COOLING DONE BY UNIT IN BTU/hr

Psych chart values

State DB F RH % WB F DP F W v h
2 80 60 69.63 64.88 92.5 13.88 33.68
3 57 90 55.27 54.09 62.5 13.21 23.38

Qt 4.5 CFM h2 h3 4.5 20, 000 33.68 23.38 927, 000 BTU hr

BTU 1 tons
Qt 927, 000 77.25 tons
hr 12, 000 BTU hr

B. WATER REMOVED FROM AIR

mw

CFM W2 W3 20, 000 92.5 62.5 386 lb
1,556 1,556 hr

C. SENSIBLE LOAD

BTU 1 tons
QS 4.5CFM hx h2 4.5 20, 000 29 23.38 505,800 42.15 tons
hr 12, 000 BTU hr

D. LATENT LOAD

BTU 1 tons
QL 4.5CFM h3 hx 4.5 20, 000 33.68 29 421, 200 35.1 tons
hr 12, 000 BTU hr

E. DEW POINT

From chart note the dew point value of leaving air as 54.16 F

F. EFFECTIVE SURFACE TEMPERATURE

From Chart EST = 49.5 F

DB2 DB3 80 57
CF 0.7540
DB2 EST 80 49.5
a. Contact factor =