Professional Documents
Culture Documents
Grids 1 and 8 were modeled in conventional structural analysis software as two-dimensional models. The second-
order option in the structural analysis program was not used. Rather, for illustration purposes, second-order effects
are calculated separately, using the B1-B2 approximation method given in Specification Section C2.1b.
The column and beam layouts for the moment frames follow. Although the frames on Grids A and F are the
same, slightly heavier seismic loads accumulate on grid F, after accounting for the atrium area on Grid A and
accidental torsion. The models are half-building models. The frame was originally modeled with W1482
interior columns and W2144 non-composite beams. This model had a drift that substantially exceeded the
0.025hsx story drift allowed per IBC Table 1617.3.1, Seismic Use Group I. The column size was incremented up
to a W1499 and the W2144 beams were upsized to W2455 (with minimum composite studs) and the beams
were modeled with a stiffness of Ieq = Is. Alternatively, the beams could be modeled
as I eq = 0.6 I LB + 0.4 I n (Formula 24), s. This equation is given in AISC Design Guide 8. These changes resulted in
a drift that satisfied the L / 400 limit. This layout is shown in the Grid A and F, Frame ( building) layout that
follows.
All of the vertical loads on the frame were modeled as point loads on the frame. As noted in the description of the
dead load, W, in IBC Section 1617.5, 0.010 kip/ft2 is included in the dead load combinations. The remainder of
the half-building model gravity loads were accumulated in the leaning column, which was connected to the frame
portion of the model with pinned ended links. See Geschwindner, AISC Engineering Journal, Fourth Quarter
1994, A Practical Approach to the Leaning Column. The dead load and live load are shown in the load cases
that follow. The wind and the seismic loads are modeled and distributed 1/14 to exterior columns and 1/7 to the
interior columns. This approach minimizes the tendency to accumulate too much load in the lateral system
nearest an externally applied load.
There are four horizontal load cases. Two are the wind load and seismic load, per the previous discussion. In
addition, notional loads of Ni = 0.002Yi were established. These load cases are shown in the load cases that
follow.
The same modeling procedures were used in the braced frame analysis. If column bases are not fixed in
construction, they should not be fixed in the analysis.
III-48
The model layout, dead loads, live loads, wind loads, seismic loads, dead load notional loads, and live load
notional loads for the moment frame are given as follows:
III-49
III-50
III-51
III-52
III-53
Three methods of determining the required strength including second-order effects are included
below. A fourth method second-order analysis by amplified first-order analysis is found in
Section C2.2b or the Specification. The method requires the inclusion of notional loads in the
analysis, but all required strengths can be determined from a first-order analysis. For guidance
on applying these methods, see the discussion in Manual Part 2 titled Required Strength,
Effective Length, and Second-Order Effects.
Seismic load dominates over winds loads in the moment frame direction of this example
building. Although the frame analysis that follows was run for all LRFD and ASD load
combinations, the column unity design check is highly dependent on the moment portion, and
therefore, the controlling equations are those with the load combinations shown below. A
typical column near the middle of the frame is analyzed, but the first interior columns and the
end columns were also checked. Beam analysis is covered after the three different methods are
shown for the typical interior column.
Note: The second-order analysis and the unity checks are based on the moments and column
loads for the particular load combination being checked, and not on the envelope of maximum
values.
A first-order frame analysis is run using the load combinations for LRFD or ASD. A minimum
lateral load (notional load) equal to 0.2% of the gravity loads is included for any load case for
which the lateral load is not already greater. The general load combinations are in ASCE 7 and
are summarized in Part 2 of the Manual.
A summary of the axial loads, moments and 1st floor drifts from the first-order computer
analysis is shown below:
LRFD ASD
1.2D 1.0E + 0.5L + 0.2S D (W or 0.7 E) (Controls for columns)
(Controls for columns and beams) D + 0.75(W or 0.7E) + 0.75L
+ 0.75(Lr or S or R) (Controls for beams)
First-order first floor drift = 0.562 in. First-order first floor drift = 0.394 in.
The required second-order flexural strength, Mr, and axial strength, Pr, are as follows:
For typical interior columns the gravity-load moments are approximately balanced, therefore,
Mnt = 0.0 kip-ft
III-54
LRFD ASD
Mr = B1Mnt + B2Mlt Mr = B1Mnt + B2Mlt Specification
Eqn C2-1a
Determine B1 Determine B1
Note that for members in axial compression Note that for members in axial compression
Pr may be taken as Pr = Pnt + Plt. For a long Pr may be taken as Pr = Pnt + Plt. For a long
frame, such as this one, the change in load to frame, such as this one, the change in load to
the interior columns, associated with lateral the interior columns, associated with lateral
load is negligible. load is negligible.
2 EI 2 EI
Pel = Pel = Specification
( K1 L ) 2
( K1 L) 2 Eqn C2-5
=
(
( 29, 000 ksi) 1,110 in 4 ) =
(
( 29, 000 ksi) 1,110 in 4 )
(1.0) ( (13.5 ft )(12 in/ft ) ) (1.0) ((13.5 ft )(12 in/ft ))
2 2
= 0.326 = 0.326
= 1.0, = 1.6,
Cm Cm
B1 = B1 =
P P Specification
1 r 1 r Eqn C2-2
Pe1 Pe1
0.326 0.326
= =
(1.0)( 335 kips) (1.6)( 247 kips)
1 1
12,100 kips 12,100 kips
Calculate B2 Calculate B2
1 1
B2 = B2 =
Pnt Pnt
1 1
P P
e2 e2
where: where:
= 1.0, = 1.6,
P nt = 5, 250 kips (from computer output) P nt = 3, 750 kips (from computer output)
and and Specification
HL HL Section C2.1b
P e2 may be taken as =RM
H
P e2 may be taken as =RM
H
where RM is taken as 0.85 for moment frames where RM is taken as 0.85 for moment frames
H = 0.562 in. (from computer output) H = 0.394 in. (from computer output)
1 1
= =
(1.0 )( 5, 250 kips ) (1.6 )( 3, 750 kips )
1 1
47,800 kips 47, 900 kips
= 1.12 1 = 1.14 1
Determine the controlling effective length Determine the controlling effective length
For out-of-plane buckling in the braced For out-of-plane buckling in the braced
frame frame
Ky=1.0 Ky=1.0
Commentary
For in-plane buckling in the moment frame, For in-plane buckling in the moment frame, Section C2.2b
use the nomograph use the nomograph
Kx=1.43 Kx=1.43
To account for leaning columns in the To account for leaning columns in the
controlling load case controlling load case
K = Ko 1 +
Q K = Ko 1 +
Q
P P
3010 2140
= 1.43 1 + = 2.13 = 1.43 1 + = 2.14
2490 1740
KL x 2.13(13.5) KL x 2.14(13.5)
= = 17.3 = = 17.4
rx / ry 1.66 rx / ry 1.66
III-57
Pc = 1, 041 kips (W14 99 @ KL = 17.3 ft) Pc = 692 kips (W14 99 @ KL = 17.4 ft) Specification
Sect H1.1
Manual
Pr 335 kips Pr 247 kips Table 4-1
= = 0.321 0.2 = = 0.357 0.2
Pc 1, 041 kips Pc 692 kips
Manual
M cx = 646 kip-ft (W14 99) M cx = 430 kip-ft (W14 99) Table 3-2
Pr 8 M rx M ry Pr 8 M rx M ry
+ + + + Specification
Pc 9 M cx M cy Pc 9 M cx M cy Eqn H1-1a
LRFD ASD
1.2D 1.0E + 0.5L + 0.2S (Controls D (W or 0.7 E) (Controls columns)
columns and beams)
D + 0.75(W or 0.7E) + 0.75L
+ 0.75(Lr or S or R) (Controls beams)
First-floor first-order drift = 0.562 in. First-floor first-order drift = 0.394 in.
LRFD ASD
Step 1: Step 1:
Deflection due to first-order elastic analysis Deflection due to first-order elastic analysis
= 0.562 in. between first and second floor = 0.394 in. between first and second floor
Drift ratio = (13.5 ft)(12 in/ft) / 0.562 in Drift ratio = (13.5 ft)(12 in/ft) / 0.394 in
= 288 = 411
Step 2: Step 2:
Design story drift limit = 0.025 hxs Design story drift limit = 0.025 hxs IBC Table
1617.3.1
= h/400 = h/400
Adjusted Lateral load = (288/ 400)(195 kips) Adjusted Lateral load = (411 / 400)(137 kips)
= 37.2 = 42.6
Manual
Interpolating from the table: B2 = 1.1 Interpolating from the table: B2 = 1.1 Page 2-12
Which matches the value obtained in the first Which matches the value obtained in the first
method to the 2 significant figures of the method to the 2 significant figures of the
table table
Note: Because the table is intentionally based on two significant figures, this value is taken as
1.1 rather than an interpolated value > 1.1. This convenient selection is within the accuracy of
the method. Since the selection is in the shaded area of the chart, K=1.0.
Step 4. Multiply all the forces and moment from the first-order analysis by the value obtained
from the table.
LRFD ASD
Mr = B2(Mnt + Mlt) Mr = B2(Mnt + Mlt)
= 1.1(0 kip-ft + 229 kip-ft) = 252 kip-ft = 1.1(0 kip-ft + 161 kip-ft) = 177 kip-ft
= 1.1(335 kips +0.0 kips) = 368 kips = 1.1(247 kips +0.0 kips) = 272 kips
Specification
Pr 8 M rx M ry Pr 8 M rx M ry
+ + + + Eqn H1-1a
Pc 9 M cx M cy Pc 9 M cx M cy
LRFD ASD
1.2D 1.0E + 0.5L + 0.2S (Controls D (W or 0.7 E) (Controls columns)
columns and beams) D + 0.75(W or 0.7E) + 0.75L
+ 0.75(Lr or S or R) (Controls beams)
For a 1st order analysis with notional loads For a 1st order analysis with notional loads
and reduced stiffness: and with reduced stiffness:
Note: For ASD, this method requires multiplying the ASD load combinations by a factor of 1.6
in analyzing the drift of the structure, and then dividing the results by 1.6 to obtain the required
strengths. The ASD forces shown above include the multiplier of 1.6.
LRFD ASD
For this method, K =1.0. For this method, K =1.0
Manual
Pc = 1,140 kips (W14 99 @ KL = 13.5 ft) Pc = 759 kips (W14 99 @ KL = 13.5 ft) Table 4-1
Determine B1 Determine B1
Note that for members in axial compression Note that for members in axial compression
Pr may be taken as Pr = Pnt + Plt. For a long Pr may be taken as Pr = Pnt + Plt. For a long
frame, such as this one, the change in load to frame, such as this one, the change in load to
the interior columns, associated with lateral the interior columns, associated with lateral
load is negligible. load is negligible.
2 EI 2 EI
Pel = Pel =
( K1 L ) 2
( K1 L) 2
=
(
( 29, 000 ksi) 1,110 in 4 ) =
(
( 29, 000 ksi) 1,110 in 4 )
(1.0) ( (13.5 ft )(12 in/ft ) ) (1.0) ((13.5 ft )(12 in/ft ))
2 2
= 0.6 0.4 (157 kip-ft / 229 kip-ft) = 0.6 0.4 (110 kip-ft / 161 kip-ft)
= 0.326 = 0.327
= 1.0, = 1.6,
Cm Cm
B1 = B1 =
Pr Pr
1 1
Pe1 Pe1
0.326 0.327
= =
(1.0)( 335 kips) (1.6)( 247 kips)
1 1
12,100 kips 12,100 kips
Calculate B2 Calculate B2
1 1
B2 = B2 =
Pnt Pnt
1 1
P P
e2 e2
where: where:
= 1.0, = 1.6,
P nt = 5, 250 kips (from computer output) P nt = 3, 750 kips (from computer output)
HL HL
P e2 may be taken as =RM
H
P e2 may be taken as =RM
H
where RM is taken as 0.85 for moment frames where RM is taken as 0.85 for moment frames
= 1.16 1 = 1.19 1
Pr 8 M rx M ry Pr 8 M rx M ry
+ + + + Specification
Pc 9 M cx M cy Pc 9 M cx M cy Eqn H1-1b
The braced frames at Grids 1 and 8 were analyzed for their lateral loads. The same stability
design requirements from Chapter C were applied to this system.
First a first-order frame analysis is run using the load combinations for LRFD and ASD. From
this analysis the critical axial loads, moments, and deflections are obtained.
The required second-order flexural strength, Mr, and axial strength, Pr, are as follows:
LRFD ASD
EI
2
EI
2 Specification
Pel = Pel = Eqn C2-5
( K1 L ) 2
( K1 L ) 2
=
( 29, 000 ksi) 425 in 4 ( ) =
( 29, 000 ksi) 425 in 4 ( )
(1.0) ( (13.5 ft )(12 in/ft ) ) (1.0) ( (13.5 ft )(12 in/ft ) )
2 2
1 1
B2 = B2 =
Pnt Pnt Specification
1 1
P P Eqn C2-3
e2 e2
1 1
= =
(1.0 )( 5, 452 kips ) (1.6 )( 3,894 kips )
1 1
150, 722 kips 150, 722 kips
= 1.04 1 = 1.04 1
P nt = 5, 452 kips (from computer output) P nt = 3,894 kips (from computer output)
HL HL
P e2 = RM
H
P e2 = RM
H Specification
Eqn C2-6b
= 1.0
(195 kips)(13.5 ft )(12 in/ft ) = 1.0
(137 kips)(13.5 ft )(12 in/ft )
0..210 in. 0.147 in.
H = 0.210 in. (from computer output) H = 0.147 in. (from computer output)
Note: Notice that the lower displacements of the braced frame produce much lower values for
B2. Similar values could be expected for the other two methods of analysis.