity PF. 27.5.

Cooling System: 28.


Date..// Contractor signature Rev. 0

Page 24 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

2 group - Number of cooling groups. 28.1.

6 set for each group - Number of fans per each group. 28.2.

900 Mm - Fan diameter. 28.3.

300000 lit/min - Rate of air discharge per fan. 28.4.

0.85 kW - Power consumption per fan. 28.5.

10.26 kW - Power consumption of cooling system. 28.6.

Date..// Contractor signature Rev. 0

Page 25 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 4 ]
Power Transformers

MVA 175 Unit Rated Power - MVA


220/66/11 kV Description

kV Lightning impulse withstand voltage: 29.

1050 - Primary windings. 29.1.

325 - Secondary windings. 29.2.

75 - Tertiary windings. 29.3.

550 - Primary neutral. 29.4.

325 accepted - Secondary neutral. 29.5.

kV Power frequency withstands voltage (test voltage): 30.

460 - Primary windings. 30.1.

Date..// Contractor signature Rev. 0

Page 26 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

140 - Secondary windings. 30.2.

28 - Tertiary windings. 30.3.

230 - Primary neutral. 30.4.

140 accepted - Secondary neutral. 30.5.

SCHEDULE [G 4]
Power Transformers

175 MVA Unit Rated Power - MVA


220/66/11 kV Description

kV/Hz Induced voltage and its frequency: 31.

460kv/100hz - Primary windings. 31.1.

140kv/100hz - Secondary windings. 31.2.


Date..// Contractor signature Rev. 0

Page 27 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

28kv/100hz - Tertiary windings. 31.3.

230kv/100hz - Primary neutral. 31.4.

140kv/100hz changed to 72 - Secondary neutral. 31.5.

Dielectric dissipation factor (tan ):for oil 32.


0.5 % - At 90 O C. 32.1.
0.1 % - At 20 OC. 32.2.

Date..// Contractor signature Rev. 0

Page 28 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 4]
Power Transformers

175 MVA Unit Rated Power - MVA


220/66/11 kV Description

O
C Temperature Rise: 33.

Date..// Contractor signature Rev. 0

Page 29 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project


- Max temperature rise over ambient temperature of
45 OC and continuous full-load with maximum current
(extreme minus tapping) in addition to 10% over-load 33.1.
with maximum current for two hours, starting from
full-load (losses at 95 OC).
O
50 C * Winding. 33.1.1.
O
65 C * Iron core. 33.1.2.
O
39 C * Oil (average). 33.1.3.
O
45 C * Oil at top. 33.1.4.
O
65 its too low for 60, we insist on 65 C * Hot spot. 33.1.5.

kA/sec Short circuit withstands current: 34.

3.28kA/2 second - Primary thermal current and duration. 34.1.

Date..// Contractor signature Rev. 0

Page 30 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 4]
Power Transformers

Rated Power - MVA 175 MVA


Unit
Description 220/66/11 kV

34.2. - Primary dynamic current and duration. 9.4KA/0.25 second

35. Noise level. dB 76(sound pressure level)

36. Construction:

36.1. - Core and Yoke:

36.1.1. * Name of manufacturer. TBEA / Wuhan Steel

36.1.2. * Place of manufacture. Hengyang, China / Wuhan, China

36.1.3. * Material. 0.27 mm, RGO silicon steel, laser treatment

36.1.4. * Kind insulation film. Inorganic insulate film / Varnish

36.1.5. * Nominal thickness of Lamination. Mm 0.27

Date..// Contractor signature Rev. 0

Page 31 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project


36.1.6. * Density. g/ cm3 0.8757.65

36.1.7. * Magnetic flux density. Tesla 1.6

36.1.8. * Specified iron loss at the magnetic flux density (1.7 T) W/ kg 0.98

36.1.9. * Space factor. 0.95

SCHEDULE [G 4]
Power Transformers

175 MVA
Unit Rated Power - MVA
220/66/11 kV Description

- Winding: 36.2.

China * Name of manufacturer. 36.2.1.

Hengyang, China * Place of manufacture. 36.2.2.

Date..// Contractor signature Rev. 0

Page 32 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

Oxygen free copper * Material of conductor. 36.2.3.

* Material of insulation: 36.2.4.

insulation paper # Primary winding. 36.2.4.1

insulation paper # Secondary winding. 36.2.4.2

insulation paper # Tertiary winding. 36.2.4.3

Kg * Weight of each winding. 36.2.5.

12500 # Primary winding. 36.2.5.1

9600 # Secondary winding. 36.2.5.2

2900 # Tertiary winding. 36.2.5.3

Date..// Contractor signature Rev. 0

Page 33 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 4]
Power Transformers

175 MVA
Unit Rated Power - MVA
220/66/11 kV Description

mm2 * Cross section of each winding. 36.2.6.

Approx.160 # Primary winding. 36.2.6.1

Approx.530 # Secondary winding. 36.2.6.2

Approx.700 # Tertiary winding. 36.2.6.3

- Number of turns per phase: 36.3.

Approx.554 * Primary. 36.3.1.

Approx.166 * Secondary. 36.3.2.

Approx.48 * Tertiary. 36.3.3.

Date..// Contractor signature Rev. 0

Page 34 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

- Oil: 36.4.

Nynas * Name of producer. 36.4.1

Sweden * Place of production. 36.4.2

Mineral Oil * Type. 36.4.3

SCHEDULE [G 4]
Power Transformers

175 MVA
Unit Rated Power - MVA
220/66/11 kV Description

kV/2.5
mm gap * Breaking strength. 36.4.4.
60kv/2.5mm gap after be filtered by vacuum oil filter

(55:60)10% # At factory testing. 36.4.4.1

Date..// Contractor signature Rev. 0

Page 35 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

70 after be filtered by vacuum oil filter # At site after purifying. 36.4.4.2

40 #Safe lowest operation 36.4.4.3


0.895 g/ cm3 # Density. 36.4.4.3

- Weights and dimensions: 36.5.


75000 Kg * Weight of core. 36.5.1.
27000 Kg * Weight of windings. 36.5.2.
50000 Kg * Weight of oil. 36.5.3.
142000 Kg * Weight of transformer ready for shipping. 36.5.4.
215000 Kg * Weight of transformer ready for operation. 36.5.5.
9.7*3.5*3.8 M Dimensions of transformer ready for shipping. 36.5.6.
10.5*7.8*7.6 M * Dimensions of transformer ready for operation. 36.5.7.

Date..// Contractor signature Rev. 0

Page 36 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 4]
Power Transformers

175 MVA Unit Rated Power - MVA


220/66/11 kV Description

hot rolled carbon steel - Material of tank. 36.6.

Mm - Thickness of tank: 36.7.

10 * Sides. 36.7.1.

16 * Cover. 36.7.2.

2016 * Bottom. 36.7.3.

Thermal Characteristics. 37

0.8 - Oil exponent (x). 37.1

7 - Winding exponent (y). 37.2.


Date..// Contractor signature Rev. 0

Page 37 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

5.3 - Loss ratio (R). 37.3.

1.3 - Hot-spot factor (H). 37.4.


2.5 H - Oil time constant (t). 37.5.
- Hot-spot temperature for unity (normal) thermal
98 o
C 37.6.
ageing.
20 o
C - Hot-spot to top-oil gradient. 37.7.

SCHEDULE [G 5]
On-Load Tap-Changer

Rated Power - MVA


Unit 175 MVA
Description

1. Standard and relevant publication. IEC 60214

2. Name of manufacturer. MR

3. Place of manufacture:

Date..// Contractor signature Rev. 0

Page 38 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project


3.1. - Country. Germany

3.2. - City. Regensburg

4. Type reference. VMIII-650Y/123C-10193W

5. Rated voltage of the tap-changer kVr.m.s. 123

6. Insulation level of the changer. KVpeak/ kVr.m.s. 550/230

7. Highest voltage for equipment.. kVr.m.s. 123

8. Rated current (For phase current). A 650

Date..// Contractor signature Rev. 0

Page 39 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 5]
On-Load Tap-Changer

Rated Power - MVA


Unit 175 MVA
Description

9. Short-circuit withstand current (test current). kA


9.1. - Thermal (2 sec.). 6.5

9.2. - Dynamic (specify the duration). 16.25

10. Winding connection. star type

11. Unit (single or three phases). three phases

12. Tapping range 220+8*1.25%

13. Tapping arrangement (linear, reversing or coarse/ fine). reversing

14. Number of service tapping positions 17

Date..// Contractor signature Rev. 0

Page 40 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

15. Position of tapping in winding (line end, middle or neutral point). neutral point

Highest tapping current of the winding to which the tap-changer is


16. A 510
to be connected (Phase current).

SCHEDULE [G 5]
On-Load Tap-Changer

Rated Power - MVA


Unit 175 MVA
Description

17. Phase voltage per step. kV 1.588, tap-changer work voltage per step

Power frequency voltage appearing between the opening and


18. kV
closing contacts of the change-over selector. 20

19. Insulation level (lightning impulse/ power frequency). KVpeak/ kVr.m.s 550/230

20. Highest voltage between:

Date..// Contractor signature Rev. 0

Page 41 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

20.1. - Extreme tapping. LI 350AC 82

20.2. - Course tapping winding section and fine tapping section. N.A

20.3. - The most onerously stressed tapping and earth. LI350AC140

20.4. - Tapping of adjacent phases. LI350AC82

20.5. - The diverter switch and earth. LI350AC82

20.6. - Phases of the diverter switch. LI350AC82

20.7. - Open diverter switch contacts. LI150AC30

Date..// Contractor signature Rev. 0

Page 42 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project

SCHEDULE [G 5]
On-Load Tap-Changer

Rated Power - MVA


Unit 175 MVA
Description

21. Maximum working pressure when oil-filled. MPa 0.03

22. Maximum pressure during oil tests on the apparatus. MPa 0.06

23. Maximum vacuum to be applied. MPa 0.000133

24. Over-load conditions (to be as relative transformer). MPa Yes

25. Contacts material. cooper-tungsten


O
26. Temperature rise of contacts. C 15

27. Motor drive:

27.1. - Rated voltage. V 400

27.2. - Rated current. A 1.9


Date..// Contractor signature Rev. 0

Page 43 of 44
Egyptian Electricity Transmission Company (EETC)

Guarantee table for Future Egypt Project


27.3. - Rated power. kW 0.75

27.4 No. of life time operation No. 500000

Date..// Contractor signature Rev. 0

Page 44 of 44