Design and Sizing of Water Supply Systems Using


Loading Units Time for a Change?

S. Ingle (1), D.C. King (2), R. Southerton (3)


1. steven.ingle@btconnect.com
2. d.c.king@ljmu.ac.uk
3. ralph.southerton@phonecoop.coop
(1), (3) Ingle Project Design (2) Liverpool John Moores University

Abstract
To design and size hot and cold water supply systems engineers must be able to
accurately assess the demand for water at sanitary appliances. To do so in large public
buildings, which may have fluctuating or unpredictable occupancies, can be complex,
since the frequency and intensity of use of appliances must be predicted.
Since the 1940s, methods used by engineers the world over have been based largely
upon variations and refinements of the loading units methodology, an approach
originally advanced by Hunter in USA as long ago as 1940. Loading units are
calculated using probability theory based upon time intervals between uses of
appliances, the length of time the appliance draws water, and the average flow rate
when in use, and the approach incorporates an acceptable failure rate when design
conditions are likely to be exceeded for short periods. A great many refinements have
been carried out piecemeal over the decades, meaning that design guidance throughout
the world, despite using the same fundamental approach, may yield very different
results. Mathematical and computational models have also been developed, some of
which are applied to the loading unit approach, while others are used independently,
though again the adoption of these across international borders is inconsistent.
This paper reviews some of the most commonly used methodologies in light of a
perception that many water supply systems are routinely and substantially over-sized.
Engineers will, in general, continue to use tried and tested methodologies, despite
recognising that they are tending to over-engineer as the prospect of system failure is
commercially and professionally unthinkable. Routine over-sizing, however, shows
disregard to the principle of sustainable development and can potentially compromise
public health.

1
CIBW062 Symposium 2014

The paper concludes that although mathematical and computational methods have been
developed and are routinely used all over the world, much more accurate and robust
models are needed for future sustainable development in buildings.

Keywords
Water supplies, pipe sizing, probability, loading units, mathematical models

1 Introduction

The basic requirement for users of cold and hot water supply systems is simple it is
that water of appropriate quality and temperature must be supplied at acceptable flow
rates and pressures whenever required. Engineers designing and sizing such systems
must satisfy this requirement without compromising public health, whilst paying due
regard to sustainability and energy efficiency.
In order to design hot and cold water supply systems and determine the sizes of
pipework and storage vessels, engineers must be able to accurately assess the demand
for water at sanitary fittings, and pipe sizes are then derived from knowledge of water
flow rates. To predict water demand and flow rates in large public buildings, which
may have fluctuating or unpredictable occupancies, can be enormously complicated
since an accurate knowledge of factors such as the frequency and intensity of use of the
appliances is required.
A solution to the conundrum of predicting required flow rates came with the
development of the loading unit methodology advanced by Hunter in 1940 in the United
States, this being based upon probability theory, which had already been used to
determine the capacity of telephone exchanges. Hunter suggested a scale of numerical
constants, termed fixture units, which engineers could use to assess water flow rates
and hence determine pipe and storage vessel sizes. These units were calculated based
upon the assumed interval between uses of a sanitary appliance, the length of time that
appliance would be likely to draw water, and the average flow rate when in use (Hunter,
1940). In Sweden around 1945, Rydberg proposed a similar idea of predicting probable
flow water rates in buildings, though his mathematical method was somewhat different
to Hunters (Konen & Goncalves, 1993). Since the 1940s, methods used by engineers
the world over have been based for the most part upon refinements to Hunters and/or
Rydbergs work, though the more modern label, loading units is used in preference to
fixture units. A great many modern design guides and codes of practice employ loading
unit methodology, see for example CIPHE (2002) and CIBSE (2014).
The mechanistic approach of the loading unit method lends itself to computer
simulation, and therefore software programmes exist (often designed by manufacturers)
which enable engineers to size systems with a fair degree of confidence. There is a
general perception, however, that the most commonly used methodologies lead to
systems being routinely and substantially over-sized.

2
CIBW062 Symposium 2014

In general, engineers will continue to use tried and tested methodologies and are often
unwilling to vary from the established design guidance unless they have considerable
experience and confidence in their judgement. Designers may well recognise that they
are tending to over-engineer, but the prospect of system failure is commercially and
professionally unthinkable. Routine over-sizing is of course is wasteful of materials, it
shows disregard to the principle of sustainable development, and it can potentially
compromise public health if water sits stationary for long periods in over-large pipes
or storage vessels for instance (Angus, Ingle, King, & Turner, 2010).
Many designers would consider a range of issues when carrying out design work and
these are presented in the mind map example shown below.

Figure 1 Example of design engineers mind map

3
CIBW062 Symposium 2014

2 A review of current practices

As stated previously, the basis for modern sizing methodologies owes much to work
carried out by Hunter (1940), who theorised that since the fixtures in a water system are
used intermittently, then the loading effect of a sanitary fitting must be dependent
upon three factors:
The time interval between uses of the fixture,
The length of time the fixture draws water,
The average flow rate of water for that fixture.
Using probability theory, Hunter developed a scale of fixture units based upon observed
usage data for sanitary fittings in use at the time in buildings in the USA. Hunter had
access to data from a number of hotels and apartment buildings, and made assumptions
based upon the time residents received morning calls and were observed to leave and
enter the buildings. From these data he was able to estimate the use of sanitary fittings
over a 24 hour period and identified the phenomenon of peak and off-peak periods.
Hunter based his development of fixture units upon probability theory, which had
already been used to determine the capacity of telephone exchanges in the USA. The
model applied to telephone exchanges allowed for a 1% failure rate, and Hunter applied
the same logic. In a telephone exchange this failure rate meant that it was expected that
for 1% of the time, the capacity of the exchange would be exceeded and any further
callers would not get a connection until another caller terminated their call. This would
appear to be a fairly minimal failure rate, probably unnoticeable for most exchange
users. When applied to water systems the result of a 1% failure rate would usually be
some reduction of pressure and flow rate for 1% of the time, and depending upon the
type of building, this may well be unnoticeable for the majority of users.
Howick (1964) adapted Hunters method to UK practice and his work became the basis
for British Standard Code of Practice 310 (BSI, 1965), a much respected and
internationally recognised design guide, upon which many of todays design guides are
based.
The Hunter method has been reviewed several times since the 1940s, and Konen (1974)
studied the effect of varying the three factors used by Hunter to construct the probability
model. Konen concluded that:
The most important parameter is the time interval between uses of a sanitary
fitting,
The length of time the fitting draws water is of intermediate importance,
The flow rate of water to the fitting is of least importance.
Konen and Gonalves (1993), in their work on mathematical models for water system
sizing, included an international survey to identify normal design procedures in a
number of countries. They made comparisons between the approaches to the design for
various types of building, including dwellings (apartments) and offices and were able to
classify three main design approaches:
Methods based on Hunters model (loading units), used across much of the
world, in particular USA, UK, Japan and India. Typically CIBSE or ASHRAE

4
CIBW062 Symposium 2014

design guidance is applied, though there are several local variants. Konen and
Gonalves (1993) identified a wide disparity between the methods used in these
countries, predicted flow rates for similar buildings differing sometimes by
factors of more than two to one.
Methods based on Rydbergs model, this being an approach developed in
Sweden which predicts flow rates using probability theory, though in a different
way to Hunter. Not surprisingly, this approach is favoured in the Scandinavian
countries.
The other main design approach is typically found in European countries such as
France and Germany, though Konen and Gonalves (1993) also report its use in
Brazil. This method is perhaps the simplest to use: the design flow rate (or
flow units) of all the appliances on a system are summated and this figure is
then multiplied by an empirically derived simultaneous demand factor. This
method almost always produces the highest design flow rates.
In addition to the different approaches listed above, each method would be refined by
reference to empirical data concerning building type and occupancy. Pinho & Abrantes
(1999) note that some countries, Russia for example, provide a more detailed selection
of buildings upon which design data may be based. However, across much of the world,
notably in Germany, UK and USA, the predominant design methods allow designers a
fairly narrow choice of building type and occupancy pattern, and there is less
opportunity for engineers to refine the design methodology they are employing.

2.1 Mathematical models


Several researchers have investigated the use of mathematical models to obtain more
precise predictions for design flow rates.
An early mathematical model was constructed by Webster (1972), who used Newtons
Binomial Theorem alongside experimental work to construct his model. Webster used a
failure rate of 0.1% that is, lower than Hunters by a factor of 10 but still predicted
flow rates lower that those predicted by the loading units approach in BS 310. The
reason for this, it is argued, is that Websters method takes a less mechanistic view and
takes due account of the unpredictable nature of human behaviour. Since Websters
method was developed in an age where computers were not readily available, and it
required a large number of complex calculations, it was not adopted, and BS 310
remained the definitive design guide for some years.
Murakawa (1985) critically analysed the Hunter approach using queuing theory as the
theoretical basis for his study. Queuing theory is a technique that enables mathematical
models to be constructed to predict queue lengths and waiting times in various scientific
and engineering applications. Murakawa monitored the use of sanitary appliances in
two apartment blocks, comparing predictions made by his mathematical model and the
Hunter loading units approach with real observed data. His results showed that the
Hunter methodology predicted significantly higher design flow rates than observed data,
whereas the queuing theory method was much more consistent with the real data.
Ilha, De Oliveria, & Goncalves (2008) continued the work by Webster and others by
looking at water demand in apartments. They compared the water demand forecast by
the Brazilian Standard with that forecast by a probabilistic method which took account

5
CIBW062 Symposium 2014

of the number of occupants in each apartment alongside the sanitary provision, and
concluded that such probabilistic model enables designers to adjust necessary
parameters in order to better reproduce the actual building systems flow rate according
to different conditions.
In furtherance of this work, Oliveira, Cheng, Gonalves, and Massolino (2010)
constructed a water usage simulation model on apartment buildings in Brazil, which
included the techniques of fuzzy logic and the Monte Carlo method to enable
unpredictable human factors to be more properly considered. Their simulations yielded
results which predicted flow rates around 30% lower than the established Brazilian
design method, and they conclude that their model could well contribute to more
accurate sizing of water supply pipework and water meters.
These works are important and it remains to be seen whether design specifications will
embrace such methods.

2.2 Failure of a system to meet design specification


Failure in a water supply system could be caused by any number of circumstances, the
most common being:
Failure of the infrastructure of the water supplier,
Failure of the electrical supply feeding booster pumps or failure of pumps
themselves,
Failure of the distribution system to deliver the required flow to every point in
the system.
For the first two items there is normally flow design data available. Precautions can be
taken to avoid loss of supply, for example by providing a standby electrical supply for
the pumps. Alternatively the pipework system may be designed to limit the number of
points affected by any failure.
Failure of the distribution system to provide the required flow rate is not so easy to
define, however, because this depends often upon occupiers perception of what might
constitute a reasonable or acceptable flow rate, and what might be considered a system
failure.
Hunter (1940) and Howick (1964) used a failure rate of 1%, a figure which was
commonly acknowledged as practical and acceptable, and this figure is used in the
British Standard Code of Practice 310 (BSI, 1965) design guide. This failure rate
actually equates to a system not being able to deliver the design flow rate for a period of
36 seconds in a one hour period. It is, however, useful to consider what actually
happens during periods of failure.
In the case of an apartment block served directly from the mains, under design
conditions a suitable pressure and flow rate would be available at the highest floors,
thus ensuring that all sanitary appliances may be used normally. During periods where
design conditions are exceeded there would be a reduced pressure and flow rate at the
upper floors. Users may not, for example, be able to shower satisfactorily and may
have to wait for WC cisterns to fill, but would still enjoy a water supply, even though
pressure and flow rate are reduced. At what stage does this reduction of flow rate
become problematic such that it is considered a system failure?

6
CIBW062 Symposium 2014

In an extreme case of failure the demand in the building would outstrip the capacity of
the distribution system (or supply connection), and upper floors would be left with no
water supply at all. It is likely, however, that users on the lower floors would
experience much less disruption to supply in conditions of high demand.
Chakrabarti & Sharma (1980) proposed a low cost solution, based upon research carried
out in apartment buildings in India. Essentially it was suggested that low pressure
fittings could be installed on upper floors and high pressure fittings could be installed
on the remaining floors, and together with flow restrictors, this would allow the system
to maintain balance during varying usage patterns, and would limit the effect of failure
periods. These techniques are often used nowadays to mitigate against periods of
reduced flow.

2.3 Pipe sizing


As has been stated, the sizing of any distribution system must be based upon the
required flow rates which have been predicted, taking account of available water
pressures and appropriate design velocities. In terms of capital cost the greatest
economy is achieved by minimising pipe sizes, though this produces a knock-on effect
of increasing flow velocities, potentially causing noise or even pipework erosion.
In recent times, life cycle costing is more likely to be considered. The operating and
running costs of any system are evaluated and added to the capital cost, to provide a life
cycle cost. Small pipe sizes would certainly minimize capital costs but, in pumped
systems, the associated greater pressure drops would increase pump power and energy
consumption over the life cycle.
As has been previously stated there is a consensus view that routine oversizing is the
norm, due to the very low acceptable failure rates applied to the loading units
methodology, although system failure often means nothing more than reduced flow
rates and pressures at peak times, and this may not even be noticeable. Angus, Ingle,
King and Turner (2010) further suggest that current sizing methods, which tend towards
over-sizing, can lead to problems of water stagnation and dirt being deposited at low
velocities during off-peak periods and this can encourage the growth of bacteria,
allowing biofilms to form, and in extreme cases even promote algae growth. There are
therefore some very convincing arguments for varying the design failure rate to allow
higher velocities depending upon the type of building, though it must be accepted that in
cases where all fittings are likely to be used simultaneously a very low failure must be
maintained.
It is also well recognised that smaller pipe sizes in the case of domestic hot water supply
systems can show a significant energy saving due to reduced heat losses from the
system as well as lower materials costs (Werden & Spielvogol, 1968), though this effect
is less pronounced on newer systems with good pipework insulation (Angus, Ingle,
King, & Turner, 2010).

7
CIBW062 Symposium 2014

3 Factors influencing demand

Many observers have set about defining and measuring the human biological need for
water for domestic purposes such as toilets, washing, cooking, drinking, bathing and
cleaning, for example see Mendes & Lucas (1978). People living and working in
buildings are, however, notoriously unpredictable, and it is well-recognised that there is
no simple way of precisely predicting occupant behaviour and ascertaining the resultant
demands for water.
For unmetered supplies, the water industry in the UK suggests an average water
consumption of 140 litres per person per day inclusive of leakage, though there is some
conjecture about this figure (King & Brady, 2014). The level of leakage in urban areas
can vary greatly and is dependent upon any number of factors, ranging from age and
maintenance of pipework and infrastructure, to topography and geography, so is
difficult to quantify accurately in most cases. The UK figure may be considered as mid-
range: other countries (notably USA) expect water use per person to be far higher, while
others, such as Germany, use a reference figure somewhat lower.
The age, health and economic status of building occupiers (and of those in the
surrounding area) are known also to have a significant effect on water demand. Socio-
economic influences and demographics of any particular development and its type,
compared to the surrounding area, strongly influence the usage pattern and the mean
peak flow demands of buildings.
The level of occupancy for a new building is often not known by the client or architects
at the design stage, so some form of estimate is often used. In the UK this is often
assessed by reference to fire regulations or to the Health & Safety Executives guidance
for acceptable maximum workplace occupancy densities. This technique frequently
leads to overestimation of building occupancy and consequent over-engineering of all
building engineering services (not just water supply systems).
If the building under consideration has public or recreational areas, these will have a
higher peak demand due to seasonal variations and weather changes when compared to
buildings with a constant year-round occupancy like factories, offices and similar.
Likewise, hotels and restaurants tend to experience unique occupancy profiles leading to
peak and off-peak water demands at different times to other buildings. In addition
facilities such as spas, swimming pools have their own individual requirements and
usage profiles as does agriculture.

3.1 Factors that influence consumption


Water metering is becoming more common, and proponents would contend that it raises
awareness of the finite nature of water supplies and so reduces unnecessary
consumption. Local metering affects system design, while charging policy can
encourage users to be more aware of unnecessary water consumption. Interestingly
though, it is not a proven fact that water metering as an independent measure actually
reduces consumption: In Germany all water use is metered and consumption per person
is around 30% less than in the UK, while in the United States water usage is also

8
CIBW062 Symposium 2014

metered, but consumption per person is almost double the UK figure (International
Bank for Reconstruction and Development, 2010).
A question that may arise as metering becomes more prevalent is whether metering has
different effects based upon socio-economic groups. Undoubtedly some people will
find metered water to be very cheap, while those with low incomes may well find the
reverse to be true.
An obvious contributor to the demand for water is the plumbing fixture itself. In the
drive to prevent water wastage, the trend in recent years has been for all sanitary
appliances to be designed and manufactured smaller and thus to consume less water.
Since Hunters day the habits of human beings have changed considerably. The most
obvious change is that people generally prefer to shower rather than bathe nowadays.
With reduced water demand from other fittings and appliances, the dominant demand in
dwellings is very often the demand from showers. It is, however, difficult to assess how
much water is used in a typical shower since habits vary so widely. Users are known
to prefer showers with high pressure jets which use large volumes of water and these
can be quite wasteful if users take long showers. One of the modern technological
developments for showers includes an air induction system which mixes air with the
water flow, thus providing what feels to the user like a high flow rate, while in reality
using low volumes of water.
While a shower unquestionably uses less water than a bath, people are tending to
shower more and more frequently, particularly in the industrialised nations. Habits as to
the length of time spent showering vary widely across the world according to many
complex economic, sociological and societal factors. In regions of the world where
water is scarce, however, local authorities may try to educate users to limit the length of
time spent showering. For example, Australians are given recommendations as to the
length of time they should shower, and are encouraged to use a timer while showering.
The use of filled washbasins for body washing has likewise declined; basins are often
used just for hand and face washing and for teeth brushing, though the practice of
leaving a tap running while brushing teeth is difficult to discourage.
There are many commonly promoted conservation practices and new technologies
designed to save water, though current design practices do not always take account of
(or permit) these. Some of these are listed:
It is known that a good general maintenance regime for sanitary equipment
throughout its working life can substantially reduce water consumption,
Low water usage taps such as spray taps, infra-red and non-concussive taps are
commonly used in public washrooms,
In several countries there are constantly updated recommendations to reduce
flow rates to taps and showers and to reduce the size of WC flushes,
Dual flush valves are now routinely fitted to WC cisterns across much of the
world,
Flow limiters are often fitted in public buildings to avoid excessive water draw-
off,
Water shut off in unoccupied parts of buildings is encouraged by BREEAM and
other environmental assessment methods, though such measure could potentially
compromise public health by allowing water to stagnate in pipework.

9
CIBW062 Symposium 2014

Automated leak detection systems are routinely made available,


Use of infra-red sensors to effect automatic urinal flushing,
The inclusion of grey water recycling and rainwater harvesting systems to
supply non potable water, thus supplementing the water supply system,
Short, well insulated dead-legs on domestic hot water systems to prevent users
running water to drain while waiting for hot water,
Older style domestic laundry and dishwashing machines used typically 112 litres
per normal cycle, whereas the more modern models of these appliances use far
less water, and also less electricity.
Some very human problems are in evidence as people adapt to new technologies and
practices, however. Typically, many people do not understand how to use dual flush
valves on WCs properly. Familiarity will inevitably overcome these issues, though it
may well be that the ergonomics of these devices could be improved.
Whilst the general trend in industrialised countries is for people to be encouraged to
consume less water, it must also be recognised that some wealthier households tend to
feature items like hot tubs, power showers, lawn sprinklers and garden irrigation
systems.

4 Conclusions - the way forward?

Although many countries across the world use versions of the loading unit methodology,
there are, as has been reviewed, wide discrepancies in its application. International
harmonisation may be part of the answer here, though there is a considerable distance to
travel to realise this aim. The loading units methodology is now unquestionably
outdated and over-simplistic in its approach, and engineers working within its
restrictions do not have sufficient flexibility to refine results that are obtained.
As the construction industry moves into a period where routine use of Building
Information Modelling (BIM) is to become common practice in all aspects of building
design, the time must now be right for the introduction of a more accurate and robust
water supply design and sizing methodology. Information gained from BIM monitoring,
where live data are collected from real buildings, could be systematically catalogued
and analysed to give accurate data across a full range of buildings (though there will
inevitably be some caveats surrounding the veracity of such data). These data may well
enable the first steps towards a harmonised loading units model to be built.
The recent innovative work carried out in Brazil (Oliveira, Cheng, Gonalves, &
Massolino, 2010) which yields computer simulations of water usage by applying fuzzy
logic to take account of human factors, could well be a premise upon which a more
robust methodology is based.
A newer design method must be far more flexible and allow engineers to consider more
factors than is currently possible without being over mechanistic and prescriptive. As
well as the obvious technical data, to realise a new model further research is needed in
the following areas:

10
CIBW062 Symposium 2014

A consideration of acceptable failure rates and an appreciation of what problems


a system failure might actually cause,
The prospect of using higher water velocities to enable smaller pipe diameters
balanced against the risks of system noise and possible erosion,
The condition of supply infrastructure and leakage data (gathered via BIM
monitoring processes).
Caution must be exercised when collecting live data from real buildings since
data gathered from one particular building type may not always be applied
accurately to other building types. Such data should be utilised in conjunction
with data obtained from simulations.
Establishment of users needs these can be further defined as peoples actual
biological needs for water (Mendes & Lucas, 1978) for washing, drinking and so
on, as compared to what might be termed psychological or aspirational needs,
the insistence of many people to shower several times per day for instance.
Hunters work was consistent with the state of engineering and technology available in
the 1940s, and his work has served us well. But in the 21st Century, as we aspire
towards sustainable development with a rapidly growing world population, we have far
more technological tools at our disposal than Hunter could have dreamed of. A more
modern sizing methodology is possible and necessary, and researchers today must
ensure that this aim is realised.

4 References

Angus, P., Ingle, S., King, D., & Turner, J. (2010). The effects of using water velocity
as a technique to control biofilm development in water supply systems. CIB
W062 36th International Symposium. Sydney: CIB.

BSI. (1965). British Standard Code of Practice CP 310 : 1965.Water Supply. British
Standard, London.

Chakrabarti, S. P., & Sharma, S. K. (1980). Peak hydraulic load on intermittent water
supply systems in multi-storey residential buildings. Rourkee, India: Central
Building Research Institute.

CIBSE. (2014). CIBSE Guide G: Public Health and Plumbing Engineering. London:
CIBSE.

CIPHE. (2002). Plumbing Engineering Services Design Guide. Hornchurch: CIPHE.

Howick, H. A. (1964). The pipe sizing of hot and cold water installations. Plumbing
Trade Journal.

Hunter, R. B. (1940). Methods of estimating loads in plumbing systems. Washington DC:


United States Department of Commerce.

11
CIBW062 Symposium 2014

Ilha, M. S., De Oliveria, L. H., & Goncalves, O. M. (2008). Design flow rate simulation
of cold water supply in residential buildings by means of open probabilistic
model. CIB W062. Rotterdam: CIB.

International Bank for Reconstruction and Development. (2010). Sustaining water for
all in a changing climate. Washington: The World Bank.

King, D., & Brady, L. (2014). Part 4: Sustainable building services. In R. M, & C. A,
Construction Technology 2: Industrial & Commercial Buildings. London:
Palgrave.

Konen, T. P. (1974). A review of the Hunter model. CIB W62 Symposium 1974. CIB
W62.

Konen, T. P., & Goncalves, O. M. (1993). Summary of Mathematical Models for the
design of water distribution systems within Buildings. CIB W62.

Mendes, M., & Lucas, C. (1978). A bacteriological survey of washrooms and toilets.
Journal of Health and Hygiene.

Murakawa, S. (1985). Study on the method for calculating water consumption and water
uses in Multi-Storey Flats. CIB W062 symposium. Tokyo: CIB.

Oliveira, L. H., Cheng, L. Y., Gonalves, O. M., & Massolino, P. M. (2010). Simulation
model of design flow rate in water submetering systems using fuzzy logic and
Monte Carlo method. CIB W062 36th International Symposium (pp. 14-29).
Sydney: CIB.

Pinho, P. J., & Abrantes, V. (1999). Pipe sizing and pressure analysis of water
distribution systems, overview and comparison of different criteria . CIB W062.

Webster, C. J. (1972). An investigation of the use of water outlets in multi-storey flats.


IHVE Journal, 215 233.

Werden, R. G., & Spielvogol, L. G. (1968). Sizing of service water heating equipment
in commercial and institutional buildings. New York: Edison Electric Institute.

12
CIBW062 Symposium 2014

5 Presentation of Authors

Derek King is a Principal Lecturer in the School of the Built


Environment at Liverpool John Moores University, being
programme leader for degree programmes in Building Services
Engineering. Among his research interests are the practicalities
of applying sustainability to public health engineering systems,
and international aspects of building services engineering
education. Derek is currently Chair of his local branch of the
CIBSE

Dr Steven Ingle is an independent consultant engineer presently


working for Ingle Project Design Consulting Engineers, UK.
Steven is involved in the design of all types of Building Services
Engineering on commercial and industrial projects in the UK and
internationally. He is also an active member of the Society of
Public Health Engineers and has several research interests.

Ralph Southerton is a consultant building services engineer


currently employed by Ingle Project Design Consulting
Engineers. He has several research interests in the field of public
health engineering.