Culture Documents
2
Vacuum circuit-breaker with magnetic drive
The magnetic actuator integrates the switching, closing and opening functions
All the functions (trip, switching, power loading and reliability check) are
operated from the integrated electronic controller
Equipped with multivoltage feeder in direct and alternating current
Note: circuit-breakers type eVM1 are also available with magnetic actuator and Switch-disconnector
protections and measurements on board Fitted with automatic trip mechanism for fuse intervention
Use of fuses according to DIN 43625 Standards for transformer
protection
Control from the front of the switchgear with manual operation
Vacuum contactors
Optimal solution for motor start-ups, changeover of power correction banks and
transformer users
Fitted with medium voltage fuses according to DIN and BS Standards (*)
Availability of operating mechanisms with electric or mechanical latching functions
Equipped with multivoltage feeder in direct and alternating current
(*) The contactor for UniGear type ZVC switchgear can only mount one or two fuses
per phase of the type according to BS Standards.
3
UniGear ZS1: an innovative solution for all installation requirements
4
Double level UniGear
switchgear. Each panel
consists of two independent
stacked units which can be
equipped with circuit-
breaker or contactor.
5
UniGear ZS1: switchgear with simple busbar system
Height
Branch connection rated current A 630 630 630 630
1250 1250 1250 1250
1600 1600 1600 1600
2000 2000 2000 2000
2500 2500 2500 2300
3150 3150 3150
Branch connection rated current A 3600 3600 3600 2500
with forced ventilation 4000 4000 4000
Width Depth
Unit width mm 550-650 550-650 550-650
800-1000 800-1000 800-1000 800-1000 A Apparatus D Instruments
1000 1000 1000 1000 B Main busbar E Gas exhaust duct
Unit height mm 2200 2200 2200 2325 C Feeder
Unit height with gas duct mm 2595 2595 2595 2720
Unit depth (1) mm 1340/1390 1340/1390 1340/1390 1700
(1) 1390 mm from 3150 to 4000 A
IF BT R RM M IFD IFDM
Incoming/Outgoing Bus-tie Bus-riser Bus-riser Measurements Direct incoming/ Direct incoming/
feeder with measurements Outgoing feeder Outgoing feeder
with measurements
Standard components Accessories Alternative solutions
6
UniGear ZS1: switchgear with fixed circuit-breaker
The new version of the UniGear ZS1 family product is Studied to offer
the fixed pattern with Vmax circuit-breaker. Very compact solution studied for solving space
It is a very safe and reliable panel with mechanical problems with reduction in the width of the
interlocks between the circuit-breaker, line discon- switchgear
nector and cable testing device. Directly connectable to any UniGear ZS1
This type of switchgear have the access to all the Three position line disconnector manually and motor
components directly from the front; all the maintenance operated
and service operation does not require rear access. Wall mounted application
Lower maintenance
Full access from the front
Height
Rated short-time withstand current kA 3s 31.5 31.5
Peak current kA 80 80
Internal arc withstand currentt kA 1s 31.5 31.5
Branch connection rated current A 630 630
1250 1250
1600 1600 Depth
2000 2000 Width
IF M BT R
Incoming/Outgoing Measurements Bus-tie Bus-riser
feeder
7
Double level UniGear ZS1 switchgear
Height
Peak current kA 125 125 100
Internal arc withstand current kA 1s 40 40 40
kA 0.5s 50 50 D e B1 D
Standard components
IF IF IF IF IF IF Accessories
Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Alternative solutions
8
UniGear ZS1: switchgear with double busbar system
The double busbar system switchgear is based on two flexibility during the inspection and maintenance
different schemes: procedures without interruption of the load
two busbar systems, two line-side isolators and a possibility of extension without turning the switchgear
circuit-breaker (up to 2500 A) off.
two busbar systems, two circuit-breaker units with one
The switchgear requires access from the rear for the
or two circuit-breakers.
installation and maintenance procedures. The service
The schemes offer redundancy of the busbar system
operations are carried out from the front.
with physical isolation between the systems. The use of
this switchgear may be necessary in the case of:
switching incoming units with unsynchronised circuit- Studied to offer
breakers Line with double isolation up to 2500 A
disconnection of loads with different levels of impor- 3150 A and 4000 A duplex line
tance under emergency conditions Segregated busbar and isolation compartments
isolation of particular outgoing units from the normal
Earthing switch with making capacity
network
Operations can be carried out from the front
balance of the outgoing units under normal service
Reliable and uninterrupted service conditions
conditions
Height
Internal arc withstand current kA 1s 31.5 31.5 25
Main busbar rated current A 1250...4000 1250...4000 1250...2500
Branch connection rated current A 630...3150 630...3150 630...2000
Branch connection rated current A 3600...4000 3600...4000
with forced ventilation
Unit width mm 650-800 650-800 800
1000 1000 1000 Depth
Unit height mm 2200 2200 2200 Width
Unit height with gas duct mm 2595 2595 2720 A Apparatus C Feeder
Unit depth (1) mm 2070/2120 2070/2120 2570 B1 Busbar 1 D Instruments
(1) 2120 mm from 3150 to 4000 A B2 Busbar 2 E Gas exhaust duct
9
UniGear ZS1: type ZVC switchgear for motor switching and control
Height
Unit height mm 2200/2595 2200/2595 A A
Unit height with gas duct mm 2675 2675
Unit depth mm 1125 1125
1 2 Depth
Width
A Apparatus D Instruments
B Main busbar E Gas exhaust duct
C Feeder
3 Off
Standard components
Accessories
Alternative solutions
10
11
We reserve the right to make changes in the course of technical development of the product.
1VCP000070 Rev. E, en Brochure 2007.09