Ua sin( ) (1)
Ub sin( 2 ) (2)
3
Uc sin( 2 ) (3)
3
The magnitude I m of the same current is obtained by passing
the error signal between the DC-link voltage (VDC) and a
reference voltage (VDC*) through a fuzzy logic controller. Fig.6.Membership functions of input
Using this magnitude and phase displacement of 120 and
240 respectively, the reference three-phase grid currents
ia*,ib* and ic* can be expressed as:
TABLE1.FLC RULE BASE
I a * I m sin( ) (4)
Ib * I m sin( 2 ) (5) NB NM NS ZE PS PM PB
3 /
Ic * I m sin( 2 ) (6) NB NB NB NB NB NM NS ZE
3
NM NB NB NM NM NS ZE PS
All the variables fuzzy subsets for the inputs and are
defined as (NB, NM, NS, Z, PS, PM, PB). The membership
function of inputs is illustrated in fig.5&6. The fuzzy control
rule is illustrated in the table I.
C. SWITCHING CONTROL
Fig.4.Basic representation of FLC
As shown in Fig. 3, the hysteresis control has been used to
keep the controlled current inside a defined band around the
The determination of the output control signal, is done in an references. The status of the switches is determined
inference engine with a rule base having if-then rules in the according to the error. When the current is increasing and the
form of error exceeds a certain positive value, the status of the
"IF is ....... AND is ......., THEN output is ........" switches changes and the current begins to decrease until the
With the rule base, the value of the output is changed error reaches a certain negative value. Then, the switches
according to the value of the error signal , and the rate-of- status changes again. Compared with linear controllers, the
error . The structure and determination of the rule base is non-linear ones based on hysteresis strategies allow faster
done using trial-and-error methods and is also done through dynamic response and better robustness with respect to the
experimentation. variation of the non-linear load. A drawback [13] [14] of the
hysteresis strategies is the switching frequency which is not
constant and can generate a large side harmonics band around
the switching frequency.
www.ijert.org 3
International Journal of Engineering Research & Technology (IJERT)
ISSN: 2278-0181
Vol. 1 Issue 4, June - 2012
www.ijert.org 4
International Journal of Engineering Research & Technology (IJERT)
ISSN: 2278-0181
Vol. 1 Issue 4, June - 2012
IV. CONCLUSION
This paper has presented a novel method to improve the
power quality at point of common coupling (PCC) for a 3- Annavarapu Ananda Kumar born in 1987, in
phase 4- wire DG system using fuzzy logic control for grid India. He received B.Tech degree in Electrical &
Electronics Engineering from Acharya
interfacing inverter. The grid interfacing inverter is effectively Nagarjuna University, India in 2008.
utilized for power conditioning. This approach eliminates the Currently he is persuing M.Tech degree from
additional power conditioning equipment to improve power JNTU University in Power System Control &
quality at PCC. Simulation results analysis has shown that the Automation. His research interest includes Power
proposed controller has fast response, high accuracy of tracking Systems, Power System Operation & Control,
Power System Stability& Analysis.
the DC-voltage reference, and strong robustness to load sudden
variations