Professional Documents
Culture Documents
Energy and exergy analysis of a latent heat storage system with phase
change material for a solar collector
Ahmet Kocaa, Hakan F. Oztopb, Tansel Koyunc, Yasin Varola,
a
Department of Mechanical Education, Firat University, 23119 Elazig, Turkey
b
Department of Mechanical Engineering, Firat University, 23119 Elazig, Turkey
c
Department of Mechanical Engineering, Suleyman Demirel University, Isparta, Turkey
Received 25 December 2006; accepted 16 March 2007
Available online 8 May 2007
Abstract
Analysis of energy and exergy has been performed for a latent heat storage system with phase change material (PCM) for a at-plate
solar collector. CaCl2 6H2O was used as PCM in thermal energy storage (TES) system. The designed collector combines in single unit
solar energy collection and storage. PCMs are stored in a storage tank, which is located under the collector. A special heat transfer uid
was used to transfer heat from collector to PCM. Exergy analysis, which is based on the second law of thermodynamics, and energy
analysis, which is based on the rst law, were applied for evaluation of the system efciency for charging period. The analyses were
performed on 3 days in October. It was observed that the average net energy and exergy efciencies are 45% and 2.2%, respectively.
r 2007 Elsevier Ltd. All rights reserved.
0960-1481/$ - see front matter r 2007 Elsevier Ltd. All rights reserved.
doi:10.1016/j.renene.2007.03.012
ARTICLE IN PRESS
568 A. Koca et al. / Renewable Energy 33 (2008) 567574
Nomenclature T temperature
V volume
E x;H i exergy of inlet energy
E x;Q_ exergy losses during transfer to water of heat Greek letters
stored in collector
E x;H o exergy of outlet energy from the collector r density
E x;Q_ i exergy of solar energy Z efciency
Q_ heat transfer
Q_ latent heat Subscripts
E x;Q_ exergy loss of energy in collector
m mass of water in collector ave average
Q_ s stored energy env environment
Cp specic heat of PCM gen generation
H enthalpy i inlet
h latent heat of phase transition l liquid
Irr irreversibility loss
M mass of PCM o outlet
PCM phase change material s solid
S entropy sys system
t time t total
Water
Inlet
300
1000
1100
collector was well insulated by industrial Floormate foam tank was located under the collector as can be seen in
isolator. Its thickness is 40 mm with heat conductivity Fig. 2. The tank contains 30 kg of PCM. As given in the
0.028 W/mK. Copper pipe was used as heat exchanger with experimental setup, the collector surface is wider than that
outer diameter and thickness 10 and 1 mm, respectively. of PCM surface. Fig. 3 shows top and side view of the pipe
Measurement of PCM temperatures were measured via 11 installation with dimensions for collector. KNO3 (0.6 kg)
thermocouples (T-type copper-constantan), which are was added into CaCl2 6H2O to crystallize the PCM. The
located in 30 mm interval. Three thermocouples were also heat transfer uid (HTF) was allowed to ow inside the
used to measure the temperatures of heat transfer oil and serpentine pipe to discharge the heat by the PCMs. The
inlet and outlet uid temperatures in the copper pipe as Mobilterm 605 with thermal conductivity 0.145 W/mK was
shown in Fig. 3. used as HTF in this experimental work. Inlet water enters
CaCl2 6H2O was used as a PCM. Its thermophysical the pipe from city water network. The energy and energy
properties are listed in Table 1. A rectangular PCM-lled performance of the latent heat TES system for solar
ARTICLE IN PRESS
570 A. Koca et al. / Renewable Energy 33 (2008) 567574
collector was analysed during three different days in E x;H i mH i H env T env S i Senv , (8)
October 2000 in Elazig, Turkey.
E x;H o mH o H env T env So Senv . (9)
3. Energy and exergy analyses for the charging period of Irreversibility can be dened as
collector with PCM Irr T env S gen . (10)
Energy and exergy analyses were carried out to evaluate Entropy generation,
the system efciency of solar collector with PCM. Control Sgen DS sys DS env X0, (11)
volume of the system was specied. The schematic
conguration is depicted in Fig. 1 to show the control DS sys mSo Si , (12)
volumes and inlet and outlet parameters. Energy and
exergy calculations were performed based on this cong- X Q_
uration. DS env . (13)
T
The heat transfer rate was calculated during the charging
3.1. Energy analysis
period as follows:
Energy balance was considered in two parts according to dT
Q_ s MC p (14)
control volume in schematic conguration. In the control dt
volume I, and latent heat as
Q_ i Q_ s Q_ (1) DV s rs h
Q_ l . (15)
and from control volume II, Dt
Q_ s Q_ 0 mH o H i , (2) Entropy variation was calcuated using
X Q_
Q_ i Q_ Q_ 0 mH o H i . So Si Sgen , (16)
T
The following equation was used to calculate energy
efciency of the solar collector: dS X Q_ X X
Sgen;sys mo S o mi S i , (17)
Transferred heat to the water dt T
Zenergy;net . (3) where
Solar energy input
It can be formulated as X X X Q_
Sgen mi S i mo S o X0, (18)
Q_ Q_ 0 T
Zenergy;net s . (4)
Q_ i Q_ i Q_ Q_ Q_ 0
Sgen mS o S i s . (19)
T env T ave T ave T ave
Finally, net exergy efciency is calculated from its
3.2. Exergy analysis denition by
Exergy uses the conservation of mass and energy Exergy recovered from unit
Zexergy;net (20)
principles together with the second law of thermodynamics Exergy input
ARTICLE IN PRESS
A. Koca et al. / Renewable Energy 33 (2008) 567574 571
and formulated as follows as In this study, results obtained from analyses of energy and
E x;H o E x;H i exergy belong to charging period of the system.
Zexergy;net . (21) Variations of stored energy and measured solar radiation
E x;Q_ i
for different times during the days are presented in
Fig. 4(a)(c). Fig. 4(a) shows the results for October 7.
4. Results and discussion Variations of solar radiation become almost constant
during morning and it increases until noon. It has a
Energy and energy analyses were performed for a solar decreasing value at the midd-noon. However, stored energy
collector with TES unit using CaCl2 6H2O as a PCM. As shows similar variation except at morning due to smaller
is well known from the literature, the exergy efciency of temperature difference and solar radiation. For October
the LHS systems is a new method to evaluate the system 12, the bell-shaped variations were obtained for stored
efciency. Analysis of exergy takes into account the loss of energy. Solar radiation also showed a similar variation
availability of heat in TES systems. Thus, it reects the with stored energy until noon. It has again a decreasing
thermodynamic, energy and economic value of the system. value at the mid-noon as obtained with previous gure.
a
500 1000
400 800
Instantaneous Solar
Stored Energy (kJ)
Radiation (W/m2)
300 600
200 400
Qs
100 200
R
0 0
8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00
Time of day
b
500 1000
450 900
400 800
Stored Energy (kJ)
Instantaneous Solar
Radiation (W/m2)
350 700
300 600
250 500
200 400
150 300
100 Qs
200
50 R 100
0 0
8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00
Time of day
c
500 1000
400 800
Stored Energy (kJ)
Instantaneous Solar
Radiation (W/m2)
300 600
200 400
100 Qs 200
R
0 0
8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00
Timeof day (hour)
Fig. 4. Variations of storage heat with radiation on different dates: (a) 7 October 2000, (b) 12 October 2000 and (c) October 15, 2000.
ARTICLE IN PRESS
572 A. Koca et al. / Renewable Energy 33 (2008) 567574
Variation of stored energy and solar radiations of October values were obtained on 12 October. It is observed that the
7 and October 15 are similar except near noon. At this average exergy efciency was only 2.2% during charging
time, contrary of other days, storage energy is higher than period. Thdsd results show that this value of the average
that of solar radiation. exergy efciencies is not enough in terms of exergy
The net energy and exergy efciencies for charging efciency. When values are compared with the net energy
period are shown in Fig. 5 for 3 days in October 2000. The efciency, the net exergy efciency of the system was lower
changes of the rates of heat and thermal energy for an LHS than that of the net energy efciency for all days. It is
unit through the charging periods are presented in Fig. 5(a) expected that the net energy efciency will be higher than
as a function of time. The net energy efciency is increased the exergy efciency. Because the quality of the net energy
with the increases in inlet temperature of the heat transfer transferred is taken into account to calculate the net energy
uid. The net energy efciency changed between 38% and efciency, the quality of energy transferred is neglected.
59%. The higher net energy efciencies are observed a Fig. 6(a) and (b) shows the effect of the temperature
October 12 except for morning hours. Also, results are very difference of the heat transfer uid at the inlet and the
close during noon. As can be seen from the gure, daily outlet of solar collector with PCM on net energy efciency
average values of net energy efciencies were calculated as (Fig. 6(a)) and net exergy efciency (Fig. 6(b)) for three
45% for October 12 and 42% for October 7 and 15. different days. Both the net energy and exergy efciencies
Fig. 5(b) shows the variation of net exergy efciency with increase with increase in temperature difference in solar
time for 3 days in October 2000. The values show little collector, which makes the temperature difference an
increase with time. The net exergy efciency changed effective parameter. The variation of temperature differ-
between 1.5% and 3.3%. The maximum exergy efciency ence is also related to time. It increased with time during
a
100
October 7,2000
80 October 12,2000
Net Energy Efficiency (%)
October 15,2000
60
40
20
0
08:00 09:00 10:00 11:00 12:00 13:00 14:00
Time of day (hour)
b
10
October 7,2000
8 October 12,2000
Net Exergy Efficiency (%) .
October 15,2000
0
08:00 09:00 10:00 11:00 12:00 13:00 14:00
Time of day (hour)
Fig. 5. Variations of efciency with time of day on for different dates: (a) energy efciency and (b) exergy efciency.
ARTICLE IN PRESS
A. Koca et al. / Renewable Energy 33 (2008) 567574 573
a
80
70
50
40
October 7, 2000
30
October 12, 2000
20 October 15, 2000
10
10 20 30 40
Temperature Difference (K)
b
October 7, 2000
6 October 12, 2000
Net Exergy Efficiency (%) .
0
10 20 30 40
Temperature Difference (K)
Fig. 6. Variations of efciency with temperature difference on for different dates: (a) energy efciency and (b) exergy efciency.
day time. Values were decreased for the value of (2) There is a signicant difference between the results of
temperature difference at 28 K due to decreasing solar energy and exergy. The net energy efciency is higher
radiation as given in Fig. 4(a)(c). This value of tempera- than that of exergy efciency. The obtained experi-
ture difference was obtained near noon. Both energy and mental data and calculations clearly show that exergy
exergy efciencies show zigzag variations for higher efciencies of latent heat storage systems with PCM are
temperature differences. The highest temperature differ- very low.
ence in LHS units of collector obtained was 37 K. (3) Area of collector surface is smaller than that of PCM
surface area. As a result of this, low outlet temperature
5. Conclusions was obtained but it increased the cost of the latent heat
storage system.
Energy and exergy analyses for a solar collector with
PCM were performed during charging period. From the
experimental study and calculations the following conclu- Acknowledgment
sion can be drawn.
The authors thank to Dr. Mehmet Esen for his valuable
(1) Both stored solar energy and instantaneous solar contribution is building the experimental set-up and is
radiation show bell-shaped variation during all days. measuring parameters.
ARTICLE IN PRESS
574 A. Koca et al. / Renewable Energy 33 (2008) 567574