Air System Design Load Summary for GF-AHU-01 w heat/humidifier

Project Name: DG Affairs- Office rev. 1 08/27/2011


Prepared by: abc 07:22AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 49.8 C / 29.9 C HEATING OA DB / WB 12.0 C / 10.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m 6701 - 44 m - -
Wall Transmission 170 m 2863 - 170 m 914 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 44 m 3863 - 44 m 1331 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 3 m 113 - 3 m 39 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 174 m 3840 - 174 m 0 -
Ceiling 29 m 911 - 29 m 0 -
Overhead Lighting 10325 W 9267 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 12400 W 11833 - 0 0 -
People 236 14778 14179 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 8125 2127 0% 0 0
>> Total Zone Loads - 62295 16306 - 2284 0
Zone Conditioning - 68364 16306 - -4440 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 5228 L/s 0 - 1248 L/s 0 -
Ventilation Load 1132 L/s 36014 32258 270 L/s 1124 -1085
Supply Fan Load 5228 L/s 2931 - 1248 L/s -1088 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 623 - 1% 23 -
>> Total System Loads - 107932 48564 - -4381 -1085
Central Cooling Coil - 108690 48564 - -13094 -1085
Central Heating Coil - -758 - - 8713 -
Humidification Load - - 0 - - 0
>> Total Conditioning - 107932 48564 - -4381 -1085
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1