Environmental friendliness
The miniaturisation of components, the widespread use of electronics and
the appearance of new power electronic base products make temperature
management a constraint similar to IP, which must more and more
frequently be taken into account in the design of electrical and/or electronic
switchboards.
Reliability and minimum failure rates are two determining factors in process
industries in which the hourly cost of installation operations is extremely
high; any failure immediately creates losses which may reach considerable
amounts.
The life of the component itself depends upon temperature and humidity
conditions in the enclosure: the ideal temperature is between + 10 to +
40 C with a relative humidity (RH) of 30 to 90 %.
cool
ventilate
cooling units
VF CLT CLL
no models 16 9 9
functions exterior fan top mounting side panel mounting
interior fan
19" rack fan
characteristics
power
electrical (W) 11 to 155 380 to 1850 290 to 1000
refrigeration (W) 600 to 3100 290 to 1800
3
flow rate (m /h) 24 to 1200
112 HIMEL
The high degree of protection (IP-54), their The CLT-CLL air-conditioning units
ease of installation and efficient operation provide optimal performance in industrial
mean the VF fans prolong and protect the installations thanks to the possibility of
life of the components installed in the interior installing them in environments with a
of the enclosure. temperature of up to 55C.
cool heat
control devices
exchangers
(air- (air-
ICT/ICL water) ICT/ICL air) RC TS
2 5 10 5
top mounting top mounting 2 models with built-in fans thermostat: temperature adjustable
side panel mounting top mounting from 0 to 60C
hygrometer: temperature adjustable
from 0 to 60C
relative humidity adjustable
from 50 to 90 %
hygrostat: relative humidity adjustable
from 30 to 100 %
90 150 10 to 500
1800 15 to 70
HIMEL 113
thermal control for electrical guide for calculating a
thermal auxiliary
switchboards
calculation method for determining Thermal equilibrium consists of comparing auxiliary to be determined and makes it
thermal management of an electrical the power dissipated by the components possible to decide whether it is necessary
panel. of the installation and that released to install a unit, bearing in mind the desired
spontaneously by the walls of the enclosure. internal and external temperatures.
This allows the internal temperature A simple technique is described below:
obtained in the enclosure with a thermal
intermediate in case of juxtaposition, located S = 1.4 B A +0.7 B C + C A Type of installation: Enclosure placed
against a wall and with top covered against a wall.
S= m2 . S = 4.13 m2.
Condensation temperature. Tr = o
C Tr = 29oC
5.- Final temperature inside the enclosure with no auxiliary thermal unit:
It is necessary to cool
114 HIMEL
thermal control for electrical guide for calculating a
thermal auxiliary
switchboards
Td min. < Ti min. Td min. > Ti min. Td max. < Ti max. Td max. > Ti max.
There is no need for a thermal auxiliary as It is necessary to install a thermal auxiliary: It is necessary to install a thermal auxiliary. There is no need for a thermal auxiliary:
a fan can be used if necessary to keep the heating resistor This could be either a fan, a heat if necessary a fan can be used for air
temperature uniform. exchanger or a air-conditioning unit. circulation so as to avoid hot spots.
1/ permanent operation of the panel:
Psis= KxS (Td min Te min) Pd Psis = Pd KxS (Td max Te max)
ventilate
Avoid hot spots Install air-circulation fans A maintenance-free, low-cost The amount of heat removed is
inside the enclosure solution, which is easy to install and relatively little.
preserves the IP rating of the
installation.
cool
temperature conditions solution advantages of the solution disadvantages
Over-dimension the A maintenance-free, low-cost solution, which The amount of heat removed is relatively
enclosure. is easy to install and preserves the IP rating slight. The dimensions are not always
of the installation. compatible with the installation.
The final temperature Td max
desired in the enclosure is at least
5C lower than the maximum Fit ventilation louvres. Low-cost maintenance-free solution. The amount of heat removed is slight
ambient temperature Te. Easy to install. and depends on the arrangement of
the components. Reduces the IP rating
(dust penetration).
Install fans to draw in An economical solution which is easy to Maintenance and periodic cleaning
cool air. install. It removes a greater quantity of heat of the filters. Can reduce the IP
and temperature control is possible. rating in some cases.
Use an air/air heat exchanger. Simple to install. The IP rating of the installation Maintenance and periodic cleaning
is maintained. Temperature control is a of the filters.
standard feature. Easy to maintain.
Use an air-conditioning Simple to install, this solution allows large Maintenance and periodic cleaning of
The final temperature Td max unit. quantities of heat to be removed even when the the filters. It cannot be used when the
desired in the enclosure is ambient temperature is high. The IP rating of ambient temperature is above 55C.
lower than the maximum the installation is preserved and temperature
ambient temperature Te. control is standard.
Use an air/water heat Simple to install, this solution allows large A water circuit is needed and the
exchanger. quantities of heat to be removed even when water consumption is high.
the ambient temperature is high. The IP rating
of the installation is preserved and temperature
control is standard.
Td max Te max + 5oC.
Heat
Exterior temperature below the Economical, reliable, and allows the Power consumption. Occupies
Heat using a heating resistor. temperature of the panel to be controlled.
minimum temperature permissible space inside the enclosure.
for the components.
Heat with a heating resistor to Economical, reliable, and allows the Power consumption. Occupies
Condensation risk. maintain the temperature above humidity of the panel to be controlled. space inside the enclosure.
the condensation temperature.
HIMEL 115
forced and natural ventilation devices VF
The range of forced ventilation devices Determining the fan + outlet grill unit
offers a wide range of solutions adapted to with the aid of a graph.
all industrial applications.
fans: VF. 4
2
Surface de
Enclosure
lenveloppe
surface
en m2 in
30
c full range of louvres and natural aeration
windows for cases where only a small
amount of power needs to be dissipated.
A variety of economic solutions to the (W) 2000 1500 1000
800 W
500 0 100 200 300
425m3/h
400
switchboards.
116 HIMEL
forced and natural ventilation devices VF
;@Q
QQ
@@
;;
230 - 17 V 65 - - FS 65 F 65 -
115 - 17 V 65/115 - - FS 65 F 65 -
230 - 11 VF 24 - - FS 24 F 24 -
- 24 2.4 VF 24/24 DC - - FS 24 F 24 -
230 - 18 VF 56 - - FS 56 F 56 FF 56
- 24 5 VF 56/24 DC - - FS 56 F 56 FF 56
- 48 5 VF 56/48 DC - - FS 56 F 56 FF 56
115 - 20 VF 56/115 - - FS 56 F 56 FF 56
230 - 18 VF 130 - - FS 130 F 130 FF 130
115 - 18 VF 130/115 - - FS 130 F 130 FF 130
- 24 4.7 VF 130/24 DC - - FS 130 F 130 FF 130
- 48 4.7 VF 130/48 DC - - FS 130 F 130 FF 130
230 - 46 VF 250 - - FS 130 F 130 FF 130
115 - 46 VF 250/115 - - FS 130 F 130 FF 130
- 24 12 VF 250/24 DC - - FS 130 F 130 FF 130
- 48 12 VF 250/48 DC - - FS 130 F 130 FF 130
230 - 70 VF 460 - - FS 460 F 460 FF 460
115 - 70 VF 460/115 - - FS 460 F 460 FF 460
230 - 155 VF 625N - - FS 460 F 460 FF 460
115 - 155 VF 625N/115 - - FS 460 F 460 FF 460
400 - 155 VF 625N/400 - - FS 460 F 460 FF 460
230 - 17 VC 150 - - - - -
230 - 34 - VR 312 - - - -
230 - 45 - VR 400 - - - -
230 - 68 - VR 624 - - - -
230 - 90 - VR 800 - - - -
230 - 135 - VR 1200 - - - -
230 - 37 - VTR 300 - - - -
230 - 85 - - VFT 400 - - -
HIMEL 117
natural ventilation systems VF
340 90 6
270 68 22
190
7
6
VET 12
dcoupe
cutting et
surface
entr'axe de fixation
and fixing axis.
228
290,5
270
270
340
228
A
F F
=
U
B
=
5,3
D
E
air-vents
To connect the interior of the enclosure with
the outside in order to prevent condensation.
Can be fitted on the outside, ref.: VM-25 and
VM-27, or on the internal side walls that
connect with the rear self-ventilation
windows of POLYMEL enclosures,
ref.: VM-35.
reference characteristics
118 HIMEL
forced ventilation systems VF
fans
Turbine type motor fan for ventilation/
extraction. For fitting to the cable entries of
the various enclosure models.
4,2
4,2
1
14
104,8
71,5
8
104,8 71,5
HIMEL 119
cooling units CLT - CLL
general characteristics:
c desired interior temperature can be
controlled from +20C to 50C.
c automatic reset pressurestat which
detects overpressure, cuts off the fan from
the external circuit and the compressor and
connects an alarm.
c exterior and interior air circuits separated
(IP-54). The interior circuit fan runs
permanently to prevent hot spots forming
in the installation.
c included in the standard order: drilling
template, instructions for assembly and
installation, seal, condensation outlet pipe.
c convenient and easy to dismantle,
enabling cleaning and maintenance of the
unit.
120 HIMEL
cooling units CLT - CLL
reference
CLT 760 CLT 1050 CLT 1460 CLT 1650 CLT 1650T CLT 2450T CLT 3100T
external dimensions height width depth 340 600 350 400 700 400 400 700 400 430 700 400 430 700 400 470 800 450 470 800 450
refrigerating power DIN 3168 L 35 - L 35* 720 W 1050 W 1460 W 2000 W 1650 W 2450 W 3100W
refrigerating power DIN 3168 L 35 - L 50* 600 W 840 W 1180 W 1650 W 1400 W 1960 W 2500 W
air flow in internal circuit 350 m3/h 430 m3/h 430 m3/h 550 m3/h 550 m3/h 750 m3/h 750 m3/h
air flow in external circuit 350 m3/h 570 m3/h 570 m3/h 620 m3/h 620 m3/h 1200 m3/h 1200 m3/h
maximum pressure reached 1,6 MPa 1,8 MPa 1,8 MPa 1,8 MPa 1,8 MPa 1,8 MPa 1,8 MPa
weight of apparatus 33 kg 41 kg 45 kg 47 kg 60 kg 65 kg 65 kg
temperature control range 20 - 50oC 20 - 50oC 20 - 50oC 20 - 50oC 20 - 50oC 20 - 50oC 20 - 50oC
operating temperature range 20 - 55oC 20 - 55oC 20 - 55oC 20 - 55oC 20 - 55oC 20 - 55oC 20 - 55oC
3 400V - 50 Hz 3 400V - 50 Hz 3 400V - 50 Hz
supply voltage* 230V - 50/60 Hz 230V - 50/60 Hz 230V - 50/60 Hz 230V - 50/60 Hz 3 440V - 60 Hz 3 440V - 60 Hz 3 440V - 60 Hz
nominal/starting current 8 / 2,4 A 11 / 2,9 A 16 / 4,2 A 18 / 4,6 A 10 / 2,3 A 14,5 / 2,8 A 14,5 / 3,4 A
electrical power consumption L 35 - L 35 380 W 500 W 700 W 800 W 800 W 1200 W 1500 W
electrical power consumption L 35 - L 50 450 W 650 W 900 W 1000 W 1000 W 1500 W 1850 W
IP internal / external circuit IP-54 / IP-34 IP-54 / IP-34 IP-54 / IP-34 IP-54 / IP-34 IP-54 / IP-34 IP-54 / IP-34 IP-54 / IP-34
* Air-conditioning units comply to standard DIN 3168 and European standard EN 814.
reference
CLL 240 CLL 370 CLL 760 CLL 1050 CLL 1650 CLL 1650T
external dimensions height width depth.5 450 350 140 620 300 170 800 350 195 900 400 195 1000 400 220 1000 400 220
refrigerating power DIN 3168 L 35 - L 35* 240 W 370 W 760 W 1050 W 1650 W 1800 W
refrigerating power DIN 3168 L 35 - L 50* 170 W 290 W 600 W 840 W 1400 W 1500 W
air flow in internal circuit 180 m3/h 160 m3/h 350 m3/h 350 m3/h 550 m3/h 550 m3/h
air flow in external circuit 330 m3/h 210 m3/h 350 m3/h 510 m3/h 620 m3/h 620 m3/h
maximum pressure reached 1,8 MPa 1,8 MPa 1,8 MPa 1,8 MPa 1,8 MPa 1,8 MPa
weight of apparatus 11 kg 21 kg 33 kg 39 kg 42 kg 46 kg
temperature control range 20 - 45oC 20 - 50oC 20 - 50oC 20 - 50oC 20 - 50oC 20 - 50oC
operating temperature range 20 - 50oC 20 - 55oC 20 - 55oC 20 - 55oC 20 - 55oC 20 - 55oC
3 400V - 50 Hz
supply voltage* 230V - 50/60 Hz 230V - 50/60 Hz 230V - 50/60 Hz 230V - 50/60 Hz 230V - 50/60 Hz 3 440V - 60 Hz
nominal/starting current 0,8 / 3,5 A 6 / 1,6 A 8 / 2,4 A 11 / 2,9 A 18 / 4,6 A 10 / 2,3 A
electrical power consumption L 35 - L 35 140 W 290 W 380 W 500 W 800 W 800 W
electrical power consumption L 35 - L 50 180 W 340 W 450 W 650 W 1000 W 1000 W
filter in external circuit optional yes yes yes yes yes
IP internal / external circuit IP-54 /IP-34 IP-54 /IP-34 IP-54 / IP-34 IP-54 / IP-34 IP-54 / IP-34 IP-54 / IP-34
* Air-conditioning units comply to standard DIN 3168 and European standard EN 814.
for fitting
reference
to units
HIMEL 121
electronically controlled CLLMP
cooling units
CLTMP
general characteristics:
c the operating temperature can be
controlled between 20C and 50C.
c exterior and interior air circuits IP-54.
The interior air circuit fan runs permanently
to avoid hot spots in the installation.
c electronic microprocessor control allows:
- operating temperature control.
- management of the door contact.
c control over the following parameters:
- minimum duration of compressor
operation.
- minimum duration of compressor rest time.
- compressor connection at a temperature
of +1C more than preset.
- compressor disconnection at a temperature
of -5C less than preset.
- types of alarms: bell and dry contact.
- manual alarm reset.
operating conditions:
c operating temperature: between 20C and
55C.
c optional filter required in the case of
installations in difficult environments.
c the coding unit has two handles to
aid transport.
c do not obstruct the air inlets or outlets.
c the apparatus must be installed more than
30 cm from the nearest wall and 10 cm from
the floor.
* Data at 50 Hz
122 HIMEL
electronically controlled CLLMP
cooling units
CLTMP
references for side panel mounting references for top cover mounting
CLLMP 1100 CLLMP 1400 CLLMP 1400T CLLMP 1800T CLTMP 1400 CLTMP 1800T
external dimensions height width depth 1030 400 235 1030 400 235 1030 400 235 1030 400 235 410 752 412 410 752 412
refrigerating power DIN 3168 A 35 - A 35 1100 W 1400 W 1400 W 1800 W 1400 W 1800 W
refrigerating power DIN 3168 A 35 - A 50 900 W 1120 W 1120 W 1440 W 1120 W 1440 W
air flow in internal circuit 340 m3/h 450 m3/h 450 m3/h 450 m3/h 320 m3/h 400 m3/h
air flow in external circuit 240 m3/h 320 m3/h 320 m3/h 400 m3/h 450 m3/h 450 m3/h
weight of apparatus 47 kg 48 kg 49 kg 51 kg 48 kg 51 kg
temperature control range 20 - 55oC 20 - 55oC 20 - 55oC 20 - 55oC 20 - 55oC 20 - 55oC
operating regulation range 20 - 50oC 20 - 50oC 20 - 50oC 20 - 50oC 20 - 50oC 20 - 50oC
supply voltage 230V - 50/60 Hz 230V - 50/60 Hz 3 400V - 50/60 Hz 3 400V - 50/60 Hz 230V - 50/60 Hz 3 400V - 50/60 Hz
nominal/starting current 14,8 / 3,5 A 19,7 / 4,5 A 12 / 1,8 A 12 / 2 A 19 / 4,5 A 12 / 2 A
electrical power consumption A 35 - A 35 700 W 800 W 700 W 900 W 800 W 1000 W
electrical power consumption A 35 - A 50 900 W 1000 W 900 W 1100 W 900 W 1100 W
external IP - internal IP IP-54 /IP-34 IP-54 / IP-34 IP-54 / IP-34 IP-54 / IP-34 IP-54 /IP-34 IP-54 / IP-34
recommended electrical protection (PIA) 6A 6A 4A 4A 6A 4A
filter unit
For installation in the external climate
control circuit. Reference: CLLMP...
Reference: CFCLL
replacement filter:
Reference: FCLL
CFCLL FCLL
to it.
HIMEL 123
air-water exchangers ICT - ICL
general characteristics
c main components: control system,
exchange cassette, fan for interior circuit in
enclosure, security device against possible
water leaks.
c the desired interior temperature can be
controlled from +25C to +50C.
c air/water exchangers have a detection
device which closes a contact on detecting a
water circuit leak. This device can be used
to: power an indicator light, alarm or the
input to a PLC which automatically cuts off
the water supply.
c the interior circuit (which moves the air in
the enclosure) runs constantly to prevent hot
spots in the electrical installation and
components.
c it includes a device to discharge water
collected from condensation to the exterior
as standard.
conditions of use:
c air/water exchangers can be used in all
cases regardless of whether the exterior
temperature is higher or lower than that
required inside the enclosure.
c the enclosure must be sealed to prevent
penetration by exterior air.
dimensions mounting
refrigeration electrical weight
reference depth width height power voltage power (Kg)
(A) (B) (C) (W/oC) (W) roof side
124 HIMEL
air-air heat exchangers ICT - ICL
replacement filters
characteristics reference
HIMEL 125
resistance haters RC
general characteristics
c extruded aluminium body.
c surface temperature limited to 60C in
ambient temperature conditions -5C.
c 500 mm power cable with silicone
insulation (except RCV-400, R-55, 90
and 150 models which have connection
terminals-blocks).
conditions of use
c the use of a temperature controller
together with heating resistors is advisable
(thermostats TS 140, TS 141 or hygrostat
HS 300).
c the enclosure must be sealed to prevent
penetration by exterior air.
c electrical protection devices must be fitted
between the power source and the
resistance heaters.
Psis = k S (Td min Te min) Pd Select one or more resistors with a total
power rating higher than the calculated
if the electrical panel is used continuously. value.
126 HIMEL
control devices TS
thermostat TS 140
The contacts of this thermostat are normally
closed (NC), such that the power supply to
a heater is disconnected when the
temperature exceeds the displayed preset
value. load
Charge
2
This device is particularly recommended
V
to avoid a sudden increase in the internal
temperature of the panel during warm
periods so as to enable the useful life of 1
the heater to be extended.
L N
c DIN rail mounting.
1 = connexion dune rsistance
c IP-30. 2
Load = Resistor
c V0 self-extinguishing thermoplastic
material conforms to UL-94.
c temperature adjustable from 0 to 60C.
c connection: 2 x 2,5 mm2 terminals.
TS 140 60 33 35 6A to 250 V 40
thermostat TS 141
The contacts of this thermostat are normally
open (N0) making it suitable for use with a
fan such that the power supply to the fan is
connected when the temperature exceeds
the displayed preset value. load
Charge
This device permits control over the interior 2
TS 141 60 33 35 2A to 250 V 40
thermostat TS 170
This thermostat has switched contacts
making it suitable for use controlling a fan
or heater when the temperature exceeds the
displayed preset value.
2
This device allows the interior temperature load
HIMEL 127
control devices TS
hygrostat HS 300
This device only measures the humidity
inside the enclosure. Used to control the
functioning of a heater when the humidity
exceeds the preset displayed value.
3
c DIN rail mounting. load 11
Charge
c IP-30. 1
c V0 self-extinguishing thermoplastic V
128 HIMEL