ESTUDIO DE COORDINACION DE PROTECCION

MEJORAMIENTO Y AMPLIACION DEL SERVICIO DE


ENERGIA MEDIANTE EL SISTEMA DE REDES
CONVENCIONALES DE LAS 36 LOCALIDADES DE
LOS DISTRITOS DE SANTA ROSA, AYNA Y
SAMUGARI DE LA PROVINCIA LA MAR -
AYACUCHO

SEP SAN FRANCISCO 69/22.9 KV - 5 MVA

MAYO del 2017


ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

INDICE

1. INTRODUCCION ................................................................................................ 3
1.1. Objetivos ............................................................................................................................................ 3
1.2. Alcances ............................................................................................................................................ 3
1.3. Antecedentes .................................................................................................................................... 4
2. CONFIGURACION Y PARAMETROS ELECTRICOS DEL SISTEMA ................ 4
2.1. Parmetros Elctricos del Sistema ................................................................................................ 5
2.1.1. Parmetros del transformador de distribucin......................................................................... 6
3. ANALISIS DE LA DEMANDA Y LA OFERTA ...................................................... 7
4. ANALISIS DE FLUJO DE CARGA Y CORTOCIRCUITO .................................... 8
4.1. Clculo de Flujo de Carga .............................................................................................................. 8
SE San Francisco AMT A4028 y A4030 ................................................................................................ 9
4.2. Clculo de Corrientes de Cortocircuito ....................................................................................... 12
SE San Francisco AMT A4028 y A4030 .............................................................................................. 12
5. AJUSTE DE LAS PROTECCIONES ................................................................. 14
5.1. Seleccin de fusible para el transformador ................................................................................ 16
5.2. Seleccin de Fusibles SEDs y Ramales ..................................................................................... 25
5.3. Proteccin de Sobrecorriente de Secuencia Negativa ............................................................. 30
6. CONCLUSIONES Y RECOMENDACIONES .................................................... 32
8. ANEXOS

Anexo 1: Base de Datos


Anexo 2: Diagramas Unifilares
Anexo 3: Anlisis de Flujo de Carga
Anexo 4: Anlisis de Corto Circuito

Pgina 2
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

MEJORAMIENTO Y AMPLIACION DEL SERVICIO DE ENERGIA MEDIANTE EL SISTEMA DE


REDES CONVENCIONALES DE LAS 36 LOCALIDADES DE LOS DISTRITOS DE SANTA ROSA,
AYNA Y SAMUGARI DE LA PROVINCIA LA MAR AYACUCHO

1. INTRODUCCION

1.1. Objetivos

El presente informe desarrolla el Anlisis de Flujo de Carga, Clculo de


Cortocircuito y Coordinacin de Proteccin para el proyecto MEJORAMIENTO
Y AMPLIACION DEL SERVICIO DE ENERGIA MEDIANTE EL SISTEMA DE
REDES CONVENCIONALES DE LAS 36 LOCALIDADES DE LOS
DISTRITOS DE SANTA ROSA, AYNA Y SAMUGARI DE LA PROVINCIA LA
MAR - AYACUCHO, al Sistema de distribucin en 22,9 kV perteneciente a los
alimentadores A4028 y A4030 de la SEP SAN FRANCISCO.

1.2. Alcances

El estudio est basado en las redes existentes del sistema elctrico San
Francisco, ste sistema comprende operacin bajo configuracin radial y
rgimen de neutro slidamente puesto a tierra en 22,9 kV.

Las corrientes base para la referencia del Cortocircuito se tomaron en la barra


de 69 kV de la SE San Francisco que a continuacin se muestra,
correspondiendo a lo publicado por el COES para el escenario de Avenida
Mxima Demanda 2017.

Subestacin/Barra kA_3ph MVA_3ph


San Francisco/69 kV 0.369 44.183

Los alcances del presente Estudio son los siguientes:

Introduccin: En esta seccin se da el objetivo, alcances y antecedentes


del Proyecto.
Configuracin y Parmetros Elctricos del Sistema: En donde se plantea
la configuracin del sistema y se define los parmetros elctricos de las
nuevas instalaciones.
Anlisis de la Demanda y Oferta del Sistema Elctrico: En donde se
realiza el anlisis de la demanda y oferta en el sistema elctrico.
Anlisis de Flujo de carga: Se simula la situacin actual y la configuracin
proyectada, para los periodos de avenida y las condiciones de mxima
demanda.
Clculo de Cortocircuito: En esta parte se realiza el clculo de cortocircuito
para la configuracin con y sin proyecto 2017.
Ajuste de las Protecciones: En esta seccin se realiza el clculo del fusible
de proteccin para los distintos transformadores que involucran el proyecto.
Anexos: Contiene los reportes de los diversos temas indicados lneas arriba.

Pgina 3
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

1.3. Antecedentes

La Municipalidad Provincial de La Mar, en coordinacin con la DGER del


Ministerio de Energa y Minas, tiene el propsito de ejecutar proyectos de
electrificacin en las reas de Distribucin. La fuente de financiamiento ser a
travs de la Direccin General de Electrificacin Rural (DGER) del Ministerio de
Energa y Minas.

El Proyecto MEJORAMIENTO Y AMPLIACION DEL SERVICIO DE ENERGIA


MEDIANTE EL SISTEMA DE REDES CONVENCIONALES DE LAS 36
LOCALIDADES DE LOS DISTRITOS DE SANTA ROSA, AYNA Y SAMUGARI
DE LA PROVINCIA LA MAR - AYACUCHO, inscrito con Cdigo SNIP 287446,
fue Declarado Viable por la OPI de la Municipalidad Provincial de La Mar,
Regional de Ayacucho, luego de aprobarse el Estudio de Pre Inversin a nivel
de Perfil; se autoriza la elaboracin del Expediente Tcnico Definitivo.

2. CONFIGURACION Y PARAMETROS ELECTRICOS DEL SISTEMA

A continuacin se muestra el diagrama unifilar resumido del sistema elctrico


San Francisco donde se muestran los equipos Existentes.

Figura. Diagrama Unifilar Reducido.

Pgina 4
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Sistema Elctrico San Francisco

La Subestacin San Francisco es alimentada por la lnea de transmisin L-6079


en 69 kV, sta es llevada a 22,9 kV por medio de un transformador de potencia
de tres devanados de 5 MVA, con grupo de conexin YN0yn0d5.

La barra de 22,9 kV cubre la demanda de energa elctrica de los alimentadores


A4027, A4028, A4029 y A4030. Los alimentadores que estn involucrados en el
proyecto son A4028 y A4030.

2.1. Parmetros Elctricos del Sistema

Los parmetros utilizados para el anlisis de flujo de potencia y clculo de


cortocircuito se han obtenido del archivo PFD del Software Digsilent publicado
por el COES correspondiente a los aos 2016-2022 y de la informacin
proporcionada por la empresa Electrocentro S.A., los parmetros de las
nuevas instalaciones se determinan a continuacin:

Name Num. Phases X1 X2 X3 Y1 Y2 Y3


T23kV_1ph 1 -1.2 0 0 10 0 0
T23kV_2ph 2 0 0.8 0 10.5 10 0
T23kV_3ph 3 -1.2 0 1.2 10.5 10 10
Tabla. Armados de lnea en 22,9 kV.

Nominal Nominal DC-Resistance GMR (Equivalent Internal


Name Voltage Current (20C) Radius) Inductance
kV kA Ohm/km mm mH/km
Al016mm 33 0.10 2.090 1.8513 0.06404104
Al025mm 33 0.125 1.310 2.3595 0.06404106
Al021.1mm 33 0.114 1.580 2.1400 0.06352074
Al035mm 33 0.160 0.952 2.7588 0.06404104
Al050mm 33 0.195 0.663 3.3033 0.06404106
Al070mm 33 0.235 0.484 4.0900 0.05557080
Al0120mm 33 0.340 0.275 5.4000 0.05614268
Cu035mm 27 0.229 0.524 2.7225 0.06404104
Cu050mm 27 0.277 0.395 3.3731 0.05541437
Tabla. Parmetros de conductores en 22,9 kV.

Pgina 5
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

2.1.1. Parmetros del transformador de distribucin

Los transformadores a implementar en el proyecto tienen las siguientes


caractersticas.

Relacin de transformacin y Potencia Regulacin de Tensin Impedancias %


Prim. Sec. Grupo S(MVA) Var. Tap Tmax. Tmin. 22,9/0,46-0,23
SED
Conex Tipo
(kV) (kV) normal 13,2 kV (%) (%) Vcc
.
2 DE AGOSTO S.E. 01 22,9 0,40-0,23 Dyn5 25 kVA fija 2,5 -2 2 4.2 %
20 DE MARZO S.E. 03 22,9 0,40-0,23 Dyn5 37.5 kVA fija 2,5 -2 2 4.2 %
AGROINDUSTRIAL S.E.
01
22,9 0,40-0,23 Dyn5 37.5 kVA fija 2,5 -2 2 4.2 %
AHUARUCHAYOCC S.E.
01
13,2 0,46-0,23 lio 37.5 kVA fija 2,5 -2 2 4.2 %
ANDRES AVELINO
CACERES 01
22,9 0,40-0,23 Dyn5 25 kVA fija 2,5 -2 2 4.2 %
ANDRES AVELINO
CACERES 02
13,2 0,46-0,23 lio 15 kVA fija 2,5 -2 2 4.2 %
BELLA ESMERALDA
S.E. 01
22,9 0,46-0,23 Dyn5 25 kVA fija 2,5 -2 2 4.2 %
CANAL 13,2 0,40-0,23 lio 10 kVA fija 2,5 -2 2 4.2 %
CARMENPAMPA S.E. 01 22,9 0,40-0,23 Dyn5 37.5 kVA fija 2,5 -2 2 4.2 %
CARMENPAMPA S.E. 02 22,9 0,40-0,23 Dyn5 25 kVA fija 2,5 -2 2 4.2 %
CATUTE 01 13,2 0,46-0,23 lio 10 kVA fija 2,5 -2 2 4.2 %
CATUTE S.E. 02 13,2 0,46-0,23 lio 10 kVA fija 2,5 -2 2 4.2 %
CERRITO LIBERTAD 13,2 0,46-0,23 lio 15 kVA fija 2,5 -2 2 4.2 %
FLOR DE CANELA 13,2 0,46-0,23 lio 37.5 kVA fija 2,5 -2 2 4.2 %
LOS LICENCIADOS S.E.
01
22,9 0,40-0,23 Dyn5 25 kVA fija 2,5 -2 2 4.2 %
LOS OLIVOS S.E. 01 22,9 0,40-0,23 Dyn5 15 kVA fija 2,5 -2 2 4.2 %
LOS PEREGRINOS S.E.
01
22,9 0,40-0,23 Dyn5 15 kVA fija 2,5 -2 2 4.2 %
LOS ROSALES S.E. 01 22,9 0,40-0,23 Dyn5 50 kVA fija 2,5 -2 2 4.2 %
MAGISTERIAL S.E. 01 22,9 0,40-0,23 Dyn5 75 kVA fija 2,5 -2 2 4.2 %
MARAVILLA 13,2 0,46-0,23 lio 15 kVA fija 2,5 -2 2 4.2 %
NUEVO PARAISO S.E.
01
22,9 0,40-0,23 Dyn5 15 kVA fija 2,5 -2 2 4.2 %
PARAISO S.E. 01 22,9 0,40-0,23 Dyn5 37.5 kVA fija 2,5 -2 2 4.2 %
PICHIWILLCA S.E. 02 22,9 0,40-0,23 Dyn5 75 kVA fija 2,5 -2 2 4.2 %
PICHIWILLCA S.E.01 22,9 0,40-0,23 Dyn5 75 kVA fija 2,5 -2 2 4.2 %
PORVENIR 13,2 0,46-0,23 lio 37.5 kVA fija 2,5 -2 2 4.2 %
SAN ANTONIO 13,2 0,46-0,23 lio 37.5 kVA fija 2,5 -2 2 4.2 %
SANTA ROSA ALTA S.E.
01
22,9 0,40-0,23 Dyn5 25 kVA fija 2,5 -2 2 4.2 %
SIATO. 22,9 0,40-0,23 Dyn5 25 kVA fija 2,5 -2 2 4.2 %
SIMARIVA S.E. 01 22,9 0,40-0,23 Dyn5 10 kVA fija 2,5 -2 2 4.2 %
SIMARIVA S.E. 02 22,9 0,40-0,23 Dyn5 10 kVA fija 2,5 -2 2 4.2 %
SIMARIVA S.E. 03 22,9 0,40-0,23 Dyn5 10 kVA fija 2,5 -2 2 4.2 %
STA ROSA ALTA S.E. 02 22,9 0,40-0,23 Dyn5 10 kVA fija 2,5 -2 2 4.2 %
STA ROSA ALTA S.E. 03 22,9 0,40-0,23 Dyn5 10 kVA fija 2,5 -2 2 4.2 %
VICTIMAS DE LA
VIOLENCIA POLITICA 22,9 0,40-0,23 Dyn5 50 kVA fija 2,5 -2 2 4.2 %
S.E.01
2 DE AGOSTO S.E. 01 22,9 0,40-0,23 Dyn5 25 kVA fija 2,5 -2 2 4.2 %
20 DE MARZO S.E. 03 22,9 0,40-0,23 Dyn5 37.5 kVA fija 2,5 -2 2 4.2 %
Tabla. Parmetros del transformador de distribucin.

Pgina 6
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

3. ANALISIS DE LA DEMANDA Y LA OFERTA

Del resultado del balance de Oferta - Demanda, y considerando las localidades


beneficiadas con el proyecto, el sistema cuenta con una oferta garantizada hasta
el final del periodo del estudio (ao 2037).

DESCRIPCIN \ AOS 2 017 2 020 2 025 2 030 2 037


Electrificacin de 36 Localidades de Santa
576.22 636.20 702.41 775.52 856.24
Rosa, Ayna y Samugari (kW)
Tabla. Demanda de Potencia del Proyecto.

OFERTA DEMANDA DEMANDA


AO
(*kW) (kW) INSATIFECHA

0
1 1,989.75 576.22 1,413.53
2 1,989.75 587.75 1,402.00
3 1,989.75 599.50 1,390.25
4 1,989.75 611.49 1,378.26
5 1,989.75 623.72 1,366.03
6 1,989.75 636.20 1,353.55
7 1,989.75 648.92 1,340.83
8 1,989.75 661.90 1,327.85
9 1,989.75 675.14 1,314.61
10 1,989.75 688.64 1,301.11
11 1,989.75 702.41 1,287.34
12 1,989.75 716.46 1,273.29
13 1,989.75 730.79 1,258.96
14 1,989.75 745.41 1,244.34
15 1,989.75 745.41 1,244.34
16 1,989.75 760.32 1,229.43
17 1,989.75 775.52 1,214.23
18 1,989.75 791.03 1,198.72
19 1,989.75 806.85 1,182.90
20 1,989.75 856.24 1,133.51
Tabla. Demanda de Potencia del Proyecto.

La mxima demanda proyectada para las 36 localidades para un horizonte de 20


aos es de 856 kW, que corresponde a las localidades consideradas en el
presente proyecto.

El balance Oferta/Demanda determina si la demanda existente y proyectada


ser cubierta por la oferta disponible en la SEP San Francisco 66/22,9 kV, 5
MVA en todo el horizonte del proyecto (20 aos). Considerando que actualmente
el transformador de potencia tiene una cargabilidad del 70 %.

Pgina 7
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

4. ANALISIS DE FLUJO DE CARGA Y CORTOCIRCUITO

4.1. Clculo de Flujo de Carga

A efectos de satisfacer los requerimientos de la Elaboracin del estudio se


llevaron a cabo las tareas necesarias que permitieron simular los flujos de
potencia del sistema en el corto plazo.

La confeccin y posterior anlisis de los flujos de potencia tienen por objeto


el suministro de valores nominales de operacin, sirviendo como
introduccin a los estudios de cortocircuito y posterior ajuste del sistema de
protecciones. Asimismo permite elaborar un diagnstico del sistema, en
cuanto a su funcionamiento en estado estacionario.

Conformacin de la Base de Datos

Inicialmente, se centr el inters en la consolidacin de la base de datos


correspondiente tanto al equipamiento principal de la SE San Francisco y
de todas las redes de distribucin primarias en 22,9 kV de los
alimentadores A4028 y A4030.

De las tareas de verificacin en campo y anlisis de coherencia resultaron


en la base de datos que se presenta en el Anexo N 1.

Una vez consolidada la base de datos del Sistema Elctrico se procedi a


la preparacin de los flujos de potencia, considerando los despachos y la
distribucin de demanda.

Se desarroll una revisin de la Base de Datos, que comprendi la


verificacin de la topologa del sistema de subtransmisin y distribucin as
como los parmetros elctricos de los transformadores del sistema de
distribucin, con lo cual se obtuvo una Base de Datos apta para los
estudios involucrados en estado estacionario y cortocircuito.

La informacin del sistema elctrico interconectado nacional fue obtenida


de la pgina web del COES.

Criterios de Evaluacin

Para evaluar los resultados de las simulaciones de Flujo de Carga, se


aplicar los siguientes criterios:

Niveles de Tensin: En primer trmino se emple la Norma Tcnica de


Calidad de los Servicios Elctricos Rurales (NTCSER), que establece que
en todos los niveles de tensin son hasta del 6% de las tensiones
nominales.

Pgina 8
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Carga de Lneas y Transformadores: La evaluacin de los lmites de carga


de lneas y transformadores en los distintos escenarios tiene en cuenta el
siguiente criterio:

Lneas de transmisin: 100% de su potencia nominal - MVA


Transformadores: 100% de su potencia nominal MVA

Anlisis de los Resultados en Operacin Normal

SE San Francisco AMT A4028 y A4030

En el escenario de estudio no se presentan sobrecargas en


transformadores ni en las lneas de distribucin.

Se simularon escenarios para las mximas demandas. De este alimentador


se entregar energa a las localidades 36 localidades que estn
involucradas en el proyecto.

Del anlisis realizado se concluye que los perfiles de tensin en el rea de


influencia del proyecto se mantienen dentro de los valores admisibles de
operacin para todos los escenarios de estudio.

En el siguiente cuadro se presentan los perfiles de tensin para los casos


analizados.

Configuracin del Proyecto


Barra Caso 0 Caso 1 Caso 2 Caso 3 Caso 4
(ao 0) (ao 5 ) (ao 10 ) (ao 15) (ao 20)
BARRA DE 22,9 KV
1.000 pu 1.000 pu 1.000 pu 1.000 pu 1.000 pu
SE SAN FRANCISCO
PUNTO CONEXIN 2 DE
0.995 pu 0.994 pu 0.984 pu 0.974 pu 0.964 pu
AGOSTO S.E. 01
PUNTO CONEXIN 20
0.978 pu 0.977 pu 0.967 pu 0.957 pu 0.947 pu
DE MARZO S.E. 03
PUNTO CONEXIN
AGROINDUSTRIAL S.E. 0.995 pu 0.994 pu 0.984 pu 0.974 pu 0.964 pu
01
PUNTO CONEXIN
AHUARUCHAYOCC S.E. 0.991 pu 0.990 pu 0.980 pu 0.970 pu 0.960 pu
01
PUNTO CONEXIN
ANDRES AVELINO 0.994 pu 0.993 pu 0.983 pu 0.973 pu 0.963 pu
CACERES 01
PUNTO CONEXIN
ANDRES AVELINO 0.989 pu 0.988 pu 0.978 pu 0.968 pu 0.958 pu
CACERES 02
PUNTO CONEXIN
BELLA ESMERALDA S.E. 0.975 pu 0.974 pu 0.964 pu 0.954 pu 0.944 pu
01
PUNTO CONEXIN
0.971 pu 0.970 pu 0.960 pu 0.950 pu 0.940 pu
CANAL
PUNTO CONEXIN
0.993 pu 0.992 pu 0.982 pu 0.972 pu 0.962 pu
CARMENPAMPA S.E. 01

Pgina 9
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Configuracin del Proyecto


Barra Caso 0 Caso 1 Caso 2 Caso 3 Caso 4
(ao 0) (ao 5 ) (ao 10 ) (ao 15) (ao 20)
PUNTO CONEXIN
0.993 pu 0.992 pu 0.982 pu 0.972 pu 0.962 pu
CARMENPAMPA S.E. 02
PUNTO CONEXIN
0.974 pu 0.973 pu 0.963 pu 0.953 pu 0.943 pu
CATUTE 01
PUNTO CONEXIN
0.974 pu 0.973 pu 0.963 pu 0.953 pu 0.943 pu
CATUTE S.E. 02
PUNTO CONEXIN
0.990 pu 0.989 pu 0.979 pu 0.969 pu 0.959 pu
CERRITO LIBERTAD
PUNTO CONEXIN
0.990 pu 0.989 pu 0.979 pu 0.969 pu 0.959 pu
FLOR DE CANELA
PUNTO CONEXIN LOS
LICENCIADOS S.E. 01
0.977 pu 0.976 pu 0.966 pu 0.956 pu 0.946 pu
PUNTO CONEXIN LOS
0.977 pu 0.976 pu 0.966 pu 0.956 pu 0.946 pu
OLIVOS S.E. 01
PUNTO CONEXIN LOS
0.977 pu 0.976 pu 0.966 pu 0.956 pu 0.946 pu
PEREGRINOS S.E. 01
PUNTO CONEXIN LOS
0.995 pu 0.994 pu 0.984 pu 0.974 pu 0.964 pu
ROSALES S.E. 01
PUNTO CONEXIN
0.977 pu 0.976 pu 0.966 pu 0.956 pu 0.946 pu
MAGISTERIAL S.E. 01
PUNTO CONEXIN
0.990 pu 0.989 pu 0.979 pu 0.969 pu 0.959 pu
MARAVILLA
PUNTO CONEXIN
0.977 pu 0.976 pu 0.966 pu 0.956 pu 0.946 pu
NUEVO PARAISO S.E. 01
PUNTO CONEXIN
PARAISO S.E. 01
0.995 pu 0.994 pu 0.984 pu 0.974 pu 0.964 pu
PUNTO CONEXIN
0.968 pu 0.967 pu 0.957 pu 0.947 pu 0.937 pu
PICHIWILLCA S.E. 02
PUNTO CONEXIN
0.968 pu 0.967 pu 0.957 pu 0.947 pu 0.937 pu
PICHIWILLCA S.E.01
PUNTO CONEXIN
0.990 pu 0.989 pu 0.979 pu 0.969 pu 0.959 pu
PORVENIR
PUNTO CONEXIN SAN
0.990 pu 0.989 pu 0.979 pu 0.969 pu 0.959 pu
ANTONIO
PUNTO CONEXIN
SANTA ROSA ALTA S.E. 0.977 pu 0.976 pu 0.966 pu 0.956 pu 0.946 pu
01
PUNTO CONEXIN
0.994 pu 0.993 pu 0.983 pu 0.973 pu 0.963 pu
SIATO.
PUNTO CONEXIN
SIMARIVA S.E. 01
0.974 pu 0.973 pu 0.963 pu 0.953 pu 0.943 pu
PUNTO CONEXIN
0.974 pu 0.973 pu 0.963 pu 0.953 pu 0.943 pu
SIMARIVA S.E. 02
PUNTO CONEXIN
0.974 pu 0.973 pu 0.963 pu 0.953 pu 0.943 pu
SIMARIVA S.E. 03
PUNTO CONEXIN STA
ROSA ALTA S.E. 02
0.979 pu 0.978 pu 0.968 pu 0.958 pu 0.948 pu
PUNTO CONEXIN STA
0.979 pu 0.978 pu 0.968 pu 0.958 pu 0.948 pu
ROSA ALTA S.E. 03
PUNTO CONEXIN
VICTIMAS DE LA
0.978 pu 0.977 pu 0.967 pu 0.957 pu 0.947 pu
VIOLENCIA POLITICA
S.E.01
Tabla. Niveles de tensin en p.u.

Pgina 10
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

DIgSILENT
1.03

Salida A4028
0.093 km
1.001 p.u.
[p.u.]

CH
4.613 km
1.004 p.u.
1.01

Vnom=1.00 pu

0.99
31.279 km
0.997 p.u.

16.761 km
0.983 p.u.
0.97

0.95

Vmin=0.94 pu

0.93
0.0000 8.0000 16.000 24.000 32.000 [km] 40.000
Line-Ground Voltage, Magnitude A Line-Ground Voltage, Magnitude B
Line-Ground Voltage, Magnitude C

Figura. Perfil de Voltaje Salida A4028, Ao 2017.

DIgSILENT
1.055

[p.u.]

1.030

Salida Red A 4030


0.034 km
1.000 p.u.

1.005
Vnom=1.00 pu

Fin Linea
31.214 km
0.974 p.u.

0.980

0.955

Vmin=0.94 pu

0.930
0.0000 8.0000 16.000 24.000 32.000 [km] 40.000
Line-Ground Voltage, Magnitude A Line-Ground Voltage, Magnitude B
Line-Ground Voltage, Magnitude C

Figura. Perfil de Voltaje Salida A4030, Ao 2017.

Pgina 11
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

4.2. Clculo de Corrientes de Cortocircuito

SE San Francisco AMT A4028 y A4030

El incremento del nmero de instalaciones elctricas en el Sistema


Elctrico Interconectado est asociado con la instalacin de nuevas
centrales de generacin, nuevas lneas de transmisin, nuevos centros de
transformacin y ampliaciones de las instalaciones existentes. Bajo este
contexto, es necesario revisar peridicamente las condiciones de
operacin del sistema con el fin de evaluar el impacto sobre el
comportamiento en estado estacionario del Sistema Elctrico San
Francisco.

A efectos de satisfacer los requerimientos para la elaboracin del Estudio


de Coordinacin de Protecciones del Sistema Elctrico, se llevaron a cabo
las tareas necesarias para calcular los niveles de corriente de cortocircuito
dentro del rea de influencia del Estudio.

El objetivo de este clculo es de brindar toda la informacin necesaria, con


respecto a los resultados de corriente de cortocircuito en las instalaciones
que son parte del alcance del ECP, que sirvan como referencia para la
verificacin de los equipos de maniobra, mallas de puesta a tierra de las
subestaciones o para especificar cualquier otro equipo para proteccin de
proyectos futuros que se quieran conectar al Sistema elctrico San
Francisco.

A su vez los resultados de cortocircuito sern usados en la verificacin de


la coordinacin de protecciones.

A continuacin se presenta los valores calculados de cortocircuito


monofsico de la red en estudio, donde se modelo con los parmetros
elctricos de la red.

Configuracin del Proyecto


Barra Caso 0 Caso 1 Caso 2 Caso 3 Caso 4
(ao 0) (ao 5 ) (ao 10 ) (ao 15) (ao 20)
BARRA DE 22,9 KV
1.253 kA 1.253 kA 1.253 kA 1.254 kA 1.254 kA
SE SAN FRANCISCO
PUNTO CONEXIN 2 DE
1.209 kA 1.209 kA 1.209 kA 1.210 kA 1.210 kA
AGOSTO S.E. 01
PUNTO CONEXIN 20
0.594 kA 0.594 kA 0.594 kA 0.595 kA 0.595 kA
DE MARZO S.E. 03
PUNTO CONEXIN
AGROINDUSTRIAL S.E. 1.152 kA 1.152 kA 1.152 kA 1.153 kA 1.153 kA
01
PUNTO CONEXIN
AHUARUCHAYOCC S.E. 0.829 kA 0.829 kA 0.829 kA 0.830 kA 0.830 kA
01
PUNTO CONEXIN
1.053 kA 1.053 kA 1.053 kA 1.054 kA 1.054 kA
ANDRES AVELINO

Pgina 12
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Configuracin del Proyecto


Barra Caso 0 Caso 1 Caso 2 Caso 3 Caso 4
(ao 0) (ao 5 ) (ao 10 ) (ao 15) (ao 20)
CACERES 01
PUNTO CONEXIN
ANDRES AVELINO 0.872 kA 0.872 kA 0.872 kA 0.873 kA 0.873 kA
CACERES 02
PUNTO CONEXIN
BELLA ESMERALDA S.E. 0.498 kA 0.498 kA 0.498 kA 0.499 kA 0.499 kA
01
PUNTO CONEXIN
0.339 kA 0.339 kA 0.339 kA 0.339 kA 0.339 kA
CANAL
PUNTO CONEXIN
1.013 kA 1.013 kA 1.013 kA 1.014 kA 1.014 kA
CARMENPAMPA S.E. 01
PUNTO CONEXIN
CARMENPAMPA S.E. 02
1.011 kA 1.011 kA 1.011 kA 1.012 kA 1.012 kA
PUNTO CONEXIN
0.400 kA 0.400 kA 0.400 kA 0.401 kA 0.401 kA
CATUTE 01
PUNTO CONEXIN
0.391 kA 0.391 kA 0.391 kA 0.392 kA 0.392 kA
CATUTE S.E. 02
PUNTO CONEXIN
0.682 kA 0.682 kA 0.682 kA 0.683 kA 0.683 kA
CERRITO LIBERTAD
PUNTO CONEXIN
0.663 kA 0.663 kA 0.663 kA 0.664 kA 0.664 kA
FLOR DE CANELA
PUNTO CONEXIN LOS
0.553 kA 0.553 kA 0.553 kA 0.554 kA 0.554 kA
LICENCIADOS S.E. 01
PUNTO CONEXIN LOS
0.580 kA 0.580 kA 0.580 kA 0.581 kA 0.581 kA
OLIVOS S.E. 01
PUNTO CONEXIN LOS
PEREGRINOS S.E. 01
0.555 kA 0.555 kA 0.555 kA 0.556 kA 0.556 kA
PUNTO CONEXIN LOS
1.181 kA 1.181 kA 1.181 kA 1.182 kA 1.182 kA
ROSALES S.E. 01
PUNTO CONEXIN
0.570 kA 0.570 kA 0.570 kA 0.571 kA 0.571 kA
MAGISTERIAL S.E. 01
PUNTO CONEXIN
0.690 kA 0.690 kA 0.690 kA 0.691 kA 0.691 kA
MARAVILLA
PUNTO CONEXIN
0.562 kA 0.562 kA 0.562 kA 0.563 kA 0.563 kA
NUEVO PARAISO S.E. 01
PUNTO CONEXIN
1.182 kA 1.182 kA 1.182 kA 1.183 kA 1.183 kA
PARAISO S.E. 01
PUNTO CONEXIN
0.294 kA 0.294 kA 0.294 kA 0.295 kA 0.295 kA
PICHIWILLCA S.E. 02
PUNTO CONEXIN
PICHIWILLCA S.E.01
0.296 kA 0.296 kA 0.296 kA 0.297 kA 0.297 kA
PUNTO CONEXIN
0.685 kA 0.685 kA 0.685 kA 0.686 kA 0.686 kA
PORVENIR
PUNTO CONEXIN SAN
0.614 kA 0.614 kA 0.614 kA 0.615 kA 0.615 kA
ANTONIO
PUNTO CONEXIN
SANTA ROSA ALTA S.E. 0.584 kA 0.584 kA 0.584 kA 0.585 kA 0.585 kA
01
PUNTO CONEXIN
0.964 kA 0.964 kA 0.964 kA 0.965 kA 0.965 kA
SIATO.
PUNTO CONEXIN
0.491 kA 0.491 kA 0.491 kA 0.492 kA 0.492 kA
SIMARIVA S.E. 01
PUNTO CONEXIN
0.478 kA 0.478 kA 0.478 kA 0.479 kA 0.479 kA
SIMARIVA S.E. 02
PUNTO CONEXIN
SIMARIVA S.E. 03
0.468 kA 0.468 kA 0.468 kA 0.469 kA 0.469 kA
PUNTO CONEXIN STA
0.630 kA 0.630 kA 0.630 kA 0.631 kA 0.631 kA
ROSA ALTA S.E. 02
PUNTO CONEXIN STA
0.624 kA 0.624 kA 0.624 kA 0.625 kA 0.625 kA
ROSA ALTA S.E. 03

Pgina 13
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Configuracin del Proyecto


Barra Caso 0 Caso 1 Caso 2 Caso 3 Caso 4
(ao 0) (ao 5 ) (ao 10 ) (ao 15) (ao 20)
PUNTO CONEXIN
VICTIMAS DE LA
0.586 kA 0.586 kA 0.586 kA 0.587 kA 0.587 kA
VIOLENCIA POLITICA
S.E.01
Tabla. Niveles de corriente de cortocircuito monofsico en kA

En el Anexo 4: Cortocircuito, se muestra los resultados del anlisis de


cortocircuitos para diferentes tipos de fallas en forma grfica.

5. AJUSTE DE LAS PROTECCIONES

En la actualidad la empresa ELECTROCENTRO S.A. ha instalado


reconectadores y seccionalizadores (en el diagrama unifilar identificado por
recloser existente REC 4028-02, REC 4030-01, SECC 4030_04 SEIN, SECC
4030_01 SEIN, SECC 4030_02 SEIN). Los cuales servirn de proteccin para
el rea del proyecto.

La mayora de fallas que se presentan en un sistema elctrico con lneas


areas, son de carcter transitorio (aproximadamente 80%); los fusibles no
discriminan si se tratan de fallas temporales o fallas permanentes y cuando la
intensidad del cortocircuito supera su curva de fusin, interrumpen el servicio
de manera permanente. Para superar este inconveniente de las fallas
transitorias ELECTRROCENTRO plante el uso de seccionalizadores
automticos de marca INAEL modelo SEIN.

Estos seccionalizadores cuentan con la funcin de medicin de corriente


(umbral de corriente) y numero de cuentas programadas con estas dos
funciones se configura la apertura de manera permanente el circuito que se
est protegiendo. Se debe tener presente que estos equipos no son capaces
de despejar una falla con presencia de corriente, es por esta caracterstica que
estos equipos tienen que trabajar con un recloser o un interruptor que cuente
con la funcin de recierre. Los seccionalizadores aperturan el circuito en el
tiempo muerto del recloser o interruptor.

Figura. Ejemplo combinacin recloser-seccionalizador

Pgina 14
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

A continuacin se muestran los ajustes de los equipos de proteccin


alcanzados por Electrocentro S.A:

Pgina 15
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

5.1. Seleccin de fusible para el transformador

Para transformadores de 5 kVA 1 MRT, 13,2 kV

P trafo = 5 kVA (Tensin 13,2 kV), I trafo = 0,38 A.


Ajuste de Sobrecarga (I>) = 1.2 x I trafo = 0,45 A.

El mtodo grafico determina el uso del Fusible equivalente a 1k.

DIgSILENT
10000

Fuse
[s] S&C Positrol 001Std

100
SED 5kVA
Srat: 0.01 MVA
uk: 3.00 %
Ipeak: 8.00/0.10 s

0.01
13.20 kV 0.1 1 10 100 1000 [pri.A] 10000
Terminal\Cub_2\Fuse SED 5kVA

La grafica anterior muestra la caracterstica de operacin corriente-tiempo


del fusibles tipo K para el transformador de distribucin (segn norma
ANSI/IEEE C37.41 y ANSI/IEEE C37.42).

Pgina 16
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Para transformadores de 10 kVA 1 MRT, 13,2 kV

P trafo = 10 kVA (Tensin 13,2 kV), I trafo = 0,76 A.


Ajuste de Sobrecarga (I>) = 1.2 x I trafo = 0,90 A.

El mtodo grafico determina el uso del Fusible equivalente a 1k.

DIgSILENT
10000

[s] Fuse
S&C Positrol 001Std

100

SED 10 kVA
Srat: 0.02 MVA
uk: 3.00 %
Ipeak: 8.00/0.10 s

0.01
13.20 kV 0.1 1 10 100 1000 [pri.A] 10000
Terminal\Cub_2\Fuse SED 10 kVA

La grafica anterior muestra la caracterstica de operacin corriente-tiempo


del fusibles tipo K para el transformador de distribucin (segn norma
ANSI/IEEE C37.41 y ANSI/IEEE C37.42).

Pgina 17
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Para transformadores de 15 kVA 1 MRT, 13,2 kV

P trafo = 15 kVA (Tensin 13,2 kV), I trafo = 1,13 A.


Ajuste de Sobrecarga (I>) = 1.2 x I trafo = 1,36 A.

El mtodo grafico determina el uso del Fusible equivalente a 1k.

DIgSILENT
10000

[s]

100

SED 15KVA
Srat: 0.03 MVA
uk: 3.00 %
Ipeak: 15.00/0.01 s

Fuse
S&C Fuse 001Std

0.01
22.90 kV 1 10 100 1000 [pri.A ] 10000

13.20 kV 10 100 1000 10000


450016612\Cub_2\Fuse SED 15KVA

La grafica anterior muestra la caracterstica de operacin corriente-tiempo


del fusibles tipo K para el transformador de distribucin (segn norma
ANSI/IEEE C37.41 y ANSI/IEEE C37.42).

Pgina 18
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Para transformadores de 25 kVA 1 MRT, 13,2 kV

P trafo = 25 kVA (Tensin 13,2 kV), I trafo = 1,89 A.


Ajuste de Sobrecarga (I>) = 1.2 x I trafo = 2,27 A.

El mtodo grafico determina el uso del Fusible equivalente a 2k.

La grafica anterior muestra la caracterstica de operacin corriente-tiempo


del fusibles tipo K para el transformador de distribucin (segn norma
ANSI/IEEE C37.41 y ANSI/IEEE C37.42).

Pgina 19
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Para transformadores de 25 kVA 3, 22,9 kV

P trafo = 25 kVA (Tensin 22,9 kV), I trafo = 0,63 A.


Ajuste de Sobrecarga (I>) = 1.2 x I trafo = 0,75 A.

El mtodo grafico determina el uso del Fusible equivalente a 1k.

La grafica anterior muestra la caracterstica de operacin corriente-tiempo


del fusibles tipo K para el transformador de distribucin (segn norma
ANSI/IEEE C37.41 y ANSI/IEEE C37.42).

Pgina 20
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Para transformadores de 37,5 kVA 3, 22,9 kV

P trafo = 37,5 kVA (Tensin 22,9 kV), I trafo = 0,945 A.


Ajuste de Sobrecarga (I>) = 1.2 x I trafo = 1,134 A.

El mtodo grafico determina el uso del Fusible equivalente a 1k.

La grafica anterior muestra la caracterstica de operacin corriente-tiempo


del fusibles tipo K para el transformador de distribucin (segn norma
ANSI/IEEE C37.41 y ANSI/IEEE C37.42).

Pgina 21
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Para transformadores de 50 kVA 3, 22,9 kV

P trafo = 50 kVA (Tensin 22,9 kV), I trafo = 1,26 A.


Ajuste de Sobrecarga (I>) = 1.2 x I trafo = 1,512 A.

El mtodo grafico determina el uso del Fusible equivalente a 1k.

La grafica anterior muestra la caracterstica de operacin corriente-tiempo


del fusibles tipo K para el transformador de distribucin (segn norma
ANSI/IEEE C37.41 y ANSI/IEEE C37.42).

Pgina 22
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Para transformadores de 75 kVA 3, 22,9 kV

P trafo = 75 kVA (Tensin 22,9 kV), I trafo = 1,89 A.


Ajuste de Sobrecarga (I>) = 1.2 x I trafo = 2,26 A.

El mtodo grafico determina el uso del Fusible equivalente a 2k.

La grafica anterior muestra la caracterstica de operacin corriente-tiempo


del fusibles tipo K para el transformador de distribucin (segn norma
ANSI/IEEE C37.41 y ANSI/IEEE C37.42).

Pgina 23
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Para transformadores de 100 kVA 3, 22,9 kV

P trafo = 100 kVA (Tensin 22,9 kV), I trafo = 2,52 A.


Ajuste de Sobrecarga (I>) = 1.2 x I trafo = 3,02 A.

El mtodo grafico determina el uso del Fusible equivalente a 2k.

La grafica anterior muestra la caracterstica de operacin corriente-tiempo


del fusibles tipo K para el transformador de distribucin (segn norma
ANSI/IEEE C37.41 y ANSI/IEEE C37.42).

Pgina 24
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

5.2. Seleccin de Fusibles SEDs y Ramales

Para la seleccin de los fusibles que se recomienda instalar en los


transformadores y en las derivaciones que alimentan un solo
transformador, se tomaron en cuenta lo siguiente:

La corriente nominal
La corriente de energizacin
La curva de dao trmico del transformador
La corriente de carga fra

A continuacin se muestra una tabla donde se indica el calibre del fusible


tipo expulsin (cut-out) en funcin de la tensin, potencia y el tipo de
alimentacin de los transformadores de distribucin.

TRAFO kVA TIPO TENSION kV CORRIENTE FUSIBLE


5 1 ph MRT 13,2 0.38 1k
10 1 ph MRT 13,2 0.75 1k
15 1 ph MRT 13,2 1.14 1k
25 1 ph MRT 13,2 1,89 2k
37.5 1 ph MRT 13,2 2.84 3k
10 3 ph 22,9 0.250 1k
15 3 ph 22,9 0.378 1k
25 3 ph 22,9 0.630 1k
37.5 3 ph 22,9 0.95 1k
50 3 ph 22,9 1.26 1k
75 3 ph 22,9 1.89 2k
100 3 ph 22,9 2.52 2k

Seleccin de Fusibles para Lneas de Distribucin

Para la seleccin de los fusibles que se recomienda instalar en las lneas


que alimentan ms de un transformador, se tomaron en cuenta lo siguiente:

La corriente nominal total


Los resultados de flujo de potencia
La corriente de energizacin total
La corriente de cortocircuito en la ubicacin del fusible
Tiempos de operacin (mnimum meelting y total clearing) para las
corrientes de cortocircuito en el punto de ubicacin del fusible.
Curvas de operacin de los rels y dems fusibles ubicados en la
red de distribucin.

Pgina 25
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Lnea Troncal:

Se ha verificado durante la operacin del sistema de distribucin, que la


perdida de una fase en una red cargada (troncal con ms de 15 Amperios)
podra provocar la operacin del rel de tierra del alimentador por aparicin
de corriente de neutro debido al desbalance. Por lo que no es
recomendable hacer coordinacin con fusibles en troncales o redes
cargadas.

Lo dicho anteriormente va de la mano con que los alimentadores


involucrados en el presente estudio tienen presencia de grandes ramales
de cargas monofsicas y esto ocasiona que en varios sectores se tengan
grandes desbalances de corriente.

Los fusibles ubicados entre dos recloser; ante fallas en su zona de


influencia se fusionan y despejan la falla pero no discriminan si es una falla
temporal o permanente con lo cual perjudican la funcin de recierre de los
recloser es por esta situacin que los fusibles ubicados entre dos recloser
van a ser usados solo como de maniobra con un valor igual a 140K.

Se recomienda que los fusibles de los seccionamientos alrededor a los


rels, recloser y en las troncales con ms de 15 amperios de carga sean
solo de maniobra y no de proteccin, para ello emplear fusibles superior o
igual a 140k.

Ramales:

Los fusibles se adecuan a la proteccin de ramales radiales y se debe


tener en cuenta la corriente de carga en el fusible; tambin la corriente de
cortocircuito y las curvas de las funciones del recloser ms prximo.

As mismo, el estar sometido a efectos electrodinmicos de fallas los


elementos fusibles pierden sus propiedades y sus caractersticas de
operacin Tiempo Corriente introduciendo aleatoriedad al momento de su
actuacin, por lo que no se recomienda implementar amplias gamas de
fusibles, en su lugar manejar un fusible para maniobra y otros pocos para
coordinacin y proteccin de los ramales.

Bajo el contexto anterior, se determina que el fusible para coordinacin sea


de valor igual a 6k.

Para Ramales que alimentan un solo transformador de distribucin se


utilizaran fusibles de igual calibre al que protege la SED involucrada.

A continuacin se muestran la curva Tiempo Corriente de operacin de


los fusible de Proteccin para las derivaciones del proyecto.

Pgina 26
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

DIgSILENT
I =840.209
=839.509 pri.A
100

[s]

Fuse Proteccion
S&C Positrol 006K
Tripping Time: 0.010 s
10 F650-A4030 PP
IEC Curve B
Ipset: 1.00 sec.A
Tpset: 0.10
Tripping Time: 9999.999 s

F650-A4030 PP
Ipset: 8.00 sec.A
Tset: 0.02 s
Tripping Time: 0.030 s

0.1

0.030 s

0.010 s
0.01
22.90 kV 10 100 1000 [pri.A ] 10000
SNFRAN22.9\Cub_4\F650-A 4030 PP 4AP01331\Cub_1(1)\Fuse Proteccion

Figura. Falla en la derivacin a CARMENPAMPA

DIgSILENT
I =636.506
=636.268 pri.A
100

[s]

10 F650-A4030 PP
IEC Curve B
Ipset: 1.00 sec.A
Tpset: 0.10
Tripping Time: 9999.999 s

0.262 s F650-A4030 PP
Ipset: 8.00 sec.A
Tset: 0.02 s
Tripping Time: 9999.999 s

0.1

0.015 s

0.010
0.000 s
0.01
22.90 kV 10 100 1000 [pri.A ] 10000
SNFRAN22.9\Cub_4\F650-A 4030 PP 4AP01374\Cub_1(1)\Fuse Proteccion

Figura. Falla en la derivacin a 20 DE MARZO

Pgina 27
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

DIgSILENT
II =629.117
=628.870
=636.506 pri.A
pri.A
100

[s]
Fuse Proteccion
S&C Positrol 006K
Tripping Time: 0.010 s

10 F650-A4030 PP
IEC Curve B
Ipset: 1.00 sec.A
Tpset: 0.10
Tripping Time: 9999.999 s

0.262 s F650-A4030 PP
Ipset: 8.00 sec.A
Tset: 0.02 s
Tripping Time: 9999.999 s

0.1

0.015 s

0.010
0.000 ss
0.01
22.90 kV 10 100 1000 [pri.A ] 10000
SNFRAN22.9\Cub_4\F650-A 4030 PP 4AP54360\Cub_1(1)\Fuse Proteccion

Figura. Falla en la derivacin a SANTA ROSA ALTA

DIgSILENT
I =402.372
=405.680 pri.A
100

[s]

REC 4030-01
IEC 255 Very Inverse
Ipset: 40.00 sec.A
10 Tpset: 0.10
Tripping Time: 0.158 s

REC 4030-01
Ipset: 480.00 sec.A
Tset: 0.02 s
Tripping Time: 9999.999 s

0.158 s

0.1
Fuse Proteccion
S&C Positrol 006K
Tripping Time: 0.010 s

0.010 s
0.01
22.90 kV 10 100 1000 [pri.A ] 10000
4AP117148\Cub_1(1)\Fuse Proteccion 4AP01396\Cub_2\REC 4030-01

Figura. Falla en la derivacin a CATUTE

Pgina 28
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

DIgSILENT
I =701.465
=701.331 pri.A
100

[s]

10 REC 4028-02
IEC 255 Very Inverse
Ipset: 30.00 sec.A
Tpset: 0.10
Tripping Time: 0.070 s

REC 4028-02
Ipset: 360.00 sec.A
Tset: 0.02 s
Tripping Time: 0.030 s

0.1

Fuse Proteccion
S&C Positrol 006K
Tripping Time: 0.010 s
0.030 s

0.010 s
0.01
22.90 kV 10 100 1000 [pri.A ] 10000
4AP120009\Cub_1(1)\Fuse Proteccion 4AP119983\Cub_2\REC 4028-02

Figura. Falla en la derivacin a MARAVILLA

DIgSILENT
I =913.077 pri.A
100

[s]
F650-A4028 PP
IEC Curve B
Ipset: 1.00 sec.A
Tpset: 0.10
10 Tripping Time: 9999.999 s

Fuse Proteccion
S&C Positrol 006K
Tripping Time: 0.010 s

0.176 s

0.1

0.014 s
0.000 s
0.01
22.90 kV 10 100 1000 [pri.A ] 10000
SNFRAN22.9\Cub_2\F650-A 4028 PP 4AP01319\Cub_1(1)\Fuse Proteccion

Figura. Falla en la derivacin a 2 DE AGOSTO

Pgina 29
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

5.3. Proteccin de Sobrecorriente de Secuencia Negativa

Se ha simulado eventos de conductor roto sin y con contacto a tierra por el


extremo carga los cuales son mostrados a continuacin:

El anlisis considera tres etapas de 100ms cada una, la primera es la


operacin en estado normal, la segunda etapa es un evento de conductor
abierto sin contacto a tierra y la ltima etapa considera cuando el conductor
roto cae a tierra por el extremo carga.

DIgSILENT
1.650 1.20
-0.075 s 0.052 s
0.998 p.u. 1.018 p.u.

1.420 0.90 0.132 s


1.009 p.u.
0.022 s
-0.068 s 0.514 p.u.
1.190 0.052 s 0.60
1.011 p.u. 1.027 p.u.

0.960 0.142 s 0.30


1.006 p.u. 0.122 s
0.000 p.u.
0.730 0.00

0.500 -0.30
-0.100 -0.040 0.020 0.080 0.140 [s] 0.200 -0.100 -0.040 0.020 0.080 0.140 [s] 0.200
BarraMT: Line-Ground Voltage, Magnitude A in p.u. LadoCarga: Line-Ground V oltage, Magnitude A in p.u.
BarraMT: Line-Ground Voltage, Magnitude B in p.u. LadoCarga: Line-Ground V oltage, Magnitude B in p.u.
BarraMT: Line-Ground Voltage, Magnitude C in p.u. LadoCarga: Line-Ground V oltage, Magnitude C in p.u.

1.00 0.20
0.032 s 0.122 s -0.075 s
0.801 p.u. 0.817 p.u. 0.172 p.u.

0.75 -0.068 s 0.15


0.923 p.u.
0.132 s
0.032 s 0.095 p.u.
0.086 p.u.
0.50 0.10

0.132 s
0.25 0.05 0.076 p.u.
0.072 s 0.022 s
0.003 p.u. 0.000 p.u.

0.00 0.00 0.132 s


0.019 p.u.

-0.25 -0.05
-0.100 -0.040 0.020 0.080 0.140 [s] 0.200 -0.100 -0.040 0.020 0.080 0.140 [s] 0.200
AMT: Phase Current, Magnitude A/Terminal i in p.u. AMT: Zero-Sequence Current, Magnitude/Terminal i in p.u.
AMT: Phase Current, Magnitude B/Terminal i in p.u. AMT: Positive-Sequence Current, Magnitude/Terminal i in p.u.
AMT: Phase Current, Magnitude C/Terminal i in p.u. AMT: Negative-Sequence Current, Magnitude/Terminal i in p.u.

Pgina 30
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

La simulacin muestra que la variable que mejor describe este defecto es


la de secuencia negativa. Cabe mencionar que al existir equipos de
maniobra asimtricas (Cut outs) podran producir operacin indebida por
secuencia negativa. As mismo, al existir cargas bifsicas y monofsicas en
el sistema en estudio existe riesgo de actuacin indebida.

Por otro lado la funcin de secuencia negativa (46) disponible en los


equipos de proteccin a la salida de los alimentadores es solo por umbral,
sin embargo la funcin de conductor roto mejor adaptada a este fenmeno
es de relacin I2/I1 que no est disponible en los equipos existentes

Bajo este anlisis el ECP considera la no activacin de esta funcin, sin


embargo si la supervisin asume los riesgos asociados, el ajuste se deduce
de la siguiente manera:

Asumiendo un sistema balanceado

Al perder una fase los valores de las componentes I1 y I2 sern:

Ajuste por umbral I2 = 0.33*Imax.dem*fs


Ajuste relacin I2/I1 = 0.50*fs

Dnde:

Fs = Factor de seguridad = 0.8


Imax.dem = Corriente de carga que circuila por el recloser

Pgina 31
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

6. CONCLUSIONES Y RECOMENDACIONES

(a) Se ha cumplido con efectuar los estudios necesarios para revisar la


coordinacin del sistema de proteccin para garantizar la selectividad de los
mismos en salvaguarda de la calidad y seguridad del sistema.

(b) El Estudio incluye el anlisis para la proteccin mediante fusibles de


transformadores de distribucin mostrando las caractersticas de corriente
nominal, corriente inrush, corriente de carga fra y curva dao trmico para
Transformadores de Distribucin 13,2 kV MRT y 22,9 kV 3.

(c) Se recomienda que el fusible del seccionamiento en la derivacin que


alimenta a un solo transformador sea del mismo calibre que el que protege
al transformador de distribucin.

(d) Del anlisis de flujo de potencia se concluye que ante el ingreso de las
localidades proyectadas al sistema elctrico San Francisco no se presentan
sobrecargas en lneas de distribucin ni en transformadores.

(e) Del anlisis de cortocircuito se concluye que el incremento de carga debido


al ingreso de las localidades del proyecto no incrementan
considerablemente las corrientes de cortocircuito.

(f) Del anlisis de la activacin de la funcin de secuencia negativa, se


concluye que al existir equipos de maniobra asimtricas (Cut Outs) podran
producir operacin indebida por secuencia negativa por lo que no se ha
considerado proponer su activacin.

(g) La seleccin de fusibles para los transformadores de distribucin del


proyecto MEJORAMIENTO Y AMPLIACION DEL SERVICIO DE ENERGIA
MEDIANTE EL SISTEMA DE REDES CONVENCIONALES DE LAS
LOCALIDADES DE LOS DISTRITOS DE SANTA ROSA, AYNA Y
SAMUGARI DE LA PROVINCIA LA MAR garantizan una adecuada
proteccin, por lo que se recomienda su implementacin.

(h) El estudio recomienda verificar la tensin en el lado de baja tensin de los


transformadores de distribucin al momento de su energizacin.

Pgina 32
Elaborado: D.F.A.
Anexo 01-Base de Datos

Estudio de Coordinacin de Proteccin


Sistema Elctrico Rural San Francisco
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

BASE DE DATOS DE LOS ARMADOS Y CONDUCTORES

Datos de armados

Name Num. Phases X1 X2 X3 Y1 Y2 Y3


T23kV_1ph 1 -1.2 0 0 10 0 0
T23kV_2ph 2 0 0.8 0 10.5 10 0
T23kV_3ph 3 -1.2 0 1.2 10.5 10 10

Datos de conductores

Nominal Nominal DC-Resistance GMR (Equivalent Internal


Name Voltage Current (20C) Radius) Inductance
kV kA Ohm/km mm mH/km
Al016mm 33 0.10 2.090 1.8513 0.06404104
Al025mm 33 0.125 1.310 2.3595 0.06404106
Al021.1mm 33 0.114 1.580 2.1400 0.06352074
Al035mm 33 0.160 0.952 2.7588 0.06404104
Al050mm 33 0.195 0.663 3.3033 0.06404106
Al070mm 33 0.235 0.484 4.0900 0.05557080
Al0120mm 33 0.340 0.275 5.4000 0.05614268
Cu035mm 27 0.229 0.524 2.7225 0.06404104
Cu050mm 27 0.277 0.395 3.3731 0.05541437

Pgina 34
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Transformador de la SE San Francisco

Pgina 35
Elaborado: D.F.A.
ESTUDIO DE COORDINACION DE PROTECCION SANTA ROSA LA MAR - AYACUCHO

Anexo 02-Diagramas Unifilares

Estudio de Coordinacin de Proteccin


Sistema Elctrico Rural San Francisco

Pgina 36
Elaborado: D.F.A.
DIgSILENT
E435 568

E43556
66
E4355
E435565

78
E 4353

E435564

E43516 4

563
E435
I410385
S&C Positrol 003K
E400 393 I410579
S&C Positrol 140k
I410221
S&C Positrol 002K

E4355 62

E435560
E400 392

I400153
S&C Positrol 140k
E43 5559
E4 35561

E
43
46
93
I410581
I410420 S&C Positrol 140k

E4354 04
S&C Positrol 006K

E435557
E435558

E4 3477 2

93
E4352
I410303 I410299
S&C Positrol 140k S&C Positrol 002K

E400391
3

E43412

E43480
7

434823
E
E401220
0
E43475

9
E43480
E43508

0
E 43412
E435
038

E434820

I410174
S&C Positrol 002K

E4 35088
99
0 19

S.E. SAN FRANCISCO


E4

E400381

CH SAN FRANCISCO
76
E4003

SF1 SF2
LLus.. LLus..
E 400390 ~ ~
SG SG

E 400382
A4028
CHSFR

XFO_SFRANCISCO
SFTXFO
2

CHSF23

1
E43507
I400148
S&C Positrol 006K

70
E4350
MAR
AVILLA

D
LIBERTA
RITO
CER
RVENIR
PO

1
SARIO
RECLOSER PROPUESTO

--RO
E4 34805
REC 4028-01

2
SARIO

9
E43525
--RO
I410292

LA
CANE
S&C Positrol 140k

E
D
FLOR
E4350 69

IO
ANTON
5
8

SAN
E43526
E43526

E4013 79

60
3 52
4
E
RECLOSER PROPUESTO
REC 4028-02

E435261
E
43
52
64
SIATO.
I410097

7
S&C Positrol 002K

E43526
2
E43526
I410430
S&C Positrol 006K E435263

E434768
20
E4354 E43526
I410304
S&C Positrol 006K
ANDR 6
ES AVELINO
CACERES I410288
01 E4352 69 S&C Positrol 140k

10288
I4
E434 122

I410289
S&C Positrol 140k
71
E4352

E4 35272

270
4

E435
E43412

02
I410302

ES
E40038 S&C Positrol 140k

CACER
0

VELINO
E435273

A
I400149

DRES
E400379 E 400384
S&C Positrol 140k

N
A
E43 4778

E434 770
I400769
S&C Positrol 003K
E 400383

I400150
S&C Positrol 003K

01
S.E .
ISO
P ARA

I400151
S&C Positrol 140k

. 01
S.E
TRIAL
. 01 A GROINDUS
S.E
A GOSTO
2 DE

. 01
PROYECTO ELECTRIFICACION

S .E
LE S
ROSA
E434766

LOS
2

E43507

FUSIBLE PROPUESTO
SNFRAN22.9

E43477

RECLOSER PROPUESTO

SE SAN FRANCISCO
RECLOSER EXISTENTE
E4 35083

E4347 76
SECCIONALIZADOR PROPUESTO

E434 773

E4 34774
46
E4347

E43477

5084
E43
E 434755

E434775
E43 4744

779
E434
35085
E4

E43474 8

SECCIONALIZADOR
4028-01
SEIN-1ph
E435086

I410096
S&C Positrol 003K

E434 763

Branches
loc_name Name [-]
loc_name Name [-]

E4347 69
ESTUDIO COORDINACIN PROTECCIONES Project: ECP
SE SAN FRANCISCO - AMT 4028 Graphic: A4028
Date: 5/3/2017
PowerFactory 15.1.7 Annex:
DIgSILENT
SE SAN FRANCISCO

SNFRAN22.9

98
0 19
4
E
I400668
S&C Positrol 140k

CARM ENPAMPA S.E. 01


S.E. SAN FRANCISCO
CARM ENPAMPA S.E. 02

A4030
AHUARUCHAYOCC S.E. 01

E43495

56
E4349

8
E 43496

I410134
S&C Positrol 002K

E43476
7

E434765

CAT UTE S.E. 02


CAT UTE 01
E434967
E435487

I410510
S&C Positrol 001K

E
40
0385

66
3 49
E4
I410367
S&C Positrol 140k

I410135
S&C Positrol 006K

03
S.E.
A
ARIV
SIM
958
E434

02
.
.E
S
I VA
R
A
IM
S
1
E43479

E
400
S .E.01 388
ICA
POLIT 20
DE

. 01
NCIA 1
MA .0
RZO

.E
VIOLE .E
LA

S
DE S .E. S

A
S 03 01

LD
OS .
IV E4 .E

A
VICTIMA

R
0 S

E
OL 03
I VA

M
OS 86

ES
L R
A

A
IM

LL
S

E
B
Fus e P..

87
E4003
S.E. 01
RECLOSER PROPUESTO

ALT A
REC 4030-01

ROSA
SANTA
I400152
S&C Positrol 140k
E434959

I410137
I400263 S&C Positrol 006K

01
S&C Positrol 140k

I AL S.E.

01
MAGISTER

S.E.
PARAISO
0534
E40

NUEVO
I410138

01
S&C Positrol 002K

S.E.
CIADOS
LICEN
60

E400535
S.E. 01
E4349

LOS
I NOS
. 03
.E
S

LOS PEREGR
L TA
A
A
OS
R
A
T
S

I410136
S&C Positrol 140k

E4 3496 1
SECCIONALIZADOR
2
.0
.E

4030-01
S
L TA
A
A
OS
R
A
T
S

SEIN-3ph

SECCIONALIZADOR
4030-03
SEIN-1ph
E43496
E434
804 3

E
434
965 E4 00532
I410094
S&C Positrol 010K

I400264
S&C Positrol 140k

I410093
S&C Positrol 006K E4 34962 SECCIONALIZADOR

E400533
E 434796

4030-04

E4 0053 6
SEIN-1ph

E4 00528
E434 790

E
43
48
02

E400529

E400530
E43 4964

E434 797
E400
531
7
E40052

26
E4005
I410139
S&C Positrol 010K
795
E434

E4347 92

7
E40053
E434794
E434 798

E400538

E4348
03

E434969
88
E4347

E4 34793

E43 4801

E43 4970

E 43497
1 I410092
S&C Positrol 003K
SECCIONALIZADOR
4030-02

8
SEIN-3ph

E 43497
4

E43497

E 434977
72
E4349
AL
N
A
C

3
E43497

9
E 43478

E40054 I410263
S&C Positrol 140k

I410141

E4 00541
S&C Positrol 002K

E40053
E4 00542
E400543

E40 0540
I410140
S&C Positrol 002K

75
4349
E

E4 00546
E400545
799
E434

E434 800

E4 00547

48
E4005
PROYECTO ELECTRIFICACION
PICHIWI LLCA S.E.01

Branches
loc_name Name [-]

FUSIBLE PROPUESTO loc_name Name [-]


PICHIWI LLCA S.E. 0 2

RECLOSER PROPUESTO
434976
E

RECLOSER EXISTENTE

SECCIONALIZADOR PROPUESTO ESTUDIO COORDINACIN PROTECCIONES Project: ECP


SE SAN FRANCISCO - AMT 4030 Graphic: A4030
Date: 5/3/2017
PowerFactory 15.1.7 Annex:
Anexo 03-Flujo de Potencia

Estudio de Coordinacin de Proteccin


Sistema Elctrico Rural San Francisco
DIgSILENT
E435 568

3 9 .67 kW
8 .0 6 k va
1 .0 4 A r

22.53 kV
13.01 kV
0.98 p.u.
-3.70 deg

E43556
3 9. 6 kvar A
8 .0 1 .0 4
kW
67
66
E4355
3 9. 6 kva A
kW r

8 .0 1 .0 4
67
3 9 .6 7 k W
8 .0 6 k v a r
1 .0 4 A

E435565
3 9 .6 7 k W
8 .0 6 k v a r k War
1 .0 4 A 8. 37 kv
-19 . 19 8 A
-38 5 .1 %
5
78 2 .6
E 4353
9k W E435564
2 4.7 kva r
5 .03 A

E43516 4
0 .65

563
1 8.6 0 k W
3 .7 8 kv ar
0 .4 9 A

E435
I410385

3 9. 6 kva A
kW r
S&C Positrol 003K

8 .0 1 .0 4
I410579

67
22.53 kV
13.01 kV E400 393 S&C Positrol 140k
0.98 p.u.
-3.70 deg I410221
24 .79 kW
5.0 3 k va r S&C Positrol 002K 22.54 kV
3 9.6 7 k W
8 .06 kv ar 0.6 5 A 13.01 kV

-14 6 .2 9 k W
-27 .88 kv ar
1 .04 A 0.98 p.u.
-3.69 deg

3.8 2 A
2.3 8 %
22.54 kV
E4355 62 13.01 kV
0.98 p.u.
-3.69 deg
24 .79 kW
5.0 3 k va r
0.6 5 A kWr
7. 46 kva

E435560
-46 . 22 A
-881 2. 19 %
5
6 .2

A
E400 392

67 kvar
4
kW

1 .0
39 .67 kWr

3 9. .0 6
8.0 6 k va

8
1.0 4 A 22.54 kV
I400153 13.02 kV
0.98 p.u.
22.53 kV
S&C Positrol 140k -3.69 deg
13.01 kV
0.98 p.u. E43 5559 E4 35561
-3.70 deg
24 -15
5. .79 -29 8.70
03 39 .67 kW
0. kvar kW

-39 .67 kW
-7.5 2 k va r
8.0 6 k va r .8 k
65 4.1 7 kv W

0.6 5 %
E

1.0 3 A
2.5 4 ar

16. 34 kW

20 A ar
43 A 1.0 4 A
9 %A

10. 32 kv
1- 17.26. 34
46

%
93

6-
I410581
I410420 S&C Positrol 140k

E4354 04
S&C Positrol 006K

3 2.2 3 k W
6 .55 kv ar
0 .84 A

kW
1. k var
8. 6. 7

A
E435557
39
06
04
E435558
22.54 kV

8 .06 kvk W
1 .04 Aar
13.01 kV

3 9.6 7
0.98 p.u.
-3.69 deg
22.54 kV
13.01 kV
0.98 p.u.
-3.69 deg
22.57 kV
13.03 kV
0.99 p.u.
-3.67 deg

22.58 kV
13.04 kV
0.99 p.u.
-3.66 deg

9 kW
-62 7 .44 kv ar
-11 5 .2 A
16 .3 0
%
10 .1 9

22.62 kV
13.06 kV
0.99 p.u.
-3.63 deg

22.63 kV
13.07 kV
0.99 p.u.
-3.62 deg

22.64 kV
13.07 kV
0.99 p.u.
-3.61 deg

-62 9.1
-11 2.1 5 kW
16 .295 kv ar
10 .18 A
%

13.18 kV
13.18 kV

E4 3477 2
1.00 p.u.

0 .2 5 kv ar
1 .2 4 kW
-3.65 deg

0 .1 0 A
-0. 0 .1 0 %
-1. 2 2 kvar A
6
kW

0 .0
24
22.67 kV
13.09 kV
0.99 p.u.
-3.59 deg

13.18 kV
13.18 kV
1.00 p.u.
-3.65 deg

22.68 kV
13.09 kV
0.99 p.u.
-3.59 deg

93
E4352
3 .7 4 8 A
kW r
1 8. 8 kva
0.
60
I410303 I410299
S&C Positrol 140k S&C Positrol 002K

22.71 kV
13.11 kV

E400391
0.99 p.u.
-3.57 deg

1 .2 26 0 kW
0 .1 6 kv ar
A
6.

-11 16 .9 7 %
kW r
5.16 kva
-65 4.25 1 A
.5
10
13.18 kV
13.18 kV
1.00 p.u.
-3.65 deg

22.72 kV
13.12 kV
0.99 p.u.
-3.56 deg

E43412
kW
20
6. 26 kvar A
1. 0. 48

22.72 kV
13.12 kV
0.99 p.u.
-3.55 deg

kW
.4 4 k var
-7 .5 0 A
-0 0. 57 %
45
0.

13.18 kV
13.18 kV
1.00 p.u.
-3.65 deg

E43480
7

0 5. 0 .1 0 %
r
-1.24 3 kvaA
7
kW

0 .0
1 .24 kW
0 .25 kv
0 .10 Aar

16 .6 7 kW
.5 1 A r
10 .9 kva
.0 8
13.24 kV

7%
-656
13.18 kV 13.24 kV

434823
-112
13.18 kV 1.00 p.u.
1.00 p.u. -3.62 deg
-8 .6 8
-3.65 deg 0 .2 4 k W
k va

kW r
A
.6 r

6.20 kva

E
06

0.48
05.3 A

1.26
%

-1.
-0. 24
13.18 kV 18
0. kvarkW
13.18 kV 0. 09
1.00 p.u. 06 A
-3.65 deg %

13.18 kV
13.18 kV
1.00 p.u.
-3.65 deg

E401220
13.18 kV
13.18 kV
1.00 p.u.
-3.64 deg

4 kW r
0 .2 .0 3 A
1 .2 5 kva
0
13.24 kV
13.24 kV

%
1.00 p.u.

A
-0 0. 0906
22.75 kV

kW r
kva
-3.62 deg

0.
13.14 kV

.08
0.99 p.u.

1- .24
-3.53 deg

0
E43475
-8.6 8
06. 0 kW
k va
06 . 6 r
. 3 A

25 kW
05

ar
%

0 . 24
0 . kv
1.

A
10
13.18 kV
13.18 kV
1.00 p.u.
-3.65 deg

22.78 kV
13.15 kV
0.99 p.u.
-3.51 deg
-6 64 .75 kW
-1 12 .01 kv a r
1 7.0 9 A
1 0.8 8 %

13.18 kV
13.18 kV
1.00 p.u.
-3.64 deg

13.24 kV
13.24 kV
1.00 p.u.
-3.62 deg

9
E43480
va r
0.5 0 k9 A
W
2.4 8 k

0.1
13.18 kV
13.18 kV
1.00 p.u.
-3.64 deg

22.79 kV
13.16 kV
1.00 p.u.
-3.50 deg

1
0 . .2 4
2 k
0 . 5k var W
10
A
E43508

-11 1 .9 4 kv ar
-66 8 .9 5 kW

17 .18 A
11 .00 %
13.24 kV

0
13.24 kV

E 43412
1.00 p.u.
-3.62 deg

3 .7 2 k va r
13.18 kV

0 .7 6 A
kW
-1 .24 kW

0 .2 9
13.18 kV 0 .87 kv
13.18 kV 1.00 p.u.
13.18 kV 0 .11 Aar
-3.64 deg 0 .07 %
1.00 p.u.
-3.64 deg

E435 13.24 kV
038 13.24 kV
1.00 p.u.
-3.62 deg
62. 0
. 6 kW
12
k va
04. 8 r
22.82 kV A
13.24 kV
13.18 kV 13.24 kV
1.00 p.u. 1.00 p.u.
-3.48 deg -3.62 deg

-3 13.24 kV
1. .7 2
0. 62 kvakW 13.24 kV
0. 31 A r 1.00 p.u.

0 .19 Aar
-2 .48 kW
19 -3.62 deg E434820

0 .40 kv

0 .12 %
%
13.24 kV
13.24 kV
1.00 p.u.
-3.62 deg 13.24 kV 2.
13.24 kV 0 .5 4 8 kW
1.00 p.u. 0
0 .1 kv ar
-3.62 deg 9A

13.24 kV
I410174 W
13.24 kV
1.00 p.u.
13.18 kV S&C Positrol 002K -6.2 0 k va r -3.62 deg
13.18 kV -1.1 2 k
1.00 p.u. 0.4 8 A
-3.64 deg 0.3 0 %

13.24 kV
13.24 kV

E4 35088
0.5 0 k va r
1.00 p.u.

2.4 8 k W

0.1 9 A
22.84 kV -3.62 deg
13.19 kV
1.00 p.u.
-3.46 deg

kW

0 0 .9 4 %
-1 2.4 0 k W 48 kvarA

kW r
-12 .3 2 kva A
5
1 .0 9 kv ar 2. 50 19

0 .7
0. 0.

4. 0
0 .9 4 A
0 .7 6 %
99
0 19

S.E. SAN FRANCISCO


E4

1 7. 0. 23 kW
1 0. 23 kvar
77
-11 2.

99 A
%
-67
E400381

6.

CH SAN FRANCISCO
1. 20
26 kW
0. kva 0 kW r
48 6 .2 6 kva
A r 1 2. 4 8 A
0.
76
E4003

22.86 kV 13.24 kV
13.20 kV 13.24 kV
1.00 p.u. 1.00 p.u.
13.18 kV -3.45 deg -3.61 deg
13.18 kV
1.00 p.u.
-3.63 deg SF1 SF2
~ ~

1 kva W
SG SG

0.48 ar
1.26 kW

2. 3 3 5 A r
-0. 2 . 00 k
E 400390

-1 0 .3 40 %
kv

E 400382
A

8. 9 kv A
- 1. 40
6 0 ar
6.20

5%

kW

1.
-31

2.
500.00 kW 500.00 kW
13.19 kV 6 .20 300.00 kvar 300.00 kvar
13.19 kV 1 .26 kW 785.43 A 785.43 A
1.00 p.u. 0 .48 kva r 53.01 % 53.01 %
-3.63 deg A

A4028
CHSFR 0.43 kV
13.21 kV 0.25 kV
13.21 kV 0.97 p.u.
22.85 kV
13.19 kV 1.00 p.u. 28.33 deg 1000.00 kW
-3.62 deg 600.00 kvar
1.00 p.u.
-3.39 deg 1570.86 A 13.25 kV
60.59 % 13.25 kV
1.00 p.u.

SFTXFO
13.25 kV -3.61 deg
2 13.25 kV
1.00 p.u.
-3.61 deg

-977.94 kW
-526.11 kvar

-0.051.4 0 %
kW r
kvaA
0
27.93 A

1.4
60.59 %

.6 0
-18
CHSF23 22.96 kV
13.25 kV
22.85 kV 1.00 p.u.
-6 .20 13.19 kV 13.21 kV -3.41 deg
13.18 kV 0.73 kvakW

3.86 %
1.00 p.u. 13.21 kV

2.72 r
kvaA
kW
13.18 kV 0.47 r -3.39 deg 1.00 p.u.

4.51
A
1.00 p.u. 0.38 % -3.62 deg

5.70
-3.63 deg

-15
22.85 kV
13.19 kV

1
E43507
1.00 p.u.
-3.40 deg

0 7. 6k k W

-4 66. 21 95 %
kW r
A
2 9 var

69 kva

-2 1 3. .8 2
0 . .7 2

A
13.19 kV

8
I400148

3
13.19 kV

86.
1.00 p.u. S&C Positrol 006K

kW r

-26 .57 %
2.41 kva
-47 0.62 A
-3.68 deg

13 8
8.5
2 2 kvar kW
1

35 A
0 . .0

7. 7 80 kW
%
-31

2 . 3. 5
70

3. 8 1 kv ar
1

4. 5 7 A
-6 .2 0

E4350

0%
2.
-1 .0 1 kW

-15
kva r

3 .72 kva r
0 .76 A
kW
0 .4
0 .488 A

0 .29
%

22.88 kV 22.94 kV
MAR 13.21 kV 13.25 kV
1.00 p.u. 1.00 p.u.
AVILLA
13.19 kV -3.43 deg -3.41 deg

1.0 0 p g
13.19 kV 22.85 kV

.u.
7 de
kV
kV
1.00 p.u. 13.20 kV

13 .17
-3.68 deg 1.00 p.u.

13 .17

11 6 .5
-3.38 deg 22.94 kV
7. 13.25 kV
1. 35
49 kW 1.00 p.u.
13.18 kV 0. kv

kW
57 ar -3.41 deg

2 67.1 3. 97 %
.22 kvar
13.18 kV A

39 kvar
4 86. 05 A
3
17 4584

kW
1.00 p.u.

8 .8
-673.
-3.63 deg

%
-108.
22.84 kV

49 kW
ar

.98
13.19 kV

0 . kv
1 . 35

10

-26 1 3. 973 %
7.
1.00 p.u.

var
-48 7. 25 A
57

kW
-3.40 deg

D
13.19 kV

6. 32 k

8 .8
LIBERTA
13.19 kV
1.00 p.u.
-3.62 deg 22.94 kV

1 . 3 kvarkW
22.89 kV 13.24 kV

3 . 8. 38
1.00 p.u.

RITO
13.22 kV

42
1
7
1.00 p.u. -3.41 deg
-3.42 deg

CER
RVENIR

kW r

26 .9 7 %
6.24 kva
48 7.48 A

8.84
22.93 kV

13
22.93 kV

PO
13.24 kV
13.24 kV 1.00 p.u.
1.00 p.u. -3.41 deg

kW r

%
6.14 kva
-3.41 deg

-48 7.77 8 A

8.84
-26 .9
13
13.19 kV

0. 49 kvakW
A r
13.19 kV

2. 25
1.00 p.u.

12.

95
-3.61 deg
22.90 kV
22.86 kV 13.22 kV

1
13.20 kV 1.00 p.u.

SARIO
0 . kv kW
1.00 p.u. -3.41 deg

95 ar
RECLOSER PROPUESTO

49 5
-3.38 deg

A
2 . 2.2
1

--RO
REC 4028-01

1.0 0 p g

0 .03 k kW
E4 34805

7 de
13 .17 .u.
13 .17 kV

64 var
kV

5. 79
SARIO

A
11 6 .5

2 4.
kW
1 . 3 kvar
3 . 38
3.7 2 W

A
0.7 6 kkva

9
1 8.

42
r

E43525
--RO
22.84 kV

7
0.2 9 A
13.19 kV
I410292

LA
1.00 p.u.

CANE
-3.40 deg W
-6.2 0 kva r
S&C Positrol 140k
0.1 8 k
0.4 7 A

E
0.3 8 %

-26 1 3. 600 %
68 kv ar
FLOR

38 %
-47 2. 78 A

08 kv ar
-4 61. 54 A
22.91 kV

kW

1 3. .4 7
8 .6
13.18 kV

kW
13.23 kV

8
2 .4 8 kW 13.18 kV

-1 08 .78 kW
1.00 p.u.

1 1 .2 7 A r

-2 63.
0 .5 0 kv ar

1 7 .3 kva

1.
1.00 p.u. -3.41 deg

8%
0 .1 9 A -3.64 deg

.12
-6 80
E4350 69

IO
ANTON
5 22.91 kV
13.23 kV
8

kW
1.00 p.u.

SAN
E43526 kW

1 . k var
3. 37
79 -3.41 deg
2 4. 3 kvarA

1 8.

A
13.19 kV E4352679 kW 5 .00 .6 4

73
42
13.19 kV
24. 03 kvar A
1.00 p.u. 5. 0. 64
-3.68 deg
kW
-7.44 kva r
A

%
-1.04

kW r
0.57 %

2- 51.19. 1932 A
66 kva

12. 9 9
0.36

7.
22.86 kV
22.84 kV 13.20 kV

4-
13.19 kV 6 .20 kW 1.00 p.u.

-0 .04 k W
1.00 p.u. 22.88 kV

0 .23 A r
1 .26 kv ar

0 .28 k va
-3.37 deg
-3.41 deg 0 .48 A 13.21 kV

-3 .72

%
1.00 p.u.
13.18 kV -3.37 deg
13.18 kV 22.88 kV
1.00 p.u. 13.21 kV
-3.64 deg 1.00 p.u.
E4013 79 -3.37 deg
13.21 kV
13.21 kV kW
-2 .4 1.00 p.u. 79 kvar A
-0 .1 8 kW -3.7 2 -3.56 deg 24. 03 64
8 -0.5 7 k W
0 . kv 5. 0.
0 1. 1 9 A ar 02. 8
k va r
13.18 kV 5% 60
01. 8 A
13.18 kV % 3 52
1.00 p.u. kW r 4
13.20 kV kW r .79 kva E

20 1.5 0 %
-3.64 deg 13.20 kV kW
. 24 kva -24 6 A

.8 4 k var
-55 .72 0 A
1.00 p.u. -37 1 1 A 2.93 k var
RECLOSER PROPUESTO -4.5 6 4

kW

1.8
0. 0%
22.84 kV -3.60 deg -0. 2 .8 2 2 % -15 .21 7 A 0 4.

kW
2 .8 11 3.8 0 %

0. 4 kvar
13.19 kV
REC 4028-02

-4 4. 79

40 A
1.00 p.u. 4.5

63
%
.2
-3.41 deg

-2

0.
22.90 kV
13.22 kV
1.00 p.u.
-3.39 deg
22.87 kV
13.20 kV
1.00 p.u.

E435261
-3.37 deg

E
43
A
79 kvar

5. 0. 64

52
kW

kW
22.89 kV

64
24. 03

02 ar
I410097 SIATO. 13.22 kV

79 k varA

8. 6 7
7

24. 03 64

1. kv
A
kW
1.00 p.u.

E43526

5. 0.

39.
06
S&C Positrol 002K -3.38 deg

13.18 kV 6 .20 kW
13.18 kV 1 .26 kv 22.88 kV
1.00 p.u. 22.87 kV 0 .16 Aa r 13.21 kV
-3.64 deg 13.20 kV 1.00 p.u.
kW 1.00 p.u. -3.36 deg
.5 5 r
-13 kvaA

1 1 .4 0 k v a r
-3.36 deg

-2 0 3 .7 6 k W
-0.55

5 .1 5 A
5 .1 4 %
1.03 %
0.64

kW 2
19 r
I410430 3 7. 5 kva A E43526
7 .5 0 .9 6
S&C Positrol 006K 2 4.
kW
r

2 .48 kW
24 .793 kva

0 .19 Aar
E435263

E434768
5 . 79

0 .50 kv
0 . 0 3 kvarkW 5.0 4 A
20 64 39 0.6
A 8. 6. 7
E4354 E43526
I410304 1. 06 k kW
02 var
S&C Positrol 006K A
13.18 kV
13.18 kV 6
1.00 p.u. ANDR
ES AVELINO I410288

kW
-3.64 deg

4. 36 kv ar
13.18 kV CACERES S&C Positrol 140k

1- 61.02. 96 %
4- 5. 47. 98

96 kvarA
01

09 A
2 .48 kW 13.18 kV

-4 10. 12
E4352 69

14

kW

7.
0 .50 kv a r 1.00 p.u.

95
2-

6.
0 .19 A -3.64 deg
1 2 .25 kW 2 4.7 9 k W
2 .4 9 kv 5 .03 kv ar
ar 22.88 kV
0 .3 2 A 0 .64 A 13.21 kV
1.00 p.u.
13.20 kV -3.36 deg
E434 122 13.20 kV
1.00 p.u. 22.88 kV kW
116.65 deg r
3 9.676 kva
18 .60 kW
I410289 13.21 kV
1.00 p.u. 8 .0 0 2 A
1.
3.7 8 k va r S&C Positrol 140k -3.36 deg
0.4 8 A 71
-5 2.0 7
kW -9 .60 kvk W E4352
48 ar
2. 50 kvar A 1 .34 A
0. 0. 19 E4 35272 0 .83 %

3 9. 6 kvar A
8 .0 1 .0 2
E435 kW
270
67
4 22.87 kV
13.21 kV
1.00 p.u.
E43412 -3.35 deg

1 2.4
I410302 -17 7.8 2 .52 0 kW

02
34 1.2 7 kW
S&C Positrol 140k 5 0 .32 k var
9.71 kv ar

ES
A
6.11 A

CACER
E40038 %
0

VELINO
- 2 4.7 9 E435273
19.4 8. 39 13.18 kV 5 .03 kvk W
1. 63 k kW 13.18 kV 0 .64 A
ar
1. 32 var

49 kW
1.00 p.u. I400149

A r
47 A

0 . kva
DRES
22.84 kV % -3.64 deg

1 . .35
E400379 E 400384
S&C Positrol 140k

5 .11 kW
13.18 kV

57

6 .39 kva r
1.00 p.u. 22.88 kV
1 .24 kW

4 .07 A
.41

%
N
13.21 kV
0 .25 kv a r

A
-3.41 deg 1.00 p.u.

-2 53
0 .10 A 24 .79
13.20 kV -3.35 deg 39 .67 kW r 5.0 3 kW
13.20 kV 8.0 6 k2va kv
1.0 A 0.6 4 ar
1.00 p.u. A
116.65 deg

E43 4778

E434 770
1 .26 kv ar
6 .20 kW

0 .48 A
I400769
S&C Positrol 003K
E 400383
I400150
24 .79
5.0 3 k W S&C Positrol 003K
0.6 4kv ar

-2 4 .7 9 kW
ar
A

0 .64 A
-4 .65 kv

0 .40 %
22.84 kV
13.18 kV
1.00 p.u. 13.20 kV
-3.42 deg 13.20 kV
1.00 p.u.
116.65 deg 01
S.E .
ISO
P ARA 22.89 kV
13.21 kV
1.00 p.u.
kW r 7k W -3.31 deg
0.90 5 kva 1 8.3 kva r
-52 A 3 .7 3 A
3 30.2
1 5.55 4 % 0 .4 7
7 6. kW
1 8.3 7k va r
3 .7 3 A
I400151 0 .4 7

S&C Positrol 140k 5k W


22.89 kV 1 2.2 kva r
13.22 kV 2 .49.32 A
0
1.00 p.u.
-3.31 deg . 01
S.E
TRIAL
. 01 A GROINDUS
S.E
A GOSTO
2 DE
22.89 kV

. 01
13.22 kV

PROYECTO ELECTRIFICACION
1.00 p.u.

S .E
-3.31 deg

va r
-59 4 .4 6 kW

.5 0kkW
4. 7 A
LE S
31 7 .1 5 kv a

0 .6 3
kW
r

0 2. 5 kvar
16 .99 A

2 49
0 . .2 4

ROSA
10
13.20 kV 8.2 9 %

E434766
13.20 kV
1.00 p.u.

0 .87 kv ar
13.20 kV

-2 .48 kW

0 .20 A
0 .13 %
116.65 deg 13.20 kV

LOS
1.00 p.u.
116.65 deg

-4 8.3 9 k W
1 8.0 3 k va r
1 .3 0 A
1 .4 6 %
13.19 kV
13.19 kV
1.00 p.u.
-3.71 deg
59
9A

-31 4.59
2. 5 0 kvar
kW

0. 0.1

16 7.57 k W
8.29 .9 9 kv ar
48

A
%
2

13.19 kV 22.89 kV
E43507

13.19 kV -5 13.22 kV
1.00 p.u. 317. 94. 1.00 p.u.

FUSIBLE PROPUESTO
-3.71 deg 22.84 kV 59 -3.29 deg
r

16. 57 kW
-2 .4 8 k W

13.18 kV
0 .4 5 k va

0 .1 2 %
0 .1 9 A

1.00 p.u. 8. 99 k var


29 A
-3.42 deg %

-2.48
0.59
0.19 k kW
0.12 var
A
%

13.20 kV
13.20 kV
1.00 p.u.
116.65 deg
SNFRAN22.9 22.89 kV
13.22 kV
1.00 p.u.
-3.29 deg

%
-1 .2 4k va r
kW
0 .1 4.0 9 A
0 .0 6
0
1

-4 5 .9 0 k W
1 6 .7 1 k v a r E43477

25 kW

A r
1 .2 3 A

0 . kva
0 . .24
1 .3 4 %

10
13.20 kV
13.20 kV
1.00 p.u.

RECLOSER PROPUESTO
116.65 deg

13.20 kV
13.20 kV
1.00 p.u.
116.65 deg

SE SAN FRANCISCO

22.83 kV
13.18 kV
RECLOSER EXISTENTE
1.00 p.u.
-3.42 deg
E4 35083
0.5 0 k va r
2.4 8 k W

0.1 9 A

kW
2 4 kvar
-1 . 2. 0 0 A
-0 0 .1 %
6
0 .0

E4347 76
0 .25 kv ar
1 .24 kW

0 .10 A
kW
.4 2 var
-43 .42 k A
15 1.1 6
3%
13.20 kV
13.20 kV
1.00 p.u.
116.65 deg
SECCIONALIZADOR PROPUESTO
1.3 22.83 kV
13.18 kV
1.00 p.u.
-3.42 deg

13.16 kV
2 .48 kW 13.16 kV
0 .50 kv a r 1.00 p.u.
0 .19 A 116.56 deg

1.2 4 k W r
0.2 5 k va
0.1 0 A

E434 773

E4 34774

22.83 kV
13.18 kV
1.00 p.u.
-3.43 deg
46
E4347

13.19 kV
13.19 kV
1.00 p.u.
1 3. 1 .0 62 %
9 kW r
-39 61 A

-3.73 deg
.6 kva

-1.2 4 k va r
kW

0.0 6 %
1 .3
8 kW r

0.0 9 A
2 .4 0 kvaA
0 .50 .1 9

-0.1 6

13.19 kV 22.83 kV
13.19 kV 13.18 kV
1.00 p.u. 1.00 p.u.
-3.74 deg -3.43 deg

kW
24 kvar A
1. 25
0. 0. 10

E43477
12. 1. 2 6 %
-3 370 2 A
8.4 kvar
kW

1.
5
0. kvarkW
-0. 48

12 A
-2.
07
19
%
0.

22.83 kV
13.18 kV
1.00 p.u.
-3.43 deg

-3 5 .
11 .2 9 7 k W
4
0.95 k va r
1.14 A
% 13.19 kV
13.19 kV
1.00 p.u.
-3.74 deg

22.83 kV
13.18 kV
1.00 p.u.
-3.43 deg

kW r
3.72 kva
0.76 A
0.29

5084
E43

-3 2.2 5 k W
1 0.9 5 k va r
0 .86 A
0 .97 %
E 434755

0.1 9 ar
0.5 0 kW
kv
A
2.4 8

kv ar
-0.5 9 kW

0.1 68 A
%
-4.9 6

0.3

E434775

22.83 kV
3 .7 6 kvarA

13.18 kV
0 .70 .2 9

1.00 p.u.
kW
2

-3.44 deg
E43 4744

0.5 0 k va r
2.4 8 k W

0.1 9 A

13.18 kV 22.83 kV
13.18 kV 13.18 kV
1.00 p.u.
-3.75 deg 1.00 p.u.
-3.44 deg

-23
8.5 .5 6
0.6 7 kvakW
0.7 3 A r
779 4%
E434

kW
48
2. 50 kvarA
0. 0. 19

22.83 kV
13.18 kV
1.00 p.u.
-3.44 deg
35085

1 .26 kW
r
kva
A
E4

6 .20

0 .48

22.83 kV
13.18 kV
1.00 p.u.
-3.44 deg

Out of Calculation
De-energized
7. 0. 1 %
-1 0 3 4 2 A
4.8 kvar
kW

6
0.
8

Voltages / Loading 22.83 kV


13.18 kV
1.00 p.u.
-3.44 deg

13.15 kV
13.15 kV
0.99 p.u.
116.54 deg

Lower Voltage Range 2 .4 8 kW


0 .5 0 kv ar
0 .1 9 A

1. p.u.
E43474 8

...
2%
-0. .1 9 A
48 kvar
kW

0 .1
-2. 11
0

0.95 p.u.
...
0.9 p.u.
Upper Voltage Range
1. p.u.
...
1.05 p.u. -1 2.4 0
5 .24 kvk W
ar
0 .34 A

...
0 .61 %

1.1 p.u.
Loading Range
80. %
...
100. %

22.83 kV
13.18 kV
1.00 p.u.
-3.44 deg

22.83 kV
13.18 kV
1.00 p.u.
-3.45 deg
%
-1 2.4 kva r
1 .77.95 A
0 kW

0 .60
0

SECCIONALIZADOR
13.18 kV
13.18 kV
4028-01
SEIN-1ph
1.00 p.u.
-3.78 deg

13.18 kV
13.18 kV
1.00 p.u.
-3.79 deg

13.18 kV
13.18 kV
1.00 p.u.
-3.80 deg

13.18 kV
13.18 kV
1.00 p.u.
-3.80 deg 13.18 kV
13.18 kV
1.00 p.u.
-3.80 deg
0.7 2 kW
0.2 6 kv ar
9A
E435086
3.7
1 .34 kv a r
0 .67 A
-8 .68 kW

0 .42 %

13.18 kV
13.18 kV
1.00 p.u.
-3.79 deg
I410096
S&C Positrol 003K

E434 763

6 .20 kW
1 .26 kv ar
-0.250.6 6 %

0 .48 A
r
-8.68 kvaA
kW

1
0.4

13.18 kV
13.18 kV
1.00 p.u.
-3.80 deg

13.18 kV
13.18 kV
1.00 p.u.
-3.81 deg
13.18 kV
13.18 kV
1.00 p.u.
-3.80 deg

Load Flow 3-phase(ABC)


Nodes Branches
U1l U1l, Magnitude [kV] Psum Total Active Power [kW]
U1 U1, Magnitude [kV] Qsum Total Reactive Power [kvar]
u1 u1, Magnitude [p.u.] I1 Positive-Sequence Current, Magnitude [A]
phiu1 U1, Angle [deg] loading Loading [%]

13.18 kV
13.18 kV
1.00 p.u.
-3.81 deg
0 .19 %
kW r
A
-2 .48 kva

0 .12

13.18 kV
-0 .39

13.18 kV
1.00 p.u.
-3.81 deg

13.18 kV
13.18 kV
1.00 p.u.

ESTUDIO COORDINACIN PROTECCIONES Project: ECP


-3.81 deg

2 .4 8 kW
0 .5 0 kv ar
0 .1 9 A

E4347 69

SE SAN FRANCISCO - AMT 4028 Graphic: A4028


Date: 5/3/2017
PowerFactory 15.1.7 Annex:
DIgSILENT
SE SAN FRANCISCO

SNFRAN22.9 22.89 kV
13.22 kV
1.00 p.u.
-3.29 deg

-16 2.4 .97 kW


31 .35 k va r
14 .52 A
%
1
-12 31

98
0 19
4
E
6. 23 A
07 kvar
1. 0. 47
-1 .0 7 k v a r

kW
-6 .0 7 k W

0 .4 7 A
0 .3 7 %
13.24 kV
13.24 kV
13.24 kV 13.24 kV
1.00 p.u. 1.00 p.u.
116.75 deg 116.75 deg

I400668
S&C Positrol 140k

22.87 kV
13.21 kV
1.00 p.u.
-3.32 deg

22.87 kV
13.20 kV
1.00 p.u.
-3.33 deg

22.86 kV
13.20 kV
1.00 p.u.
-3.35 deg

CARM ENPAMPA S.E. 01


22.85 kV
13.19 kV 22.85 kV
1.00 p.u. 13.19 kV
1.00 p.u. -1 22 3 .7 5 kW
-3.37 deg -1 62 .39 kv a r
-3.37 deg

-3 0.6 3 k W
-6 .1 1 kv ar
3 1.2 0 A

1 8.3 7 k W

-1 8.3 8 k W
3 .7 3 kv ar

-3 .7 3 kv ar

0 .4 9 %
0 .4 7 A

0 .4 7 A

0 .7 9 A
0 .3 0 %
1 4.5 2 %

S.E. SAN FRANCISCO


CARM ENPAMPA S.E. 02
22.85 kV
13.19 kV
1.00 p.u.
-3.37 deg

-1 2.2 5 k W
-2 .4 9 kv ar
1 2.2 5 k W
2 .4 9 kv ar

0 .2 0 %
0 .3 2 A

0 .3 2 A
A4030
22.83 kV
13.18 kV
1.00 p.u.
-3.40 deg

AHUARUCHAYOCC S.E. 01
13.16 kV
13.16 kV
1.00 p.u.
-3.61 deg

1 8.3 8 k W

-1 8.3 8 k W
3 .7 3 kv ar

-3 .7 3 kv ar
1 .4 2 A

1 .4 2 A
0 .8 9 %
-11 7 3.7 5 k W
-15 5 .3 2 kv a
29 .95 A r
13 .95 %

22.82 kV
13.18 kV
1.00 p.u.
-3.41 deg

E43495

7
9.
1. 1 1
8 kW
0. 5 kvar
71
A

13.15 kV
13.15 kV
0.99 p.u.
-3.66 deg
6 .07 kva r
1 .23.47 A
kW
56

0
E4349

13.15 kV

-1 .33 kv ar
-9 .11 kW

0 .70 A
0 .44 %
13.15 kV
0.99 p.u. 13.15 kV
-3.66 deg 13.15 kV
0.99 p.u.
-3.66 deg
13.20 kV
13.20 kV
1.00 p.u.
116.67 deg
-0 .3 .1 1 kW
0 .6 9 kv ar

-9.1 1 k va r
0 4. 3 A

kW

0.4 4 %
%

0.7 0 A
2
-9

-0.8 9
13.15 kV
13.20 kV 13.15 kV
13.20 kV 0.99 p.u. 8 12.94 kV
1.00 p.u. -3.66 deg E 43496 12.94 kV
116.67 deg -1166.59 kW kW 0.98 p.u.
-154.68 kvar 3 .0 4
k va r -4.15 deg
29.80 A 0 .6 22 4 A
13.95 % 0.

-0 .38 kv a r
-3 .04 kW

0 .15 %
0 .24 A
12.94 kV
12.94 kV
0.98 p.u.
I410134 -4.15 deg

S&C Positrol 002K


-0. 0 .6 9 %
-9. 65 kvar A
3
kW

0 .4
11

E43476
7
3.0
0.6 4 kW
0.2 2 kva
3A r

13.20 kV
13.20 kV
1.00 p.u.
116.67 deg

E434765
ar
-3 .04 kW

13.20 kV
0 .23 A
-0 .57 kv

0 .15 %

13.20 kV 13.20 kV
1.00 p.u. 13.20 kV 6 .07 kW
116.66 deg 1.00 p.u. 1 .23 kv
116.67 deg ar
0 .47 A
-1 .01 kv a r

12.94 kV
-9 .11 kW

0 .43 %
0 .69 A

12.94 kV 12.94 kV

CAT UTE S.E. 02


0.98 p.u. 12.94 kV
-4.15 deg 0.98 p.u.
-4.15 deg

-1 .7 5 k va r
-9 .8 0 k W

0 .7 7 A
0 .4 8 %
0 .9 9 kv ar

-0 .9 9 kv ar
4 .9 0 kW

-4 .9 0 kW
0 .3 9 A

0 .3 9 A
0 .2 4 %
12.94 kV
12.94 kV
0.98 p.u.

CAT UTE 01
-4.15 deg

-0 .99 kv a r
-4 .90 kW

0 .24 %
0 .9 9 kv ar
4 .9 0 kW

0 .39 A
0 .3 9 A
13.20 kV
13.20 kV
1.00 p.u.
116.67 deg W
7.4 9 k
-1 14 .28 kv ar
-1 54 9.3 5 A
2 5%
1 3.9

22.79 kV
13.15 kV
0.99 p.u.
-3.48 deg
13.19 kV 12.94 kV
13.19 kV
12.94 kV E434967
1.00 p.u. 0.98 p.u.
0 .6 2 k v a r

116.65 deg
E435487

-4.15 deg
3 .0 4 k W

0 .2 3 A

1 5.19
3 .0 kW
8
1 .2 kv ar
0A

I410510
S&C Positrol 001K 12.94 kV
12.94 kV
0.98 p.u.
-4.15 deg

k Wr
.8 4 kva
-12
-1.56 0 A
1.0 2 %
0.6

12.94 kV
12.94 kV
0.98 p.u.
-4.15 deg

1.19 %
r
A
kva
kW

0.75
1. 9

-2.81
-15
-1 1 43 .46 kW
-1 5 4.2 5 k va r
2 9 .27 A 12.94 kV
1 3 .95 % 12.94 kV
0.98 p.u. W
03k r
-4.15 deg -28 . kva
22.76 kV -4.08 9A
2.1 %
13.14 kV 7
1.3
0.99 p.u.
-3.52 deg

12.94 kV
12.94 kV
0.98 p.u.
-4.14 deg

22.75 kV
13.14 kV
0.99 p.u.
-3.54 deg

E
40
0385
15
3.08 1. 9
kW
0.39 kva
r
A

12.94 kV
12.94 kV
0.98 p.u.
-4.14 deg

12.94 kV
12.94 kV
0.98 p.u.
W

-4.14 deg
28 .89 6 kv ar

22.73 kV
-15 2.0.76 k

A
%

13.12 kV
-11 26

13 .79

0.99 p.u.
-3.58 deg

66
3 49
E4
19 kvar A
I410367

15. 08 20
kW

3. 1.
S&C Positrol 140k
.64 W
1 3 .7 5 A r
2 8 .3 kva
-1 49 5 .2 7 k

-2 1.2
9%

-2 .56 7 kW
1 .63 k va
-1 10

1 .02 A r
%

22.72 kV
13.12 kV
0.99 p.u.
-3.61 deg

I410135
S&C Positrol 006K

12.95 kV
12.95 kV
0.98 p.u.
-4.13 deg
kW
22
-4 3. 4 3 kvarA
-6 . 3 .3 8 %
1
2 .1

22.55 kV
13.02 kV 22.55 kV
0.98 p.u. 13.02 kV
-3.90 deg 0.98 p.u.

-5 1. 11 %
-4 .2 1 12 A
ar
-3.90 deg

kW
3. 23 kv

2.
22.71 kV
13.11 kV
0.99 p.u.
-3.62 deg

W
0k kvar
0- .0 69 A
0. 0. 02 %
02
0.
22.55 kV
13.02 kV
0.98 p.u.
-3.90 deg

-3 .9 0 d e g
2 2 .5 5 k V
1 3 .0 2 k V
0 .9 8 p .u .
kW
90 kvar A
4. 99
0. 0. 13
03
S.E.
A
22.55 kV
13.02 kV ARIV
13.17 kV 0.98 p.u. SIM
13.17 kV -3.90 deg
1.00 p.u.
958

116.60 deg
E434
kW r
3 .0.6 2 A
4 kva
0 .2 4
0

2 2 .5 5 k V
1 3 .0 2 k V
0 .9 8 p .u .
-3 .9 0 d e g
kW
90 kvar A
4. 99
0. 0. 13
02
.
.E
S
I VA
R
A
IM
S
22.55 kV
1 13.02 kV
0.98 p.u. 22.55 kV
E43479 -3.90 deg 13.02 kV

1 .8 1 %
-7 0.28 k va r
0k W

A
22.55 kV 0.98 p.u.

2 .5 4
7 kW r -3.90 deg
6 .0 3 kvaA 13.02 kV

-7 .3
1 .20 .4 7 0.98 p.u.
-3.89 deg

13.17 kV 22.68 kV
13.17 kV 13.09 kV
1.00 p.u. 0.99 p.u.
116.59 deg -3.67 deg

22.55 kV
13.02 kV
E

-3 .9 0 d e g
0.98 p.u.

2 2 .5 5 k V
1 3 .0 2 k V
0 .9 8 p .u .
S .E.01 400 -3.90 deg
ICA 388

. 01

25 kvar A
POLIT 20 kW

12. 49 32
.E

kW
NCIA DE 1 60 90 kvar

2. 0.
4. 99 A

S
MA .0 12 .75
VIOLE RZO 0. 0. 13

A
LA .E 22.58 kV .34 kW

LD
S 13.04 kV 1.5 kv 01
DE S .E. 9 A ar

A
S 0.99 p.u. .
03 .E

R
OS

E
VICTIMA IV -3.85 deg E4 S

M
0
I VA

ES
OL 03
R
12 60 .75 86

A
OS kW A
L .34

LL
35 kvar IM
7. 49 A 1. kvakW 22.57 kV S

E
1 8.3
0k W 1. 0. 19 59

B
13.17 kV 3 .73 7 kW 13.03 kV
13.17 kV 2 4.5 kva r kva A r 0.99 p.u.
4 .97.64 A

-3 .8 1 d e g
2 2 .6 0 k V
1 3 .0 5 k V
0 .48 r

0 .9 9 p .u .
1.00 p.u. 0 A -3.87 deg

2 2 .6 0 k V
1 3 .0 5 k V
0 .9 9 p .u .
-3 .8 1 d e g
116.60 deg

-2 4 .5 0 kW -1 8.3 7 k W 22.55 kV
-4 .97 kv a r -3 .7 3 kv ar 13.02 kV
0 .64 A 0 .4 8 A 0.98 p.u.
0 .40 % 0 .3 0 % -3.89 deg
kW
0.2 7 A r
0.4 kva
-6.08

9%

2 30 kW
-0.92

1 1. 1.0 kvar
1 08. 65

631A
8 13.

%
W
3k
-1 8.2 kva r

2 1. 8.4 5 8 kW
-2 .78

1 1. 0 1 2 kvar
A
1 .40 %

-3 .8 1 d e g
2 2 .6 0 k V
1 3 .0 5 k V
0 .9 9 p .u .

-10 3.

63 A
0 .88

%
-81
13.17 kV
22.59 kV
13.17 kV -4 2.8 8 k W 13.04 kV
1.00 p.u. -8 .1 6 kv ar 0.99 p.u.
116.60 deg 1 .1 1 A -3.83 deg
0 .7 0 %
22.57 kV
13.03 kV
75 .9 5 k W 0.99 p.u.
13 .2 8 k va r
-3.87 deg
1.9 7 A
1.2 3 %

87
E4003
1 21 7 k va r
A
.50 kW
22.60 kV

3 .17
13.05 kV
0.99 p.u.

2 4.6
-3.81 deg

S.E. 01
RECLOSER PROPUESTO

12 .2 5 va r
kW

0.2 0 %
2.4 7 k2 A
0.3
kW r

ALT A
. 15 6 3.7 0 k W

REC 4030-01

12 .25 kW r
-12 0 8 kvaA

0.3 2 A
2.4 9 k va
22.66 kV 1 0.9 5 k va r
-2. 0 .9 4 % 13.08 kV 1 .6 5 A
9
0 .5

ROSA
0.99 p.u. 1 .0 3 %
-3.70 deg
22.56 kV
6 .0 3 kva A

-100 22.56 kV 13.02 kV


kW r

SANTA
1 .2 0 .4 7

-141 1.90
I400152 13.03 kV 0.98 p.u.
7

25 .63 0.99 p.u. -3.89 deg


E434959

13 .85 kW
13.17 kV
.70
A
kvar S&C Positrol 140k -3.88 deg -70.
-5. 22
% 42
13.17 kV 1. kvarkW
2. 81
1.00 p.u. 54 A
116.60 deg 22.59 kV %
22.61 kV 13.04 kV I410137

01
13.05 kV 0.99 p.u. I400263 S&C Positrol 006K

36 .7 5 va r
kW

0.6 0 %
0.9 6 A
0.99 p.u. -3.83 deg

I AL S.E.
S&C Positrol 140k

7.3 7 k
-3.79 deg
4 k kvaW
0 .4 7 A r

2 6.9 5 k W

5 kWr
0 .2 9 %

0.9 6 A
7.4 6 k va
4 .2 8 kv ar
-6 7

k va r
-7 3.0 9 9 kW
-1 .0 .0

0 .7 0 A

36 .7

9 .62 % A
0 .4 4 %

01
MAGISTER
13.17 kV

-6 30 .9

1 6.2 7
13.17 kV

S.E.
1.00 p.u.
116.59 deg

PARAISO
22.55 kV 0534

7.3 5 k va r

-6 7.0 5 4 kW
13.02 kV

0.1 9 A

1 4.2 3k va r
W
E40

-7.3 5 k va r
0.98 p.u.

A
kW

0.1 2 %

1.4 9 k

9 .3 3 %
-1.4 9 9 A

NUEVO
13.17 kV

-5 51 .5
-3.90 deg
13.17 kV W

0.1
.1 9 k
1.00 p.u. -9.1 15 kv ar
116.59 deg -1.4 1 kW 3.08 A
22.62 kV 1 kv 1.18
13.06 kV 1 9 .6 0 k W 0.7 0 ar
0.99 p.u. 3 .3 0 k v a r 0.4 4 A I410138
0 .5 1 A %
-3.78 deg

01
0 .3 2 % S&C Positrol 002K

S.E.
kW
6 .07 kv ar 13.09 kV

CIADOS
1 .23.47 A 13.09 kV
0 0.99 p.u.
116.39 deg

LICEN
12 .2 5 va r
kW

0.3 2 A
-12 .2 5k va r
60

kW

0.2 0 %

2.4 9 k
0.3 2 A
S.E. 01
E4349

E400535
-2.4 9

LOS
. 5 k va r
0. %
. 01 9 A
kW

.2

3 .0 8 kW
kW

01

1 .1 8 k var
90 kvar 22.59 kV

I NOS

73
14
4. 99 A

7.3 5 k W r

A
1 5.19
1.4 9 k va
. 03 13.04 kV

0.1 9 A
0. 0. 13
.E 0.99 p.u.
S -3.83 deg

LOS PEREGR
L TA
A
A
OS
R
A -3 0 .3 8
T -6 .08 kvk W
S 22.55 kV ar
13.02 kV 2 .37 A
13.11 kV 0.98 p.u. 1 .89 %
13.11 kV -3.91 deg
0.99 p.u.
22.65 kV 116.47 deg
13.08 kV
0.99 p.u.
-3.72 deg
-1 00 .56 kv ar
kW

5%
-1 41 5.9 7 A

22.63 kV
7 .9 5

1 3.7

13.07 kV
0.99 p.u.
2

-3.76 deg
kW r

-15 28 .2 0 %
kva
-10 1.55 9 A
.8
.1 7

13
98

22.51 kV
13.00 kV
0.98 p.u.
-3.98 deg
I410136 22.54 kV
13.01 kV
3.0 4 k W
0.6 2 k va r
S&C Positrol 140k 0.98 p.u.
-3.92 deg
0.2 4 A

E4 3496 1
22.50 kV
12.99 kV
SECCIONALIZADOR
2
.0

0.98 p.u.
.E

-3.99 deg

4030-01
S

13.11 kV
L TA

13.11 kV
A

0.99 p.u.
A

116.47 deg
OS
R
9 0 kvar A

A
4. 9 9 1 3

T
kW

S
0. 0.

SEIN-3ph

SECCIONALIZADOR 22.54 kV
13.01 kV
0.98 p.u.
-3.93 deg

4030-03
SEIN-1ph 13.01 kV
13.11 kV
13.11 kV
13.01 kV 0.99 p.u.
0.98 p.u. 116.46 deg
-4.02 deg 9.1
E43496
-60 .79 kWr

1.8 1
-5.9 7 k va

2.9 3 %

kW
4.7 0 A

0.7 5 kva
E434 1A r
804 9 3
1 . 1. 1
8 kW
0 . 5 kvar E 22.52 kV
434

14. 54 7 kW
13.01 kV 71 13.00 kV
6. A 965

9. 2 4 k var
1 .2037 k W 13.01 kV 0.98 p.u.

33 A
.9
k va
. 8 r I410094 0.98 p.u. E4 00532 -3.96 deg

-550
04

%
A

-69.
-4.03 deg
S&C Positrol 010K 13.01 kV
22.53 kV
13.01 kV
13.01 kV 0.98 p.u.
13.00 kV 0.98 p.u. -3.94 deg 15 .19 kW
13.00 kV 13.00 kV -4.03 deg 3.0 8 k va r
0.4 0 A

-3 7 5.5 1 k Wr
kv a
13.00 kV 0.98 p.u.

4 .4 4 %
-4 3 .27 A
0.98 p.u. -4.04 deg kW

9 .6 9
-4.05 deg . 30 r
-24 2 1 kvaA I400264
-4. 1 .9 0 %
-3.4 7 kW
2.8 va r

13.00 kV 8
13.00 kV 1 .1 S&C Positrol 140k
1.7 62 A
-36 .47
k

0.98 p.u. 6.0 7 k W


-5 4.79 k va r
0k W

4 .2 2 %
A

-4.04 deg r
1.2 3 k8 va 22.52 kV
2 .6 4

SECCIONALIZADOR
0.4 A

08 kW
13.00 kV

1. k var
-5 .0

0.98 p.u.

3. 1 9

A
I410093

19
-3.96 deg

15.
S&C Positrol 006K E4 34962

E400533
E 434796
22.49 kV
kW -16 0 .19 kW 12.99 kV

4030-04
6.07 kv ar -23 .5 2 k va r 0.98 p.u.
1.23 A 12 .4 9 A -4.00 deg
0.48 13.01 kV
13.01 kV 9.9 9 %
0.98 p.u.
-4.02 deg
12.95 kV
kW 12.95 kV
-18 .2 3k va r 0.98 p.u.

E4 0053 6
SEIN-1ph

15 .19 r
kW

15 .1 9 k W
-1.6 8 1 A

E4 00528

1.2 0 A

3.0 8 k va r
3.0 8 k va
-124.23 deg

1.2 0 A
1.4
0.8 8 %

22.49 kV
12.98 kV
0.98 p.u.
-4.01 deg
-2. 2 .3 %
-30 71 5 A
3. 8 kvar

7
kW

1 .4

kW
07
-6 . 0 8 kvarA 13.00 kV
-1 . 0 .4 7 % 13.00 kV
0
0 .3 0.98 p.u.
-4.05 deg

13.01 kV
13.01 kV
0.98 p.u.
-4.02 deg

12.96 kV
12.96 kV
%

0.98 p.u.
-2 1.2 k va r
-1 .30.64 A
7k W

13.00 kV -124.20 deg


1 .02

13.00 kV
1

0.98 p.u.
-4.05 deg

13.00 kV
13.00 kV 13.00 kV
0.98 p.u. 13.00 kV
-4.05 deg 0.98 p.u.
-4.04 deg

9.1 1 k W
1.8 5 k va r
0.7 2 A

1 1. .6 4 kW
9 . 30 kvar
-20 4. 88

04 A
%
12.95 kV

-14
12.95 kV
0.98 p.u.
-124.21 deg
E434 790

-15
-0. .1
54 9k
1 W
0 . .1 7 kva
13.00 kV 73 A r
%
13.00 kV
0.98 p.u. -1 5.1 9 k W kW
4- 2. 32 kvar
-4.05 deg -2 .82 kv ar 6- .4 55
1 .19 A 1- 02.4. 37 98 A
3. 3 kW 1- 7. %
0 .74 % 2. 3 2 kvar 38 12.95 kV
66 A 6.
12.95 kV % 12.95 kV
0.98 p.u.
12.95 kV -124.22 deg
0.98 p.u.
-124.22 deg
E 12.95 kV
43 12.95 kV 22.48 kV
48 0.98 p.u. 12.98 kV
3. 02 0.98 p.u.
0. 04 -124.23 deg
-4.03 deg
0. 62 kW
24 kvar
A

13.00 kV
13.00 kV
0.98 p.u.
-4.07 deg 13.00 kV
13.00 kV
0.98 p.u.
-4.04 deg

kW
2.25 r
-1 0 .6 4 k va
-1 4 .98 A
7 %
6 .38

13.00 kV
13.00 kV
0.98 p.u.
-4.04 deg

13.01 kV
13.01 kV
0.98 p.u.
-4.02 deg

13.00 kV
13.00 kV
0. 6 kW
15 A r
0. 24 kva

0.98 p.u.
0- .4 .0 4

-4.07 deg
%
3-

12.94 kV
12.94 kV
12.95 kV 0.98 p.u.
12.95 kV -124.25 deg
0.98 p.u.
-124.22 deg

13.00 kV
13.00 kV
0.98 p.u. -1 8 .
-4.06 deg -2 .302 3 k W
1.41 kva r
0.88 A
%
E400529

12.94 kV
12.94 kV 1 5.1 22.47 kV
0.98 p.u. 3 .08 9 kW 12.98 kV
-124.25 deg 1 .20 k var 0.98 p.u.
A -4.04 deg

-4
-6 2. 53
.8 kW
3. 3 kvar
2. 33
12.95 kV 66 A
%
12.95 kV
E43 4964

0.98 p.u. E400530


3 .08 kv a r
1 5 .1 9 kW

-124.23 deg
1 .19 A

15
E434 797 13.01 kV 3. 1. 9
13.01 kV 08 kW
1. k var
0.98 p.u. 20 E400
A 531
-4.02 deg

12.94 kV
6 .0 W
1 .2 37kkva 12.94 kV 91.1
r 0.98 p.u. . 5 kW
18
0 .4 8 A 07. 2k va r
13.00 kV -124.25 deg A
13.00 kV
0.98 p.u.
-4.04 deg
12.93 kV
12.93 kV
0.98 p.u.
-124.26 deg

5. kv kW
4. 59 A ar
80 1
12.93 kV

-8. 8

%
12.93 kV

-71.

-1 .65 kv ar
48
0.98 p.u.

-9 .11 kW

0 .57 %
0 .72 A
-124.26 deg

12.93 kV
-6 2 .70 kW 12.93 kV
-7 .3 9 kv 0.98 p.u.
7

4 .8 8 Aa r -124.26 deg
E40052

3 .0 5 %
kW
19 r
1 5. 8 kva A
85 kW

A r

3 .0 1 .2 0
0 . kva
1 . .11
9

26
72

E4005
I410139
S&C Positrol 010K
13.00 kV
0 .71 k va r
kW

13.00 kV
0 .44 A
-9 .11

%
-1 .09

0.98 p.u.
-4.07 deg
795

22.47 kV
12.97 kV
E434

0.98 p.u.
-4.05 deg
kW r

1.23 A
6.07 kva
0.48

13.00 kV
13.00 kV
0.98 p.u.
-4.07 deg E4347 92

3 .04 kW
0 .62 kv ar 13.00 kV
0 .24 A 13.00 kV
0.98 p.u.

7
E40053
-4.05 deg

1 . 8k varkW
3 . 5. 19
13.00 kV

A
19
13.00 kV

1
0
0.98 p.u.
-4.06 deg -1 8.2 3
-2 .19 k W
kv a
1 .42 A r 13.07 kV
0 .89 % 13.07 kV
0.99 p.u.
12.95 kV 116.35 deg
12.95 kV
-12 .15 kWr

You might also like