Commercial SPD Catalogue

Surge Protective Devices

www.siemens.ca/surge
www.siemens.ca/surge

Siemens Full-line of
Surge Protective Devices
UL 1449 3rd Edition

In todays electronic world, home and business electrical Our next generation UL 1449 3rd Edition TPS3 SPDs carry on
systems arent complete unless they incorporate surge this same legacy by maintaining the highest degree of safety
protection. This is best accomplished by Stopping Surges while delivering the industrys best performance ratings
Before They Get In through the application of hard-wired lowest Voltage Protection Ratings (VPRs), Type 1 and 20 kA
surge protective devices (SPDs) at key surge entry paths I nominal ratings nearly across the board, and surge current
located within an electrical system. ratings from 50 kA to 1000 kA. This safety and performance
know-how is infused within every Siemens TPS.
Locating SPD installation points is a relatively easy step in
developing a surge protection plan. Selecting and sizing Electrical disturbances will always occur, but they dont
surge protective devices is not as simple, but Siemens has have to cause surge protectors to fail in an unsafe manner.
solutions for virtually all applications. Safer surge protection means uncompromised electrical
system protection, safety, and reliability.
Even at their inception over 18 years ago, our Transient
Protection System (TPS) family of surge protectors included
a number of industry SPD safety control firsts including the
patented Ceramgard and TranSafe circuitry, coordinated
fusing and thermal cutouts, dielectric isolation, mechanical
reinforcing taping resulting in a design that ensured the
highest possible electrical system protection and reliability.

EXTERNAL INTERNAL
Table of Contents

SPD SIZING & SELECTION CHART 4

EXTERNAL SPDs (5-20)


TPS3 03 5
TPS3 03 DC 7
TPS3 09 9
TPS3 11 11
TPS3 12 13
TPS3 L12 (10-mode SPD) 15
TPS3 15 17
TPS3 L15 (10-mode SPD) 19

INTERNAL SPDs (21-32)


TPS3 01 21
TPS3 L1 (10-mode SPD) 23
TPS3 02 25
TPS3 L2 (10-mode SPD) 27
TPS3 05 29
TPS3 L5 (10-mode SPD) 31
TPS3 06 33
TPS3 L6 (10-mode SPD) 35

FREQUENTLY ASKED QUESTIONS 37

SERVICES & SUPPORT 38

www.siemens.ca/surge
Sizing Chart
Surge Protective Devices
www.siemens.ca/surge

TPS3 12 TPS3 11 TPS3 09 TPS3 03

Service Entrance Greater than 2000A


Exposure Level High Exposure Medium Exposure Low Exposure Lowest Exposure
kA per phase 300 kA 200 kA 150 kA 100 kA
Model TPS3_1230 TPS3_1220 TPS3_1215 TPS3_1110

Service Entrance 1200A - 2000A


Exposure Level High Exposure Medium Exposure Low Exposure Lowest Exposure
kA per phase 250 kA 200 kA 150 kA 100 kA
Model TPS3_1225 TPS3_1220 TPS3_1115 TPS3_0910

Service Entrance 800A - 1200A


Exposure Level High Exposure Medium Exposure Low Exposure Lowest Exposure
kA per phase 200 kA 150 kA 100 kA 50 kA
Model TPS3_1120 TPS3_1115 TPS3_0910 TPS3_0305

Distribution/Branch Panel 800A - 1200A


Exposure Level High Exposure Medium Exposure Low Exposure Lowest Exposure
kA per phase 200 kA 150 kA 100 kA 50 kA
Model TPS3_1120 TPS3_1115 TPS3_0910 TPS3_0305

Distribution/Branch Panel Less than 800A


Exposure Level High Exposure Medium Exposure Low Exposure Lowest Exposure
kA per phase 150 kA 100 kA 100 kA 50 kA
Model TPS3_1115 TPS3_1110 TPS3_0910 TPS3_0305

PRICING & PRODUCT INFORMATION - Phone: 888.333.3545 or visit www.siemens.ca/surge


4
TPS3 03
Type 1 Surge Protective Device (SPD)
Mounts External to Electrical Distribution
Equipment
Features:
UL 1449 3rd Edition 2009, cUL
Type 1 SPD (Type 2 cUL)
Mounts external to electrical distribution equipment
-- Recommended for Line Side or Load Side Applications
Bracket included for multiple mounting options
20 kA In (most models)
200 kA SCCR (most models)
All UL-required OCP & safety coordination included
UL96A Lightning Protection Master Label compliant (@ 20 kA In)

SPD Specifications
-- Surge Current Rating Per Phase
Per Phase L-N (L-G: Delta)
50 kA 50 kA
-- 100% monitoring (Every MOV is monitored)
-- Individually fused and thermally protected MOVs
-- Solid state bi-directional operation
-- Repetitive impulse: 5,000 hits
-- Less than 1 nanosecond response time
-- Relative humidity range: 0 - 95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

Standard Configuration
-- Standard NEMA 4X polycarbonate enclosure (UL 746C (f1), UL 94-5VA)
-- Wire size: Prewired with 3 (91.4 cm) of #10 AWG
-- Standard size: 3.25 x 3.25 x 3.3 (82.6 mm x 82.6 mm x 83.8 mm)
-- Standard weight: 2 lbs. (0.9 kg)

UL 1449 3rd Edition SPD

5
SPD Features SPD Features Available Accessories
-- UL 1449 3rd Edition effective September -- Large-block 34mm square MOVs -- RMSIE = Remote monitor
2009 -- 5 year warranty
-- Designed, manufactured and tested Key Bid Specifications
consistent with: SPD Monitoring -- UL 1449 3rd Edition 2009, cUL
-- ANSI/IEEE C62.41.1-2002, -- LED indicators -- Type 2 SPD
c62.41.2-2002, C62.45-2002, -- Protection modes on L-N/L-G, L-L
-- 1992/2000 NEMA LS-1 Available Options -- In Rating 20kA
-- NEC Article 285 -- Dry contacts & audible alarm -- Short Circuit Current Rating 200 kA
-- IEC 61643, CE -- Surge Current Rating 50 kA per phase

Ordering Information

Catalogue # TPS3 o 03 oo o 2

Voltage Code Surge Current (kA) Options


A = 120/240V, 1, 3W (Fig 1) 05 = 50 kA per phase D = Dry contact & audible alarm
B = 120/240V, 3, 4W (Fig 3)
C = 120/208V, 3, 4W (Fig 2)
D = 240V, 3, 3W (Fig 4)
E = 277/480V, 3, 4W (Fig 2)
F = 480V, 3, 3W (Fig 4) -- Example: TPS3C0305D2 = Type 2 SPD for a 208/120V application with a surge
G = 600V, 3, 3W (Fig 4) current capacity of 50 kA per phase, in a standard NEMA 4X enclosure with dry
K = 380/220V, 3, 4W (Fig 2) contacts and audible alarm option
L = 600/347V, 3, 4W (Fig 2) -- When an option is not selected, include a zero (0) in the field

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)

Voltage Code Service Voltage L-N (L-G: Delta) L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 600 1000 Type 2 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 600 / 1200 1000 / 1500 Type 2 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 600 1000 Type 2 20 kA 200 kA 150
D 240V, 3, 3W (Fig 4) 1200 1500 Type 2 20 kA 200 kA 320
E 277/480V, 3, 4W (Fig 2) 1200 2000 Type 2 20 kA 200 kA 320
F 480V, 3, 3W (Fig 4) 1800 3000 Type 2 10 kA 200 kA 552
G 600V, 3, 3W (Fig 4) 2500 2500 Type 2 20 kA 200 kA 690
K 380/220V, 3, 4W (Fig 2) 1200 2000 Type 2 20 kA 200 kA 320
L 600/347V, 3, 4W (Fig 2) 1500 2500 Type 2 20 kA 200 kA 420

Phase A (BLK)
Siemens Canada Limited
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V 1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK) Oakville, ON L6H 0H6

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
C Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 Figure 4 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.

Notes: www.siemens.ca/surge
Type 1 UL www.siemens.ca
5.28.13.lh #8437
6
TPS3 03 DC
For DC Photovoltaic Applications

TPS3 03 DC is available in 300VDC, 600VDC and 1000VDC versions, which


are designed to protect photovoltaic electrical systems. Typical PV
installation would be on the DC solar panel side and also on the AC side of
the inverter/converter. AC voltage TPS3 03s are also available. SPDs are
highly recommended when lightning activity is present to protect
sensitive electrical photovoltaic components.

TPS3 03 DC is designed as a stand alone device in a NEMA 4X


polycarbonate enclosure. Large block, thermally protected 50 kA MOVs
are utilized. A green LED illuminates for diagnostic monitoring. TPS3 03
DC comes standard with a Tri-Mount installation kit which allows it to be
Nipple, DIN-rail or Bracket mounted.

Diagram Tri-Mount Installation Dimensions


Mounting Kit Included 3.26

red wire black wire


3.31 3.57

4.13 Weight: 1.60 lbs


(0.73 kg)
Std. 3/4-14 Nipple DIN-rail Mount 3.26
(rail not incl.)

3/4-14

Ground
1.15
green / yellow wire
Sized for std 35mm DIN-rail
Bracket Mount for Flat Surfaces

UL 1449 3rd Edition SPD

7
Performance Data
Siemens Part Number TPS3M03052 TPS3R03052 TPS3P03052
Modes of Protection DC+ DC- , DC+ Ground, DC- Ground
Nominal Network Voltage Un 300VDC 600VDC 1000VDC
Technology Large Block, Thermally Protected 50kA MOVs

Maximum Continuous Operating Voltage DC Uc 425VDC 760VDC 1180VDC

Maximum Surge Current (8/20 s) Imax 50kA 50kA 50kA

Nominal Discharge Current (8/20 s) In 20kA 20kA 10kA

Voltage Protection Level (3kA 8/20s) Up <600V <1800V <2500V

Operating Temperature -40oC + 65oC

Response Time tA <1ns

Installation mounting method DIN Rail, Nipple or Bracket

Enclosure Material NEMA 4X Polycarbonate

Wiring (red = + , black = - , green / yellow =gnd) Pre-wired w/3(~1m) of 8AWG + 6AWG Ground Conductor

Diagnostic circuit Low Consumption LED Indicator

Safety Disconnectors Thermal/Overcurrent Protection; Arc-Breaking Slide Gate


UL Listing UL listed to UL 1449 as DC SPD for use in PV applications
Warranty 5 Years

Siemens Canada Limited


1577 North Service Road East
Oakville, ON L6H 0H6

SPD Hotline: 888.333.3545


info@purgethesurge.com

2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.

www.siemens.ca/surge
www.siemens.ca
5.28.13.lh #8443
8
TPS3 09
Type 1 Surge Protective Device (SPD)
Mounts External to Electrical Distribution Equipment or
Internal to P1, P2 Lighting Panelboards, P3 Power
Panelboards and Busway Systems
Features:
UL 1449 3rd Edition 2009, cUL
Type 1 SPD (Type 2 cUL)
Mounts external to electrical distribution equipment
-- Weatherproof hub included
Mounts internal to P1 panelboards & busway
-- P1 - Field retrofit or factory install
-- P2 and P3 - Factory install only
Consult factory for field retrofit
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In(most models)
200 kA SCCR (most models)
All UL-required OCP & safety coordination included
UL96A Lightning Protection Master Label compliant (@ 20 kA In)
SPD Specifications
-- Surge Current Rating Per Phase
Per Phase L-N L-G N-G
100 kA 50 kA 50 kA 50 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- Individually fused and thermally protected MOVs
-- Solid state bi-directional operation
-- Repetitive impulse: 5,000 hits
-- Less than 1 nanosecond response time
-- Relative humidity range: 0 -95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -40C (-40F) to +85C (185F)

Standard Configuration
-- Standard NEMA 4X polycarbonate enclosure (UL 746C (f1),
UL 94-5VA)
-- Wire size: Prewired with 3 (91.4cm) of #10 AWG
-- Standard size: 8.3 x 3.6 x 3.0 (211 mm x 91 mm x 77 mm)
-- Standard weight: 3 lbs. (1.4 kg)

UL 1449 3rd Edition SPD

9
SPD Features SPD Monitoring Key Bid Specifications
-- UL 1449 3rd Edition effective September -- LED indicators -- UL 1449 3rd Edition 2009, cUL
2009 -- Type 2 SPD
-- Designed, manufactured and tested Available Options -- Protection modes on L-N, L-G, L-L, N-G
consistent with: -- Dry contacts & audible alarm -- In Rating 20 kA
-- ANSI/IEEE C62.41.1-2002, -- Short Circuit Current Rating 200 kA
c62.41.2-2002, C62.45-2002, Available Accessories -- Surge Current Rating
-- 1992/2000 NEMA LS-1 -- RMSIE = Remote monitor Per Phase = L-N + L-G
-- NEC Article 285 -- FMKITC = Flush mount plate 100 kA 50 kA 50 kA
-- IEC 61643, CE -- TPS9IKITP1 = Mounting bracket for
-- Large block, individually fused, installation in P1 panels
thermally protected, 50 kA MOVs -- TPS9IKITP2 = Mounting bracket for
-- 10 year warranty installation in P2 panels
(factory install only)

Ordering Information

Catalogue # TPS3 o 09 oo ooo 2


Voltage Code Surge Current (kA) Options
A = 120/240V, 1, 3W (Fig 1) 10 = 100 kA per phase E = Extended indicator light
B = 120/240V, 3, 4W (Fig 3) I = Internal mounting in P1, P2 panels
C = 120/208V, 3, 4W (Fig 2) D = Dry contact & audible alarm
D = 240V, 3, 3W (Fig 4)
E = 277/480V, 3, 4W (Fig 2)
F = 480V, 3, 3W (Fig 4)
G = 600V, 3, 3W, (Fig 4) -- Example: TPS3C0910D002 = Type 2 SPD for a 208/120V panelboard with a surge current capacity of
K = 380/220V, 3, 4W (Fig 2) 100 kA per phase with standard NEMA 4X enclosure, dry contacts and audible alarm option.
L = 600/347V, 3, 4W (Fig 2) -- Available for field retrofit in P1 panels
S = 400/230V, 3, 4W (Fig 2) -- When an option is not selected, include a zero (0) in the field

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 600 700 500 1000 Type 2 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 600 / 1200 700 / 1200 500 1000/ 1000 Type 2 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 600 700 500 1000 Type 2 20 kA 200 kA 150
D 240V, 3, 3W (Fig 4) 1200 1200 Type 2 20 kA 200 kA 320
E 277/480V, 3, 4W (Fig 2) 1200 1200 1000 1800 Type 2 20 kA 200 kA 320
F 480V, 3, 3W (Fig 4) 1800 1800 Type 2 10 kA 200 kA 552
G 600V, 3, 3W (Fig 4) 2500 2500 Type 2 10 kA 200 kA 690
K 380/220V, 3, 4W (Fig 2) 1200 1200 1000 1800 Type 2 20 kA 200 kA 320
L 600/347V, 3, 4W (Fig 2) 1500 1500 1500 2500 Type 2 10 kA 200 kA 420
S 400/230V, 3, 4W (Fig 2) 1200 1200 1000 1800 Type 2 20 kA 200 kA 320

Phase A (BLK) Siemens Canada Limited


}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V
1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)
Oakville, ON L6H 0H6
}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 Figure 4 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
Split Wye Hi-Leg Delta (B High) Delta & HRG Wye
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd trademark of Siemens AG. Product names
3 Hots, (B High), 3 Hots, 1 Grnd
1 Neu, 1 Grnd mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.
Notes:
Type 1 UL www.siemens.ca/surge
Requires TPS9IKITP1 or TPS9IKITP2 mounting bracket accessory, see available Accessories www.siemens.ca
3.2.15.lh

10
TPS3 11
Type 1 Surge Protective Device (SPD)
Mounts External to Electrical Distribution
Equipment
Features:
UL 1449 3rd Edition 2009, cUL
Type 1 SPD (Type 2 cUL)
Mounts external to electrical distribution equipment
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In (most models)
200 kA SCCR (most models)
All UL-required OCP & safety coordination included
UL96A Lightning Protection Master Label compliant (@ 20 kA In)

SPD Specifications
-- Surge Current Rating Per Phase
Per Phase L-N L-G N-G
100 kA 50 kA 50 kA 50 kA
150 kA 100 kA 50 kA 50 kA
200 kA 100 kA 100 kA 100 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- Individually fused and thermally protected MOVs
-- Solid state bi-directional operation
-- EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than 1 nanosecond response time
-- Relative humidity range: 0 -95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

Standard Configuration
-- Standard NEMA 4X polycarbonate enclosure (UL 746C (f1), UL 94-5VA)
-- Wire size: #8 AWG to #10 AWG
-- Standard size: 6 x 6 x 4 (152 mm x 152 mm x 102 mm)
-- Standard weight: 5 lbs. (2.27 kg)

UL 1449 3rd Edition SPD

11
SPD Features SPD Features Available Accessories
-- UL 1449 3rd Edition effective September -- Large block, individually fused, thermally -- RMSIE = Remote monitor
2009 protected, 50 kA MOVs -- KITFMXF = Flush mount plate
-- Designed, manufactured and tested
consistent with: SPD Monitoring Key Bid Specifications
-- ANSI/IEEE C62.41.1-2002, -- LED indicators -- UL 1449 3rd Edition 2009, cUL
c62.41.2-2002, C62.45-2002, -- UL 1283
-- 1992/2000 NEMA LS-1 Available Options -- Type 2 SPD
-- NEC Article 285 -- Dry contacts & audible alarm -- Protection modes on L-N, L-G, L-L, N-G
-- IEC 61643, CE -- In Rating 20 kA
-- 10 year warranty -- Short Circuit Current Rating 200 kA
-- Surge Current Rating
Per Phase = L-N + L-G
100 kA 50 kA 50 kA

Ordering Information

Catalogue # TPS3 o 11 oo o 2

Voltage Code Surge Current (kA) Options


A = 120/240V, 1, 3W (Fig 1) 10 = 100 kA per phase D = Dry contacts & audible alarm
B = 120/240V, 3, 4W (Fig 3) 15 = 150 kA per phase
C = 120/208V, 3, 4W (Fig 2) 20 = 200 kA per phase
D = 240V, 3, 3W (Fig 4)
E = 277/480V, 3, 4W (Fig 2)
F = 480V, 3, 3W (Fig 4)
G = 600V, 3, 3W (Fig 4) -- Example: TPS3C1110D2 = Type 2 SPD for a 208/120V application with a surge current
K = 380/220V, 3, 4W (Fig 2) capacity of 100 kA per phase, in a standard NEMA 4X enclosure with dry contacts and
L = 600/347V, 3, 4W (Fig 2) audible alarm option
S = 400/230V, 3, 4W (Fig 2) -- When an option is not selected, include a zero (0) in the field

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 700 700 600 1000 Type 2 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 700 / 1200 700 / 1200 600 1000 Type 2 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 700 700 600 1000 Type 2 20 kA 200 kA 150
D 240V, 3, 3W (Fig 4) 1200 2000 Type 2 20 kA 200 kA 320
E 277/480V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 2 20 kA 200 kA 320
F 480V, 3, 3W (Fig 4) 1800 2000 Type 2 10 kA 200 kA 552
G 600V, 3, 3W (Fig 4) 2500 2500 Type 2 10 kA 200 kA 690
K 380/220V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 2 20 kA 200 kA 320
L 600/347V, 3, 4W (Fig 2) 1500 1500 1500 2500 Type 2 10 kA 200 kA 420
S 400/230V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 2 20 kA 200 kA 320

Phase A (BLK)
Siemens Canada Limited
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V 1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK) Oakville, ON L6H 0H6

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
C Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 Figure 4 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.
Notes:
Type 1 UL www.siemens.ca/surge
Available in 100 kA per phase only www.siemens.ca
5.28.13.lh

12
TPS3 12
Type 1 Surge Protective Device (SPD)
For Line Side or Load Side Applications
Features:
UL 1449 3rd Edition 2009, cUL
Type 1 SPD (Type 2 cUL)
Mounts external to electrical distribution equipment
-- Recommended for line side or load side applications
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In (most models)
200 kA SCCR (most models)
Provides replaceable module protection for low to high exposure applications
All UL-required OCP & safety coordination included
UL96A Lightning Protection Master Label compliant (@ 20 kA In)

SPD Specifications
-- Surge Current Rating Per Phase
Per Phase L-N L-G N-G
100 kA 50 kA 50 kA 50 kA
150 kA 100 kA 50 kA 50 kA
200 kA 100 kA 100 kA 100 kA
250 kA 150 kA 100 kA 100 kA
300 kA 150 kA 150 kA 150 kA
400 kA 200 kA 200 kA 200 kA
500 kA 250 kA 250 kA 250 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- Individually fused and thermally protected MOVs
-- Solid state bi-directional operation
-- EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than 1 nanosecond response time
-- Relative humidity range: 0 -95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

Standard Configuration
-- Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure
-- Wire size: #8 AWG to 1/0
-- Standard size: 12 x 12 x 7 (305 mm x 305 mm x 178 mm) *
-- Standard weight: 20 lbs. (9.07 kg) *
*Internal disconnect options and other NEMA ratings may increase enclosure size and weight

UL 1449 3rd Edition SPD

13
SPD Features SPD Monitoring Available Accessories
-- UL 1449 3rd Edition effective September -- LED indicators -- RMSIE = Remote monitor
2009 -- Audible alarm with silence switch and test
-- Designed, manufactured and tested button Key Bid Specifications
consistent with: -- Dry contacts -- UL 1449 3rd Edition 2009, cUL
-- ANSI/IEEE C62.41.1-2002, -- Type2 SPD
c62.41.2-2002, C62.45-2002, Available Options -- Protection modes on L-N, L-G, L-L, N-G
-- 1992/2000 NEMA LS-1 -- Surge counter -- In Rating 20 kA
-- NEC Article 285 -- Internal rotary disconnect switch -- Short Circuit Current Rating 200 kA
-- IEC 61643, CE -- Thru-door disconnect switch -- Surge Current Rating
-- Large block, individually fused, -- NEMA 4X non-metallic enclosure Per Phase = L-N + L-G
thermally protected, 50 kA MOVs -- NEMA 4X stainless steel enclosure 100 kA 50 kA 50 kA
-- 10 year warranty -- Flush mount enclosure
-- NEMA 1 Enclosure with extended display

Ordering Information

Catalogue # TPS3 o 12 oo o oo 2
Voltage Code Surge Current (kA) Enclosure Options
A = 120/240V, 1, 3W (Fig 1) 10 = 100 kA per phase 0 = Standard NEMA 1/12/3R/4 Steel D = Internal rotary disconnect
B = 120/240V, 3, 4W (Fig 3) 15 = 150 kA per phase V = NEMA 4X non-metallic T = Thru-door disconnect
C = 120/208V, 3, 4W (Fig 2) 20 = 200 kA per phase S = NEMA 4X stainless steel X = Surge counter
D = 240V, 3, 3W (Fig 4) 25 = 250 kA per phase F = NEMA 1 flush mount
E = 277/480V, 3, 4W (Fig 2) 30 = 300 kA per phase P = NEMA 1 screwcover pullbox with extended display on 6ft cable
F = 480V, 3, 3W (Fig 4) 40 = 400 kA per phase for line side mounting in SWBD/SWGR
G = 600V, 3, 3W (Fig 4) 50 = 500 kA per phase
K = 380/220V, 3, 4W (Fig 2) -- Example: TPS3C12100XD2 = Type 2 SPD for a 208/120V application with a surge current capacity
L = 600/347V, 3, 4W (Fig 2) of 100 kA per phase, in a standard NEMA 1/12/3R/4 enclosure with a surge counter and internal
S = 400/230V, 3, 4W (Fig 2) rotary disconnect option
-- When an option is not selected, include a zero (0) in the field

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 700 700 700 1200 Type 2 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 700 / 1200 700 / 1200 700 1800/1800 Type 2 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 700 700 700 1200 Type 2 20 kA 200 kA 150
D 240V, 3, 3W (Fig 4) 1200 1200 Type 2 20 kA 200 kA 320
E 277/480V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 2 20 kA 200 kA 320
F 480V, 3, 3W (Fig 4) 1800 1800 Type 2 20 kA 200 kA 552
G 600V, 3, 3W (Fig 4) 2500 2500 Type 2 10 kA 200 kA 690
K 380/220V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 2 20 kA 200 kA 320
L 600/347V, 3, 4W (Fig 2) 1500 1500 1500 2500 Type 2 20 kA 200 kA 420
S 400/230V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 2 20 kA 200 kA 320

Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V

}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK) Siemens Canada Limited

}
Hot (BLK) Phase C (BLK) 1577 North Service Road East
V Phase C (BLK)
Neutral (WHT)
Ground (GRN)
Phase C (BLK)
Ground (GRN) Ground (GRN) Oakville, ON L6H 0H6
C Ground (GRN)

SPD Hotline: 888.333.3545


Figure 1 Figure 2 Figure 3 Figure 4 info@purgethesurge.com

2013 Siemens Canada Limited, Inc.


Notes: All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
Type 2 cUL
mentioned may be trademarks or registered
For line side mounting in SWBD/SWGR
trademarks of their respective companies.
Not available in 500 kA Specifications are subject to change without
Available in 100 kA, 150 kA, 200 kA & 250 kA only notice.
In rating for100-300 kA per phase is 10 kA
VPR may increase when disconnect switch is added; www.siemens.ca/surge
VPR may decrease for products 400 & 500 kA per phase www.siemens.ca
3.2.15.lh

14
TPS3 L12
True 10 Mode Protection
Type 1 Surge Protective Device (SPD)
For Line Side or Load Side Applications
UL 1449 3rd Edition 2009, cUL
Type 1 SPD (Type 2 cUL)
Mounts external to electrical distribution equipment
-- Recommended for line side or load side applications
Large block, individually fused, thermally protected,
50 kA MOVs
20 kA In (most models)
200 kA SCCR (most models)
Single TPS1 style replaceable modules
Provides replaceable module protection for low to high exposure
applications
All UL-required OCP & safety coordination included
UL96A Lightning Protection Master Label compliant (@ 20 kA In)

SPD SPECIFICATIONS
-- Directly connected discrete protection elements between all possible
modes providing true 10 mode protection
-- Surge Current Rating Per Phase
Per Phase L-N L-G L-L N-G
150 kA 50 kA 50 kA 50 kA 50 kA
300 kA 100 kA 100 kA 100 kA 100 kA
450 kA 150 kA 150 kA 150 kA 150 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- Individually fused and thermally protected MOVs
-- Solid state bi-directional operation
-- EMI/RFI filtering: active tracking up to -50 db from 10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than 1 nanosecond response time
-- Relative humidity range: 0 -95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

Standard Configuration
-- Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure
-- Wire size: #8 AWG to 1/0
-- Standard size: 12 x 12 x 7 (305 mm x 305 mm x 178 mm) *
-- Standard weight: 20 lbs. (9.07 kg) *
*Internal disconnect options and other NEMA ratings may increase enclosure size and weight

UL 1449 3rd Edtion SPD

15
SPD Features SPD Monitoring Available Accessories
-- UL 1449 3rd Edition effective -- LED indicators -- RMSIE = Remote monitor
September 2009 -- Audible alarm with silence switch
-- Designed, manufactured and tested and test button Key Bid Specifications
consistent with: -- Dry contacts -- UL 1449 3rd Edition 2009, cUL
-- ANSI/IEEE C62.41.1-2002, -- Type 2 SPD
c62.41.2-2002, C62.45-2002, Available Options -- Protection modes on L-N, L-G, L-L, N-G
-- 1992/2000 NEMA LS-1 -- Surge counter -- In Rating 20 kA
-- NEC Article 285 -- Internal rotary disconnect switch -- Short Circuit Current Rating 200 kA
-- IEC 61643, CE -- Thru-door disconnect switch -- Surge Current Rating
-- Large block, individually fused, -- NEMA 4X non-metallic enclosure Per Phase = L-N + L-G + L-L
thermally protected, 50 kA MOVs -- NEMA 4X stainless steel enclosure 150 kA 50 kA 50 kA 50 kA
-- 10 year warranty -- Flush mount enclosure
-- NEMA 1 enclosure with extended display

Ordering Information

Catalogue # TPS3 o L12 oo o oo 2


Voltage Code Surge Current (kA) Enclosure Options
A = 120/240V, 1, 3W (Fig 1) 15 = 150 kA per phase 0 = Standard NEMA 1/12/3R/4 steel D = UL98 internal rotary disonnect
B = 120/240V, 3, 4W (Fig 3) 30 = 300 kA per phase V = NEMA 4X non-metallic T = UL98 thru-door disconnect
C = 120/208V, 3, 4W (Fig 2) 45 = 450 kA per phase S = NEMA 4X stainless steel X = Surge counter
E = 277/480V, 3, 4W (Fig 2) F = NEMA 1 flush mount
K = 380/220V, 3, 4W (Fig 2) P = NEMA 1 screwcover pullbox with extended display on 6 ft
S = 400/230V, 3, 4W (Fig 2) cable for line side mounting in SWBD/SWGR

-- Example: TPS3CL12150XD2 = 10 Mode, Type 2 SPD for a 208/120V application with a surge current
capacity of 150kA per phase, in a standard NEMA 1/12/3R/4 enclosure with a surge counter and internal
rotary disconnect option
-- When an option is not selected, include a zero (0) in the field

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 700 700 700 1000 Type 2 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 800 / 1500 700 / 1200 700 1800/1800 Type 2 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 700 700 700 1000 Type 2 20 kA 200 kA 150
E 277/480V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 2 20 kA 200 kA 320
K 380/220V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 2 20 kA 200 kA 320
S 400/230V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 2 20 kA 200 kA 320

Phase A (BLK) Phase A (BLK)


Siemens Canada Limited
Hot (BLK)
}V A B Phase B (BLK) Phase B (ORNG) 1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }V Oakville, ON L6H 0H6

}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
C Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
mentioned may be trademarks or registered
trademarks of their respective companies.
Notes:
Specifications are subject to change without
Type 1 UL notice.
For line side mounting in SWBD/SWGR
VPR may increase when disconnect switch is added www.siemens.ca/surge
VPR may decrease for 450 kA per phase www.siemens.ca
3.2.15.lh

16
TPS3 15
Type 1 Surge Protective Device (SPD)
For Line Side or Load Side Applications
Features:
UL 1449 3rd Edition 2009, cUL
Type 1 SPD (Type 2 cUL)
Mounts external to electrical distribution equipment
-- Recommended for line side or load side applications
When P option is selected, TPS3 15, Type 1 SPD mounts internal
to: SMP, FCI, FCII switchboards, Type WL low voltage switchgear and
TIASTAR motor control centres
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In (most models)
200 kA SCCR (most models)
Provides redundant replaceable module protection for low to high
exposure applications
All UL-required OCP & safety coordination included
UL96A Lightning Protection Master Label compliant (@ 20 kA In)

SPD Specifications
-- Surge Current Rating Per Phase
Per Phase L-N L-G N-G
600 kA 300 kA 300 kA 300 kA
800 kA 400 kA 400 kA 400 kA
1000 kA 500 kA 500 kA 500 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- Individually fused and thermally protected MOVs
-- Solid state bi-directional operation
-- EMI/RFI filtering: active tracking up to -50 db from 10 kHz to
100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than 1 nanosecond response time
-- Relative humidity range: 0 -95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

Standard Configuration
-- Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure
-- Internal rotary disconnect switch
-- Wire size: #8 AWG to 1/0
-- Standard size: 20 x 20 x 7 (508 mm x 508 mm x 178 mm) *
-- Standard weight: 64 lbs. (29 kg) *
*Other NEMA ratings may increase enclosure size and weight

UL 1449 3rd Edition SPD

17
SPD Features SPD Monitoring Available Accessories
-- UL 1449 3rd Edition effective -- LED indicators -- RMSIE = Remote monitor
September 2009 -- Audible alarm with silence switch
-- Designed, manufactured and tested and test button Key Bid Specifications
consistent with: -- Dry contacts -- UL 1449 3rd Edition 2009, cUL
-- ANSI/IEEE C62.41.1-2002, -- Type 2 SPD
c62.41.2-2002, C62.45-2002, Available Options
-- 1992/2000 NEMA LS-1 -- Surge counter -- Protection modes on L-N, L-G, L-L, N-G
-- NEC Article 285 -- Thru-door disconnect switch -- In Rating 20 kA
-- IEC 61643, CE -- NEMA 4X non-metallic enclosure -- Short Circuit Current Rating 200 kA
-- Large block, individually fused, thermally -- NEMA 4X stainless steel enclosure -- Surge Current Rating
protected, 50 kA MOVs -- Flush mount enclosure Per Phase = L-N + L-G
-- Internal rotary disconnect switch -- NEMA 1 enclosure with extended display 600 kA 300 kA 300 kA
-- 10 year warranty

Ordering Information

Catalogue # TPS3 o 15 oo o oo 2
Voltage Code Surge Current (kA) Enclosure Options
A = 120/240V, 1, 3W (Fig 1) 40 = 400 kA per phase 0 = Standard NEMA 1/12/3R/4 steel T = Thru-door disconnect
B = 120/240V, 3, 4W (Fig 3) 50 = 500 kA per phase V = NEMA 4X Non-metallic X = Surge counter
C = 120/208V, 3, 4W (Fig 2) 60 = 600 kA per phase S = NEMA 4X Stainless steel
D = 240V, 3, 3W (Fig 4) 80 = 800 kA per phase F = NEMA 1 Flush mount
E = 277/480V, 3, 4W (Fig 2) 1K = 1000 kA per phase P = NEMA 1 Screwcover pullbox with extended display on 5ft cable
F = 480V, 3, 3W (Fig 4) for line side mounting in SWBD/SWGR
G 600V, 3, 3W (Fig 4)
-- Example: TPS3C1560SX02 = Type 2 SPD for a 208/120V application with a surge current
K = 380/220V, 3, 4W (Fig 2) capacity of 600 kA per phase, in a NEMA 4X stainless steel enclosure with a surge counter
L = 600/347V, 3, 4W (Fig 2) option and standard disconnect switch
S = 400/230V, 3, 4W (Fig 2) -- When an option is not selected, include a zero (0) in the field

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L TYPE In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 600 600 700 1000 Type 2 20 kA 200 kA 150
B 120/240V, 3, 4W (Fig 3) 600 / 1000 600 / 1000 700 1000 Type 2 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 600 600 700 1000 Type 2 20 kA 200 kA 150
D 240V, 3, 3W (Fig 4) 1000 1800 Type 2 20 kA 200 kA 320
E 277/480V, 3, 4W (Fig 2) 1100 1000 1000 1800 Type 2 20 kA 200 kA 320
F 480V, 3, 3W (Fig 4) 1800 1800 Type 2 20 kA 200 kA 550
G 600V, 3, 3W (Fig 4) 2500 2500 Type 2 20 kA 200 kA 690
K 380/220V, 3, 4W (Fig 2) 1100 1000 1000 1800 Type 2 20 kA 200 kA 320
L 600/347V, 3, 4W (Fig 2) 1500 1500 1500 2500 Type 2 20 kA 200 kA 420
S 400/230V, 3, 4W (Fig 2) 1100 1000 1000 1800 Type 2 20 kA 200 kA 320

Phase A (BLK)
Siemens Canada Limited
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V 1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }
V Phase B (BLK) Oakville, ON L6H 0H6

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
C Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 Figure 4 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
Notes: mentioned may be trademarks or registered
trademarks of their respective companies.
Type 1 UL Specifications are subject to change without
For line side mounting in SWBD/SWGR notice.
Available in G voltage code only
Available in 600 kA & 800 kA only www.siemens.ca/surge
Available in 400 kA & 500 kA only www.siemens.ca
3.2.15.lh

18
TPS3 L15
True 10 Mode Protection
Type 1 Surge Protective Device (SPD)
For Line Side or Load Side Applications
Features:
UL 1449 3rd Edition 2009, cUL
Type 1 SPD (Type 2 cUL)
Mounts external to electrical distribution equipment
-- Recommended for line side or load side applications
When P option is selected, TPS3 15, Type 1 SPD mounts internal
to: SMP, FCI, FCII switchboards, Type WL low voltage switchgear and
TIASTAR motor control centres
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In (most models)
200 kA SCCR (most models)
Single TPS6 style replaceable modules
Provides redundant replaceable module protection for medium to
high exposure applications
Internal rotary disconnect switch included
All UL-required OCP & safety coordination included
UL96A Lightning Protection Master Label compliant (@ 20 kA In)

SPD Specifications
-- Directly connected discrete protection elements between all possible
modes providing true 10 mode protection
-- Surge Current Rating Per Phase
Per Phase L-N L-G L-L N-G
600 kA 300 kA 300 kA 300 kA 300 kA
900 kA 450 kA 450 kA 450 kA 450 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- Individually fused and thermally protected MOVs
-- Solid state bi-directional operation
-- EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than 1 nanosecond response time
-- Relative humidity range: 0 -95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

Standard Configuraton
-- Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure
-- Internal rotary disconnect switch
-- Wire size: #8 AWG to 1/0
-- Standard size: 20 X 20 X 7 (508 mm X 508 mm X 178 mm) *
-- Standard weight: 64 lbs. (29 kg) *
*Other NEMA ratings may increase enclosure size and weight

UL 1449 3rd Edition SPD

19
SPD Features SPD Monitoring Available Accessories
-- UL 1449 3rd Edition effective September -- LED indicators -- RMSIE = Remote monitor
2009 -- Audible alarm with silence switch
-- Designed, manufactured and tested and test button Key Bid Specifications
consistent with: -- Dry contacts -- UL 1449 3rd Edition 2009, cUL
-- ANSI/IEEE C62.41.1-2002, -- Type 2 SPD
c62.41.2-2002, C62.45-2002, Available Options -- Protection modes on L-N, L-G,
-- 1992/2000 NEMA LS-1 -- Surge counter L-L, N-G
-- NEC Article 285 -- Thru-door disconnect switch -- In Rating 20 kA
-- IEC 61643, CE -- NEMA 4X non-metallic enclosure -- Short Circuit Current Rating 200 kA
-- Large block, individually fused, -- NEMA 4X stainless steel enclosure -- Surge Current Rating
thermally protected, 50 kA MOVs -- Flush mount enclosure Per Phase = L-N + L-G + L-L
-- Internal rotary disconnect switch -- NEMA 1 enclosure with extended display 600 kA 200 kA 200 kA 200 kA
-- 10 year warranty

Ordering Information

Catalogue # TPS3 o L15 oo o oo 2


Voltage Code Surge Current (kA) Enclosure Options
A = 120/240V, 1, 3W (Fig 1) 60 = 600 kA per phase 0 = Standard NEMA 1/12/3R/4 steel T = Thru-door disconnect
B = 120/240V, 3, 4W (Fig 3) 90 = 900 kA per phase V = NEMA 4X non-metallic X = Surge counter
C = 120/208V, 3, 4W (Fig 2) S = NEMA 4X stainless steel
E = 277/480V, 3, 4W (Fig 2) F = NEMA 1 flush mount
K = 380/220V, 3, 4W (Fig 2) P = NEMA 1 screwcover pullbox with extended display on 6 ft
S = 400/230V, 3, 4W (Fig 2) cable for line side mounting in SWBD/SWGR
-- Example: TPS3CL15600X02 = 10 Mode, Type 2 SPD for a 208/120V application with a surge
current capacity of 600 kA per phase, in a standard NEMA 1/12/3R/4 enclosure with a surge
counter option
-- When an option is not selected, include a zero (0) in the field

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L TYPE In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 600 600 700 1000 Type 2 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 600 / 1100 600 / 1000 700 1000/1800 Type 2 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 600 600 700 1000 Type 2 20 kA 200 kA 150
E 277/480V, 3, 4W (Fig 2) 1100 1000 1000 1800 Type 2 20 kA 200 kA 320
K 380/220V, 3, 4W (Fig 2) 1100 1000 1000 1800 Type 2 20 kA 200 kA 320
S 400/230V, 3, 4W (Fig 2) 1100 1000 1000 1800 Type 2 20 kA 200 kA 320

Phase A (BLK) Phase A (BLK)


Siemens Canada Limited
Hot (BLK)
}V A B Phase B (BLK) Phase B (ORNG) 1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }V Oakville, ON L6H 0H6

}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
C Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.
Notes:
Type 1 UL www.siemens.ca/surge
For line side mounting in SWBD/SWGR www.siemens.ca
3.2.15.lh

20
TPS3 01
Surge Protection Device (SPD)
for P1, P2 Lighting Panelboards and P3 Power Distribution
Panelboards, Motor Control Centres and Busway Systems
Features:
Mounts internal to:
-- P1, P2 and P3 panels
-- TIASTAR motor control centres - standard 6 bucket
Consult factory for field retrofit in P1 panels
UL 1449 3rd Edition 2009, cUL
Type 4 SPD intended for use in Type 1 applications (Type 2 cUL)
UL Type 1 tested with all internal OCP and safety coordination
features included
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In (most models)
200 kA SCCR (most models)

Applications
-- Provides main service or downstream protection for sensitive
computer and electronic loads
-- Standard redundancy use: 100 kA per phase
-- Increased redundancy use: 200 kA per phase
-- Maximum redundancy use: 300 kA per phase

SPD Specification
-- Surge Current Rating Per Phase
Per Phase L-N L-G N-G
100 kA 50 kA 50 kA 50 kA
150 kA 100 kA 50 kA 50 kA
200 kA 100 kA 100 kA 100 kA
250 kA 150 kA 100 kA 100 kA
300 kA 150 kA 150 kA 150 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than nanosecond response time
-- Relative humidity range: 1-95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

UL 1449 3rd Edition SPD

21
SPD Features SPD Features Available Accessories
-- UL 1449 3rd Edition effective -- Direct bus connected or can be wired to a -- RMSIE = Remote monitor
September 2009 circuit breaker (include W option)
-- Designed, manufactured & tested -- 10 year warranty Key Bid Specifications
consistent with: -- UL 1449 3rd Edition - 2009, cUL
-- ANSI/IEEE C62.41.1-2002, Standard Monitoring -- Audible alarm with silence switch and test
C62.41.2-2002, and -- LED indicators button
C62.45-2002 -- Audible alarm with silence switch and test -- Dry contacts
-- 1992/2000 NEMA LS-1 button -- EMI/RFI filtering
-- NEC Article 285 -- Dry contacts -- Protection modes on L-N, L-G, L-L, N-G
-- IEC 61643, CE -- In Rating - 20 kA
-- Large block, individually fused, Available Options -- Short Circuit Current Rating - 200 kA
thermally protected, 50 kA MOVs -- Surge counter -- Surge Current Rating
-- Terminal lug for circuit breaker connection Per Phase = L-N + L-G
100 kA 50 kA 50 kA

Ordering Information

Catalogue # TPS3 o 01 oo ooo


Voltage Code Surge Current (kA) Options
A = 120/240V, 1, 3W (Fig 1) 10 = 100 kA per phase B = Busway application
B = 120/240V, 3, 4W (Fig 3) 15 = 150 kA per phase M = MCC application
C = 120/208V, 3, 4W (Fig 2) 20 = 200 kA per phase W = Terminal lug
D = 240V, 3, 3W (Fig 4) 25 = 250 kA per phase X = Surge counter
E = 277/480V, 3, 4W (Fig 2) 30 = 300 kA per phase
F = 480V, 3, 3W (Fig 4)
G = 600V, 3, 3W (Fig 4) -- Example: TPS3C0120X00 = SPD for a 208/120V panelboard with a surge current
K = 380/220V, 3, 4W (Fig 2) capacity of 200 kA per phase and a surge counter option
L = 600/347V, 3, 4W (Fig 2) -- When an option is not selected, include a zero (0) in the field
S = 400/230V, 3, 4W (Fig 2)

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 700 700 700 1200 Type 4 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 700 / 1200 700 / 1200 700 1800 / 1800 Type 4 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 700 700 700 1200 Type 4 20 kA 200 kA 150
D 240V, 3, 3W (Fig 4) 1200 1200 Type 4 10 kA 200 kA 320
E 277/480V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 4 20 kA 200 kA 320
F 480V, 3, 3W (Fig 4) 1800 1800 Type 4 10 kA 200 kA 550
G 600V, 3, 3W (Fig 4) 2500 2500 Type 4 10 kA 200 kA 690
K 380/220V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 4 20 kA 200 kA 320
L 600/347V, 3, 4W (Fig 2) 1500 1500 1500 2500 Type 4 10 kA 200 kA 420
S 400/230V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 4 20 kA 200 kA 320

Phase A (BLK)
Siemens Canada Limited
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V 1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK) Oakville, ON L6H 0H6

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
C Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 Figure 4 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.

Notes: www.siemens.ca/surge
Available 100 kA & 150 kA only www.siemens.ca
3.2.15.lh

22
TPS3 L1
True 10 Mode Protection
Surge Protection Device (SPD)
for P1, P2 Lighting and P3 Power Distribution Panelboards,
Motor Control Centres and Busway Systems
Features:
Mounts internal to:
-- P1, P2 and P3 panels
-- TIASTAR motor control centres - standard 6 bucket
Consult factory for field retrofit in P1 panels
UL 1449 3rd Edition 2009, cUL
Type 4 SPD intended for use in Type 1 applications (Type 2 cUL)
UL Type 1 tested with all internal OCP and safety coordination features
included
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In
200 kA SCCR (most models)

Applications
-- Provides main service or downstream protection for sensitive
computer and electronic loads
-- Standard redundancy use: 150 kA per phase
-- Maximum redundancy use: 300 kA per phase

SPD Specifications
-- Directly connected discrete protection elements between all possible
modes providing true 10 mode protection
-- Surge Current Rating Per Phase
Per Phase L-N L-G L-L N-G
150 kA 50 kA 50 kA 50 kA 50 kA
300 kA 100 kA 100 kA 100 kA 100 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than nanosecond response time
-- Relative humidity range: 1-95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

UL 1449 3rd Edition SPD

23
SPD Features SPD Features Available Accessories
-- UL 1449 3rd Edition effective -- Direct bus connected or can be wired to a -- RMSIE = Remote monitor
September 2009 circuit breaker (include W option)
-- Designed, manufactured & tested -- 10 year warranty Key Bid Specifications
consistent with: -- UL 1449 3rd Edition - 2009, cUL
-- ANSI/IEEE C62.41.1-2002, Standard Monitoring
-- Audible alarm with silence switch and test
C62.41.2-2002, and C62.45-2002 -- LED indicators
button
-- 1992/2000 NEMA LS-1 -- Audible alarm with silence switch and test
-- Dry contacts
-- NEC Article 285 button
-- EMI/RFI filtering
-- IEC 61643, CE -- Dry contacts
-- Protection modes on L-N, L-G, L-L, N-G
-- Large block, individually fused, -- In Rating - 20 kA
Available Options
thermally protected, 50 kA MOVs -- Short Circuit Current Rating - 200 kA
-- Surge counter
-- Terminal lug for circuit breaker connection -- Surge Current Rating
Per Phase = L-N + L-G + L-L
150 kA 50 kA 50 kA 50 kA

Ordering Information

Catalogue # TPS3 o L1 oo ooo


Voltage Code Surge Current (kA) Options
A = 120/240V, 1, 3W (Fig 1) 15 = 150 kA per phase B = Busway application
B = 120/240V, 3, 4W (Fig 3) 30 = 300 kA per phase M = MCC application
C = 120/208V, 3, 4W (Fig 2) W = Terminal lug
E = 277/480V, 3, 4W (Fig 2) X = Surge counter
K = 380/220V, 3, 4W (Fig 2) -- Example: TPS3CL130X00 = 10 Mode SPD for a 208/120V panelboard with a
S = 400/230V, 3, 4W (Fig 2) surge current capacity of 300 kA per phase and a surge counter option
-- When an option is not selected, include a zero (0) in the field

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 700 700 700 1000 Type 4 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 800 / 1500 700 / 1200 700 1800 / 1800 Type 4 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 700 700 700 1000 Type 4 20 kA 200 kA 150
E 277/480V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 4 20 kA 200 kA 320
K 380/220V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 4 20 kA 200 kA 320
S 400/230V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 4 20 kA 200 kA 320

Phase A (BLK) Phase A (BLK)


Siemens Canada Limited
Hot (BLK)
}V A B Phase B (BLK) Phase B (ORNG) 1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }V Oakville, ON L6H 0H6

}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
C Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.

www.siemens.ca/surge
www.siemens.ca
3.2.15.lh

24
TPS3 02
Surge Protection Device (SPD)
for Next Gen P1 Lighting Panelboards

Features:
Mounts internal to:
-- Next Gen P1 Lighting Panelboards
Consult factory for field retrofit in Next Gen P1 Lighting Panelboards
UL 1449 3rd Edition Recognized
UL 1283
Type 4 SPD intended for use in Type 1 applications (Type 2, cUL)
UL Type 1 tested with all internal OCP and safety coordination
features included
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In (most models)
200 kA SCCR (most models)
UL96A Lightning Protection Master Label appropriate (@ 20 kA In)

Applications
-- Provides main service or downstream protection for sensitive
computer and electronic loads
-- Standard redundancy use: 100 kA per phase
-- Increased redundancy use: 200 kA per phase
-- Maximum redundancy use: 300 kA per phase

SPD Specification
-- Surge Current Rating Per Phase
Per Phase L-N L-G N-G
100kA 50kA 50kA 50kA
150 kA 100 kA 50 kA 50 kA
200kA 100kA 100kA 100kA
250kA 150kA 100kA 100kA
300kA 150kA 150kA 150kA

-- 100% monitoring (Every MOV is monitored, incl. N-G)


-- EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than nanosecond response time
-- Relative humidity range: 1-95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

UL 1449 3rd Edition SPD

25
SPD Features SPD Features Key Bid Specifications
-- UL 1449 3rd Edition effective -- Direct bus connected -- UL 1449 3rd Edition Recognized
September 2009 -- Can be wired to a circuit breaker (consult -- UL 1283
-- Designed, manufactured & tested factory at time of order or see installation -- Audible alarm with silence switch
consistent with: manual for retrofit) and test button
-- ANSI/IEEE C62.41.1-2002, -- 10 year warranty -- Dry contacts
C62.41.2-2002, and -- EMI/RFI filtering
C62.45-2002 Standard Monitoring -- Protection modes on L-N, L-G, L-L, N-G
-- 1992/2000 NEMA LS-1 -- LED indicators -- In Rating - 20 kA
-- NEC Article 285 -- Audible alarm with silence switch and test -- Short Circuit Current Rating - 200 kA
-- IEC 61643, CE button -- Surge Current Rating
-- Large block, individually fused, -- Dry contacts Per Phase = L-N + L-G
thermally protected, 50 kA MOVs 100 kA 50 kA 50 kA
Available Options
-- Surge counter
-- Terminal lug for circuit breaker connection

Ordering Information

Catalog # TPS3 o 02 oo o
Voltage Code Surge Current (kA) Options
A = 120/240V, 1, 3W (Fig 1) 10 = 100 kA per phase X = Surge counter
B = 120/240V, 3, 4W (Fig 3) 15 = 150 kA per phase
C = 120/208V, 3, 4W (Fig 2) 20 = 200 kA per phase
D = 240V, 3, 3W (Fig 4) 25 = 250 kA per phase
E = 277/480V, 3, 4W (Fig 2) 30 = 300 kA per phase
F = 480V, 3, 3W (Fig 4)
G = 600V, 3, 3W (Fig 4) -- Example: TPS3C0220X = SPD for a 208/120V panelboard with a surge current capacity of 200
K = 380/220V, 3, 4W (Fig 2) kA per phase and a surge counter option
L = 600/347V, 3, 4W (Fig 2) -- When an option is not selected, include a zero (0) in the field
S = 400/230V, 3, 4W (Fig 2) Available Accessories: Ordered Separately
-- RMSIE - Remote monitor

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3kA)
Voltage Code Service Voltage L-N L-G N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 700 700 700 1200 Type 4 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 700 / 1200 700 / 1200 700 1800 / 1800 Type 4 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 700 700 700 1200 Type 4 20 kA 200 kA 150
D 240V, 3, 3W (Fig 4) 1200 1200 Type 4 10 kA 200 kA 320
E 277/480V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 4 20 kA 200 kA 320
F 480V, 3, 3W (Fig 4) 1800 1800 Type 4 10 kA 200 kA 550
G 600V, 3, 3W (Fig 4) 2500 2500 Type 4 10 kA 200 kA 690
K 380/220V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 4 20 kA 200 kA 320
L 600/347V, 3, 4W (Fig 2) 1500 1500 1500 2500 Type 4 10 kA 200 kA 420
S 400/230V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 4 20 kA 200 kA 320

Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V Siemens Canada Limited
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK) 1577 North Service Road East

}
Phase C (BLK)
Hot (BLK)
V Phase C (BLK) Oakville, ON L6H 0H6
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)
SPD Hotline: 888.333.3545
info@purgethesurge.com
Figure 1 Figure 2 Figure 3 Figure 4
2013 Siemens Canada Limited, Inc.
Split Wye Hi-Leg Delta (B High) Delta & HRG Wye All Rights Reserved. Siemens is a registered
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), 3 Hots, 1 Grnd
trademark of Siemens AG. Product names
1 Neu, 1 Grnd
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.
Notes:
Available 100 kA & 150 kA only www.siemens.ca/surge
www.siemens.ca
6.26.15.lh
26
TPS3 L2
True 10 Mode Protection
Surge Protection Device (SPD)
for Revised P1 Lighting Distribution Panelboards

Features:
Mounts internal to:
-- Revised P1 Lighting Panelboards
Consult factory for field retrofit in Revised P1 Lighting Panelboards
UL 1449 3rd Edition Recognized
UL 1283
Type 4 SPD intended for use in Type 1 applications (Type 2, cUL)
UL Type 1 tested with all internal OCP and safety coordination
features included
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In (most models)
200 kA SCCR (most models)
UL96A Lightning Protection Master Label appropriate (@ 20 kA In)

Applications
-- Provides main service or downstream protection for sensitive computer
and electronic loads
-- Standard redundancy use: 150 kA per phase
-- Maximum redundancy use: 300 kA per phase

SPD Specifications
-- Directly connected discrete protection elements between all possible
modes providing true 10 mode protection
-- Surge Current Rating Per Phase
Per Phase L-N L-G L-L N-G
150 kA 50 kA 50 kA 50 kA 50 kA
300 kA 100 kA 100 kA 100 kA 100 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than nanosecond response time
-- Relative humidity range: 1-95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

UL 1449 3rd Edition SPD

27
SPD Features SPD Features Key Bid Specifications
-- UL 1449 3rd Edition effective -- Direct bus connected -- UL 1449 3rd Edition Recognized - 2009
September 2009 -- Can be wired to a circuit breaker (consult -- UL 1283
-- Designed, manufactured & tested factory at time of order or see installation -- Audible alarm with silence switch and
consistent with: manual for retrofit) test button
-- ANSI/IEEE C62.41.1-2002, -- 10 year warranty -- Dry contacts
C62.41.2-2002, and C62.45-2002 -- EMI/RFI filtering
-- 1992/2000 NEMA LS-1 Standard Monitoring -- Protection modes on L-N, L-G, L-L, N-G
-- NEC Article 285 -- LED indicators -- In Rating - 20 kA
-- IEC 61643, CE -- Audible alarm with silence switch and test -- Short Circuit Current Rating - 200 kA
-- Large block, individually fused, button -- Surge Current Rating
thermally protected, 50 kA MOVs -- Dry contacts Per Phase = L-N + L-G + L-L
150 kA 50 kA 50 kA 50 kA
Available Options
-- Surge counter
-- Terminal lug for circuit breaker connection

Ordering Information

Catalog # TPS3 o L2 oo oo
Voltage Code Surge Current (kA) Options
A = 120/240V, 1, 3W (Fig 1) 15 = 150 kA per phase W = Terminal lug
B = 120/240V, 3, 4W (Fig 3) 30 = 300 kA per phase X = Surge counter
C = 120/208V, 3, 4W (Fig 2)
E = 277/480V, 3, 4W (Fig 2)
K = 380/220V, 3, 4W (Fig 2)
S = 400/230V, 3, 4W (Fig 2) -- Example: TPS3CL230X0 = 10 Mode SPD for a 208/120V panelboard with a
surge current capacity of 300 kA per phase and a surge counter option
-- When surge counter is not selected, include a zero (0) in the field
Available Accessories: Ordered Separately
-- RMSIE - Remote monitor

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 700 700 700 1000 Type 4 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 800 / 1500 700 / 1200 700 1800 / 1800 Type 4 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 700 700 700 1000 Type 4 20 kA 200 kA 150
E 277/480V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 4 20 kA 200 kA 320
K 380/220V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 4 20 kA 200 kA 320
S 400/230V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 4 20 kA 200 kA 320

Hot (BLK) Phase A (BLK) Phase A (BLK)


}V A B Phase B (BLK) Phase B (ORNG) Siemens Canada Limited
}V Neutral (WHT)
N
Neutral (WHT) }V 1577 North Service Road East

}
Phase C (BLK)
Hot (BLK)
V Oakville, ON L6H 0H6
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)
SPD Hotline: 888.333.3545
info@purgethesurge.com
Figure 1 Figure 2 Figure 3
2013 Siemens Canada Limited, Inc.
Split Wye Hi-Leg Delta (B High)
All Rights Reserved. Siemens is a registered
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High),
trademark of Siemens AG. Product names
1 Neu, 1 Grnd
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.

www.siemens.ca/surge
www.siemens.ca
2.16.15.lh
28
TPS3 05
Surge Protection Device (SPD)
for S5 & F2 Powerpanel and SMP, FC1, FC2
Distribution Switchboards
Features:
Mounts internal to:
-- S5 & F2 powerpanel and distribultion switchboards
UL 1449 3rd Edition 2009, cUL
Type 1 SPD (Type 2 cUL)
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In (most models)
200 kA SCCR (most models)
All UL-required OCP & safety coordination included

Panelboard Features
-- Copper or aluminum bus
-- MB or MLO

Switchboard Features
-- Copper or aluminum bus
-- 200% rated neutral bus for harmonic-rich applications
-- CSA, UL 891, UL 67 and NEMA PB-2

Applications
-- Provides main service or downstream protection for sensitive
computer and electronic loads
-- Standard redundancy use: 100 kA per phase
-- Increased redundancy use: 200 kA per phase
-- Maximum redundancy use: 300 kA per phase

SPD Specifications
-- Surge Current Rating Per Phase
Per Phase L-N L-G N-G
100 kA 50 kA 50 kA 50 kA
150 kA 100 kA 50 kA 50 kA
200 kA 100 kA 100 kA 100kA
250 kA 150 kA 100 kA 100 kA
300 kA 150 kA 150 kA 150 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than nanosecond response time
-- Relative humidity range: 1-95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

UL 1449 3rd Edition SPD

29
SPD Features SPD Monitoring Key Bid Specifications
-- UL 1449 3rd Edition effective -- LED indicators -- UL 1449 3rd Edition - 2009, cUL
September 2009 -- Audible alarm with silence switch and test -- Audible alarm with silence switch and test
-- Designed, manufactured & button button
tested consistent with: -- Dry contacts -- Type 2 SPD
-- ANSI/IEEE C62.41.1-2002, -- Dry contacts
C62.41.2-2002, and Available Options -- EMI/RFI filtering
C62.45-2002 -- Surge counter -- Protection modes on L-N, L-G, L-L, N-G
-- 1992/2000 NEMA LS-1 -- In Rating - 20 kA
-- NEC Article 285 Available Accessories -- Short Circuit Current Rating - 200 kA
-- IEC 61643, CE -- RMSIE = Remote monitor -- Surge Current Rating
-- Large block, individually fused, Per Phase = L-N + L-G
thermally protected, 50 kA MOVs 100 kA 50 kA 50 kA
-- Internal rotary disconnect switch
-- 10 year warranty

Ordering Information

Catalogue # TPS3 o 05 oo o 2
Voltage Code Surge Current (kA) Options
A = 120/240V, 1, 3W (Fig 1) 10 = 100 kA per phase X = Surge counter
B = 120/240V, 3, 4W (Fig 3) 15 = 150 kA per phase
C = 120/208V, 3, 4W (Fig 2) 20 = 200 kA per phase
D = 240V, 3, 3W (Fig 4) 25 = 250 kA per phase
E = 277/480V, 3, 4W (Fig 2) 30 = 300 kA per phase
F = 480V, 3, 3W (Fig 4) -- Example: TPS3C0530X2 = Type 2 SPD for a 208/120V power panel with a surge
G = 600V, 3, 3W (Fig 4) current capacity of 300 kA per phase and a surge counter option
K = 380/220V, 3, 4W (Fig 2) -- When an option is not selected, include a zero (0) in the field
L = 600/347V, 3, 4W (Fig 2)
S = 400/230V, 3, 4W (Fig 2)

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 800 700 700 1200 Type 2 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 800 / 1500 700 / 1200 700 1800 / 1800 Type 2 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 800 700 700 1200 Type 2 20 kA 200 kA 150
D 240V, 3, 3W (Fig 4) 1200 1500 Type 2 20 kA 200 kA 320
E 277/480V, 3, 4W (Fig 2) 1500 1200 1200 2500 Type 2 20 kA 200 kA 320
F 480V, 3, 3W (Fig 4) 1800 1800 Type 2 10 kA 200 kA 552
G 600V, 3, 3W (Fig 4) 2500 2500 Type 2 10 kA 200 kA 690
K 380/220V, 3, 4W (Fig 2) 1500 1200 1200 2500 Type 2 20 kA 200 kA 320
L 600/347V, 3, 4W (Fig 2) 1500 1500 1500 2500 Type 2 10 kA 200 kA 420
S 400/230V, 3, 4W (Fig 2) 1500 1200 1200 2500 Type 2 20 kA 200 kA 320

Phase A (BLK)
Siemens Canada Limited
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V 1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK) Oakville, ON L6H 0H6

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
C Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 Figure 4 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.
Notes:
Type 1 UL www.siemens.ca/surge
Available 100 kA & 150 kA only www.siemens.ca
3.2.15.lh

30
TPS3 L5
True 10 Mode Protection
Surge Protection Device (SPD)
for S5 & F2 Powerpanels and SMP, FC1, FC2
Distribution Switchboards
Features:
Mounts internal to:
-- S5 & F2 powerpanels and distribution switchboards
UL 1449 3rd Edition 2009, cUL
Type 1 SPD (Type 2 cUL)
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In (most models)
200 kA SCCR (most models)
All UL required OCP & safety coordination included

Panelboard
-- Copper or aluminum bus
-- MB or MLO

Switchboard Features
-- Copper or aluminum bus
-- 200% rated neutral bus for harmonic-rich applications
-- CSA, UL 891, UL 67 and NEMA PB-2

Applications
-- Provides main service or downstream protection for sensitive
computer and electronic loads
-- Standard redundancy use: 150 kA per phase
-- Maximum redundancy use: 300 kA per phase

SPD Specifications
-- Directly connected discrete protection elements between
all possible modes providing true 10 mode protection
-- Surge Current Rating Per Phase
Per Phase L-N L-G N-G
150 kA 50 kA 50 kA 50 kA
300 kA 100 kA 100 kA 100 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- EMI/RFI filtering: active tracking up to -50 db from
10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than nanosecond response time
-- Relative humidity range: 1-95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

UL 1449 3rd Edition SPD

31
SPD Features SPD Monitoring Available Accessories
-- UL 1449 3rd Edition effective -- LED indicators -- RMSIE = Remote monitor
September 2009 -- Audible alarm with silence switch and test
-- Designed, manufactured & tested button Key Specifications
consistent with: -- Dry contacts -- UL 1449 3rd Edition - 2009, cUL
-- ANSI/IEEE C62.41.1-2002, -- Internal rotary disconnect switch -- Type 2 SPD
C62.41.2-2002, and C62.45-2002 -- Audible alarm with silence switch and test
-- 1992/2000 NEMA LS-1 Available Options button
-- NEC Article 285 -- Surge counter -- Dry Contacts
-- IEC 61643, CE -- EMI/RFI Filtering
-- Large block, individually fused, -- Protection modes on L-N, L-G, L-L, N-G
thermally protected, 50 kA MOVs -- In Rating - 20 kA
-- Direct bus connected or can be wired to a -- Short Circuit Current Rating - 200 kA
circuit breaker (include W option) -- Surge Current Rating
-- 10 year warranty Per Phase = L-N + L-G + L-L
150 kA 50 kA 50 kA 50 kA

Ordering Information

Catalogue # TPS3 o L5 oo o 2
Voltage Code Surge Current (kA) Options
A = 120/240V, 1, 3W (Fig 1) 15 = 150 kA per phase X = Surge Counter
B = 120/240V, 3, 4W (Fig 3) 30 = 300 kA per phase
C = 120/208V, 3, 4W (Fig 2)
E = 277/480V, 3, 4W (Fig 2) -- Example: TPS3CL530X2 = 10 mode, Type 2 SPD for a 208/120V Power Panel with a
K = 380/220V, 3, 4W (Fig 2) surge current capacity of 300 kA per phase and a surge counter option
S = 400/230V, 3, 4W (Fig 2) -- When an option is not selected include, a zero (0) in the field

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 700 700 700 1200 Type 2 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 800 / 1500 700 / 1200 700 1800/1800 Type 2 20 kA 200 kA 150 / 320
C 120/208V, 3, 4W (Fig 2) 700 700 700 1000 Type 2 20 kA 200 kA 150
E 277/480V, 3, 4W (Fig 2) 1500 1200 1200 1800 Type 2 20 kA 200 kA 320
K 380/220V, 3, 4W (Fig 2) 1500 1200 1200 1800 Type 2 20 kA 200 kA 320
S 400/230V, 3, 4W (Fig 2) 1500 1200 1200 1800 Type 2 20 kA 200 kA 320

Phase A (BLK) Phase A (BLK)


Siemens Canada Limited
Hot (BLK)
}V A B Phase B (BLK) Phase B (ORNG) 1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }
V Oakville, ON L6H 0H6

}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
C Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.

Notes: www.siemens.ca/surge
Type 1 UL www.siemens.ca
3.2.15.lh

32
TPS3 06
Surge Protection Device (SPD)
for Service Entrance Applications FC1, FC2
Switchboards, Type WL Low Voltage Switchgear, Motor
Control Centres and Busway Systems
Features:
Mounts internal to:
-- FC1, FC2 switchboards
-- Type WL low voltage switchgear
-- TIASTAR motor control centres - standard 12 bucket
UL 1449 3rd Edition 2009, cUL
Type 4 SPD intended for use in Type 1 applications (Type 2 cUL)
UL Type 1 tested with all internal OCP and safety coordination
features included
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In (most models)
200 kA SCCR (most models)
Rotary disconnect switch included
All UL-required OCP & safety coordination included
Applications
-- Provides main service entrance or downstream protection for sensitive
computer and electronic loads
-- Standard redundancy use: 300 kA per phase
-- Increased redundancy use: 400 kA per phase
-- Maximum redundancy use: 500 kA per phase

SPD Specifications
-- Surge Current Rating Per Phase
Per Phase L-N L-G N-G
100 kA 50 kA 50 kA 50 kA
150 kA 100 kA 50 kA 50 kA
200 kA 100 kA 100 kA 100 kA
250 kA 150 kA 100 kA 100 kA
300 kA 150 kA 150 kA 150 kA
400 kA 200 kA 200 kA 200 kA
500 kA 250 kA 250 kA 250 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than nanosecond response time
-- Relative humidity range: 1-95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

UL 1449 3rd Edition SPD

33
SPD Features SPD Monitoring Available Accessories
-- UL 1449 3rd Edition effective -- LED indicators -- RMSIE = Remote monitor
September 2009 -- Ribbon Length -- WHXWDP120 = 10 Display cable
-- Designed, manufactured & tested -- 60 Standard extension
consistent with: -- 30 MCC
-- ANSI/IEEE C62.41.1-2002, -- Audible alarm with silence switch and test Key Bid Specifications
C62.41.2-2002, and C62.45-2002 button -- UL 1449 3rd Edition - 2009, cUL
-- 1992/2000 NEMA LS-1 -- Dry contacts -- Audible alarm with silence switch and test
-- NEC Article 285 button
-- IEC 61643, CE Available Options -- Dry contacts
-- Large block, individually fused, -- Surge counter -- EMI/RFI filtering
thermally protected, 50 kA MOVs -- Protection modes on L-N, L-G, L-L, N-G
-- Rotary disconnect switch -- In Rating - 20 kA
-- 10 year warranty -- Short Circuit Current Rating - 200 kA
-- Surge Current Rating
Per Phase = L-N + L-G
300 kA 150 kA 150 kA
Ordering Information

Catalogue # TPS3 o 06 oo oo
Voltage Code Surge Current (kA) Options
A = 120/240V, 1, 3W (Fig 1) 10 = 100 kA per phase B = Busway application
B = 120/240V, 3, 4W (Fig 3) 15 = 150 kA per phase M = MCC application
C = 120/208V, 3, 4W (Fig 2) 20 = 200 kA per phase X = Surge counter
D = 240V, 3, 3W (Fig 4) 25 = 250 kA per phase
E = 277/480V, 3, 4W (Fig 2) 30 = 300 kA per phase
F = 480V, 3, 3W (Fig 4) 40 = 400 kA per phase
G = 600V, 3, 3W (Fig 4) 50 = 500 kA per phase
K = 380/220V, 3, 4W (Fig 2) -- Example: TPS3C0640X0 = SPD for a 208/120V switchboard with a surge current capacity of
L = 600/347V, 3, 4W (Fig 2) 400 kA per phase and a surge counter option
S = 400/230V, 3, 4W (Fig 2) -- When an option is not selected, include a zero (0) in the field

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3kA)
Voltage Code Service Voltage L-N L-G N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 700 700 700 1200 Type 4 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 700 / 1200 700 / 1200 700 1800 / 1800 Type 4 20 kA 200 kA 150 / 275
C 120/208V, 3, 4W (Fig 2) 700 700 700 1200 Type 4 20 kA 200 kA 150
D 240V, 3, 3W (Fig 4) 1200 1200 Type 4 20 kA 200 kA 320
E 277/480V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 4 20 kA 200 kA 320
F 480V, 3, 3W (Fig 4) 1800 1800 Type 4 20 kA 200 kA 550
G 600V, 3, 3W (Fig 4) 2500 2500 Type 4 10 kA 200 kA 690
K 380/220V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 4 20 kA 200 kA 320
L 600/347V, 3, 4W (Fig 2) 1500 1500 1500 2500 Type 4 20 kA 200 kA 420
S 400/230V, 3, 4W (Fig 2) 1200 1200 1200 2000 Type 4 20 kA 200 kA 320

Phase A (BLK)
Siemens Canada Limited
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V 1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK) Oakville, ON L6H 0H6

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
C Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 Figure 4 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
Notes: trademark of Siemens AG. Product names
mentioned may be trademarks or registered
G voltage code only available in 200 & 250 kA
trademarks of their respective companies.
Not available in 500 kA
Specifications are subject to change without
VPR may increase when disconnect switch is added notice.
VPR may decrease for products 400 & 500 kA per phase
In rating for 100 - 300 kA per phase is 10 kA www.siemens.ca/surge
www.siemens.ca
3.2.15.lh

34
TPS3 L6
True 10 Mode Protection
Surge Protection Device (SPD)
for Service Entrance Applications FC1, FC2
Switchboards, Type WL Low Voltage Switchgear, Motor
Control Centres and Busway Systems

Features:
Mounts internal to:
-- FC1, and FC2 switchboards
-- Type WL low voltage switchgear
-- TIASTAR motor control centres - standard 12 bucket
-- STP series busplug on SX series busway
UL 1449 3rd Edition 2009, cUL
Type 4 SPD intended for use in Type 1 applications (Type 2 cUL)
UL Type 1 tested with all internal OCP and safety coordination
features included
Large block, individually fused, thermally protected, 50 kA MOVs
20 kA In
200 kA SCCR (most models)
Rotary disconnect switch included
All UL required OCP & safety coordination included

Applications
-- Provides main service entrance or downstream protection for sensitive
computer and electronic loads
-- Standard redundancy use: 300 kA per phase
-- Maximum redundancy use: 450 kA per phase

SPD Specifications
-- Surge Current Rating Per Phase
Per Phase L-N L-G L-L N-G
150 kA 50 kA 50 kA 50 kA 50 kA
300 kA 100 kA 100 kA 100 kA 100 kA
450 kA 150 kA 150 kA 150 kA 150 kA
-- 100% monitoring (Every MOV is monitored, incl. N-G)
-- EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
-- Repetitive impulse: 5,000 hits
-- Less than nanosecond response time
-- Relative humidity range: 1-95% non-condensing
-- Operating frequency: 47-63 Hz
-- Operating temperature: -25C (-15F) to +60C (140F)

UL 1449 3rd Edition SPD

35
SPD Features SPD Monitoring Available Accessories
-- UL 1449 3rd Edition effective -- LED indicators -- RMSIE = Remote monitor
September 2009 -- Audible alarm with silence switch and test
-- Designed, manufactured & tested button Key Bid Specifications
consistent with: -- Dry contacts -- UL 1449 3rd Edition - 2009, cUL
-- ANSI/IEEE C62.41.1-2002, -- Rotary disconnect switch -- Audible alarm with silence switch and test
C62.41.2-2002, and C62.45-2002 button
-- 1992/2000 NEMA LS-1 Available Options -- Dry contacts
-- NEC Article 285 -- Surge counter -- EMI/RFI filtering
-- IEC 61643, CE -- Protection modes on L-N, L-G, L-L, N-G
-- Large block, individually fused, -- In Rating - 20 kA
thermally protected, 50 kA MOVs -- Short Circuit Current Rating - 200 kA
-- 10 year warranty -- Surge Current Rating
Per Phase = L-N + L-G + L-L
300 kA 100 kA 100 kA 100 kA

Ordering Information

Catalogue # TPS3 o L6 oo oo
Voltage Code Surge Current (kA) Options
A = 120/240V, 1, 3W (Fig 1) 15 = 150 kA per phase B = Busway application
B= 120/240V, 3, 4W (Fig 3) 30 = 300 kA per phase M = MCC application
C= 120/208V, 3, 4W (Fig 2) 45 = 450 kA per phase X = Surge counter
E = 277/480V, 3, 4W (Fig 2)
-- Example: TPS3CL645X0 = 10 mode SPD for a 208/120V switchboard with a
K = 380/220V, 3, 4W (Fig 2)
surge current capacity of 450 kA per phase and a surge counter option
S = 400/230V, 3, 4W (Fig 2) -- When an option is not selected, include a zero (0) in the field

UL 1449 3rd Edition - 2009 Test Data Summary


Voltage Protection Rating (VPR - 6kV, 3 kA)
Voltage Code Service Voltage L-N L-L N-G L-L Type In SCCR MCOV
A 120/240V, 1, 3W (Fig 1) 700 700 700 1000 Type 4 20 kA 100 kA 150
B 120/240V, 3, 4W (Fig 3) 800 / 1500 700 / 1200 700 1800/1800 Type 4 20 kA 200 kA 150 / 275
C 120/208V, 3, 4W (Fig 2) 700 700 700 1000 Type 4 20 kA 200 kA 150
E 277/480V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 4 20 kA 200 kA 320
K 380/220V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 4 20 kA 200 kA 320
S 400/230V, 3, 4W (Fig 2) 1200 1200 1200 1800 Type 4 20 kA 200 kA 320

Phase A (BLK) Phase A (BLK)


Siemens Canada Limited
Hot (BLK)
}V A B Phase B (BLK) Phase B (ORNG) 1577 North Service Road East
}V Neutral (WHT)
N
Neutral (WHT) }V Oakville, ON L6H 0H6

}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) SPD Hotline: 888.333.3545
C Ground (GRN)
info@purgethesurge.com

Figure 1 Figure 2 Figure 3 2013 Siemens Canada Limited, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.
Notes:
VPR may increase when disconnect switch is added www.siemens.ca/surge
VPR may decrease for 450 kA per phase www.siemens.ca
3.2.15.lh

36
www.siemens.ca/surge

Frequently Asked Questions

WHAT IS A SURGE PROTECTIVE DEVICE OR SPD? WHAT TYPES OF COMPONENTS MAKE UP A SPD?
A Surge Protective Device is a device that attenuates (reduces in The device most commonly used in AC voltage surge suppressors are
magnitude) random, high energy, short duration overvoltages caused by MOVs, a solid-state device made of zinc oxide materials.
lightning, utilities, switching, etc. Such anomalies occur in the form of
voltage and current spikes with a duration of less than half an ac voltage MOVs are voltage sensitive semiconductors, which change from high
cycle. These high energy power spikes can damage sensitive electronic impedance to low impedance when sensing an overvoltage condition.
equipment, such as computers, instrumentation, and process controllers. MOVs are packaged for specific voltages and current handling capacities.

HOW DO SPDs WORK? Other devices (more typically found in DC applications) include single
Surge Suppressors divert high energy power away from a load by junction diodes and gas tubes that ionize at preset voltages.
providing a lower impedance path to common point earth ground. This
is similar in concept to pressure relief valves that protect water heaters WHAT FEATURES SHOULD BE CONSIDERED
from overpressure. Surge suppressors used most often for protection of WHEN SELECTING SPDs?
AC Power have metal oxide varistors (MOVs) connected in parallel. Two important areas to consider during the selection of a surge suppressor
are performance and safety, and include the following criteria:
WHERE ARE SPDs INSTALLED?
AC voltage surge suppressors are typically installed in these three areas: at Performance: 1) surge current capacity; and 2) clamping voltage.
a utility service entrance for protection of an entire facility, in distribution
panelboards and switchboards for protection of sensitive downstream Safety: 1) the individual suppression circuit should be fused to clear
loads; connected to a wall outlet for individual protection of a specific piece an inoperative MOV during an extreme transient event, and 2) provide
of equipment, such as a computer or solid-state controller. overcurrent protection for the surge suppressor during a fault condition.

WHAT IS CLAMPING VOLTAGE? WHAT SURGE CURRENT CAPACITY IS REQUIRED?


Clamping voltage, also referred to as peak let through or suppressed voltage Surge current capacity is dependent on the application and the amount of
rating, is the amount of voltage a surge suppressor permits to pass through required protection. The selection of the proper surge suppressor is not an
it to the attached load during a transient event. Clamping voltage is a exact science and cannot be scientifically calculated from a standard algorithm.
performance measurement of a surge suppressors ability to attenuate a
transient. For example, a surge suppressor might limit a 6,000V surge so Questions to consider when specifying the proper surge current capacity
that only 700V is visible to the load. The Voltage Protection Rating is 700V, for a surge suppressor include:
commonly called Clamping Voltage. This performance value is confirmed by
Underwriters Laboratories during tests conducted while evaluating a surge What is the geographic location of the facility and its susceptibility to
suppressor for listing. lightning? (For example, Florida is a high-lightning area; California is a
low lightning area.)
Is the facility in a rural or urban setting?
WHAT IS SURGE CURRENT CAPACITY? Is the facility the tallest building around?
Surge current capacity is the maximum amount of surge current that a
Is the facility at the end of the utility grid?
surge suppressor can pass for a single transient event. This level is used to
If it is an existing facility, what is its power quality history?
indicate the protection capacity of a particular surge suppressor design,
and when specifying surge suppressors. For example, in a high exposure
Based on the above information, and taking into account the cost of
application with very large transients present from lightning, a higher
protection, the following is a good rule of thumb: a surge suppressor with
level surge current capacity might be desired. Be aware that surges have
a surge current capacity in the range of 100kA to 300kA would be used in
natural limitations and that larger surge current capacity tends to add
conjunction with a service entrance panelboard or switchboard. A surge
redundancy rather than the implied ability to handle an extremely large
suppressor with a surge current capacity in the range of 100kA to 200kA
surge. For example, an entire lightning strike cannot go through wire; it is
would be used in conjunction with a downstream panelboard.
much like trying to put the output from a fire hose through a soda straw.
Consequently, suppressors do not need to be sized for entire lightning
strikes. There are valid reasons for adding excess surge current capacity
for redundancy reasons.

37
www.siemens.ca/surge

Siemens SPD Team


Services and Support
Our Commitment to You

As our commitment to you, the Siemens SPD Team is here to assist you with all of your surge
protection needs. Each region is designated with a highly trained representative to provide
you with the best support possible.

Pre-Bid Support Post-Bid Support

Over 1000 jobs are downloaded per month from Project Tracking to Conclusion
the Electronic Plan Rooms, which provides us with
complete take-offs, from drawings & specs. Electrical Contractor Award Notification
Notifications are sent to the Siemens Sales Engineer After bid day, we determine which Electrical
and Siemens distributor, listing the jobs bidding in Contractor won the job.
your area. Electrical Contractor information is promptly sent to
Detailed quotes with product information are sent to the Siemens Sales Engineer and Siemens Distributor to
the Siemens Sales Engineer and Siemens distributor to make sure they are the first to know.
enter into COMPAS or Industry Mall.
Prior Approval Packages (PAPs) are sent on any jobs where Job Follow Up
Siemens Surge Protective Devices are not approved. Ensures that you are competitively priced to win job.
1. Sending PAPs allow us to identify Consulting Engineers Shop Drawing Submittals are provided to Siemens
who specify Siemens gear but not Surge Protective Sales Engineer and Siemens Distributor.
Devices. This is done in an effort to gain approval. Engineering support is provided for any rejections or
2. We have over 27 years of approval history questions from Consulting Engineers.
documented in our proprietary database.
Ongoing Support

Customized Collaterals (i.e. flyers, handouts)


Design Guides
Proper Product Selection Recommendations
Competitor Product Comparison
Specification Interpretation
Webinars/Lunch & Learns
On Site Visits
Seminars at the Factory for CEU/PDH Credits
24/7 Online SPD Training via www.usa.siemens.com/step
Troubleshooting
Product Forensics
Returns

38
www.siemens.ca/surge

Thank you...
for choosing Siemens for your surge protection needs.

Your Technical Support Team is here to assist you.

(888) 333-3545
Learn more about our new UL 1449 3rd Edition TPS3 Surge Protective Devices (SPDs) by visiting:
Step 2000 - Basics of Surge Protection at www.usa.siemens.com/step.
39
Siemens Canada Limited
1577 North Service Road East
Oakville, ON l6H 0H6

SPD Hotline: 888.333.3545


info@purgethesurge.com

2015 Siemens Industry, Inc.


All Rights Reserved. Siemens is a registered
trademark of Siemens AG. Product names
mentioned may be trademarks or registered
trademarks of their respective companies.
Specifications are subject to change without
notice.

www.siemens.ca/surge