You are on page 1of 12

UniGear ZS1

Medium voltage, arc proof, air insulated switchgear


for primary distribution
UniGear ZS1: an innovative solution for all installation requirements

ABB UniGear is medium voltage metal-clad, arc


proof, air insulated switchgear. Apparatus which can be installed
in UniGear switchgear
It is the result of ABB global know-how integrated
in a single technological solution and is ABBs
answer to the range of solutions requested on the
global market.
UniGear is Made in ABB in the 5 continents with
the same design and quality standards and offers
the best solutions for compact MCC, double level,
duplex and special unit switchgear.
It is primary distribution switchgear for all
applications. Thanks to the REF542plus multi-
function units, it offers the most intelligent
solutions for satisfying all installation
requirements.
The pre-assembled module construction system
allows each unit to be produced efficiently,
rapidly and with high quality. Modern calculation
Vacuum circuit-breaker
instruments make configuration and
Circuit-breaker for all fields of application
customisation of the switchgear simple and rapid. Vacuum interrupters with interruption system with axial
magnetic flow with even distribution of the arc over the
UniGear switchgear is safe because it is built as whole surface of the contacts to obtain the best
arc proof and is free of any operating errors performances at all the current values
Epoxy resin poles for greater protection of the
thanks to being fitted with safety interlocks.
interrupters
UniGear switchgear is tested in accordance with
the IEC Standards. Further tests are carried out
according to the prescriptions of Shipping
Registers and to particular installation
requirements.
Vacuum circuit-breakers and contactors, gas
insulated circuit-breakers and switch-
disconnectors can be installed in UniGear
switchgear.
The earthing switch, with full making capacity, is
operated from the front and is provided with safe
and reliable position indicators.
UniGear switchgear is certified Industrial IT, and
is therefore ready for integration in the powerful
open software architecture, based on Aspect
Object technology.
Conformity with the Industrial IT standard means
easy intelligent Unigear Plug & Produce
Gas circuit-breaker
integration in all software systems, with access to
Circuit-breaker for all fields of application
the right information in real time.
Suitable for plant retrofitting and revamping
UniGear has limited dimensions, especially in the Autopuffer breaking system to obtain the best
performances at all the current values
double level version.
Insulation withstand and breaking capacity voltage up to
All compartments are accessible from the front. 30% of the rated value with zero relative pressure

2
Vacuum circuit-breaker with magnetic drive
The magnetic actuator integrates the switching, closing and opening functions
All the functions (trip, switching, power loading and reliability check) are
operated from the integrated electronic controller
Equipped with multivoltage feeder in direct and alternating current

Note: circuit-breakers type eVM1 are also available with magnetic actuator and Switch-disconnector
protections and measurements on board Fitted with automatic trip mechanism for fuse intervention
Use of fuses according to DIN 43625 Standards for transformer
protection
Control from the front of the switchgear with manual operation

Contactor for UniGear type ZVC


switchgear up to 7.2 kV.

Contactor for UniGear type ZS1


switchgear up to 12 kV.

Vacuum contactors
Optimal solution for motor start-ups, changeover of power correction banks and
transformer users
Fitted with medium voltage fuses according to DIN and BS Standards (*)
Availability of operating mechanisms with electric or mechanical latching functions
Equipped with multivoltage feeder in direct and alternating current

(*) The contactor for UniGear type ZVC switchgear can only mount one or two fuses
per phase of the type according to BS Standards.

3
UniGear ZS1: an innovative solution for all installation requirements

Fixed circuit-breaker with


simple busbar system. Very
compact solution 500 mm
wide. It is equipped with fixed
vacuum circuit-breaker
removable in one hour.

UniGear switchgear with


simple busbar system coupled
to UniGear type ZVC contactor
units. Each type ZVC unit is
equipped with a withdrawable
vacuum contactor with fuses.

4
Double level UniGear
switchgear. Each panel
consists of two independent
stacked units which can be
equipped with circuit-
breaker or contactor.

UniGear switchgear with


simple busbar system.
Each panel consists of a
single unit which can be
equipped with circuit-
breaker, contactors or
switch-disconnector.

UniGear switchgear with


double busbar system.
The double busbar system
switchgear is based on two
different schemes.

5
UniGear ZS1: switchgear with simple busbar system

Each panel consists of a single unit which can be Studied to offer


equipped with circuit-breaker, contactors or switch- Flexible applications
disconnector, as well as with all the accessories Complete range of units and apparatus
available for the conventional units of the switchgear. Service continuity
Each panel is provided with a cubicle to take the Personnel safety
auxiliary instrumentation, placed in the upper part. Simple maintenance
The units can be coupled together directly with ZVC Effective use of space
units and with double-level units, with the possibility of Built-up modular solutions
extension on both ends of the switchgear. Full access from the front
The switchgear does not require access from the rear for
the installation and maintenance procedures.
All the service operations are carried out from the front.

Electrical characteristics Typical unit cross-section


Rated voltage kV 7.2 12 17.5 24
Rated insulation voltage kV 7.2 12 17.5 24
Rated power frequency withstand voltage kV 1min 20 28 38 50
Rated lightning impulse withstand voltage kV 60 75 95 125
Rated frequency Hz 50-60 50-60 50-60 50-60

Height with gas exhaust duct


Rated short time withstand current kA 3s 50 50 50 31.5
Peak current kA 125 125 125 80
Internal arc withstand current kA 1s 50 50 50 31.5
Main busbar rated current A 4000 4000 4000 3150

Height
Branch connection rated current A 630 630 630 630
1250 1250 1250 1250
1600 1600 1600 1600
2000 2000 2000 2000
2500 2500 2500 2300
3150 3150 3150
Branch connection rated current A 3600 3600 3600 2500
with forced ventilation 4000 4000 4000
Width Depth
Unit width mm 550-650 550-650 550-650
800-1000 800-1000 800-1000 800-1000 A Apparatus D Instruments
1000 1000 1000 1000 B Main busbar E Gas exhaust duct
Unit height mm 2200 2200 2200 2325 C Feeder
Unit height with gas duct mm 2595 2595 2595 2720
Unit depth (1) mm 1340/1390 1340/1390 1340/1390 1700
(1) 1390 mm from 3150 to 4000 A

Single-line diagram of the main typical units

IF BT R RM M IFD IFDM
Incoming/Outgoing Bus-tie Bus-riser Bus-riser Measurements Direct incoming/ Direct incoming/
feeder with measurements Outgoing feeder Outgoing feeder
with measurements
Standard components Accessories Alternative solutions

6
UniGear ZS1: switchgear with fixed circuit-breaker

The new version of the UniGear ZS1 family product is Studied to offer
the fixed pattern with Vmax circuit-breaker. Very compact solution studied for solving space
It is a very safe and reliable panel with mechanical problems with reduction in the width of the
interlocks between the circuit-breaker, line discon- switchgear
nector and cable testing device. Directly connectable to any UniGear ZS1
This type of switchgear have the access to all the Three position line disconnector manually and motor
components directly from the front; all the maintenance operated
and service operation does not require rear access. Wall mounted application
Lower maintenance
Full access from the front

Electrical characteristics Typical unit cross-section


Rated voltage kV 12 17.5
Rated insulation voltage kV 12 17.5
Rated power frequency withstand voltage kV 1min 28 38
Rated power frequency over the isolation distance kV 1min 32 45

Height with gas exhaust duct


Rated lightning impulse withstand voltage kV 75 95
Rated lightning impulse withstand voltage
over the isolation distance kV 85 110
Rated frequency Hz 50-60 50-60

Height
Rated short-time withstand current kA 3s 31.5 31.5
Peak current kA 80 80
Internal arc withstand currentt kA 1s 31.5 31.5
Branch connection rated current A 630 630
1250 1250
1600 1600 Depth
2000 2000 Width

Main busbar rated current A ...4000 ...4000


A Apparatus
B Main busbar
C Instruments
D Gas exhaust duct

Single-line diagram of the main typical units

IF M BT R
Incoming/Outgoing Measurements Bus-tie Bus-riser
feeder

Standard components Accessories Alternative solutions

7
Double level UniGear ZS1 switchgear

Each panel consists of two independent stacked units Studied to offer


which can be equipped with circuit-breaker or contactor.
Numerous alternative combinations of typical units, to
A compartment for the auxiliary instrumentation of both
adapt the switchgear suitably to the plant characteri-
the units is provided in the middle part. An additional
stics
cubicle is available in the top part of the panel to house
Efficient use of space for switchgear with numerous
other instruments.
users
The double level units can be coupled directly with
Great reduction in the width of the switchgear
single level units, on both ends of the switchgear.
(30...40% in typical configurations)
The switchgear requires access from the rear for the
The same service and maintenance procedures as
installation and maintenance procedures. The service
the single level switchgear
operations are carried out from the front.
Duplex version available.

Electrical characteristics Typical unit cross-section


Rated voltage kV 7.2 12 17.5
Rated insulation voltage kV 7.2 12 17.5 d d
B2 E
Rated power frequency withstand voltage kV 1min 20 28 38
Rated lightning impulse withstand voltage kV 60 75 95
Rated frequency Hz 50-60 50-60 50-60 A2
C2 A2
Rated short time withstand current kA 3s 50 50 40

Height
Peak current kA 125 125 100
Internal arc withstand current kA 1s 40 40 40
kA 0.5s 50 50 D e B1 D

Main busbar rated current A 1600 1600 1600


Branch connection rated current A 630 630 630
A1 C1 A1
1000 1000 1000
1250 1250 1250
1600 1600 1600
Unit width mm 750 750 750 Width Depth
900 900 900
Unit height mm 2698 2698 2698 A Apparatus D - d Instruments
Unit height with gas duct mm 2698 2698 2698 B Main busbar E Gas exhaust duct
Unit depth mm 1976 1976 1976 C Feeder

Single-line diagram of the main typical units


IF BT R RM J JM
Incoming/Outgoing Bus-tie Bus-riser Bus-riser with meas. Connection Connection with meas.
2 nd Level
1 st Level

Standard components
IF IF IF IF IF IF Accessories
Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Alternative solutions

8
UniGear ZS1: switchgear with double busbar system

The double busbar system switchgear is based on two flexibility during the inspection and maintenance
different schemes: procedures without interruption of the load
two busbar systems, two line-side isolators and a possibility of extension without turning the switchgear
circuit-breaker (up to 2500 A) off.
two busbar systems, two circuit-breaker units with one
The switchgear requires access from the rear for the
or two circuit-breakers.
installation and maintenance procedures. The service
The schemes offer redundancy of the busbar system
operations are carried out from the front.
with physical isolation between the systems. The use of
this switchgear may be necessary in the case of:
switching incoming units with unsynchronised circuit- Studied to offer
breakers Line with double isolation up to 2500 A
disconnection of loads with different levels of impor- 3150 A and 4000 A duplex line
tance under emergency conditions Segregated busbar and isolation compartments
isolation of particular outgoing units from the normal
Earthing switch with making capacity
network
Operations can be carried out from the front
balance of the outgoing units under normal service
Reliable and uninterrupted service conditions
conditions

Electrical characteristics Typical unit cross-section


Rated voltage kV 12 17.5 24
Rated insulation voltage kV 12 17.5 24
Rated power frequency withstand voltage kV 1min. 28 38 50

Height with gas exhaust duct


Rated lightning impulse withstand voltage kV 75 95 125
Rated frequency Hz 50-60 50-60 50-60
Rated short time withstand current kA 3s ...31,5 ...31,5 ...25
Peak current kA ...80 ...80 ...63

Height
Internal arc withstand current kA 1s 31.5 31.5 25
Main busbar rated current A 1250...4000 1250...4000 1250...2500
Branch connection rated current A 630...3150 630...3150 630...2000
Branch connection rated current A 3600...4000 3600...4000
with forced ventilation
Unit width mm 650-800 650-800 800
1000 1000 1000 Depth
Unit height mm 2200 2200 2200 Width

Unit height with gas duct mm 2595 2595 2720 A Apparatus C Feeder
Unit depth (1) mm 2070/2120 2070/2120 2570 B1 Busbar 1 D Instruments
(1) 2120 mm from 3150 to 4000 A B2 Busbar 2 E Gas exhaust duct

Single-line diagram of the main typical units

IF IF - IFM BTT M BTL RL


Incoming/Outgoing Busbar duplex (ex. A) Transverse Measurements Longitudinal Longitudinal
bus-tie Bus-tie bus riser

Standard components Accessories Alternative solutions

9
UniGear ZS1: type ZVC switchgear for motor switching and control

Each unit is equipped with a withdrawable vacuum Studied to offer


contactor with fuses.
Configurable for all types of motor starting
The use of medium voltage protection fuses strongly
Drastic reduction in the width of the switchgear and of
limits the let-through fault energy, making it possible to
the surface area occupied (the typical unit is 325 mm
reduce the cross-section of the connection cables to the
wide), also using more than one contactor for
motor. This characteristic contributes to safeguarding
complex motor start-ups
the insulation levels and increasing the electrical life of
The same service and maintenance procedures as
the cables and of the machine connected.
the UniGear type ZS1 switchgear
For users with high consumption levels, it is possible to
Full access from the front
fit the contactor with two fuses in parallel for each of the
Typical motor start-ups: direct, reversal of direction,
phases.
reactor, autotransformer, star delta
The units can be coupled directly with the main switch-
gear, with the possibility of extension on both ends.

Electrical characteristics Typical unit cross-section


Rated voltage kV 3.6 7.2
Rated insulation voltage kV 3.6 7.2
Rated power frequency withstand voltage kV 1min 16 20
E E
Rated lightning impulse withstand voltage kV 40 60
Rated frequency Hz 50-60 50-60
Rated short time withstand current kA (3s) 50 50
Peak current kA 125 125
Internal arc withstand current kA 1s 40 40

Height with gas exhaust duct


D B D
kA 0.5s 50 50
Main busbar rated current A 4000 4000
Branch connection rated current A 400 400
Unit width mm 325 325

Height
Unit height mm 2200/2595 2200/2595 A A
Unit height with gas duct mm 2675 2675
Unit depth mm 1125 1125

Single-line diagram of the main typical units


C C

1 2 Depth

Width

A Apparatus D Instruments
B Main busbar E Gas exhaust duct
C Feeder
3 Off

1 Contactor with electrical latching


2 Contactor with mechanical latching
3 Two pole transformer for supply of
operating circuits

Standard components
Accessories
Alternative solutions

10
11
We reserve the right to make changes in the course of technical development of the product.
1VCP000070 Rev. E, en Brochure 2007.09
The data and illustrations are not binding.

ABB Power Technologies S.p.A. ABB AG


Unit Operativa Sace Calor Emag Medium Voltage Products
Via Friuli, 4 Oberhausener Strasse 33 Petzower Strasse 8