You are on page 1of 33

Revision Instructions SF6Gas Insulated

Switchgear ELK3

FastActing Earthing Switch ELKEB3

1HC0037777 E01 / AC05


Revision Instructions SF6Gas Insulated Switchgear ELK3

Content

Content

1 Important Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Supplier and manufacturer address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Contact address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Validity of this revision instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Purpose of this revision instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5 Safety note . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.6 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2 Component description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3 Revision/Repair of the FastActing Earthing Switch ELKEB3 . . . . . 7


3.1 Safety hints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Revision work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.3 Checklist for trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 General information concerning revision . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4.1 Tools, Apparatus and Replacement Materials . . . . . . . . . . 9
3.4.2 Tools for the revision of FastActing Earthing Switch
ELKEB3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4.3 Apparatus for the Revision of FastActing Earthing
Switch ELKEB3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4.4 Replacement Parts for FastActing Earthing Switch
ELKEB3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4.5 Loctite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.5 Preparation of the Revision Tools and Materials . . . . . . . . . . . . . . . . . . . . 11
3.6 Taking the FastActing Earthing Switch ELKEB3 out of Service . . . . . . 11

4 Changing Parts of the FastActing Earthing Switch ELKEB3 . . . . . . 12


4.1 Removing of FastActing Earthing Switch ELKEB3 . . . . . . . . . . . . . . . . . 12
4.2 Removing of Fixed Contact of FastActing Earthing Switch ELKEB3 . . 13
4.3 Dismounting of Moving Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.4 Mounting of new Moving Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.5 Changing of Auxiliary Switch and Heating Element . . . . . . . . . . . . . . . . . 23
4.5.1 Dismounting of Auxiliary Switch . . . . . . . . . . . . . . . . . . . . . . 23
4.5.2 Remounting of new Auxiliary Switch . . . . . . . . . . . . . . . . . . 25
4.5.3 Dismounting of Heating Element . . . . . . . . . . . . . . . . . . . . . 29
4.5.4 Remounting of Heating Element . . . . . . . . . . . . . . . . . . . . . 30
4.6 Mounting of Fixed Contact of FastActing Earthing Switch ELKEB3 . . 31
4.7 Remount the FastActing Earthing Switch ELKEB3 . . . . . . . . . . . . . . . . 32

Template: Inhalt 2
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

List of Figures

List of Figures

Fig.1: Fastacting earthing switch ELKEB3 principle . . . . . . . . . . . . . . . . . . . . . 6


Fig.2: Tools for the revision of a fastacting earthing switch ELKEB3 . . . . . . . 9
Fig.3: Handcrank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Fig.4: Replacement parts for fastacting earthing switch ELKEB3 . . . . . . . . . . 10
Fig.5: Remove fastacting earthing switch ELKEB3 . . . . . . . . . . . . . . . . . . . . . . 12
Fig.6: Remove fixed contact of fastacting earthing switch ELKEB3 . . . . . . . . 13
Fig.7: Dismounted fastacting earthing switch ELKEB3 . . . . . . . . . . . . . . . . . . 14
Fig.8: Draw out screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fig.9: Loosen of guide segment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fig.10: Disassemble contact bush with tubular contact . . . . . . . . . . . . . . . . . . . . 16
Fig.11: Disassemble tubular contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fig.12: Remove tubular contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fig.13: Clean and grease sliding piece and guide segment . . . . . . . . . . . . . . . . 18
Fig.14: Regreasing (example) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Fig.15: Inserting moving contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Fig.16: Lift up reversing lever . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Fig.17: Connect tubular contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fig.18: Place guide segment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fig.19: Assemble contact bush and tubular contact . . . . . . . . . . . . . . . . . . . . . . . 21
Fig.20: Move contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fig.21: Fasten screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fig.22: Mount screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Fig.23: Fix screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Fig.24: Unscrew cover and connection plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Fig.25: Remove fixings and connections to auxiliary switch . . . . . . . . . . . . . . . . 23
Fig.26: Remove auxiliary switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fig.27: Remove all cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fig.28: Connect cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fig.29: Control moving contact closed position C" . . . . . . . . . . . . . . . . . . . . . . . 25
Fig.30: Correct switch position of auxiliary switch . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fig.31: Insert distance ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fig.32: Insert auxiliary switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Fig.33: Fix auxiliary switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Fig.34: Screw on cover and connection plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Fig.35: Disconnect cables of heating element . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Fig.36: Remove heating element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Fig.37: Mount heating element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fig.38: Connect cables of heating element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fig.39: Mount fixed contact of fastacting earthing switch ELKEB3 . . . . . . . . . 31
Fig.40: Fasten cover in case of noninstalled fastacting earthing switch
ELKEB3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Fig.41: Mount fastacting earthing switch ELKEB3 . . . . . . . . . . . . . . . . . . . . . . . . 32

Template: Figur 3
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

List of Tables

List of Tables

Tab.1: Overview of revisions in progress . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7


Tab.2: Checklist for trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Template: Tabelle 4
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Copyright and Address

1 Important Notes

1.1 Supplier and manufacturer address


ABB Switzerland Ltd
High Voltage Products
Brown Boveri Strasse 5
8050 Zurich / Switzerland

1.2 Contact address


ABB Switzerland Ltd
Service High Voltage Products
Brown Boveri Strasse 5
8050 Zurich / Switzerland
Telephone (24 hours): +41 (0)844 845 845
Fax: +41 (0)58 588 1723
EMail: retrofit.support@ch.abb.com
Internet: www.abb.ch

1.3 Validity of this revision instructions


This revision instructions are valid only in combination with the Operating Instructions
SF6Gas Insulated Switchgear ELK3.

1.4 Purpose of this revision instructions


This revision instructions describes the maintenance and revision of the fastacting
earthing switch ELKEB3.

1.5 Safety note


Activities described under Revision" must only be carried out when the notes in the
Operating Instructions SF6Gas Insulated Switchgear ELK3" have been both read and
understood and the preconditions described there fulfilled. Otherwise, the manufac
turer shall not be liable for damage of any kind as a result of improper handling.

1.6 Copyright
We reserve all rights concerning this document and the components described therein.
It must not be reproduced or disclosed to third parties and the contents must not be
made use of neither in part nor in whole without our prior written permission.
E ABB Switzerland Ltd, Division High Voltage Products

Template: CR 5
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Componentdescription

2 Component description

In Fig.1 the individual elements of the fastacting earthing switch ELKEB3 are shown.
Detailed information regarding the installation, the function and the technical data of
the fastacting earthing switch ELKEB3 are to be found in the documents Operating
Instructions SF6Gas Insulated Switchgear ELK3" and Project Specific Data".

4
3
7

5
6

1 Earthed enclosure ELKDB3


2 SF6gas 5 Moving contact
3 Fastacting earthing switch 6 Earthing fixed contact
ELKEB3 7 Insulator
4 Operating mechanism 8 Earth connection

Fig.1: Fastacting earthing switch ELKEB3 principle

Template: Description_EB3 6
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Revision/Repair of the FastActing Earthing Switch ELKEB3

3 Revision/Repair of the FastActing Earthing Switch


ELKEB3

3.1 Safety hints


You are only allowed to execute the operations listed under "Revision" if you have
Warning read the notices (especially the safety hints) contained in the beginning sections
of the document Operating Instructions SF6Gas Insulated Switchgear ELK3"
and you pass the stated requirements. Otherwise, the manufacturer will reject any
liabilities for damages which result from improper operations.

Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the
Operating Instructions SF6Gas Insulated Switchgear ELK3", chapter Working on
gas compartments and partition insulators" and the document 1HC0028459 Manual
Handling Sulphur Hexafluoride SF6" have to be executed.
Before reassembling the affected components, the regulations in the Operating In
structions SF6Gas Insulated Switchgear ELK3", chapter Working on gas compart
ments and partition insulators" and the document 1HC0028459 Manual Handling Sul
phur Hexafluoride SF6" have to be followed. With improper treatment, reliable operation
of the installation is not assured.

3.2 Revision work

Activity Description reference

Trouble shooting in accordance with check list These instructions are given in section 3.3
(only in case of error).

Putting out of operation Instructions of the plant operator


"Operating Instructions SF6Gas Insu
lated Switchgear ELK3, chapter
Maintenance, Inspection and Over
haul"

SF6Gas handling Operating Instructions SF6Gas Insulated


Switchgear ELK3", chapter Working on gas
compartments and partition insulators" and
document 1HC0028459 Manual Handling
Sulphur Hexafluoride SF6"

Changing parts of the fastacting earthing These instruction, chapter 4


switch ELKEB3

Commissioning Instructions of the plant operator

Disposal of replaced parts According to local regulations

Tab.1: Overview of revisions in progress

Template: Repair_Revision_EB3 7
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Revision/Repair of the FastActing Earthing Switch ELKEB3

3.3 Checklist for trouble shooting


If an error occurs during operation, the following outlined procedures should be fol
lowed. It was emphasized that as little labor as possible is required.
The error and repair instructions describe the symptoms caused by errors, the possible
causes of errors and how one can proceed most effectively.

Opening the housing without safety measurements is life threatening.


Danger

In the following table the possible causes for potential problems with the fastacting
earthing switch ELKEB3 are listed. In order to restrict the fault location and the cause
of error, this list should be reviewed thoroughly prior to completing the revision works.

Error/status Possible cause Solution

No or incomplete circuit Problem in the operating Replace or overhaul fastact


(contacts do not drive into mechanism ing earthing switch operating
end position) mechanism ELKDB3 in ac
cordance with instruction
1HC0037774.

No or incomplete circuit The fastacting earthing Revision according to instruc


(contacts do not drive into switch ELKEB3 has a me tions on hand
end position) chanical defect

Tab.2: Checklist for trouble shooting

Template: Repair_Revision_EB3 8
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Revision/Repair of the FastActing Earthing Switch ELKEB3

3.4 General information concerning revision

3.4.1 Tools, Apparatus and Replacement Materials


All necessary tools and apparatus used for revision are shown in Fig.2.
The replacement materials are given in section 3.4.4, Fig.4

3.4.2 Tools for the revision of FastActing Earthing Switch ELKEB3

1 2 3 4 5 8 9 10 11 12 13 14

1 Torque wrench SW19, 2090 Nm 8 Ring fork wrench SW19


2 Torque wrench 3/8", 1045 Nm 9 Screw driver hex. socket 6 mm
3 Hex. socket 3/8", 6 mm 10 Screw driver hex. socket WS 10 mm
(length 160 mm) (for nuts)
4 Torque wrench 1/8", 06 Nm 11 Screw driver 4
5 Extension 1/8", length 150 mm 12 Screw driver 0
6 Extension 1/8", length 55 mm 13 Wire for guiding
7 Hex. socket 1/8", 5 mm 14 Flat pliers

Fig.2: Tools for the revision of a fastacting earthing switch ELKEB3

3.4.3 Apparatus for the Revision of FastActing Earthing Switch ELKEB3


All needed apparatus for the dismounting/mounting of a whole fastacting earthing
switch ELKEB3 and the earthing fixed contact are described in the pertaining manuals,
where the earthing switch is fitted in.
This handcrank is also used in this manual.

Fig.3: Handcrank

Template: Repair_Revision_EB3 9
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Revision/Repair of the FastActing Earthing Switch ELKEB3

3.4.4 Replacement Parts for FastActing Earthing Switch ELKEB3


The following replacement parts are required for the revision of the fastacting earthing
switch ELKEB3
Moving contact ELKEB3 (not insulated) 1HC0023474R1030
Moving contact ELKEB3 (insulated) 1HC0023474R1035
Fixed contact (used in connecting piece ELKVT3) 1HC0023474R1020
Set of spare seals 1HC0023474R1010
Heating element (depends on supply voltage) 1HC0023474R.......
Auxiliary switch 1HC0023474R1060
Auxiliary switch 24pol. 1HC0023474R1065

Moving contact

Fixed contact

Auxiliary switch Heating element

Fig.4: Replacement parts for fastacting earthing switch ELKEB3

3.4.5 Loctite
Screws are usually secured and sealed using Loctite in the socket. Whenever Loctite
is mandatory during reassembly it is mentioned in the corresponding figure. The follow
ing Loctite has to be used:

Loctite No. 241 (blue, easy to release)

Template: Repair_Revision_EB3 10
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Revision/Repair of the FastActing Earthing Switch ELKEB3

3.5 Preparation of the Revision Tools and Materials


Prior to start the revision of the fastacting earthing switch ELKEB3, the necessary se
curity measures including requisite processes of putting out of operation (described
in section 3.6) must be adhered to.
Following preparations must be performed before starting the revision:
Prepare the tools at your workplace according to Fig.2
Prepare apparatus case according to 3.4.3
Prepare the replacement parts according to section 3.4.4, Fig.4
Prepare the cleaning materials
Prepare the adhesive (Loctite)
Prepare the following documents:
S Operating Instructions SF6Gas Insulated Switchgear ELK3, with chapter
Working on gas compartments and partition insulators"
S This revision instructions
S Document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6"
S Document HASV600715 Corrosion Protection and Sealing"
S Revision instructions for the fastacting earthing switch operating mechanism
ELKDB3 (1HC0037774)
S Revision instructions for the pertaining components (disconnector ELKTV3,
1HC0038184) the fastacting earthing switch ELKEB3 is mounted on
S Gas handling devices with the respective instruction manuals
To ensure safe working, a stable working position at the side of the fastacting
Caution earthing switch ELKEB3 is required.

3.6 Taking the FastActing Earthing Switch ELKEB3 out of Service


Before any work is carried out, the pertaining components the fastacting earthing
switch ELKEB3 is mounted on must be isolated on both ends, i.e. separated from the
high voltage system and earthed.
The scheduled sequence of measures necessary for this work is dependent on the pe
culiarities of the respective installation and requires special instructions.

Procedure:
Putting out of operation of the GISinstallation section, which contains the built in
fastacting earthing switch ELKEB3, adhering to all security measurements (see
chapter Maintenance, Inspection and Overhaul" in Operating Instructions SF6
Gas Insulated Switchgear ELK3)
The fastacting earthing switch ELKEB3 should be in the "O" (open) switch posi
tion
Unplug all external cable connections of the fastacting earthing switch ELKEB3
and fastacting earthing switch operating mechanism ELKDB3, adhering to all se
curity measurements (see chapter Maintenance, Inspection and Overhaul" in Op
erating Instructions SF6Gas Insulated Switchgear ELK3)
In accordance with the operating Instructions SF6Gas Insulated Switchgear
ELK3, chapter Working on gas compartments and partition insulators" and the
document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6", remove
gas (evacuate) to overhaul the earthing switch ELKEM3 and ventilate with air.

Template: Repair_Revision_EB3 11
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

4 Changing Parts of the FastActing Earthing Switch ELK


EB3

4.1 Removing of FastActing Earthing Switch ELKEB3


Before the process of changing parts of the fastacting earthing switch ELKEB3 could
be started, the fastacting earthing switch ELKEB3 has to be removed from the pertain
ing component (described in document 1HC0037774 Revision Instructions ELKDB3").

Fastacting Fastacting
earthing switch earthing switch
Insulator
Fastacting earthing fixed
contact

Noninsulated fastacting earthing Insulated fastacting earthing


switch ELKEB3 switch ELKEB3

Cap nut M12


Earth
connection

Screw M10

Fig.5: Remove fastacting earthing switch ELKEB3

Noninsulated fastacting earthing switch ELKEB3


Loosen screws 8xM12
Remove fastacting earthing switch ELKEB3 carefully
(weight approx. 20 kg)

Insulated fastacting earthing switch ELKEB3


Dismount earth connection
Loosen cap nuts 4xM12
Remove screws 4xM10
Remove earth connection
Loosen cap nuts 12xM12
Remove fastacting earthing switch ELKEB3 carefully
(weight approx. 20 kg)
Remove insulator

Template: ChangeParts_EB3 12
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

4.2 Removing of Fixed Contact of FastActing Earthing Switch ELKEB3


The removing process of fixed contact is shown in Fig.6. The mounting process of fixed
contact is shown in Fig.39.
The changing process of parts of fastacting earthing switch starts in Fig.7.

Pin wrench

Flange

Shown with connector


design ELKTV3
Fastacting earthing Pins
fixed contact

Fig.6: Remove fixed contact of fastacting earthing switch ELKEB3


Fasten pin wrench for fixed contact of fastacting earthing switch on flange
Engage pins of pin wrench in the holes of fastacting earthing fixed contact
Turn until fastacting earthing fixed contact is unscrewed
Dismount pin wrench for fixed contact of fastacting earthing switch on flange
Remove earthing fixed contact carefully
Fig.7 shows the fastacting earthing switch ELKEB3 after dismounting from the pertain
ing components, before starting any other work.

Template: ChangeParts_EB3 13
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

Fig.7: Dismounted fastacting earthing switch ELKEB3

Template: ChangeParts_EB3 14
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

4.3 Dismounting of Moving Contact

Fig.8: Draw out screen

Dismounting screen by loosen screws 3xM6


Draw out screen
Remove connection of the insulated electrode for novoltage indicator/PDmea
surement.

If the auxiliary switch or/and the heating element would be changed, refer to sec
Information tion 4.5.

Template: ChangeParts_EB3 15
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

Guide segment

Fig.9: Loosen of guide segment


Loosen screws 4XM12
Do not remove the guide segment at the moment (guide for sliding piece)
Information

Fig.10: Disassemble contact bush with tubular contact


Loosen screws 4xM8

Template: ChangeParts_EB3 16
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

Guide segment Sliding piece

Tubular contact

Fig.11: Disassemble tubular contact


Remove guide segment
Remove sliding piece
Draw out tubular contact with contact bush

Reversing lever
Tubular contact

Cable Guide segment

Sliding piece

Operating shaft

Fig.12: Remove tubular contact


Draw out reversing lever from operating shaft
Remove tubular contact
Draw out the cable carefully
The dismounting process is now finished.

Template: ChangeParts_EB3 17
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

4.4 Mounting of new Moving Contact

Fig.13: Clean and grease sliding piece and guide segment


Clean sliding piece and guide segment according to the Operating Instructions
SF6Gas Insulated Switchgear ELK3, chapter Installation of GIS", section Clean
ing"
Grease sliding piece and guide segment according to the document HASV600715
Corrosion Protection and Sealing"
Insert a new sealing ring

Fig.14: Regreasing (example)


Regrease tubular contact and housing flanges, according to the document
HASV600715 Corrosion Protection and Sealing".

Template: ChangeParts_EB3 18
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

Flange for guide segment


Guide segment

Long slot

Cable

Wire for guiding

Wiring conduit

Fig.15: Inserting moving contact


Insert reversing lever, the long slot has to be in direction to the flange for the guide
segment
Insert cable carefully in wiring conduit (use a wire, approx. 2.5 mm2)
Draw in tubular contact

Fig.16: Lift up reversing lever


Insert a wire with a hook at flange hole to lift up reversing lever, by drawing in the
tubular contact

Template: ChangeParts_EB3 19
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

Reversing lever
Tubular contact

Cable Guide segment

Sliding piece

Operating shaft

Fig.17: Connect tubular contact


Connect reversing lever with operating shaft
Insert sliding piece

Fig.18: Place guide segment


Place guide segment and fix with screws 4xM12 (Loctite, do not tighten)

Template: ChangeParts_EB3 20
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

Fig.19: Assemble contact bush and tubular contact


Fix screws 4xM8 (Loctite, do not tighten)

Handcrank Tubular contact

Fig.20: Move contact


Insert Handcrank
Move tubular contact by using handcrank, 3times into both endpositions
(for centering position of the mounted parts)

Fig.21: Fasten screws


Fasten screws 4xM8 (13 Nm, Loctite is applicated in Fig.19) of contact bush
Fasten screws 4x M12 (70 Nm, Loctite is applicated in Fig.18) of guide segment

Template: ChangeParts_EB3 21
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

Second slot First slot


(Non insulated version) (Insulated version)

Fig.22: Mount screen

Premount screws 3xM6 (Loctite), with 2 washers each


Connect cable shoe of insulated electrode for novoltage indicator/PDmeasure
ment with screen.
Look for a tighten connection.
Caution

Draw in screen, both washers have to be inside screen


The following positions of screen have to be used:
S Non insulated version: second slot (see Fig.22)
S Insulated version: first slot (see Fig.22)
The length of screens are different for both versions!

Fig.23: Fix screen

Fix screen with screws 3xM6 carefully.

The changing of moving contact is now finished.

Template: ChangeParts_EB3 22
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

4.5 Changing of Auxiliary Switch and Heating Element


Before the changing could be started, the fastacting earthing switch ELKEB3 has to be
switched with the handcrank in position C" (Closed)

Cover Connection plate

Fig.24: Unscrew cover and connection plate


Loosen screws 6xM6 and remove cover
Remove screws 4xM6 of connection plate
The dismounting/remounting of auxiliary switch is described in sections 4.5.1 and 4.5.2.
The dismounting/remounting of heating element is described in sections 4.5.3 and
4.5.4.

4.5.1 Dismounting of Auxiliary Switch

Screws
Terminals
Cables of heating
supply voltage

Fig.25: Remove fixings and connections to auxiliary switch


Disconnect cables of heating voltage supply, by using a screw driver (size 0) to open
contacts of terminals
Remove screws 2xM6

Template: ChangeParts_EB3 23
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

Fig.26: Remove auxiliary switch


Remove auxiliary switch with connection plate

Fig.27: Remove all cables


Remove all cables from auxiliary switch
The dismounting process of auxiliary switch is now finished.

Template: ChangeParts_EB3 24
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

4.5.2 Remounting of new Auxiliary Switch

Fig.28: Connect cables


Connect all cables with auxiliary switch
Fastacting earthing switch ELKEB3 has to be in closed position C", (see position
Information indicator)

Tubular contact

Handcrank Depth gauge

Fig.29: Control moving contact closed position C"


Measure the distance between flange and contact end.
The following measures have to be observed (by using a depth gauge):
S Non insulated version: L = 323.5 mm
S Insulated version: L = 383.5 mm
If the position is not as indicated, next steps have to be done now.
Insert handcrank
Move tubular contact into close position (as shown in Fig.29)

Template: ChangeParts_EB3 25
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

90
Position

Fig.30: Correct switch position of auxiliary switch


Control correct switching position of auxiliary switch (on site of terminals)

Distance ring Distance ring

Fig.31: Insert distance ring


Insert distance ring as shown in Fig.31

Template: ChangeParts_EB3 26
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

Fig.32: Insert auxiliary switch


Insert auxiliary switch with connection plate

Screws
Terminals
Cables of heating
supply voltage

Fig.33: Fix auxiliary switch


Put 2 earthing connection cables of connecting plate under screws 2xM6
Screw in screws 2xM6 (5.5 Nm, Loctite) in and fasten auxiliary switch
Connect cables of heating voltage supply, by using a screw driver (size 0) to open
contacts of terminals

Template: ChangeParts_EB3 27
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

Connection plate Cover

Fig.34: Screw on cover and connection plate


Screw on connection plate with screws 4xM6 (5.5 Nm, Loctite)
Screw on cover screws 6xM6 (5.5 Nm, Loctite)
The changing of auxiliary switch is now finished.

Template: ChangeParts_EB3 28
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

4.5.3 Dismounting of Heating Element


To get access to heating element, dismount auxiliary switch according 4.5.1, Fig.25 and
Fig.26.

Fig.35: Disconnect cables of heating element


Disconnect cables of heating element, by using a screw driver (size 0) to open con
tacts of terminals

Heating element

Clamp

Screw

Fig.36: Remove heating element


Loosen one screw heating element could be removed from clamps
The dismounting process of auxiliary switch is now finished.

Template: ChangeParts_EB3 29
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

4.5.4 Remounting of Heating Element

Heating element

Clamp

Screw

Fig.37: Mount heating element


Put heating element between the two clamps and fasten screw

Fig.38: Connect cables of heating element


Connect cables of heating element, by using a screw driver (size 0) to open contacts
of terminals
The changing process of heating element is now finished.
The reinstallation of auxiliary switch has to be done according to 4.5.2, without opera
tions described in Fig.28.

Template: ChangeParts_EB3 30
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

4.6 Mounting of Fixed Contact of FastActing Earthing Switch ELKEB3

Pin wrench

Flange

Shown with connector


design ELKTV3
Earthing fixed contact Adjusting plate Pins

Fig.39: Mount fixed contact of fastacting earthing switch ELKEB3


Insert earthing fixed contact (applicated with Loctite) carefully by hand
Fasten pin wrench for fixed contact of earthing switch on flange
Engage pins of pin wrench in the holes of earthing fixed contact
Fasten earthing fixed contact (120 Nm, Loctite)
Dismount pin wrench for fixed contact of earthing switch on flange
In case of noninstalled fastacting earthing switch ELKEB3 close the connection
Information flange with cover

Enclosure

Screws 8xM12 Cover

Fig.40: Fasten cover in case of noninstalled fastacting earthing switch ELKEB3


Insert new sealing ring in cover
Fasten cover with screws 8xM12 (70 Nm, Loctite)

Template: ChangeParts_EB3 31
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

4.7 Remount the FastActing Earthing Switch ELKEB3


In case of installed fastacting earthing switch ELKEB3 the following steps have
Information to be done. The installation of operating switch ELKDB3 is described in the docu
mentation (1HC0037774)

Fastacting Fastacting
earthing switch earthing switch
Insulator
Fastacting earthing fixed
contact

Noninsulated fastacting earthing Insulated fastacting earthing


switch ELKEB3 switch ELKEB3

Cap nut M12


Earth
connection

Screw M10

Fig.41: Mount fastacting earthing switch ELKEB3

Noninsulated fastacting earthing switch ELKEB3


Insert fastacting earthing switch ELKEB3 with new sealing ring carefully
(weight approx. 20 kg)
Fasten screws 8xM12 (Loctite) by hand
Insert handcrank in fastacting earthing switch ELKEB3
Bring fastacting earthing switch ELKEB3 in position C" close
Fasten screws 8xM12 (70 Nm, Loctite)
Bring fastacting earthing switch ELKEB3 in position O" open and remove hand
crank

Insulated fastacting earthing switch ELKEB3


Insert insulator with new sealing ring
Insert fastacting earthing switch ELKEB3 with new sealing ring carefully
(weight approx. 20 kg)
Fasten cap nuts 12xM10 (Loctite) by hand
Insert handcrank in fastacting earthing switch ELKEB3
Bring fastacting earthing switch ELKEB3 in position C" close
Fasten cap nuts 12xM10 (42 Nm, Loctite)

Template: ChangeParts_EB3 32
Manual: 1HC0037777 E01 / AC05
Revision Instructions SF6Gas Insulated Switchgear ELK3

Disassembly of the FastActing Earthing Switch ELKEB3

Bring fastacting earthing switch ELKEB3 in position O" open and remove hand
crank
Mount earth connection
Attach earth connection
Fasten screws 4xM10 (42 Nm, Loctite)
Fasten cap nuts 4xM10 (42 Nm, Loctite)

The remounting of the fastacting earthing switch ELKEB3 is now finished. The mount
ing process of the operating mechanism ELKDB3 is described in revision instructions
1HC0037774.

Template: ChangeParts_EB3 33
Manual: 1HC0037777 E01 / AC05