You are on page 1of 10

524 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO.

2, APRIL 2010

Ampacity Calculations for Deeply Installed Cables


Eric Dorison, George J. Anders, Fellow, IEEE, and Frederic Lesur

AbstractIn this paper, a new method is proposed for ampacity In case of large tunnels, additional circuits may be installed
calculations of deeply installed cables. Two factors make these without a loss of existing rating capabilities by the intro-
types of installations different from more common situations of duction of forced air circulation.
cables located up to five meters underground. On the one hand,
the time constant of the soil layer above the cable trench is very An advantageous thermal environment is created, permit-
large, resulting in a very slow conductor temperature rise when ting improved heat dissipation.
the cable is first loaded, and, on the other hand, the weekly and The last bullet is of particular interest in the context of cable
yearly load-cycle variations can be taken into account to take the rating calculations and will be explored in this paper.
advantage of the greater laying depth. Both issues are explored An advantageous thermal environment for deeply buried ca-
in this paper. This paper introduces the concept of the equivalent
laying depth which makes it possible to use the rating rules appli-
bles is a result of several factors. On the one hand, the soil tends
cable to the steady-state conditions and avoid transient analysis. to have higher moisture content at large depth due to the pene-
tration of ground waters. On the other hand, daily, weekly, and
Index TermsAmpacities, cable rating, direct drilling, load cy- even yearly load variations have a profound effect on the ratings
cling, power cables. of deeply buried cables. This effect is not so pronounced for ca-
bles buried at the usual depths. In addition, the large amount of
soil above the cable trench results in the very large time constant
I. INTRODUCTION of the thermal circuit and a slow heating of cable conductor.
These facts, even though well recognized by the cable ex-
perts, have not been harnessed in practical mathematical for-
NSTALLATION of new cable lines in large metropolitan mulae that could be included in the cable rating standards. Even
I areas in industrialized countries becomes more and more
difficult. Obtaining necessary permissions is only one of the
though there are several publications dealing with ratings of
cables in tunnels, a literature search conducted by the authors
problems. From a technical point of view, most of the avail- revealed that only one article has recently been published ad-
able right-of-ways are already occupied either by other power dressing the advantages of the deeply buried tunnels. The paper
or communication circuits or by other infrastructures such as by Matsumura et al., [14] suggests the use of transient calcula-
heating, sewage, and water pipes or underground transportation tions to account for the very large thermal capacitance of the soil
corridors. surrounding deep tunnels. This approach has been used success-
Therefore, burying cables at great depths is more and more fully in the past by specialists in the field but it is cumbersome
frequent and, in spite of fairly high costs, laying of cables in and requires significant skills and knowledge.
deep tunnels become attractive; for instance, such tunnels were The aim of this paper is to introduce a new simple method of
recently built in Toronto, Berlin or London, and several projects cable ampacity calculations specifically taking advantage of the
are under consideration in major European and North American special heating regime of deeply buried cables, which could be
cities. The most important are as follows. incorporated into the next revision of the IEC standard dedicated
The civil engineering work does not have to distract pedes- to the calculation of the continuous current rating of cables [1].
trian or vehicular traffic. The paper brings forward the definition of an equivalent depth,
The length of the cable route can be minimized. which allows using the rating rules applicable to the steady-state
Cables can be laid independently of the structure of the conditions, thus avoiding transient analysis. As the equivalent
buildings above the right-of-way. depth depends upon a limited number of parameters, charts may
Access to the circuits is facilitated if they are laid in large be developed to determine the value to be taken into account in
tunnels. an actual case.
The influence of electromagnetic fields at the earth surface We will start by presenting mathematical formulae which take
is considerably diminished in comparison with the stan- advantage of the high thermal constant of such installations as
dard installations. well as daily, weekly, and yearly load variations, and conclude
by considering several practical examples.

II. TEMPERATURE CHANGES FOR DEEPLY BURIED CABLES


Manuscript received May 12, 2009. First published March 08, 2010; current
version published March 24, 2010. Paper no. TPWRD-00220-2008. The time constants for deeply buried cables are very large.
E. Dorison is with Electricit de France, Moret sur Loing 77818, France
(e-mail: eric.dorison@edf.fr).
This can be illustrated using standard computational procedures
G. J. Anders is with the Technical University of Lodz, Lodz 90-924, Poland for the steady state [1] and transient ratings [2], [3]. Table I
(e-mail: george.anders@attglobal.net). summarizes the results of such analysis for a typical XLPE cable
F. Lesur is with RTE, the French TSO, Paris 92000, France (e-mail: frederic.
lesur@rte-france.com). circuit laid 10, 20, and 40 m deep with a step current applied at
Digital Object Identifier 10.1109/TPWRD.2009.2033961 .

0885-8977/$26.00 2010 IEEE


DORISON et al.: AMPACITY CALCULATIONS FOR DEEPLY INSTALLED CABLES 525

TABLE I where:
EXAMPLE OF AMPACITIES AND TEMPERATURES OF DEEPLY BURIED CABLES
a.c. resistance of the conductor (ohm/m);
internal thermal resistance of the cable (K m/W);
internal thermal resistance for dielectric losses
(K m/W);
sheath and armor loss factors;
attainment factor for the outer cable surface;
external thermal resistance (K m/W);
dielectric losses (W/m).
and are functions of the cable diameter (m) and
the laying depth (m), and are defined by

(2)

(3)

where

soil thermal resistivity (K m/W);


Fig. 1. Temperature profile for cables buried at various depth with an applica- exponential integral;
tion of a step function at t = 0.
soil thermal diffusivity (m /s).
For large , the first exponential integral in (3) can be approx-
As can be seen, after 40 years, the cable conductor has not imated by [4]
reached its maximum allowable temperature of 90 C when the
cable is buried at the depth greater than 20 m. This point is (4)
illustrated further in Fig. 1 by the temperature profiles of the
same installations over a period of time. Combining (2)(4), we have
The temperature is computed with a standard equation for the
external thermal resistance using an exponential integral [3].
In Fig. 1 the temperature rises quickly at first but then the
growth is very slow.
(5)
Analysis of these results suggests that applying the standard
steady-state calculation algorithm would yield ampacities that
are too small. A more appropriate approach would be to use the Let be the external thermal resistance for the same cable,
transient analysis algorithm and iteratively find out what value but with the depth smaller than . Let be the maximum
of the current would give the desired temperature at the end of permissible current for a continuous load, corresponding to the
the study period. This suggests that one can define an equivalent maximum conductor temperature rise above ambient .
depth of the cable circuit that with the application of the steady- This temperature rise is obtained from the standard equation
state algorithm would give the same value of current as obtained
(6)
from the transient analysis. This approach is presented in the
next section. If after time , the steady-state allowable temperature is
reached
III. EQUIVALENT DEPTH OF DEEPLY BURIED CABLES
(7)
A. A Single Cable
Let be the conductor temperature rise at time due to Substituting (1) and (6) into (7), results in the following
a current step , [3]: equation:

(8)
(1)
526 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 2, APRIL 2010

Fig. 3. Relationship between the actual depth and an equivalent depth as a func-
=
tion of the soil thermal diffusivity for t 40 years.

Fig. 2. Relationship between actual depth L and an equivalent depth L as a B. Multiple Cables
function of the study period.
xIn this section we will examine an implication of the fact
The equivalent depth is obtained assuming , which that for deeply buried cables the presence of the adjacent cables
leads to may have a more profound effect on the rated cable than might
(9) be the case for cables buried at a normal depth.
Considering a group of equally loaded cables (each with the
Substituting (5) for the left-hand side in (9) and using (2) for joule losses ), the external thermal resistance of the hottest
with replacing , we finally obtain cable may be expressed as

(11)

(10)
The equivalent depth is a function of the time and the soil where is the spacing between cables and and is the
thermal diffusivity . Fig. 2 illustrates the relation between the spacing between cable and the image of cable .
equivalent and actual depth for a typical value of soil thermal The transient temperature rise of the outer surface is
diffusivity of m /s. shown in (12) at the bottom of the page.
Fig. 2 indicates that the longer the study period the higher an Since for deeply buried cables, we can assume for every cable
equivalent depth will be. However, in all cases, the equivalent
depth is much lower than the actual depth if the cable is laid at
(13)
large depth.
The equivalent depth is a function of the soil diffusivity as we have
well. Fig. 3 shows this dependence for a typical value of the
time horizon, 40 years.
We can observe that the value of soil thermal diffusivity plays (14)
an important role in the definition of the equivalent depth. The
equivalent depth more than doubles when we move for a soil and using an approximation of the exponential integral as in (4)
with diffusivity of m /s to the value that is four times with the assumption of low values of , shown in (15) at
higher. the bottom of the page.

(12)

(15)
DORISON et al.: AMPACITY CALCULATIONS FOR DEEPLY INSTALLED CABLES 527

This gives the same equivalent depth as in the case of a single


cable.

IV. CASE OF DEEP TUNNELS


Calculation of temperatures of cable tunnels, ventilated or
not, may be complex because of the combination of heat trans-
fers, (conduction, convection and radiation) between cables and
tunnel wall, as well as longitudinal circulation of air [5]. We only
focus here on the conductive heat transfer between the outer side
of the tunnel wall and the ground surface.
The case of deep tunnels involves special considerations as
follows.
Depth value can easily reach hundreds of meters (tunnel
between two valleys in a mountainous area).
Fig. 4. Comparison of accurate and approximate formulae of equivalent depth.
The initial temperature of rocky soils at the core of moun- Tunnel diameter 8 m, depth 30 m. Soil diffusivity 0.5E-6 m /s.
tains can reach unexpected temperature values (more than
50 C).
The heating source can be the combination of cable losses, Finally, the equivalent depth of the tunnel is found from (17)
other circulating fluids thermal effects (in multipurpose
structures), but also water-cooling and forced ventilation
(20)
with cold air renewal.
The installation of cables in shared tunnels (e.g., railway tun-
nels) can lead to large diameters, because some tunnel-boring A question arises of when to use (10) and when to use the
machines are capable of excavating a diameter greater than eight more complex equations (18)(20). Fig. 4 shows that the ap-
meters. Therefore, some of our assumptions in Chapter III re- proximation given by (10) is very good, even for deep tunnels.
garding the depth and the diameter may no longer be valid and a However, the approximation would not work for low values of
more accurate, although somewhat more complex, solution may the duration of the transient, because the equivalent depth would
be required as shown below. be smaller than the radius of the tunnel.
We introduce new parameters We observe that the approximate value of is lower than
the accurate one, which means that the value of the thermal re-
sistance of the external environment is not on the safe side
when this approximation is used. However, investigations by the
authors have shown that the error decreases rapidly with a de-
crease of the tunnel diameter and an increase of the depth of
The exact formula for the external thermal resistance of the laying.
round tunnel is given by

(16) V. DAILY, WEEKLY, AND YEARLY LOAD VARIATIONS


When the cable circuit is located at large depths, for example,
where
in a deeply buried tunnel, the heating time constant is very large,
and in addition to daily load variations, the load changes over
(17) a week or a year could be considered. Representation of daily,
weekly, and yearly load cycles is discussed next.
When the value of exceeds 10, a good approximation (with
the error smaller than 0.1%) is given by (2). However, as men- A. Daily Load Variations
tioned before, for large tunnels, (16) should be used.
Using (16) in (9), we obtain Neher and McGrath [6] proposed a simple method to account
for the cyclic loading of a cable. Their approach requires a mod-
ification of the external thermal resistance of the cable. The un-
derlying principles are discussed below.
(18) In order to evaluate the effect of a cyclic load upon the max-
imum temperature rise of a cable system, Neher [7] observed
Denoting by the calculated value of the right-hand-side of that one can look upon a heating effect of a cyclical load as a
(18), the solution is given by wave front that progresses alternately outwardly and inwardly
in respect to the conductor during the cycle. He further assumed
that, with the total joule losses generated in the cable equal to
(19) (W/m), the heat flow during the loss cycle is represented by
528 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 2, APRIL 2010

a steady component of magnitude plus a transient compo- cycle lasting 24 h and with a representative soil diffusivity of
nent , which operates for a period of time during m /s is 212 mm (or 8.3 in.).
each cycle. The transient component of the heat flow will pen- Expressions equivalent to (23) can be developed based on
etrate the earth only to a limited distance from the cable, thus methodology applied in the IEC standards (Appendix A) or
the corresponding thermal resistance will be smaller than through solving heat-transfer equations (Appendix B). The re-
its counterpart which pertains to steady-state conditions. sulting characteristic diameter is given by
Assuming that the temperature rise over the internal thermal
cable resistance is complete by the end of the transient period (25)
, the maximum temperature rise at the conductor may be ex-
pressed as with ranging from 0.97 to 1.37 for cable diameters of up to
100 mm. Hence, the IEC and NeherMcGrath approach can be
(21) considered to be equivalent in this case. For larger diameters
(ducts and tunnels), the value of increases with the heating
where is the apparent internal thermal resistance of the cable, source diameter and is given by (see Appendix B)
defined as
(26)

Alternative expressions for (in millimeters) are given by


where is the external thermal resistance with constant load, Heinhold [8]
is the effective transient thermal resistance in the earth, and
is the temperature rise due to dielectric losses (we will omit (27)
them from now on).
Further, Neher [7] assumed that the last thermal resistance in (28)
(21) may be represented with sufficient accuracy by an expres-
sion of the general form (29)

(22) where is the length of the period and


day.
in which constants and were evaluated empirically to best Heinhold assumes the following relationship:
fit the temperature rises calculated over a range of cable sizes.
Using measured data, Neher obtained the following values for
the constants: and when is expressed
in hours and is expressed in m /s. Thus, when we take the recommended value of the soil
Introducing the notation thermal diffusivity of m/s (the corresponding value
of the thermal resistivity equal to 1 K m/W), (27) is equivalent
(23) to the Nehers expression.
The choice of the method to compute the fictitious diameter
with expressed in meters, the external thermal resistance in depends partially on the analysts preferences and partially on
(21) can be written as the available information. If the daily load cycle variations are
known, the IEC 60853 [2], [3] approach can be used. On the
other hand, when a sinusoidal load shape can be assumed, ei-
ther (23) or (25) or (27) can be applied. In other cases, IEC ap-
proach for load cycles where the shape is unknown and only the
loss-load factor is known or (28) or (29) should be used, re-
(24)
membering that these are approximate equations.
The following numerical example shows the results for all the
where is the loss factor.
formulae for sinusoidal load variations.
The right-hand-side of (24) can be interpreted as follows.
Consider three, single-core, 1000 mm Cu XLPE 123 kV
Inside the circle of diameter , the temperature changes ac-
cables with a PE jacket. Cables are in flat formation 1m un-
cording to the peak value of the losses. Outside this circle, it
derground spaced 0.2 m apart. Additional parameters are as
changes with the average losses.
follows:
From (23), we observe that the fictitious diameter at
Soil thermal characteristics: ambient : 10 C-resistivity 1.0
which the effect of loss factor commences is a function of the
K m/Wdiffusivity m /s (for the Heinhold formula
diffusivity of the medium and the length of the loss cycle.
the value of 4.67 is used instead).
In the majority of cases, the soil diffusivity will not be known.
For IEC calculations, the sinusoidal load curve is simulated
In these cases, a value of m /s can be used. This
by 24 steps as follows:
value is based on a soil thermal resistivity of 1.0 K m/W and a
moisture content of about 7% of dry weight [see Section 5.4 of
with
[4] for more details on this subject]. The value of for a load
DORISON et al.: AMPACITY CALCULATIONS FOR DEEPLY INSTALLED CABLES 529

TABLE II
CABLE DIMENSIONS

TABLE III
RESULTS ARE SUMMARIZED

The right-hand column steps in Table III is the result of 1-h


steps superposition until convergence is reached.
Hence, we can see that the approaches are really equivalent.
Equations (27) to (29) are independent of the cable diameter.
Investigations by Brakelmann [13] have shown that these equa-
tions are valid for cables with diameters between 5 and 150 mm.
For larger ducts and tunnels, the expressions developed in Ap-
pendix B or discussed in the next section should be used.

B. Weekly and Yearly Load Variations


In the majority of practical cases, the load variations will
exhibit a more complex pattern than the one described by a
daily load cycle. For example, loading of cables is usually
much lighter during the weekend than during the weekdays.
For deeply buried cables, the yearly load variations will play a Fig. 5. Characteristic diameter for cables in tunnel: the rows correspond to
significant role because of the very long time constants at great
daily, weekly and yearly load cycles, respectively, and the columns to  =
0:4; 1:0 and 2.5 K1m/W, respectively. D is the tunnel diameter.
depths.
For cables in deep tunnels, the characteristic diameter can
be obtained from the curves in Fig. 5 [9], [10]. Brakelmann
VI. AMBIENT TEMPERATURE VARIATIONS
used Fourier analysis to obtain those curves for tunnel diam-
eters ranging from 2 m (the upper boundary of the region) to A sinusoidal variation of the air ambient temperature leads to
5 m (lower boundary) for two shapes of the load cycle: sinu- a sinusoidal variation of the temperature in the ground, with a
soidal (region bounded by straight lines) and rectilinear (region damping factor and a time delay, which both depend upon the
bounded by curved lines). soil diffusivity and the period.
The external thermal resistance of the cable or tunnel located The temperature at depth as a function of the time can be
at large depth can be obtained from the following expression expressed as [12]
[8][11]:

(31)

where

(30)
maximum ambient temperature, C;
where subscripts and correspond to daily, weekly and duration of the cycle period (in seconds s);
yearly load variations and represent the ex- soil diffusivity, m /s.
ternal thermal resistances of the tunnel, daily, weekly, and yearly
fictitious diameters, respectively. The characteristic diameters Fig. 6 illustrates (31) for day, C, and soil
are given by (25)(29) or (42) with the appropriate length of the diffusivity m /s. It can be seen that for deeply buried
period. cables, the surrounding soil temperature is nearly constant.
530 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 2, APRIL 2010

A. Standard Computations
The external thermal resistance of the tunnel is computed
from the following expression [8]:

where
height and width of the
tunnel, depth of soil above the tunnel plus the thickness of
Fig. 6. Soil temperature daily variations for different depths. the tunnel wall (it is assumed that the tunnel wall has the same
thermal resistivity as the soil).
This gives K m/W and the ampacity of 258 A.

B. Equivalent Depth Scenario


Let us assume that the time horizon of interest is 40 years
and soil thermal diffusivity equals to m /s. For the
cable system considered here, the equivalent depth of the tunnel
can be obtained by applying the approximation given by (10),
yielding the equation shown at the bottom of the page.
The external thermal resistance of the tunnel is equal to 0.607
K m/W, and the resulting ampacity is 267A.

C. Daily, Weekly, and Yearly Load Variations


We will assume the following average loss factors for daily,
weekly, and yearly load variations:
Fig. 7. Installation of cables in tunnel.

Assuming rectilinear load shapes, the following characteristic


VII. EFFECT ON CABLE AMPACITY diameters correspond to these values (see Fig. 5):

The various approaches described in the previous chapters


will be used to illustrate the effect of the depth of the cable
on its rating. We will compute the ratings of six circuits, each The external thermal resistances between characteristic diam-
in trefoil formation located in a horizontal tunnel as shown in eters and the earth surface are equal, respectively to
Fig. 7. The 15-kV XLPE cables with concentric neutral wires
bonded at both ends have the following parameters:

Considering now daily, weekly, and yearly load cycles, from


(30), we have

The tunnel has a square cross section with a height of 2.0


m with 0.5 m concrete walls and 18 m of soil above the roof.
The thermal resistivity of the soil is 1.0 K m/W and the ambient
temperature is 15 C.
DORISON et al.: AMPACITY CALCULATIONS FOR DEEPLY INSTALLED CABLES 531

where

measure of the equivalent square current


between and h prior to the expected
time of maximum conductor temperature;
iratio of the core temperature at time hours
to the core temperature at steady state and is
equal to [4]

for
(33)
and
(34)

with the subscripts and corresponding


to the core and the external cable surface,
respectively. are the conductor losses
Fig. 8. Relationship between fictitious and cable diameters. and represents the total joule losses of
the cable;
and cable attainment factors. For the long
The cable rating corresponding to this value of the external durations considered here, we can assume
thermal resistance of the tunnel is equal to 313 A, a 21% increase and is computed from (3).
compared with the standard calculations. Remembering that and , (32) can be
approximated by

VIII. CONCLUSION
The effect of laying cables at great depth has a profound influ-
ence on its rating. The influence depends to a large extent on the
ratio of the depth of laying to the cable/duct/tunnel diameter and (35)
on the time horizon being considered. This paper presents sev-
eral new developments on ampacity calculations of such cables. Introducing a notation and substituting (33)
Fictitious diameters computed according to Heinholds or into (35), we obtain
Brakelmanns formulae for nonsinusoidal shapes are slightly
higher than diameters resulting from the IEC formula. recom-
mended for unknown load shape. (36)
The numerical examples presented in the paper show that the
effect can be particularly significant if cyclic load variations Because , (36) has the same form as (21) with
over the week and the year are considered. (6) representing and thus can be approximated by

(37)

Using approximation with an exponential integral (valid for


APPENDIX A an infinite thin wire), may also be written as
CHARACTERISTIC DIAMETERIEC STANDARD
Following the IEC approach and taking the six-hour-load (38)
variation before the maximum conductor temperature is ob-
tained, the maximum cable temperature may be written as (see Comparing the right-hand-sides of (37) and (38), we obtain
(5.25) in [4]): (25). More generally, for a cycle of length hours

(39)
(32)
which leads to (25) with .
532 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 2, APRIL 2010

TABLE IV
VALUE OF K

The maximum cable/tunnel surface temperature can be


written as

(41)
Fig. 9. Relationship between fictitious and tunnel diameters for three values of
soil diffusivity.
Figs. 8 and 9 show the relationships between fictitious diam-
eter and the cable/tunnel diameters. The relationships are almost
linear with the fitting equations shown in the graphs. The fol-
APPENDIX B
lowing relationship can be applied to all curves:
CHARACTERISTIC DIAMETER FOR SINUSOIDAL
LOAD AND LARGE TUNNEL DIAMETER
(42)
The approximations considered above assumed that a cable is
represented by an infinitely small wire. In the developments pre- This leads to an error less than 3% for up to 3 m, for
sented below, this assumption is dropped and, as a consequence, every type of variations, with soil diffusivity ranging from
the cable diameter influences the diameter of the area affected to m /s. Equation (42) is the most general expression
by load variations. This is particularly important for cables in for fictitious diameter, covering virtually all practical cases.
tunnels, where the tunnel diameter replaces the diameter of the For tunnels with large diameters, daily and weekly variations
cable. lead to characteristic diameters close to the tunnel diameter.
For a sinusoidal load (with magnitude and period ), the For cables directly buried, can be approximated with
temperature around the cable/tunnel may be expressed, with the
complex notation, as
(43)
(40) The is given in Table IV and is not far from the value of 1.02
given by Neher.
with
REFERENCES
[1] Calculation of the Continuous Current Rating of Cables (100% Load
Factor), IEC Std. 60287 (1969, 1982, 1994), 1st ed. 1969, 2nd ed. 1982,
3rd ed. 19941995.
where [2] Calculation of the Cyclic and Emergency Current Ratings of Cables.
Part 1: Cyclic Rating Factor for Cables up to and Including 18/30 (36)
kV, IEC Std., (1985), Publ. 853-1.
[3] Calculation of the Cyclic and Emergency Current Ratings of Cables.
cable/tunnel radius; Part 2: Cyclic Rating Factor of Cables Greater Than 18/30 (36) kV and
is the soil thermal resistivity, is the soil Emergency Ratings for Cables of All Voltages, IEC Std., (1989), Publ.
853-2.
diffusivity; [4] G. J. Anders, Rating of Electric Power Cables. Ampacity Computations
for Transmission, Distributions and Industrial Applications, ser. IEEE
and are modified Bessel functions. Press Power Eng. Ser. New York: IEEE Press, , 1997.
DORISON et al.: AMPACITY CALCULATIONS FOR DEEPLY INSTALLED CABLES 533

[5] Calculation of Temperatures in Ventilated Cable Tunnels CIGR WG George J. Anders (M74SM84F99) received
Rep. 21.08, Aug. 1992, Electra No. 143. the M.Sc. degree in electrical engineering from
[6] J. H. Neher and M. H. McGrath, The calculation of the temperature the Technical University of Lodz, Lodz, Poland,
rise and load capability of cable systems, AIEE Trans., vol. 76, pt. 3, in 1973, and the M.Sc. degree in mathematics and
pp. 752772, Oct. 1957. Ph.D. degree in power system reliability from the
[7] J. H. Neher, Procedures for calculating the temperature rise of pipe University of Toronto, Toronto, ON, Canada, in 1977
cable and buried cables for sinusoidal and rectangular loss cycles, and 1980, respectively.
AIEE Trans., vol. 72, pt. III, pp. 541545, Jun. 1953. Since 1975, he has been with Ontario Hydro as a
[8] L. Heinhold, Power Cables and Their Application. Part 1, 3rd ed. System Design Engineer in the Transmission System
Berlin, Germany: Siemens Aktiengesellschaft, 1990. Design Department of the System Planning Division
[9] H. Brakelmann, Kabelbelastbarkeit bei Bercksichtigung von Tages and as a Principal Engineer in Kinectrics, Inc., (a suc-
und Wochenlastzyklen, Elektrizitstwirtschaft, pp. 368372, 1995a, cessor company to Ontario Hydro Technologies).
Jg. 94, Heft 7. Dr. Anders is the author of two books on power cables Rating of Electric
[10] H. Brakelmann, Kabelbelastbarkeit im Unbelfteten Tunnel, Elek- Power Cables, (IEEE Press, 1997 and McGraw-Hill, 1998) and Rating of Elec-
trizitstwirtschaft, pp. 368372, 1995b, Jg. 94, Heft 26. tric Power Cables in Unfavorable Thermal Environment (IEEE Press/Wiley,
[11] G. J. Anders, Rating of Electric Power Cables in Unfavourable 2005). He is a registered Professional Engineer in the Province of Ontario.
Thermal Environment, ser. IEEE Press Power Eng. Ser. New York:
Wiley, 2005.
[12] H. S. Carslaw and J. C. Jaeger, Conduction of Heat in Solids, 2nd ed.
Oxford, U.K.: Oxford. Frederic Lesur was a Research Engineer with Silec
[13] H. Brakelmann, Balastbarkeiten der EnergiekabelBerechnungsme- and was involved in the development of 400 kV un-
toden und Parameteranalysen. Berlin/Offenburg: VDE-Verlag, derground lines in modeling and engineering tools
1989. design. He moved to EDF utility in 1999, and was re-
[14] M. Matsumura, K. Fukuda, E. Fujiwara, T. Shiro, M. Watanabe, Y. sponsible for the cable system testing facility of Les
Sakaguchi, and T. Ooimo, Transmission capacity design of under- Renardires. He has been working in he engineering
ground power cables installed in deep tunnel, presented at the Power branch of RTE, the French Transmission System Op-
Eng. Soc. General Meeting, Jun. 1822, 2006. erator, since 2007.
Mr. Lesur is the Secretary of the technical com-
Eric Dorison is Design Engineer in the field of un- mittee of Jicable conference and is involved in var-
derground cables, within the Research and Develop- ious CIGR activities.
ment Department Electricit de France, where he has
been since 1978.
For several years, he has been Project Manager for
technoeconomical optimization of bulk power trans-
mission underground lines, using VHV synthetic ca-
bles. He is currently involved in cable thermal rating
matters and development of a health index dedicated
to underground links as an asset management tool.
Mr. Dorison is a member of several IEC and
CIGRE working groups.

You might also like