Professional Documents
Culture Documents
2
2.1 Electrical connection single-phase pumps Actual mains connection is shown in fig. 3.
Note: The user or the installer is responsible for the installation of Fig. 3
the correct earthing and protection according to valid national and MGE 71 and MGE 80
local standards. All operations must be carried out by a qualified
electrician.
Never make any connections in the pump terminal
box unless the electricity supply has been switched I
off for at least 5 minutes.
N N
ELCB Max. 10 A PE
L L
PE
3
2.2 Electrical connection three-phase pumps 2.2.6 Supply voltage
Note: The user or the installer is responsible for the installation of 3 x 460-480 V 10%, 60 Hz, PE.
the correct earthing and protection according to valid national and The supply voltage and frequency are marked on the pump
local standards. All operations must be carried out by a qualified nameplate. Please make sure that the motor is suitable for the
electrician. electricity supply on which it will be used.
Never make any connections in the pump terminal The wires in the pump terminal box must be as short as possible.
box unless the electricity supply has been switched Excepted from this is the protective earth conductor which must
off for at least 5 minutes. be so long that it is the last one to be disconnected in case the
cable is inadvertently pulled out of the cable entry.
2.2.1 Mains switch
Figure 4 shows an example of a mains-connected pump with
The pump must be connected to an external all-pole mains switch mains switch, back-up fuses and additional protection.
with a contact separation of at least 3 mm in each pole according Fig. 4
to IEC 364.
MGE 90 to MGE 132
2.2.2 Protection against electric shock indirect contact
Max. 16/32 A
The pump must be earthed and protected against L1 L1
indirect contact in accordance with national regula-
ELCB
Note: When an earth leakage circuit breaker is selected, the total 2.2.7 Start/stop of pump
leakage current of all the electrical equipment in the installation The number of starts and stops via the mains voltage must not
must be taken into account. exceed 4 times per hour.
The leakage current of the pump can be found in section When the pump is switched on via the mains, it will start after ap-
13.2 Leakage current. prox. 5 seconds.
2.2.4 Motor protection If a higher number of starts and stops is desired, the input for ex-
ternal start/stop must be used when starting/stopping the pump.
The pump requires no external motor protection. The motor incor-
When the pump is started/stopped via an external on/off switch, it
porates thermal protection against slow overloading and blocking
will start immediately.
(IEC 34-11: TP 211).
2.2.5 Overvoltage protection
The pump is overvoltage-protected through built-in varistors be-
tween the phases and between phases and earth.
4
2.3 Other connections Fig. 8
The connection terminals of external potential-free contacts for MGE 90 and MGE 100
start/stop and digital function, external setpoint signal, sensor sig-
nal, GENIbus and relay signal are shown in figs. 7, 8 and 9.
Note: If no external on/off switch is connected, short-circuit termi- 8: +24 V
0/4-20 mA
nals 2 and 3 using a short wire. 0-5/10 V 4-20 mA 7: Sensor input
Note: As a precaution, the wires to be connected to the following 6: GND (frame)
connection groups must be separated from each other by rein- 10 k 5: +5 V
Group 1
0/4-20 mA 0-5/10 V
forced insulation in their entire lengths: 4: Setpoint input
3: GND (frame)
1. Inputs (external start/stop, digital function, setpoint and sen- 2: Start/stop
sor signals, terminals 1-9, and bus connection, A, Y, B). 1: Digital input
All inputs (group 1) are internally separated from the mains- A: RS-485A
conducting parts by reinforced insulation and galvanically Y: Screen
B: RS-485B
separated from other circuits.
All control terminals are supplied by protective extra-low volt-
age (PELV), thus ensuring protection against electric shock.
2. Output (relay signal, terminals NC, NO, C). C NO NC
Group 2 Group 3
The output (group 2) is galvanically separated from other cir- Signal relay
cuits. Therefore, the supply voltage or protective extra-low
voltage can be connected to the output as desired. L1
3. Supply voltage (terminals L and N or L1, L2, L3). L2 Mains
connection
Group 3
NC C NO N PE L
0/4-20 mA 8: +24 V
0-5/10 V 4-20 mA 7: Sensor input
6: GND (frame)
10 k 5: +5 V
Group 1
0/4-20 mA 0-5/10 V 4: Setpoint input
3: GND (frame)
2: Start/stop
1: Digital input
A: RS-485A
Y: Screen
0-10 V 1: Digital input
0/4-20 mA 4-20 mA 9: GND (frame) B: RS-485B
8: +24 V
Group 1
0/1
7: Sensor input
B: RS-485B
1 9 8 7 B Y A Y: Screen
Group 2
A: RS-485A NC
NO Signal relay
STOP C
RUN
6: GND (frame)
0/4-20 mA 0-10 V 5: +10 V L1
TM02 0795 4702
3: GND (frame) L2
Mains
2: Start/stop connection
6 5 4 3 2
L3
TM00 7666 1002
5
2.4 Signal cables Fig. 13
Use screened cables having a cross-sectional area of min. H
0.5 mm and max. 1.5 mm for external on/off switch, digital in-
put, setpoint and sensor signals.
Max.
The screens of the cables must be connected to frame at both
ends with good frame connection. They must be as close as
The max. curve can for instance be used in connection with the
venting procedure during installation.
The min. curve can be used in periods in which a minimum flow is
required.
The light fields on the control panel will indicate the setpoint set.
See the following examples, figs. 15 and 16.
Example: Pump in controlled-operation mode (pressure control):
Q Q
Figure 15 shows that the light fields 5 and 6 are activated, indicat-
ing a desired setpoint of 3 bar with a sensor measuring range
The pumps have been factory-set to uncontrolled operation, see from 0 to 6 bar. The setting range is equal to the sensor measur-
section 3.1 Factory setting. ing range (see sensor nameplate).
In addition to normal operation (controlled or uncontrolled opera- Fig. 15
tion), the following operating modes can be selected, Stop, Min.
[bar]
or Max., fig. 13. 6
TM00 7743 1896
6
Example: Pump in uncontrolled-operation mode: 5. Setting by means of R100
In uncontrolled-operation mode, the pump performance is set The pump is designed for wireless communication with the
within the range from min. to max. curve, fig. 16. GRUNDFOS remote control R100.
Fig. 16 The R100 communicates with the pump via infra-red light. The
transmitter and the receiver are incorporated in the pump control
H
panel, fig. 19.
Fig. 19
H
TM00 7345 1196
Q
Max. curve
H
TM00 7346 1196
Q
Min. curve
7
The displays are divided into four parallel menus, fig. 20:
0. GENERAL (see operating instructions for the R100)
1. OPERATION
2. STATUS
3. INSTALLATION
The number stated at each individual display in fig. 20 refers to
the section in which the display is described.
Fig. 20
5.2.4 5.3.4
5.1.4
5.2.5 5.3.5
5.2.6 5.3.6
5.3.7
5.3.8
5.3.9
5.3.10
8
5.1 Menu OPERATION Setpoint signal outside signal range (only 4-20 mA)
When communication between the R100 and the pump has been External fault
established, the first display in this menu will appear. Dry running
5.1.1 Setpoint setting Other fault
A fault indication can be reset in this display if the cause of the
fault has disappeared.
5.1.4 Alarm log
Setpoint set
Actual setpoint
Actual value
In this display, the setpoint is set. If faults have been indicated, the last five fault indications will ap-
pear in the alarm log. Alarm log 1 shows the newest/latest fault.
In controlled-operation mode, the setting range is equal to the
sensor measuring range. The example shows the fault indication Undervoltage, the fault
code and the number of minutes the pump has been connected to
In uncontrolled-operation mode, the setpoint is set in % of the
the electricity supply after the fault occurred.
maximum performance. The setting range will lie between the
min. and max. curves. The time cannot be displayed for three-phase pumps as the soft-
ware does not support this function.
Select one of the following operating modes:
Stop, 5.2 Menu STATUS
Min. (min. curve), The displays appearing in this menu are status displays only. It is
Max. (max. curve). not possible to change or set values.
If the pump is connected to an external setpoint signal, the set- The displayed values are the values that applied when the last
point in this display will be the maximum value of the external set- communication between the pump and the R100 took place. If a
point signal, see section 7. External setpoint signal. status value is to be updated, point the R100 at the control panel
If the pump is controlled via external signals (Stop, Min. curve or and press OK.
Max. curve) or a bus, this will be indicated in the display if set- If a parameter, e.g. speed, should be called up continuously,
point setting is attempted. press OK constantly during the period in which the parameter in
question should be monitored.
In this case, the number of possible settings will be reduced, see
section 9. Priority of settings. The tolerance of the displayed value is stated under each display.
The tolerances are stated as a guide in % of the maximum values
5.1.2 Setting of operating mode of the parameters.
5.2.1 Display of actual setpoint
This display shows the actual operating mode (Stop, Min., Normal
(duty) or Max.). Furthermore, it shows where this operating mode
If the pump is faulty, the cause will appear in this display. was selected (R100, Pump, BUS, External or Stop func.). For fur-
ther details about the stop function (Stop func.), see section
Possible causes:
5.3.8 Setting of stop function.
Too high motor temperature
5.2.3 Display of actual value
Undervoltage
Overvoltage
Phase failure (three-phase pumps only)
Mains supply failure (three-phase pumps only)
Too many restarts (after faults)
Overload
Sensor signal outside signal range (only 4-20 mA)
9
The actually measured value of a connected sensor will appear in In this display, the gain (Kp) and the integral-action time (Ti) of the
this display. built-in PI controller can be set if the factory setting is not the op-
If no sensor is connected to the pump, will appear in the dis- timum setting:
play. The gain (Kp) is set within the range from 0.1 to 20.
5.2.4 Display of actual speed The integral-action time (T i) is set within the range from 0.1 to
3600 s. If 3600 s is selected, the controller will function as a
P controller.
Furthermore, it is possible to set the controller to inverse control
(if the setpoint is increased, the speed will be reduced). In the
case of inverse control, the gain (Kp) must be set within the range
from 0.1 to 20.
Setting the PI controller:
For most applications, the factory setting of the controller con-
Tolerance: 5%
stants Kp and Ti will ensure optimum pump operation. In the fol-
The actual pump speed will appear in this display. lowing cases, a change of the setting can be useful or necessary.
5.2.5 Display of input power and power consumption A change of the Ti setting can be useful:
In a differential-pressure control system if the sensor is placed
far away from the pump.
A change of the Ti setting, and in some cases the Kp setting, may
be necessary:
If the pump is controlled on the basis of temperature or differ-
ential temperature.
The table below shows the recommended controller settings:
Tolerance: 10%
This display shows the actual pump input power from the mains Kp
supply. The power is displayed in W or kW. System/
Heating Cooling Ti
application
The pump power consumption can also be read from this display. 1) 2)
The value of power consumption is an accumulated value calcu- system system
lated from the pumps birth and it cannot be reset.
5.2.6 Display of operating hours
0.5 0.5
Dp
L [m]
L < 5 m: 0.5
0.5 L > 5 m: 3
Dp L > 10 m: 5
Tolerance: 2%
The value of operating hours is an accumulated value and cannot
be reset.
0.5 0.5
5.3 Menu INSTALLATION
5.3.1 Selection of control mode p
Q 0.5 0.5
0.5 0.5 10 + 5L
t
Select one of the following control modes (see fig. 12): L [m]
Controlled,
Uncontrolled.
The desired performance is set in section 5.1.1 Setpoint setting.
Dt 0.5 10 + 5L
Note: If the pump is connected to a bus (see section 8. Bus sig-
nal), it is not possible to select the control mode via the R100.
L [m]
5.3.2 Setting of controller
L [m]
t 0.5 0.5 30 + 5L
10
5.3.3 Selection of external setpoint signal The digital input of the pump (terminal 1, fig. 7, 8 or 9) can be set
to different functions.
Select one of the following functions:
Min. (min. curve),
Max. (max. curve),
Ext. fault (external fault),
Flow switch.
The selected function is activated by closing the contact between
The input for external setpoint signal can be set to different signal
the following terminals:
types.
1 and 9 of single-phase pumps (fig. 7) and
Select one of the following types:
1 and 3 of three-phase pumps (fig. 8 or 9).
0-5 V (potentiometer) (three-phase pumps only),
See also section 6.2 Digital input.
0-10 V,
Min.:
0-20 mA,
When the input is activated, the pump is operating according to
4-20 mA, the min. curve.
Not active. Max.:
If Not active is selected, the setpoint set by means of the R100 or When the input is activated, the pump is operating according to
on the control panel will apply. the max. curve.
The setpoint set is the maximum value of the external setpoint Ext. fault:
signal, section 7. External setpoint signal. The actual value of the When the input is activated, a timer is started. If the input is acti-
external setpoint can be read from section 5.2.1 Display of actual vated for more than 5 seconds, the pump is stopped and a fault is
setpoint. indicated. If the connection is disconnected for more than 5 sec-
onds, the fault condition will cease and the pump can be restarted
5.3.4 Selection of fault, operating or ready signal relay
manually by resetting the fault indication.
The typical application will be detection of missing inlet pressure
or water shortage by means of a pressure switch installed on the
suction side of a pump.
Flow switch:
When this function is active, the pump will be stopped when a
connected flow switch detects a low flow.
It is only possible to use this function if the pump is connected to
It can be selected in which situation the relay should be activated: a pressure sensor.
Fault (fault indication), When the input is activated for more than 5 seconds, the stop
function incorporated in the pump will take over, see section
Operation (operating indication),
5.3.8 Setting of stop function.
Ready (ready indication).
5.3.8 Setting of stop function
See section 10. Indicator lights and signal relay.
5.3.5 Blocking of the buttons on the pump
When the stop function is active, the pump will be stopped at very
low flows to avoid unnecessary power consumption.
The buttons + and on the pump can be set to: It is only possible to use this function if the pump is connected to
Active, a pressure sensor.
Not active. The stop function can be set to:
Active,
5.3.6 Allocation of pump number
Not active.
There are two possibilities of low-flow detection:
1. By means of the built-in low-flow detector which automati-
cally starts functioning if no flow switch is chosen/connected to
the digital input. The pump will check the flow regularly by re-
ducing the speed for a short time, thus checking the change in
pressure. If there is no or a small change in pressure, the
pump will detect a low flow.
A number between 1 and 64 can be allocated to the pump. In the
case of bus communication, a number must be allocated to each 2. By means of a flow switch connected to the digital input. When
pump. the input is activated for more than 5 seconds, the stop func-
tion of the pump takes over. Unlike the built-in low-flow detec-
5.3.7 Selection of function for digital input
tor, the flow switch measures the minimum flow at which the
pump must stop. The pump will not check the flow regularly by
reducing the speed.
When the pump detects a low flow, the speed will be increased
until the stop pressure (actual setpoint + 0.5 x H) is reached and
the pump stops. When the pressure has fallen to the start pres-
sure (actual setpoint 0.5 x H), the pump will restart.
11
H indicates the difference between start and stop pressures, fig. 5.3.10 Setting of min. and max. curves
21.
Fig. 21
H
O
pe
Note: The non-return valve must be fitted immediately before the
ra
pump, fig. 22. If the non-return valve is fitted between pump and
g
diaphragm tank, the pressure sensor must be fitted after the non-
ra
12%
ng
return valve.
e
Fig. 22
Q
Diaphragm tank
The max. curve can be adjusted within the range from maxi-
mum performance (100%) to min. curve.
Correctly installed The min. curve can be adjusted within the range from max.
TM00 7745 1896
non-return valve curve to 12% of maximum performance. The pump has been
factory-set to 24% of maximum performance.
The operating range lies between the min. and max. curves.
Pump
The stop function requires a diaphragm tank of a certain minimum 6. External forced-control signals
size. The tank must be installed immediately after the pump and The pump has inputs for external signals for the forced-control
the precharge pressure must be 0.7 x actual setpoint. functions:
Recommended diaphragm tank size when no flow switch is con- Start/stop of pump.
nected. Digital function.
Nominal flow of pump Diaphragm tank size 6.1 Start/stop input
[gpm] [gallons]
Functional diagram: Start/stop input:
0-30 4.4
31-95 8.0 Start/stop (terminals 2 and 3)
96-140 34.0 H
141-340 86.0 Normal duty
If a diaphragm tank of the above size is installed in the system, Q
the factory setting of H is the correct setting.
If the tank installed is too small, the pump will start and stop too H
often. This can be remedied by increasing H. Stop
5.3.9 Setting of sensor Q
12
Functional diagram: Input for digital function: In uncontrolled-operation mode, the setpoint can be set exter-
nally within the range from the min. curve to the setpoint set on
Digital function the pump or by means of the R100, fig. 25.
(terminals 1 and 9 single-phase pumps) Fig. 25
(terminals 1 and 3 three-phase pumps)
%
H
Normal duty
Max. curve
Q
Setpoint set on pump or with the R100
H
Min. curve
Q
H Min. curve
1 Stop
3 Stop
0 5 V (three-phase pumps only)
0 10 V 4 Max. curve
0 20 mA
4 20 mA 5 Min. curve Min. curve
Example: At a lower pressure-sensor value of 0 bar, a setpoint 6 Setpoint setting Setpoint setting
set of 5 bar and an external setpoint of 80%, the actual setpoint
will be as follows: Example: If, via the digital input, the pump has been forced to op-
Hactual = (Hset - Hlower) x %external setpoint + Hlower erate according to the max. curve, the pump control panel and
the R100 can only set the pump to stop.
= (5 - 0) x 80% + 0
= 4 bar
13
With bus signal
10. Indicator lights and signal relay
The operating condition of the pump is indicated by the green and
Possible settings red indicator lights on the pump control panel, fig. 26.
Control Fig. 26
Priority panel on External
Bus signal
pump or signals
R100
2 Max. curve
3 Stop Stop
Green Red
4 Max. curve The pump incorporates an output for a potential-free signal via an
internal relay.
5 Min. curve
The signal output can be set to fault, operating or ready indication
Setpoint by means of the R100, see section 5.3.4 Selection of fault, oper-
6
setting ating or ready signal relay.
Example: If, via the digital input, the pump has been forced to op- The functions of the two indicator lights and the signal relay are
erate according to the max. curve, the pump control panel, the as shown in the following table:
R100 and the bus signal can only set the pump to stop.
A fault indication can be reset in one of the following ways: 11. Megging
By briefly pressing the button + or on the pump. This will Note: Megging of an installation incorporating E-pumps is not al-
not change the setting of the pump. lowed, as the built-in electronics may be damaged.
A fault indication cannot be reset by means of + or if the
buttons have been locked.
By switching off the electricity supply until the indicator lights
are off.
By means of the R100, see section 5.1.3 Fault indications.
When the R100 communicates with the pump, the red indicator
light will flash rapidly.
14
12. Technical data single-phase pumps 13. Technical data three-phase pumps
12.1 Supply voltage 13.1 Supply voltage
1 x 200-240 V 10%, 50/60 Hz, PE. 3 x 460 - 480V 10%, 60 Hz, PE.
See nameplate. See nameplate.
Back-up fuse Back-up fuse
Motor sizes from 0.5 hp to 1.5 hp: Max. 10 A. Motor sizes from 1.0 to 7.5 hp: Max. 16 A.
Standard as well as quick-blow or slow-blow fuses may be used. Motor size 10 hp : Max. 32 A.
Standard as well as quick-blow or slow-blow fuses may be used.
12.2 Leakage current
Earth leakage current < 3.5 mA. 13.2 Leakage current
The leakage currents are measured in accordance with Motor size Leakage current
EN 60 355-1. [hp] [mA]
1.0 to 4.0 < 3.5
12.3 Inputs/output
5.0 to 7.5 hp <5
Start/stop
7.5 hp, 1400-1800 min-1 < 10
External potential-free switch.
Voltage: 5 VDC. 10 < 10
Current: < 5 mA.
Screened cable.* The leakage currents are measured in accordance with
EN 60 355-1.
Digital
External potential-free switch. 13.3 Inputs/output
Voltage: 5 VDC.
Start/stop
Current: < 5 mA.
External potential-free switch.
Screened cable.*
Voltage: 5 VDC.
Setpoint signals Current: < 5 mA.
Potentiometer Screened cable.*
0-10 VDC, 50 k (via internal voltage supply). Digital
Screened cable. * External potential-free switch.
Maximum cable length: 100 m. Voltage: 5 VDC.
Voltage signal Current: < 5 mA.
0-10 VDC, R i >50 k Screened cable.*
Tolerance: +0%/3% at maximum voltage signal. Setpoint signals
Screened cable. *
Potentiometer
Maximum cable length: 500 m.
0-5 VDC, 10 k (via internal voltage supply).
Current signal Screened cable.*
DC 0-20 mA/4-20 mA, Ri = 175 Maximum cable length: 100 m.
Tolerance: +0%/3% at maximum current signal.
Voltage signal
Screened cable. *
0-5 VDC/0-10 VDC, R i >50 k
Maximum cable length: 500 m.
Tolerance: +0%/3% at maximum voltage signal.
Sensor signals Screened cable.*
Voltage signal Maximum cable length: 500 m.
0-10 VDC, R i >50 k (via internal voltage supply). Current signal
Tolerance: +0%/3% at maximum voltage signal. DC 0-20 mA/4-20 mA, Ri = 250
Screened cable. * Tolerance: +0%/3% at maximum current signal.
Maximum cable length: 500 m. Screened cable.*
Current signal Maximum cable length: 500 m.
DC 0-20 mA/4-20 mA, Ri = 175 . Sensor signals
Tolerance: +0%/3% at maximum current signal.
Voltage signal
Screened cable. *
Maximum cable length: 500 m. 0-5 VDC/0-10 VDC, R i >50 k (via internal voltage supply).
Tolerance: +0%/3% at maximum voltage signal.
Electricity supply to sensor: Screened cable.*
+24 VDC, max. 40 mA. Maximum cable length: 500 m.
Signal output Current signal
Potential-free changeover contact. DC 0-20 mA/4-20 mA, Ri = 250.
Maximum contact load: 250 VAC, 2 A. Tolerance: +0%/3% at maximum current signal.
Minimum contact load: 5 VDC, 1 mA. Screened cable.*
Screened cable: 0.5 - 2.5 mm. Maximum cable length: 500 m.
Maximum cable length: 500 m.
Electricity supply to sensor:
Bus input +24 VDC, max. 40 mA.
GRUNDFOS bus protocol, GENIbus protocol, RS-485.
Signal output
0.5 - 1.5 mm screened 2-core cable.
Potential-free changeover contact.
Maximum cable length: 500 m.
Maximum contact load: 250 VAC, 2 A.
* Cross section min. 0.5 mm and max. 1.5 mm. Minimum contact load: 5 VDC, 1 mA.
Screened cable: 0.5 - 2.5 mm.
Maximum cable length: 500 m.
Bus input
GRUNDFOS bus protocol, GENIbus protocol, RS-485.
0.5 - 1.5 mm screened 2-core cable.
Maximum cable length: 500 m.
* Cross section min. 0.5 mm and max. 1.5 mm.
15
13.4 Other technical data Sound pressure level
EMC (electromagnetic compatibility) Single-phase pumps:
EN 61 800-3. <70 dB(A).
Motors of 0.5 to 7.5 hp, except for 7.5 hp, 1400-1800 min-1: Three-phase pumps:
Residential areas - unlimited distribution,
corresponding to CISPR 11, class B, group 1. Motor Speed stated Sound pressure
Motors of 10 hp and 7.5 hp, 1400-1800 min-1: on nameplate level
Residential areas - limited distribution. [hp] [min-1] [dB(A)]
Industrial areas - unlimited distribution,
2800-3000 63
corresponding to CISPR 11, class A, group 1. 1.0
When pumps fitted with motors of 10 hp and 7.5 hp, 3400-3600 68
1400-1800 min-1, are installed in residential areas, an additional 2800-3000 63
EMC filter is required to obtain class B, group 1 status. 1.5
3400-3600 68
The motor fulfils EN 50 178.
2800-3000 63
Contact GRUNDFOS for further information. 2
3400-3600 68
Enclosure class
2800-3000 64
Standard: IP 55 (IEC 34-5). 3
Insulation class 3400-3600 68
F (IEC 85). 2800-3000 64
4
Ambient temperature 3400-3600 68
During operation: 4F to +104F (20C to +40C) 2800-3000 68
During storage/transport: 40F to +140F (40C to +60C)
5 3400-3600 73
Relative air humidity
Maximum 95%. 4200-4500 75
2800-3000 68
7.5 3400-3600 73
4200-4500 75
2800-3000 74
10 3400-3600 79
4200-4500 80
14. Disposal
Disposal of this product or parts of it must be carried out accord-
ing to the following guidelines:
1. Use the local public or private waste collection service.
2. In case such waste collection service does not exist or cannot
handle the materials used in the product, please deliver the
product or any hazardous materials from it to your nearest
GRUNDFOS company or service workshop.
Subject to alterations.
16
LIMITED WARRANTY
Products manufactured by GRUNDFOS PUMPS CORPORATION (GRUNDFOS) are warranted to
the original user only to be free of defects in material and workmanship for a period of 24
months from date of installation, but not more than 30 months from date of manufacture.
GRUNDFOS' liability under this warranty shall be limited to repairing or replacing at
GRUNDFOS' option, without charge, F.O.B. GRUNDFOS' factory or authorized service station,
any product of GRUNDFOS' manufacture. GRUNDFOS will not be liable for any costs of
removal, installation, transportation, or any other charges which may arise in connection with
a warranty claim. Products which are sold but not manufactured by GRUNDFOS are subject to
the warranty provided by the manufacturer of said products and not by GRUNDFOS' warranty.
GRUNDFOS will not be liable for damage or wear to products caused by abnormal operating
conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not
installed in accordance with GRUNDFOS' printed installation and operating instructions.
To obtain service under this warranty, the defective product must be returned to the
distributor or dealer of GRUNDFOS' products from which it was purchased together with proof
of purchase and installation date, failure date, and supporting installation data. Unless
otherwise provided, the distributor or dealer will contact GRUNDFOS or an authorized service
station for instructions. Any defective product to be returned to GRUNDFOS or a service station
must be sent freight prepaid; documentation supporting the warranty claim and/or a Return
Material Authorization must be included if so instructed.
GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES,
OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO
EXPRESS OR IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED
TO ABOVE.
L-MLE-TL-02 8/04
PRINTED IN USA
Subject to alterations
North American
GrundfosRegional
Pumps Corporation
Headquarters Grundfos
Grundfos Canada,
Canada,
Inc.
Inc. Bombas Grundfos de Mexico, S.A. de C.V.
Grundfos17100
Pumps
W. 118th
Corporation
Terrace 2941
2941
Brighton
Brighton
Road
Road Boulevard TLC #15
17100 W.Olathe,
118th KS
Terrace
66061 Oakville,
Oakville,
Ontario
Ontario
L6H
L6H
6C9
6C9,Canada
Canada Parque Stiva Aeropuerto
Olathe, Telephone
KS 66061 913 227 3400 Telephone:
Telephone:905
(905)
829829-9533
9533 Apodaca, N.L. 66600
Mexico Mexico
Telephone
Fax:(913)
913 227
227-3400
3500 Fax:
Fax:
905
(905)
829829-9512
9512 C.P. 66600 52 81 8144 4000
Telephone:
Fax: (913) 227-3500 Telephone:
Fax: 52 81 8144
52-81-8144-4000
4010
www.grundfos.com Fax: 52-81-8144-4010
www.grundfos.com