Professional Documents
Culture Documents
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for
testing or instructional purposes only to students enrolled in courses for which the textbook has been
adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108
of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
Requests for permission or further information should be addressed to the Permission Department, John
Wiley & Sons, Inc, 111 River Street, Hoboken, NJ 07030.
Chapter 1
0.04 Ibm/(ft-hr) Ns
(c) x1.488 = 16.5
3600 sec/hr m2
Btu 1
(e) 12,000 x = 3.52 kW
Ibm 3.412
Ibf
(f) 14.7 x 6894.76 = 101 kPa
in2
lbf / in2
1-2 (a) 120 kPa x = 17.4 lbf/in2
6.89476kPa
W
(b) 100 x 0.5778 = 57.8 Btu/hr-ft-F
m K
W
(c) 0.8 2
x 0.1761 = 0.14 Btu/hr-ft2-F
m K
1 lbm
(d) 10-6 N-s/m2 x = 6.7 x 10-7
1.488 ft sec
kJ 1 Btu 1 kg Btu
(f) 1000 x x = 430
kg 1.055 kJ 2.2046 lbm lbm
m
1-3 Hp = 50 (ft) x 0.3048 ( ) = 15.2 m
ft
15.2 m 9.807 N
P = x ( ) x 1000 (kg/m3) = 149 kPa
1000 Pa/kPa 1 kg
4 m 9.807 N kg
1-4 P = (ft) x 0.3048 ( ) x ( ) x 1000 ( 3 )
12 ft 1 kg m
1-5
+ METER CHARGE
hrs days
(11) (22) = 242 hrs / month
day months
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
3
ratio =
( 624 ) kw = 1.57
( 96,000 ) kw hr
( 242 ) hr
1-7 This is a trial and error solution since eq. 1-1 cannot be solved
explicitly for i.
Answer converges at just over 4.2% using eq. 1-1
1-8 Determine present worth of savings using eq. 1-1
(12 )(12 )
0.012
( $1000 ) 1- 1+
12
P=
0.012
12
P = $134,000
(b) A= (0.3)2 = 7.07 x 10-2 m2
4
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
4
1-11
q = mc
p T c p = 4.183 kJ/(kg-K)
= 983.2 kg/m3
1-11 (contd)
3
q = (1) m ( 983.2 ) kg ( 4.183 ) kJ ( 5 )c = 20,564 kJ
s m3 kg K s
q = 20,564 kw
11,200(1)(10) =
5000x60x14.7x144x0.24(t 2 50)
=
(53.35x510)
q wat = - q air
6279(90-t2) = 29,400
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
5
29,400
t2 = 90 - = 85.3 C
6279
1-14 q = hA(ts- t )
q = hA(ts- t )
q 1250
h= = ; h = 4.42 W/(m2 C)
A(t s -t ) 3.1416(100 10)
1-16 q = mc
p (t2-t1) ; m x
=Q
= P/RT = 14.7x144/53.35(76+460)
= 0.074 lbm/ft3
c p = 0.24 Btu/lbm-F
1cp (t3-t1) +
1-17 m
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
6
2cp2 (t3-t2) = 0
m
c p1 = c p2
1t1 +
(m 2t 2 )
m
t3 =
(m1+ 2)
m
= 1000x
1 = Q 14.7x144
m 2 1 = 73.5 lbm/min
53.35(460 + 50)
1-17 (contd)
= 600x
2 =Q 14.7x144
m 2 2 = 46.7 lbm/min
53.35(460 + 50)
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
7
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for
testing or instructional purposes only to students enrolled in courses for which the textbook has been
adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108
of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
Requests for permission or further information should be addressed to the Permission Department, John
Wiley & Sons, Inc, 111 River Street, Hoboken, NJ 07030.
Chapter 2
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for
testing or instructional purposes only to students enrolled in courses for which the textbook has been
adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108
of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
Requests for permission or further information should be addressed to the Permission Department, John
Wiley & Sons, Inc, 111 River Street, Hoboken, NJ 07030.
Chapter 3
Pv P 1430
(b) = RvT or v = v ; v = = 0.0104 kg/m3
v Rv T 462.5(297)
0.196(144)
or = 0.00062 lbv/ft3
85.78(535)
0.6219 (1.43)
(c) W = = 0.00893 kgv/kga
(99.57)
0.6219(0.196)
or = 0.00854 lbv/lba
14.5
Pv 0.6219 (0.507)
W = 0.6219 = = 0.0222 lbv/lba
Pa (14.696 0.507)
Ra T 53.35(460 + 80)
v= = = 13.61 ft3/lbm
Pa (14.696 0.507)144
3-2 (contd)
0.6219(0.089) lbmv
W= = 0.00379
(14.696 0.089) lbma
53.35(492)
v= = 12.48 ft3/lbma
(14.696 0.089)144
Pv 0.6219(3.6) kgv
W = 0.6219 = = 0.0229
Pa (101.325 3.6) kga
Ra T 0.287(300)
v= = =0.88 m3 /kga
Pa (101.325 - 3.6)
0.6219(0.61)
W= =0.00377 kgv/kga
(101.325 - 0.61)
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
9
0.287(273)
v= = 0.778 m3 /kga
(101.325 - 0.61)
3-3 (a) English Units 5000 ft elevation, P = 12.24 psia = 24.92 in.Hg
Pv 0.6219(0.507)
W = 0.6219 = = 0.0269 lbv/lba
Pa (12.24 - 0.507)
RaT 53.35(540)
v= = = 17.05 ft3 / lbma
Pa (12.24 - 0.507) 144
0.6219(0.089)
W= = 0.00456 lbmv/lbma
(12.24 0.089)
53.35(492)
v= = 15.00 ft3/lbma
(12.24 0.089)144
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
10
0.6219x3.60
W= = 0.0277 kgv/kga
(84.436 3.60)
3-3 (contd)
0.287x300
v= = 1.065 m3 / kga
(84.436 - 3.60)
0.6219 x 0.61
W= = 0.00453 kgv / kga
(84.436 - 0.61)
0.287 x 273
v= = 0.935 m3 / kga
(84.436 - 0.61)
0.6219 (0.272)
W= = 0.0117 lbmv / lbma
(14.696 - 0.272)
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
11
0.6219 (0.272)
W= = 0.0141 lbmv / lbma
(12.24 - 0.272)
3-4 SI Units
3-4 (contd)
0.6219 x 1.755
W= = 0.0110 kgv / kga
(101.325 - 1.755)
0.6219 x 1.755
W= = 0.0132 kgv / kga
(84.186 - 1.755)
Pv
= or Pv = Ps ; Pv = 0.5(0.3918) = 0.196 psia
Ps
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
12
3-5 (contd)
(a) At 55F, 80% RH, va = 13.12 ft3 / lba and a = 0.0752 lbma / ft3
3-6 SI Units
t dp = (t sat @ Pv ) = 64.5 F
3-7 SI Units
3-8 t dp 9C (48F)
Chart 1a & 1b
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
14
Copyright 1992 90
AMERICAN S OCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
15
5000 0 .8 .026
.0
2. 0 -2 00 0
-
3000 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
-8
TOTAL HEAT Qt
0 .5 -4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
0 -1. LB
0 TE
MP 55
0. 3
-0 .5
RA
50
- 0.4
-0.3 80 TU
0 RE
0.2
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
ENTHALPY 'h
HU MIDITY RATIO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
70 .016
D
30
F
Problem 3-8
R
O
TU
D
N
A
U
ER
PO
P
M
R
45
TE
70
PE
.014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
.012
N
E
65
1 4 .0
60 %
90
VO
LU
ME
% .010
80 60 40
20
-C
55
42 %
U.F
%
70
T. P
.008
ER
50 55
dp % Room LB
60
W=0.0071 .D
13
RY
45
.5
15 50
%
50
A IR
.006
DR Y BUL B T EMPERAT UR E - F
40
45 35
4 0%
35
40
.004
1 3.
30 %
35
0
20 %
.002
1 2.
Y
I VE H UMIDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
48 (9) 72 (22) ENTHALPY - BT U PER POUND OF DRY AIR
3-9 (contd)
= 58.7 lbm/hr
(b) m
2 = 1027 cfm
Q
0.6219 (0.3095)
3-12 (a) W2* = = 0.0134 kgv / kga
(14.696 0.3095)
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
16
3-12 (contd)
0.231
1 = = 0.46 or 46%
0.507
0.6219 x (0.3095)
W2* = = 0.01613 lbv/lba
(12.24 - 0.3095)
0.244
1 = = 0.48 or 48%
0.507
Dew Mass
Dry Wet Humid. Enthalpy Rel.
point Density
Bulb, F Bulb, F Ratio, lba/lbv Btu/lba Humid., %
F lba/ft3
85 60 40.6 0.0053 26.6 21 0.072
75 59.6 49.2 0.0074 26.1 40 0.073
74.6 65.1 60.1 0.0111 30 60 0.073
88.6 70 60.9 0.01143 33.8 40 0.071
100 85.8 81.7 0.0235 50 56 0.068
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
17
Dew Mass
Dry Wet Humid. Enthalpy Rel.
point Density
Bulb, F Bulb, F Ratio, lba/lbv Btu/lba Humid., %
F lba/ft3
85 60 45.1 0.0076 28.7 25 0.060
75 58.6 49.2 0.0089 27.7 40 0.061
71.2 61.6 56.7 0.0118 30 60 0.061
102.7 70 55.8 0.01143 37.3 22 0.058
100 81.3 76.1 0.0235 50 47 0.057
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
18
3-14
ASHRAE PSYCHROMETRIC CHART NO.1
55 60
NORMAL TEMPERATURE
R
BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY R
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
T OTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
-1 LB
.0
0
TE 55
MP
0. 3
-0 .5
RA
50
- 0.4
80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
ENTHAL PY 'h
HU MIDITY RAT IO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
70 .016
D
Problem 3-14
F
30
R
O
TU
D
N
A
U
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
14
60
.0 V
%
90
OL
U
Max RH=49.6 %
ME
% .010
80 60
40
20
-C
55
U.F
%
70
T.
W=0.0083
PE
.008
50 55
dp Room
RL
%
60
B. D
13
R
45
.5
15 50
YA
%
50 .006
IR
DR Y BUL B T EMPERATUR E - F
40
45 35
4 0%
35
40
.004
30%
1 3.
35
0
20 %
.002
1 2.
Y
IVE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
2.4
(b) q = m
(i1 i2 ) = (57.1 - 34) = 63.95 kJ / s = 63.95 k W
0.867
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
19
3-15 (contd)
5000(60)
(b) q = (32 - 22.6)= 203,317. Btu/hr
13.87
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
T OTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
0 -1. LB
0 TE
MP 55
0. 3
E
-0 .5
RA
50
- 0.4
80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
ENT HAL PY 'h
HU MIDIT Y RAT IO 'W 75
35 50
14 .5
.018
75
IR
A
Problem 3-15
Y
F
R
70 .016
D
E
F
30
R
O
TU
D
N
A
U
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
1
SA
TH
N
.012
E
65
1 4 .0
60 %
90
VO
LU
ME
% .010
80 60 40
20
-C
55
U.F
ADP 70
%
T. P
2 .008
ER
50 55
%
L B.
60
1 3 .5
DR
45 50
15
YA
%
50 .006
IR
DR Y BUL B T EMPERAT UR E - F
40
45 35
4 0%
35
40
.004
1 3.
30%
35
0
20 %
.002
1 2.
Y
IVE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
52 (10) 55 (13) 80 (27) ENTHALPY - BT U PER POUND OF DRY AIR
lbv
3-16 (a) i1 = 30 Btu / lba; v1 = 13.78 ft3 / lba; W = 0.0103 ; 1 = 50%
lba
v1 = 0.86 m3 / kga
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
20
3-16 (contd)
kgv
W1 = 0.0103
kga
1 = 50%
q = 148,239 Btu/hr
q s = 102,235 Btu/hr
SHF = 0.69
3-18 Use the Heat Transfer option of program PSYCH for sensible heat
transfer only:
q s = 178,911 Btu/hr
6000 ft elevation.
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
21
3-19 (contd)
(21,600 17,100)100
PD = = 20.8%
21,600
= 190,224 Btu/hr
(b) at 6000 ft, q
(200,534 190,224)100
(c) PD = = 5.1 %
200,543
PB = 29.92 in.Hg. ; q = 0
i
= iw = 180.2 + 0.8 (970.2)
W
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
22
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
TOTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2.0 0 WE .024
200 0.4 T BU
0 -1. LB
0 TE
MP 55
0. 3
-0 .5
RA
50
- 0.4
80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
ENT HAL PY 'h
HU MIDITY RATIO 'W 75 2
35 50
14 .5
.018
75
60 %
IR
A
Y
F
R
-
70 .016
D
Problem 3-21
F
30
R
O
TU
D
N
A
U
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
14
60
.0 V
%
90
OL
U ME
% .010
80 60
40
20
-C
55
U.F
%
70
T. P
.008
ER
50 55
%
LB
60
.D
13
RY
45
.5
15 50
%
50
A IR
.006
DR Y BULB T EMPERATUR E - F
40
45 1 35
4 0%
35
40
.004
30%
1 3.
35
0
20 %
.002
1 2.
Y
IVE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
91.5 (32) 98 (38) ENTHALPY - BT U PER POUND OF DRY AIR
PB = 101.325 kPa
i
= iw = 419.04 + (0.8 x 2257)
W
iW = 2224.6 kJ / kg
From chart 1b; t2 = 32 C
3-22 (contd)
i
= iw = 1090 Btu / lbm
W
x = 0.931 or about 93 %
Copyright 1992 90
SEA LEVEL 60
1.0 1 .0 85
15
50 00 0 .8 .026
.0
2.0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
0 .5
T OTAL HEAT Qt
-8
-4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
0 -1. LB
0 TE
MP 55
0. 3
E
-0 .5
RA
50
- 0.4
80 TU
-0.3
0 a
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
1090 80
1 000
.020
ENT HAL PY 'h
HU MIDIT Y RATIO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
70 .016
D
E
F
30
R
O
TU
Problem 3-22
D
N
b
U
ER
PO
P
M
R
45
TE
70
PE
.014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
.012
N
E
65
1 4 .0
60 60
90
%
VO
LU
ME
% .010
80 60 40
20
-C
55
U.F
%
70
T. P
.008
ER
50 55
%
L B.
60
13
DR
45 1
.5
50
YA
15
%
50 .006
IR
DR Y BUL B T EMPERAT UR E - F
40
45 35
4 0%
35
40
.004
1 3.
30%
35
0
20 %
.002
1 2.
Y
I VE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
80 ENTHALPY - BT U PER POUND OF DRY AIR
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
24
i 272.1
= iw = kJ / kg
W 1000
t2 = 22.6 C
ASHRAE PSYCHROMETRIC CHART NO.1
11 0 12
NORMAL TEMPERATURE 0
30
R
BAROMETRIC PRESSURE: 101.325 kPa R
Copyright 1992
10 0
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
28
SEA LEVEL 30
0 .9
1.0 1 .0
4
12 0
0 .8 1 .5 26
-5. 0 90
10 .0
0.7 2. 0
- 0. 6 SENSIB LE HEAT Qs 4 .0 -2.0 30
WE
T OTAL HEAT Qt TB
5.0
0.5
-2
-4.0
.0
0.272
0.0
UL
BT
EM 24
0. 4 PE
-1 R AT
.0 UR
80 E-
0. 3
4. 0 1 .0 C
-0 .5
11 0
0.2
-0.2
0 22
0 .1
0 .9
2
3 .0
2 .0
70 25
2.5
20
ENTHALPY 'h
HU MIDITY RAT IO 'W
10 0
25
18
60
R
0 .9
AI
Y
0
R
C
D
16
F
O
Problem 3-23
R
AM
TU
R
50
20
A
G
20 90
ER
O
IL
P
EM
K
2
R
14
T
E
N
P
O
J
20
R
Y
LP
TU
80 %
0 .8
A
40
SA
TH
8
N
12
E
% 80
15 90
% 10
30 80
0 .8
15
6V
%
70
OL
8
U
10
1
ME
%
20 60 70
-C
UB
0. 8
10
IC M
0%
4
5 6
D RY BU LB TEMPERA TU RE - C
5
ET
ER
40 %
PE
0 .8
10 5
Rk
4
2
gD
3 0%
60
R
YA
0 .8
20 %
IR
0
2
0 .7
10% RE LAT
25
10
15
20
30
35
40
45
50
5
10 20 30 40 50
22.6 38 ENTHALPY - KJ PER KILOGRAM OF DRY AIR
i
(a) = iw = 1131 Btu / lbw
W
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
25
3-24 (contd)
q c = m
a (i2 - i1)
a = 2000 x 60 / 13.14
m
a = 9132 lba / hr
m
w = m
m a (W3 - W2 ) ; W3 = 0.0167; W2 = 0.0032 lbv/lba
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
26
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -200 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
T OTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2.0 0 WE .024
200 0.4 T BU
0 -1. LB
0 TE
MP 55
0. 3
-0 .5
RA
- 0.4
50 80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
1131 80
1 000
.020
ENTHALPY 'h
HU MIDIT Y RAT IO 'W 75
35 50
14 .5
.018
75
3
IR
A
Y
F
R
70 .016
D
E
F
30
R
O
TU
D
N
Problem 3-24
A
U
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
1 4 .0
60 %
90
VO
LU
ME
30 %
% .010
80 60 40
20
-C
55
U.F
%
70
T. P
.008
ER
50 55
%
L B.
60
1 3 .5
DR
45 50
15
YA
%
50 .006
IR
DR Y BULB TEMPERATUR E - F
40
45 35
4 0%
35
40
.004
1 30%
1 3.
35
0
2
20 %
.002
1 2.
Y
VE H UM IDIT
10% REL ATI
5
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
32 2000 Q 2
= = 1=
12 3000 Q3 3
W3 = 0.007 lbv/lba
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
27
I3 = 22.2 Btu/lba
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -200 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
T OTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2.0 0 WE .024
200 0.4 T BU
0 -1. LB
0 TE
MP 55
0. 3
-0 .5
RA
- 0.4 50 80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
77 80
1 000
.020
ENTHALPY 'h
HU MIDIT Y RAT IO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
70 .016
D
E
F
30
R
O
Problem 3-25
TU
D
2
N
A
U
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
1 4 .0
60 %
90
VO
LU
ME
% .010
80 60 40
20
-C
55
52
U.F
%
70
T. P
.008
ER
50 55
%
3 60 L B.
1 3 .5
DR
45 50
15
YA
%
50 .006
IR
DR Y BULB TEMPERATUR E - F
40
45 35
4 0%
35 35
40
.004
30%
1 3.
35
0
1 20 %
.002
1 2.
Y
VE H UM IDIT
10% REL ATI
5
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
40 (4) 58.4 (15) 100 (38) ENTHALPY - BT U PER POUND OF DRY AIR
i3 = 34 kJ / kga
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
28
3-26 (contd)
32 a1
m 9479
= = = 0.695
12 m a1+m a2 9479 + 4155
W3 = 0.0067 lbu/lba
(0.007 0.0067)100
For W, % Error = = 4.5
0.0067
(22.2 21.5)100
For I, % Error = = 3.3
21.5
250,000
3-27 SHF = = 0.8
200,000
59
or SHF = = .81
73
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
29
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
0 .8 .026
0.8
50 00
2. 0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
TOTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
0 -1. LB
0 TE
MP 55
0. 3
-0 .5 4
RA
- 0.
50 80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
ENTHALPY 'h
HU MIDITY RATIO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
-
70 .016
D
E
F
30
R
O
TU
D
N
Problem 3-27
A
U
ER
PO
28.2
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
50 %
1 4 .0
60 %
90
VO
LU
21.5
ME
% .010
80 60 40
20
-C
55
1
U .F
%
70
T. P
.008
ER
50 55
%
L B.
2 60
1 3 .5
DR
45 50
15
YA
%
50 .006
DR Y BULB T EMPERATUR E - F
IR
40
45 35
4 0%
35
40
.004
30%
1 3.
35
0
20 %
.002
1 2.
Y
IVE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
53 (12) 75 (24) ENTHALPY - BT U PER POUND O F DRY AIR
(a) q = m
a (i1 - i2 ); i1 = 28.2; i2 = 21.5
=m
Q a v 2 = 37,313 x 13.09 / 60 = 8,140 ft 3 / min
= 3.85 m3 / s
(b) similar procedure; Q
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
30
3-29 (a) Use the AirQuantity option of program PSYCH, iterating on the
= 0.852 (iterated)
ts = 56F
= 9,360 cfm
Qs
= 0.882
ts = 56F
= 10,014 cfm
Q s
= 0.92
ts = 56.1 56 F
= 11,303 cfm
Q s
500,000
3-31 (a) SHF = = 0.91
550,000
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
31
3-31 (contd)
(b) q = m
a (i2 -i1)
a = q/(i
or m 2 -i1)
550,000
a =
m
(34.3 22.8)
a =47,826lba hr
m
=m a v 2 47,826
Q 2 = x 14.62=11,654 cfm or 5.5 m3/s
60 60
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
32
Copyright 1992 90
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1.0 85
1 5 .0
0.8
0.91 .026
5000
2. 0 -2000
-
300 0 0. 6 SENSIBLE HEAT Qs 4 .0 -1 00 0
8 .0 45
TOTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2. 0 WE .024
0.4 0 T
200
-1.
BU
0
0 LB
TE 55
MP
0. 3
E RA
-0 .5 4
50
- 0.
80 TU
-0.3
0 RE
0.2
-0 .2
- F
-0 .1
.022
0 .1
0 40
15
00
80
1 000
.020
ENTHALPY 'h
HU MIDITY RATIO 'W 75
34.3 35 50
14 .5
.018
75
IR
A
Y
F
R
70 .016
-
D
30
E
F
R
O
TU
D
Problem 3-31
N
A
U
ER
PO
P
M
R
45
TE
70
PE
.014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
22.8
E
65
1 4 .0
60 %
90
VO
LU
ME
% .010
80
20 60
30 % 40
-C
55
U.F
%
70
T. P
.008
ER
50 55
%
L B.
60
1 3 .5
DR
45 50
YA
15
50 % .006
IR
DR Y BULB TEMPERATUR E - F
40
45
1 35
4 0%
35
40
.004
1 3.
30 %
35
0
20 %
.002
1 2.
Y
IVE H UMIDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
72 (22) ENTHALPY - BT U PER POUND OF DRY AIR 115 (46)
=m
3-32 q a (i2 -i1)
q
i2 = +i
a 1
m
1400 x 60
a
m = 5,915.5
14.2
-5 x 12,000
i2 = +38.5
5,915.5
i 2 = 2 8 .3 6 Btu/lba
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
33
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2. 0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
TOTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
0 -1. LB
0 TE
MP 55
0. 3
-0 .5
RA
- 0.4
50 80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
'h
75
ENTHALPY
HU MIDIT Y RAT IO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
70 .016
D
Problem 3-32 1
E
F
30
R
O
TU
D
N
A
U
ER
28.4
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
14
60
.0 V
%
90
OL
2
U ME
% .010
ADP55 80 60
40
20
-C
U .F
%
70
T. P
.008
ER
50 55
%
LB
60
.D
13
R
45
.5
15 50
YA
%
50 .006
DR Y BULB T EMPERAT UR E - F
IR
40
45 35
4 0%
35
40
.004
1 3.
30%
35
0
20 %
.002
1 2.
Y
I VE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
3-33 Use Adiabatic Mixing option of PSYCH with the Properties option to
Tmix,db = 84.2 F
Tmix,wb = 71.3 F
Iteration on the supply volume flow rate is required. This is the same as the
3-34 (contd)
(c) Air enters the coil at 74.6 F db, 60.5 F wb at a rate of 9,740 cfm
Iteration on the supply volume flow rate is required. This is the same as the
(c) Air enters the coil at 74.6 F db, 62.1 F wb at a rate of 11,697 cfm
t s =120 / 74 F
s= q 200,000
m =
(is -ir ) (37.2 22.8)
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
35
1
= 13,889 lb/hr = m
=m
Q sv s = m
s (14.78)/60 = 3,421 ft 3 / min
s
r 13,889 4758
m
= = 0.66; From Chart 1a t1 = 61/ 47 F
1
m 13,889
t 3 - t1 = (119 61)
w= m
(c) m s (Ws -W2 ) = 13,889 (0.0075 - 0.0036) = 54.2 lbm/hr
(d) q f = m
1(i3 -i1) =13,889 (32.8 18.6) = 197,224 Btu/hr
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
36
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
0.8 300 0
-
0. 6 SENSIB LE HEAT Qs 4 .0
8 .0
2.0 -2 00 0
-1 00 0
45
T OTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2.0 0 WE .024
200 0.4 T BU
-1 LB
.0
0
TE 55
MP
0. 3
-0 .5
RA
50
- 0.4
80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
1150 80
1 000
.020
ENT HAL PY 'h
HU MIDIT Y RAT IO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
-
70 .016
D
E
F
30
R
O
TU
D
N
A
U
ER
Problem 3-36
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
14
60
.0 V
%
90
OL
U ME
% .010
80
20 60
30 % 40
-C
55
U.F
%
70
T.
PE
.008 s
47 50 55
RL
%
60
B.
13
DR
45
.5
15 50
YA
%
50 .006
DR Y BUL B T EMPERAT UR E - F
IR
40
45
r 35
4 0%
35
40
1
.004
30%
1 3.
35 1 3
0
20 %
.002
1 2.
Y
IVE H UM IDIT
5
10% RE LAT
0 30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
40 61 72 ENTHALPY - BT U PER POUND OF DRY AIR 120
r 13,605 3947
m
= = 0.71; t1 = 62.8 / 47 F
1
m 13,605
w =m
(c) m s (w s -W1) = 13,605 (0.0088 - 0.0046) = 57.14 lbw/hr
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
37
9384
s =
m x 60 = 42,915 lbm/hr; Prob 3-34
13.12
W fan + qduct = ms (is ic )
11,180
ic = 20.8 = 20.54 Btu/lbm
42,915
(d) q coil =m
1(i1-ic ) = 42,915 (26.8 - 20.54) = 268,648 Btu/hr
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
38
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
T OTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
-1 LB
.0
0
TE 55
MP
0. 3
-0 .5
RA
50
- 0.4
80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
0
80
1 000
.020
ENTHAL PY 'h
HU MIDITY RAT IO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
-
70 .016
Problem 3-38
D
E
F
30
R
O
TU
D
N
A
U
ER
PO
50 %
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
14
60
.0 V
%
90
OL
U
1
ME
% .010
20.54 20
80 60
40
-C
55
U.F
%
70
T.
PE
.008
50 55 r
RL
c %
60
B.
13
DR
45 s 50
.5
15
YA
%
50 .006
DR Y BULB T EMPERAT UR E - F
IR
40
45 35
4 0%
35
40
.004
1 3.
30%
35
0
20 %
.002
1 2.
Y
IVE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
q r = m
s (i r i s ); W s (i s i c )
3-39 fan = m
q r = 1,320,000 Btu/hr
W fan = 30 x 2545 = 76350 Btu/hr
W fan = 30 x 2545 = 76,350 = ma (is -ic )
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
39
q s = 1,320,000 = m
a(ir -is )
Copyright 1992 50
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
.028
5000 FEET 60
1 8 .0
80
1.0 1 .0
0.8 50 00
-
0 .8
2. 0 -2 000 45
.026
-0 .5
-
-0 .4
50 40 F
- 0.3
0
0.2
-0 .2
-0 .1
0 .022
0 .1
15
17 .5
00
75
10 00
.020
ENTHALPY 'h
35 70
HU MIDIT Y RATIO 'W
50
.018
R
F
AI
70
RY
E
UR
D
AT
F
O
30 65
ER
ND
.016
P
U
M
PO
Problem 3-39
TE
17 .0
50 %
R
N
PE
O
TI
TU
RA
65 45
-B
.014
TU
59 (15)
Y
SA
60
LP
25
TH
s
EN
c .012
60
%
55 90
%
16
80 .010
.5 V
20 40
55
50
OL
%
70
U
ME
-C
.008
45 50 %
U .F
60
T. P
15
ER
16 .0
40 45 %
50
LB
.006
DR Y BUL B T EMPERATUR E - F
0
.D
35 40 35
R
4 0%
YA
IR
35
.004
30 %
1 5 .5
20%
.002
I TY
TIV E HUMID
10% RELA
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
Solve simultaneous:
W
fa n + q s = m a (ir -i c )
1 ,3 2 0 ,0 0 + 7 6 ,3 5 0
a=
m
(3 3 .7 -2 8 )
a = 2 4 4 ,9 7 4 lb a /h r
m
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
40
is = ir - ( q s m
a)
1,320,000
is = 33.7 - =28.3 Btu/lba
244,974
= 31.2 m 3 s
(b) Q s
imin =i0 =31.1 Btu/lba and sat. air ; t min =64.5 F; PSYCH
imin =i0 = 42.5 Btu/lba and sat. air ; tmin = 76.8 F; PSYCH
Shreveport, Louisiana
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
41
259 FEET 60
1.0 1 .0 85
15 .0
50 00 0 .8 .026
2.0 -2 000
-
300 0 0 .6 SENSIBL E HEAT Qs 4 .0 -1 000
8 .0 45
T OTAL HEAT Qt
0 .5 -8
-4.0.0 85
WE
-2. 0 TB .024
200 0. 4 0 UL
-1 BT
.0
0
EM 55
PE
0. 3
80 R AT
-0 .5
UR
-0 .4
50
- 0.3
0 E-
0.2
-0 .2
F
-0 .1
0 .022
0 .1
40
15
00
80
10 00
.020
ENT HAL PY 'h TLO
HU MIDIT Y RAT IO 'W
75
35 50
.018
75
R
AI
Y
14 .5
F
Problem 3-40
R
70
-
SL
D
E .016
F
30
R
O
U
D
AT
N
Shreveport, LA
U
R
PO
PE
M
ER
TE
70 45
.014
P
N
TU
65
I
-B
AT
U
LP
AT
25
A
TH
S
N
.012
E
65
60
%
90
1 4.
% .010
0V
55 80 60 40
20
OL
UM
%
70
E-
50 55 .008
CU
.FT
%
60
.P
ER
45 50
15
%
50 LB .
1 3.
.006
DR Y BUL B T EMPERATUR E - F
5
DR
40
45 YA
35
4 0%
35
IR
40
.004
35 30%
1 3 .0
20 %
.002
IVE HUMIDITY
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
76.8 95 ENTHALPY - BT U PER PO UND O F DRY AIR
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
42
2556 FEET 60
16 .
5
1.0 1 .0 85
50 00 0 .8 .026
2. 0 -2 000
- 45
300 0 0 .6 SENSIBL E HEAT Qs 4 .0 -1 000
8 .0
-8
T OTAL HEAT Qt 80
0 .5 -4.0.0
-2. 0 .024
200 0. 4 0
-1
.0
0
55
0. 3
-0 .5
-0 .4
50 80
- 0.3
0 WE
0.2
-0 .2
40
-0 .1
0
TB .022
0 .1
UL
15
BT
00
EM
P ER
75 A TU
1 6 .0
RE
- F
10 00
.020
ENT HAL PY 'h
HU MIDIT Y RAT IO 'W 35
75 50
.018
70
Problem 3-40
IR
A
F
-
Y
R
E
D
Tucson, Arizona
R
F
.016
TU
30
O
70
D
ER
N
U
P
O
EM
P
65
R
T
PE
45
O
TU
1 5 .5
.014
TI
TLO
A
-B
R
TU
Y
SA
65
A
25
TH
60
EN
.012
%
90
60
55
%
80 .010
40
20
1 5.
%
50 7 055
0V
OL
.00 8
UM
%
60
45
E-
50
CU
15
%
50
.FT
40 45 TA .00 6
DR Y BUL B T EMPERAT UR E - F
.P
1 4.
ER
35
35 4 0%
5
LB
40
DR.
.00 4
35 30 %
YA
IR
1 4 .0
20%
.00 2
ITY
TIV E HU MID
10% RELA
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
3-41 q = m
s (ir i s )
o r1
m 13
= = = 0.55 or 55%
s r0 23.5
m
0.046 m3 / s - kW
(b) Q s
0 /m
m s 55%
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
43
Copyright 1992 50
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
.028
5000 FEET 60
1 8 .0
80
1.0 1 .0
50 00 0 .8 .026
2.0 -2 000 45
-
300 0 0 .6 SENSIBL E HEAT Qs 4 .0 -1 000
8 .0 80
TOTAL HEAT Qt W
0.7 200
0 .5
0. 4
-2.
0
-8
-4.0.0
0
ET
BU
LB
TE
MP
.024
-1 ER
.0
0
AT 55
75 U
0. 3
RE
-0
- F
-0 .4
50
.5
40
- 0.3
0
0.2
-0 .2
-0.1
0 .022
0 .1
15
17 .5
00
75
10 00
.020
ENT HALPY 'h
35 70
HU MIDIT Y RAT IO 'W
50
.018
R
F
AI
- 70
Y
RE
DR
TU
F
RA
O
30 65
D
.016
PE
UN
M
PO
TE
Problem 3-41
17 .0
R
N
PE
IO
AT
TU
65 45
UR
-B
.014
T
PY
SA
60
AL
55 90
%
60 40 % .012
% 1 6 .5
80 .010
20 55 40
VO
50 r
LU
%
70
ME
-C
.008
45 50 %
U.F
60
s
T. P
15
ER
16 .0
40 45 %
50
1
10 %
L B.
.006
DR Y BUL B T EMPERAT UR E - F
DR
35 40 35
4 0%
YA
IR
35 0 .004
30 %
1 5 .5
20%
.002
IVE HUMIDI TY
10% REL AT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
500,000
3-42 q = m
2 (i2 i3 ); m
2 =
(41.1 21.9)
2 = 26,042 lba/hr
m
0 /m
m 3 = 0.25; t mix = 67.5 / 49.5 F
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
44
3-42 (contd)
Preheat Coil:
q ph = m
0c p (t 4 -t 0 ) = 6511 x 0.24 (60-6) = 84,383 Btu/hr
Heat Coil:
q h = m
2 (i5 -i1) = 26,042 (28.4 - 20) = 218,753 Btu/hr
Humidifier:
w= m
m 2 (W2 -W5 ) = 26,042 (0.0144 - 0.0035)
= 283.9 lbw/hr
w = 0.036 kg/s
m
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
45
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -2 000
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
TOTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2.0 0 WE .024
200 0.4 T BU
0 -1. LB
0 TE
MP 55
0. 3
-0 .5
RA
- 0.4
50 80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
1153 80
1 000
.020
ENT HAL PY 'h
HU MIDITY RATIO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
-
70 .016
D
E
F
30
Problem 3-42
R
O
TU
D
N
2
U
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
1 4 .0
60 %
90
VO
LU
ME
% .010
80 60 40
20
-C
55
30 %
U.F
%
70
T. P
.008
ER
50 55
%
L B.
60
1 3 .5
DR
45 50
15
YA
50 % .006
IR
DR Y BUL B TEMPERATUR E - F
40
45 3 35
4 0%
35
40
1 .004
1 3.
30%
35
0
5
20 %
.002
1 2.
H UM IDITY
REL ATI VE
5
10%
4 30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
a = q d /(ir i s )
or m
= 0.20
Q = 1,242 cfm
Q
m d
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
46
= 2.93 m3 /s; Q
(b) Q = .59 m3 /s; t = 17/14 C
d m m
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0
0.8 85
1 5 .0
50 00 0 .8 .026
2. 0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
-8
T OTAL HEAT Qt
0 .5
0.6 200 0. 4
-1.
-2.
-4 .0.0
0 0
85
WE
T BU
.024
0
0 LB
TE 55
MP
0. 3
E
-0 .5 50
RA
- 0.4
80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
ENT HAL PY 'h
HU MIDIT Y RAT IO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
70 .016
D
E
F
30
R
O
Problem 3-43
TU
D
N
A
U
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
14
60
.0 V
%
90
OL
U
r
ME
.010
m 80 % 60 40
20
-C
55
U.F
s %
70
T. P .008
50 55 ER
%
L B.
60
1 3 .5
DR
45 50
15
YA
%
50 .006
IR
DR Y BUL B T EMPERAT UR E - F
40
45 35
4 0%
35
40
.004
1 3.
30%
35
0
62 (17) 20 %
.002
1 2.
Y
IVE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
60 (16) 75 (24) ENTHALPY - BT U PER PO UND O F DRY AIR
15.0 x 12,000
3-44 a =
(a) m = 29,508 lba/hr
(31.2 - 25.1)
= 1,574 cfm
tm = 62.5 / 58 F
=3.7 m3 / s; Q
(b) Q = 0.74 m3 /s; t = 17 /14.4 C
s m m
r
m 10
3-45 Use Chart 1a; = 0.8 =
1
m 0r
is = ir - q m / m
s
Q 50 x 12,000
s =
m d
=
ir i s (29.35 - 22.3)
s = 85,106 lba/hr; m
m s is constant for all conditions
si s + m
(b) m b i1' = (m
c +m
b ) i s'
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
48
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0
0.9 85
1 5 .0
50 00 0 .8 .026
2.0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
T OTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
0 -1. LB
0 TE
MP 55
0. 3
-0 .5
RA
- 0.4
50 80 TU
-0.3
0
0.2
RE
-0 .2
0
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
ENT HAL PY 'h
HU MIDIT Y RATIO 'W 75
35 50
0'
14 .5
.018
75
Problem 3-45
IR
A
Y
F
R
-
70 .016
D
E
F
30
50 %
R
O
TU
D
N
A
U
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65 1'
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
1 4 .0
60 % 1
90
VO
LU
s'
ME
% .010
80 60 40
20
-C
55 r
U.F
%
70
T. P
.008
ER
50 55
s %
L B.
60
1 3 .5
DR
45 50
15
YA
%
50 .006
IR
DR Y BUL B T EMPERAT UR E - F
40
45 35
4 0%
35
40
.004
30%
1 3.
35
0
20 %
.002
1 2.
Y
I VE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
55 (13) 64 (18) 77 (25) 85 (29) 95 (35) ENTHALPY - BT U PER POUND OF DRY AIR
saturation curve.
(b) Cool the air to state 1' and then heat to state 2.
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
49
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
-8
T OTAL HEAT Qt
0 .5 -4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
0 -1. LB
0 TE 55
MP
0. 3
-0 .5
RA
50
- 0.4
80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
ENTHAL PY 'h
HU MIDIT Y RAT IO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
-
70 .016
D
E
F
30
R
O
90 %
TU
Problem 3-47
D
N
A
U
67
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65 1
14
60
.0 V
%
90
OL
UME
% .010
20 54 80 60 40
-C
55
U .F
%
70
T.
PE
50 1' 55
.008
RL
%
60
B. D
2
13
RY
45
.5
15 50
%
50
A IR
.006
DR Y BUL B TEMPERATUR E - F
40
45 35
4 0%
35
40
.004
1 3.
30%
35
0
20 %
.002
1 2.
Y
IVE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
52 (11) 60 (16) 80 (27) ENTHALPY - BT U PER POUND OF DRY AIR
c sh
m
3-48 (a) = =.837
s ch
m
h cs
m
= = 0.163
s ch
m
c 0.837
m
= = 5.14
h 0.163
m
q = m
s (ir is )
50 x 12,000
s =
m = 93,750 lba/hr
(28.2-21.8)
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
50
= 9.7 m3 /s
(b) Q s
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
T OTAL HEAT Qt
0 .5 -8
-4 .0.0
0.65 200
0
0. 4
-1.
0
-2.
0
0
85
WE
T BU
LB
.024
TE 55
MP
0. 3
E
-0
RA
- 0.4
50 80
.5
TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0. 1
0 40
15
00
80
1 000
.020
ENT HAL PY 'h
HU MIDIT Y RAT IO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
Problem 3-48
-
70 .016
D
E
F
30
R
O
TU
D
N
A
U
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
90 %
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
14
60
.0 V
%
90
OL
U ME
% .010
80 60 r 40
20
-C
55
U.F
%
70
T. P
.008
20 %
ER
50 55
%
LB
60
.D
c
13
s
R
45 h
.5
15 50
YA
%
50 .006
IR
DR Y BUL B T EMPERAT UR E - F
40
45 35
4 0%
35
40
.004
30%
1 3.
35
0
20 %
.002
1 2.
Y
VE H UM IDIT
10% REL ATI
5
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
52 (11) 75 (24) 90 (32) ENTHALPY - BT U PER POUND O F DRY AIR
c
m 36 h 10.1
m c
m 0.9
(a) = = 0.9; = = 0.10 ; = = 9.0
s 46.3
m s 46.3
m h 0.10
m
50 x 12,000
s =
m = 83,333 lba/hr
(30.1 - 22.9)
=10.3 m3 /s
(b) Q s
c
m
= 0.837; q c = m
c (ir -ic ); m
c = 0.714 x m
s = 0.837 x 93,750
s
m
3-51 SI Units
= 13 Q
Q = 0.69 x 1.18 = 0.815 m3/s
2 3
12
=Q
and Q -Q
= 1.18 0.815 = 0.365 m3/s
1 3 2
(b)
Q
q 34 = m
a3 (i4 -i3 ) = 3 (i -i )
4 3
v3
1.18
q 34 = (47.8-41.0) = 9.6 kW
0.835
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
52
R
BAROMETRIC PRESSURE: 101.325 kPa R
Copyright 1992
10 0
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
28
SEA LEVEL 30
0 .9
1.0 1 .0
4
12 0
0 .8 1 .5 26
-5.0 90
10 .0
0. 7 2. 0
- 0. 6 4 .0 30
Problem 3-51
0.5
SENSIB LE HEAT
T OTAL HEAT
Qs
Qt
-4.0
-2.0
WE
TB
UL
BT
-2 0.0 E 24
5.0
.0 MP
0. 4 ER
-1 AT
.0 UR
80 E-
0. 3
4. 0 1 .0 C
-0 .5
11 0
0.2
-0.2
0 22
0 .1
0 .9
2
3 .0
2 .0
70 25
2.5
20
ENT HAL PY 'h
HU MIDIT Y RAT IO 'W
10 0
25
18
60
Problem 3-51 R
0 .9
AI
Y
0
R
C
D
-
16
50 %
F
O
E
R
AM
TU
R
50
A
G
20 90
ER
O
IL
P
EM
K
R
T
14
E
N
P
O
J
20
R
Y
1
LP
TU
0 .8
A
40
SA
TH
8
N
12
E
%
14.7 15 90
10
80
30 %
80 3 4
0 .8
15
6V
%
70
11
OL
2 8
U
10
ME
%
20 60 70
-C
UB
0.8
10
IC M
%
4
50 6
D RY BU LB TEMPERA TU RE - C
5
ET
ER
40 %
PE
0 .8
10 5
Rk 4
2
g
3 0% DR
YA 60
0 .8
20 %
IR
0
2
0 .7
10% RE LAT
25
10
15
20
30
35
40
45
50
5
10 20 30 40 50
English Units
3-52 (a),(b)
From Chart 1b, states 1.4 and ADP are known. Based on approx.
Then for full load design condition air is cooled from 1 to 2 and the
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
53
For the high latent load condition, the air at 2 is reheated to state 3
Q
(c) q 24 = m
a (i4 -i2 ) = 2 (i4 -i2 )
v2
1.82
q 12 = m
a (i1-i2 ) = (60.6-32)
0.817
q 12 = 63.7 kW
1.82
q 34 = m
a (i4 -i3 )= (47.7-39.4)
0.817
q 34 = 18.5 kW
q 23 = q 24 - q 34 = 35-18.5=16.5 kW
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
54
R
BAROMETRIC PRESSURE: 101.325 kPa R
Copyright 1992
10 0
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
28
SEA LEVEL 30
Problem 3-52
0 .9
1.0 1 .0
4
12 0
0 .8 1 .5 26
-5. 0 90
10 .0
0.7 2.0
- 0. 6 SENSIB LE HEAT Qs 4 .0 -2.0 30
WE
T OTAL HEAT Qt TB
0.5 UL
-4.0 BT
-2 0.0 E 24
5.0
.0 MP
0. 4 ER
-1. AT
0 UR
80 E-
0. 3
1 .0 C
-0 .5
4. 0
11 0
0.2
-0.2
0 22
0 .1
0 .9
2
3 .0
2 .0
70 25
2.5
20
ENTHALPY 'h
HU MIDIT Y RAT IO 'W
10 0
25
18
60
R
0 .9
AI
Problem 3-52
Y
0
R
C
D
-
21 16
F
O
E
R
AM
TU
R
50
A
G
20 90
ER
O
IL
P
EM
K
R
14
E
N
P
1
O
J
20
R
Y
LP
TU
0 .8
17
A
40
SA
TH
8
N
12
E
% 80
15 90
30
14 80
%
15
4 0 .8
10
11
6V
%
70
OL
8
U
10
ME
ADP 2 % 3
20 60 70
-C
UB
0 .8
10
IC M
%
50
4
D RY BU LB TEMPERA TU RE - C
5
ET
ER
40 %
PE
0 .8
10 5
Rk
4
2
gD
3 0%
60
R
YA
0 .8
20 %
IR
0
2
0 .7
10% RE LAT
25
10
15
20
30
35
40
45
50
5
9 11.8
10
19 20
23 27 30 40
ENTHALPY - KJ PER KILO GRAM O F DRY AIR
50
(c) Q 2
12 =221,243 Btu/hr
= 4103cfm ; q
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
55
is = ir - q /m
s =28.2 10 x 12,000 / 22,727 = 22.9 Btu/lba
m r 0m
m
(b) = = 0.462 r
m 0r
m s
m
m r 0'm'
(c) = =0.578
m'
m 0'r
= 2,156 cfm
(d) q c = m
s (im' -is ) = 22,727 (28.4 - 22.8) = 127,271 Btu/hr
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
56
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -2 00 0
0.8 300 0
-
0. 6 SENSIB LE HEAT Qs 4 .0
8 .0
-1 00 0
45
-8
T OTAL HEAT Qt
0 .5 -4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
0 -1. LB
0 TE 55
MP
0. 3
-0 .5
RA
50
- 0.4
80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
1150 80
1 000
.020
ENTHAL PY 'h
HU MIDITY RAT IO 'W 75
35 50
14 .5
.018
75
IR
A
Problem 3-53
Y
F
R
-
70 .016
D
E
F
30
R
O
TU
D
N
A
U
ER
90 %
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
0'
TH
N
.012
E
65
14
60
50 %
.0 V
%
90 m'
OL
UME
% .010
80 60 40
20
-C
55
r
U.F
%
70
T. P
.008
ER
50 55
s %
L B.
60
13
DR
45
.5
15 ADP 50
YA
%
50 .006
IR
DR Y BUL B TEMPERATUR E - F
40
45 35
4 0%
35
40 m .004
43 (6)
1 3.
30%
35
0
20 %
.002
1 2.
0 70 (21)
IVE H UM IDIT
Y
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
3-53 SI Units
=1.17m3 s
=1.13m3 s ; Q
(b) Qr o
=1.41m3 s ; Q
(c) Q =1.02m3 s
r o'
(d) q c = 37.3 kW
o mr
m
= =0.36
r 0r
m
R
BAROMETRIC PRESSURE: 101.325 kPa R
Copyright 1992
10 0
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
28
SEA LEVEL 30
0 .9
1.0 1 .0
4
12 0
0 .8 1 .5 26
-5.0 90
10 .0
0.7 2. 0
- 0. 6 SENSIB LE HEAT Qs 4 .0 -2.0 30
WE
TOTAL HEAT Qt TB
0.5 UL
-4.0 BT
5.0 -2 .0 0.0 EM 24
0. 4 PE
0.6 -1.
0
80
R AT
UR
E-
0. 3
4. 0 1 .0 C
-0 .5
11 0
0.2
-0.2
0 22
0 .1
0 .9
2
3 .0
2 .0
70 25
2.5
20
ENT HAL PY 'h
HU MIDIT Y RATIO 'W
10 0
25
18
60
57
R
0 .9
AI
Y
0
R
Problem 3-54
C
D
16
F
O
E
R
AM
TU
R
50
A
G
20 90
ER
O
IL
P
EM
K
R
14
E
N
P
0
O
J
m2
A
r
Y
0
LP
TU
0 .8
A
40
SA
TH
8
N
12
E
90
s% 80
15
% 10
30 80
0 .8
15
6V
%
70
OL
8
U
10
ME
%
20 60 70
-C
UB
0. 8
10
IC M
0%
4
5 6
D RY BU LB TEMPERA TU RE - C
5
ET
ER
40 %
PE
0 .8
10 5
Rk
4
2
gD
3 0%
60
RY
0 .8
20 (68)
A IR
20 %
0
2
0 .7
10% RE LAT
25
10
15
20
30
35
40
45
50
5
10 20 30 40 50
18 (64) 25 (77) ENTHALPY - KJ PER KI LO GRAM O F DRY AIR
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
58
424,000
3-55 SHF = = -4
530,000 424,000
mixing processes.
sen = -424,000 = m
(a) q sc p (t r -t s )
424,000
s =
m = 88,333 lba/hr
0.24 (75 95)
m r hm
(b) = r = 0.33 x 88,333 lba/hr
=0.33; m
mm hr
h
m
h = 0.67 x 88,333
=1 0.33 = 0.67; m
m
m
= 59,183 x 13.1/60
h = 59,183 lba/hr; Q
m h
(c) q ph =m
hc p (th -t o ) = 59,183 x 0.24 (60-35)
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
59
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
T OTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
-1.
-4 LB
0
0 TE
MP
55
0. 3
-0 .5
RA
- 0.4
50 80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
ENT HAL PY 'h
HU MIDIT Y RAT IO 'W 75
35 50
14 .5
.018
75
IR
A
Y
F
R
70 .016
D
Problem 3-55
F
30
R
O
TU
D
N
A
U
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
AL
25
SA
TH
N
.012
E
65
1 4 .0
60
90
% 50 %
VO
LU
ME
% .010
80 60 r 40
20
-C
55
U.F
%
70
T. P
20 % .008
ER
50 55
%
L B.
60
1 3 .5
DR
45 50
15
YA
50 % .006
DR Y BUL B T EMPERATUR E - F
IR
40
45 35
4 0%
35
40 m .004
1 3.
30%
35
0
s
20 %
.002
1 2.
Y
0 h IVE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
(a)
q 34 = m x 60 (i -i )
a3 (i4 -i3 ) = Q3 4 3
v3
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
60
= 31
(c) Q 2 ; Q3 = 0.754 x 75.7 = 57 cfm or 0.028 m3 /s
12
= 76 - 57 = 19 cfm or 0.012 m3 /s
Q1
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
SEA LEVEL 60
1.0 1 .0 85
1 5 .0
50 00 0 .8 .026
2.0 -2 00 0
-
0.8 300 0 0. 6 SENSIB LE HEAT
T OTAL HEAT
Qs
Qt
4 .0
8 .0
-1 00 0
45
0 .5 -8
-4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
0 -1. LB
0 TE
MP 55
0. 3
E
-0 .5
RA
50
- 0.4
80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
ENT HAL PY 'h
HU MIDIT Y RATIO 'W 75
35 50
90 %
14 .5
.018
Problem 3-56 75
IR
A
Y
70
R
70 .016
D
E
F
30
50 %
R
O
TU
D
N
A
U
ER
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
TU
P
62
AL
25
SA
TH
N
.012
E
65
1 4 .0
60 %
90
VO
LU
ME
% .010
80 60 40
20
-C
55
U.F
70
% 4
T. P
.008
ER
50 55
3 %
L B.
60
1 3 .5
DR
45 50
15 2
YA
%
50 .006
DR Y BULB T EMPERAT UR E - F
IR
40
45 35
4 0%
35
40
.004
30%
1 3.
35
0
20 %
.002
1 2.
Y
I VE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10
50 58.5
15
75 84 20 25
ENTHALPY - BT U PER PO UND O F DRY AIR
A reheat system is required. Process 1-2 is for the coil. Process 3-4
is defined by the SHF = 0.5
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
61
condition lines.
(b)
x 60
Q
q 34 = m
a3 (i4 -i3 ) = 3 (i4 -i3 )
v3
= q 34 v 3 = 100,000 x 13.4
Q 3
60(i4 -i3 ) 60(28.2-23.9)
(c)
5,194 x 60
q 12 = m
a (i1-i2 ) = (34.2-20.2)
13.4
5,194 x 60
q 23 = (23.9-20.2)
13.4
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
62
Copyright 1992 90
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
50 .028
1.0
SEA LEVEL 1 .0
60
85
15
50 00 0 .8 .026
.0
2.0 -2 00 0
-
300 0 0. 6 SENSIB LE HEAT Qs 4 .0 -1 00 0
8 .0 45
TOTAL HEAT Qt
0 .5 -8
-4 .0.0 85
-2. 0 WE .024
200 0. 4 0 T BU
0 -1. LB
0 TE 55
MP
0. 3
-0 .5
RA
- 0.4
50 80 TU
-0.3
0
0.2
RE
-0 .2
-0 .1
- F .022
0 .1
0 40
15
00
80
1 000
.020
ENT HALPY 'h
HU MIDIT Y RAT IO 'W 75
35 50
14 .5
.018
Problem 3-57 75
IR
A
Y
F 70
R
-
70 .016
D
E
F
30
R
O
TU
D
N
A
U
ER
50 %
PO
P
M
R
45
TE
PE
70 .014
N
U
O
T
65
TI
-B
62 1
P
TU
AL
25
SA
TH
N
.012
E
65
1 4 .0
60 %
90
VO
LU
56
ME
% .010
20 80 60
40
-C
55
4
U.F
%
70
T.
PE
.008
50 55
RL
%
60
B. D
2 3
13
ADP45
R
.5
15 50
YA
%
50 .006
DR Y BULB TEMPERATUR E - F
IR
40 35
45
4 0%
35
40
.004
30%
1 3.
35
0
20 %
.002
1 2.
Y
IVE H UM IDIT
5
10% RE LAT
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
66
10 15 20 25
processes on
Supply Air:
sc p (t s -tr )
q sen = 120,000 x 0.5 = 60,000 Btu/hr = m
60,000
s =
m = 53,192 lba/hr
0.24 (75-70.3)
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
63
Mixed Air:
Reheat:
q rh = m
c c p (t s -t c ) = 53,192 x 0.24 (70.3-55.2)
Coil:
q c =m
m (im -ic ) = 53,192 (34.4 - 24.2) = 542,558 Btu/hr or 159 kW
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
64
Copyright 1992 50
AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.
.028
5000 FEET 60
1 8 .0
80
1.0 1 .0
50 00 0 .8 .026
2. 0 -2 000 45
-
300 0 0 .6 SENSIBL E HEAT Qs 4 .0 -1 000
8 .0 80
TOTAL HEAT Qt WE
0 .5 -8
-4.0.0 T BU
-2. 0 LB .024
0. 4 0 TE
0.6 MP
200
-1 ER
.0
75
0
AT 55
75 U RE
0. 3
-0 .5
-
-0 .4
50 40 F
- 0.3
0
0.2
-0 .2
0.5 0
-0 .1
.022
0 .1
15
17 .5
00
10 00
75 50 %
.020
ENTHALPY 'h
35 70
HU MIDIT Y RATIO 'W 0
50
.018
R
F
AI
- 70
RY
E
UR
D
AT
F
O
65
Problem 3-58 30
90 %
ER
ND
.016
P
U
M
PO
TE
17 .0
R
N
PE
O
TI
TU
RA
65 45
-B
.014
TU
m
Y
SA
60
LP
25
TH
EN
.012
60
%
55 90
%
r 16
80 .5 V .010
20 40
55
50 c s
OL
%
70
U
ME
-C
.008
45 50 %
U .F
60
T. P
15
ER
16 .0
40 45 %
50
LB
.006
DR Y BUL B T EMPERATUR E - F
.D
35 40 35
R
4 0%
YA
IR
35
.004
30 %
1 5 .5
20%
10% RELA
TIV E HUMID
I TY 70 (21) .002
30
12 0
100
105
110
115
60
75
80
85
90
35
40
45
50
55
65
70
95
10 15 20 25
55 (13) 75 (24) 90 (32) ENTHALPY - BT U PER POUND OF DRY AIR
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted
by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.
Exerpts from this wrk may be reproduced by instructors for distribution on a not-for-prort basis for
testing or instructional purposes only t students enrolled in courses for which the textbok has been
adopted. ny other reproduction or trnstin ofthis work beyond tht permitted by Sections ]07 or ]08
of the 1976 United Sttes Copyright ct withut the permissin of the copyright owner is unwful.
Requests for permission or further informtion should be ddressed to the Permission Deprtment, John
Wiley & Sons, nc, ] ] Rier Street' Hoboken, NJ 07030'
Chapter 4
(c) comfortabe
(d) too dry
(c) comfortable
(d) too dry
4-3 (a) Assume sedentary dry bulb of 78 F, clo = o.5, met. = 1 .8,
using equation 4-4a, to,act = 75 - 5.4(1 + 0.5)(1.8 - 1 .2) = 71 F
Relative humidity should be less than 50%
(b) Should wear a S\/eater or light jacket and slacks.
(clo = 0.8)
4-6 From fig 4-3 @200 fpm, temp rise 5.3 F (2.9 C)
with t,,"-t _ 9 F (5 c), temp rise 6.5 F (3.6 c)
tmft:82For27'8C
tu x72 F
with met = 2.0. to, active = 78 - 5.4 (1 + 0.5) (2 - 1.2) = 71.5 F, (22C)
Exerpts fiom this work may be reprdued by instrutors for distribution on a not-1br-proit basis for testing or instrutiona puoses only to
students enrolled in urses for whih the textbook has been adopted' ny ther reproduction r trnstion of this wrk beynd ha permited
by Secions 107 r ]08 ofthe 976 Unied Stqes CopriPh cwithou he oermission fthe cpyrigh wner is unlful.
s an approximation
Tmrt = 2To _, and Tflx = Tno * ci121Tg _ ,
) Eq ' (4-1)
ta=85F(30C)
4-11 (a) Even if the suit was heavy weight, many executives would be
Xcets from this work may be reprodued by instuctors for distribution on a not-for-pro1'it basis for testing or instructional purpses ony to
students enrolld in ourses for which th tetbook has been adpted. ny other reproducion or trnstion f his rk beyond ht permitted
by Secions ] 07 or 108 o{ the ] 97 6 United Sttes Copyrigh c ithout the permissin of the coyright oner is unfu.
cool if sedentary.
4-13 Too much air motion in the cold winter months tends to cause drafts and
make people uncomfortabe. Air velocity just sufficient to prevent large
temperature gradients from floor to ceiling is best for winter. he opposite
is true for hot summer months. Higher air velocity tends to compensate
for high temperature and humidity.
4-14 (a) Raising the chiled water temperature will cause the cooling coil to
operate with a higher surface temperature and the relative humidity in
the space will tend to rise if the latent heat gain is signifcant such as
would be the case with many occupants, this could lead to
u ncomfortable cond itions.
(b) Yes, during the unoccupied hours the space load may be almost totaly
erpts from thrs work may be reproduced by instructors for distribution on a not-fr-profit basis for testing or instrutional puoses only to
students enrolled in ourses for whih the textbok has been adopled' ny other reproducion or rnsion of this rk beynd h permied
by Sections ] 07 or 108 f the 97 6 United Sttes Copyright c ithu he permissin f the cpyright oner is unlful.
Sensibe heat gain and the load is much less than the design value. ln
this case the chiled water temperature may be increased.
4-15 hese fans may bring air down in the Summer, increasing the
velocity of air in the occupied zone and providing improved comfort.
ln the winter, air may be drawn upward, pushing the warm air at the
ceiling downward where it can increase the temperature in the
occupied zone without increasing significantly the air motion below
the fan.
4'16 (a) able 4-2 gives a minimum required amount of ventilation air
of 15 ft3 /min per occupant. this is the minimum amount of
outdoor air that should be used under any circumstances.
(b) on the basis of floor area, the occupancy woud be 25 and the
minimum ventilation requirement would be
= (2001196 + (O.25l9o)
XctS from this work may be reprduced by instrutors for distribution on a not_tbr-profit basis for tosting or instrutional purposes only to
students enoled in courses for which the textbook has been adopted. ny her reprduction or rnsin of his ork beyond ha permied
by Secions ] 07 or 1 08 of he 97 6 Unied Stes Copyrigh c w ithul the permission of the cpyrigh oner is unlful.
or using Sl Units
N=n(5.Oml/s)
: 2.8 (1000-280) / 5.
4-19 Use the M-100 media of fig. 4-8. From table 4-3, select a
Ecerpts fiom this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructinal puoses only to
Studnts enroed in ourses for which the tetbook has been adopted. ny oher reproduction or rnston f his ork beyond ht permied
by Secions 1 07 r 1 08 of he 976 Unied Sttes Copyrigh c lithu he permission f the copyright oner is unful.
;g =(2000 l 514) = 3.89 or 4. This is a satisfactory number.
4-20 Use the M-100 media from Tabe 4-3 select a O.3 x O.6 x-O.2 unit.
This is rated at 0.3 m'/s with 1oo pa pressure drop.
t P 60 pa the alowabte flow rate for each unit would be
=
Q = (0.62) (60/1}q1t2 =
0.48 This would require more than two
units of this size. conomies would determine the best choice.
m=(2.8)/0.336=8.3
a (2.8)m3 /s
=1.73m1s
VelocitY =
FAc AREA (0.3)(0.6)(e)m2
Velocity
a 0.4
=2.22m1s
=
A (0,3)(o 6)
4-24 No solution exists due to the fixed air quantity for the unit. This
part of the problem is intended to show the student that typical
direct expansion equipment cannot be used in this \May. lt also
shows that the load due to outdoor air is very large.
4-25
exhaust
sHF= 0.7
66.8 F wb
''''J8?r;
is = 31 .- '' = 23'46 Btu / lbm
:8695'7 lb / hr
tr, = il1 = ^
-- 23.46)
(27 .6
() Design filters for 2014 cfm, use M-200 media of fig 4-8.
Try the 24x24x8 units of table 4-3. 920 cfm @0.4 in. wg.
purpses only to
on a not-for-profit basis for testing or instrutional
Excerpts tiom this work nay be reproduced by instructors fr distribution work beyond th permied
or trnslionf ths
students enrolled in ourses for which tl-e textbook -,u, ..n uopt"J '
ny oher reprduction
c thi permission ofhe copyright oner is unlwfu'
by Sectins ] 07 r 108 o7 he-|97|6 tJnited Sttes Copyrigh \,'ithout
75
--
A fresh air balance on the filter gives QrEt + Qo = Qs
Q. is supply air.
= 7 .2 modules
RQr={-2OOxO.85[180-(1-0.8)0.0]+(10x150x35'32)]l
RQ.
' =(0.65)(0.7)(220)
-9-*_!1!5^, = 15.53 cfm/person
4-31 (a) This type of space will require a high ventilation (supply air)
rate to handle the load, air cleanliness is not the main criterion.
Therefore, a low efficiency filter with low pressure drop is
acceptable. From table 4-2, assume occupancy will be about 30
persons / l OOO ft2. So the total design occupancy is 90
persons. he design will be based on this occupancy although
the cooling requirements may dictate a larger supply air rate.
Excets from this work may be reproduced by instrutors 1br distribution n a not-fr-prfit basls for testing r instructinal purposes only to
students enroled in courses or which the textbok has been adopted. ny ther reprducion or trnstion of his ork beyond
ht permitted
by Secins 1 07 or ] 08 of the 97 6 [Jnied Sttes Cpyright c thout the permissin f he copyright oner is unlful.
77
4-31 (continued)
(b) A higher efficiency would reduce the total amount of air and
x13 ft3 / ba
Qs = 3,149 cfm
(b) , = o = 15 x225
, = 3,375 cfm
-D 50 52
(c) Q. must be 3,375 cfm, find ne\/ Supply air condition
Excets frm this work may be reprodued by instrutors or distribution on a not-tbr-profit basis for testing r instructional purposes only to
students enroed in courses for which the textbook has been adopted. ny her reproduction or rnsation of his work beyond th permitted
by Sections 107 r ]08 ofhe )976 Unied SeS Cpyright ct withut the permissin fhe cpyright o]ner unl:wful.
Exets from this work may be reprodued by instructors for distribution on a not-for-profit basis for
testing or instrutional purposes only to students enrlled in courses for which the textbook has been
adopted. ny other reproduction or trnsltin of this work beyond tht permitted by Sections 07 or ]0B
of the 976 United Sttes Copyright ct without the permission of the copyright owner is unlwful.
Requests for permission or further informtion should be ddressed to the Permission Deprtment' John
Wiley & Sns, nc, ] ] ] Rier Street, Hoboken, NJ 07030.
Chapter 5
tnb
2
n2
5-5 R'= +
2k| 2koL
AssumeL=1ft
k:0'2 Btu - in' t(ft2 _hr_F); kp =314 Btu-in te _hr_F)
81
lnsulation 1 1.0
110 " :
, = "14.14)
-)- " +1=
116 7.41J
0 o77Btu / (r',..-tt' -r)
2x4 4'27
2x6 6.7
R = 3.55 (hr - ft2 _F) / Btu or 0.62 (.2 _c/W) [abte 5-3a]
q./
or
" --l'
U^ _ = o.625; q. / = 0.625(63 - 43) = 12'5 W/m2
(2x0
, _ '4
|l _[ l' 'l
/ a '.4l
Q/A..
l(
='n'L1oO] l _1o] l'
-]'
I I_
(o.O7 x117'2) + (O.4 x 17.78) + (0'81 x25'0)
117.2
Remove R for metal bath and plaster of 0.47 (f''. tt' - f)/Btu and
\"' - )
Uw= 9!+=oe71wr(m2-c)
0.1761 \ /
U = U*A* + U6 + + Uwinwin
5-19
R = '1
'375 l 1.25 R = 1 '375 l 1'25
Ro = 0.25 Ro = 0.17
R, = 2.03 R* = '1.95
Rn ' ., = ++
=U-R', 1.og
1 .O1 = 1'94, Un = O.52 Btu/1lr-ft2-F)
5-23 (a) Uw = o.o89 Btu /(hr - tt2 _ 11 or O.51 W/(m2 _ c)ale 5-9
l l-
,.Jfl _ .o29 Btu
-'L) lJur\ll/ (hr --Lft2 _F)
_|
l or O'16 W/
Jlv'l\J vYl1l (-'_c)
-)
ante 5-1o
xerpts from this work may be reprodued by instrutors for distribution on a not-for-profit basis for testing or instructional purposes only to
students enrolled in ourses for which the textbook has been adopted. ny ther reproducion or trnsltion f his ork beyond tht permited
..-_''r-] ^_':'_^'- ! ^'.'. ^'.4'
86
5-23 (continued)
tg__35'8-22 = 13.8; t:72re2c)
q* = 0.89 (4 x 20 x7) (72 - 1 3'8) = 2,900 Btu / hr or 0.85 kW
qn = 0.029 (20 x20) (72 - 13.8) = 675 Btu /hr or 0.2 kW
Re 2.08 36.6
=
#"+ =
Rf =
-:
0029
+ (1 tO.4s):\ 36.6
5-26 Rins =
# = 4'1z (rrr _f( _r)l tu
Excerpts fom this work may be reproduced by instrutors for distribution on a not-for-prfit basis for testing r instructional purposes only to
studentsenrolledincoursesforwhichthetextbokhasbeenadopted. nyherreproductionrrnstionofhisrkbeyondhpermied
'l-''':'''
bSecti.s1[]7ny nn{t]o 1076'b;l.)l-l-"/-^4'-')-"} :"'''.^''' l / .*'
87
Then from Fig. 5-8, U' = 0.85 Btu/(hr -f( -F) or 1.47 W(m-C)
Q= U'P (ti - to) = 0.85 x 300172 -101 = 15,8'10 Btu/hr or 4.63 kW
R^- 1 +7.22=26.5
- 0.052
U" = o.o38 Btu / (hr -ft2 _F) or o'22l(m'z_c)
Rn:++(t69)+ lw
0.16 \ '
(1 t4.6) =6.611m2-c1
Ecerpts frm this work may be reproduced by instructors for distribution on a not-for_pofit basis fr testing or instrutional purposes only to
students enolled in courses for which the textbook has been adopted . ny ther reproduction or trnsltion of his rk beynd ht permied
hi 9"};.-" a ^'' ]9 ^.}L- oaA L-;.^) c'-''^' '.''-:-' ^'"-^-:' "'-5{i ' . . .
88
(a) q/P = 0.81 (70 - 5) = 52'7 Btu / (hr - ft) or 50.7 W/m
(b) q/P = 1.37 (70 - 5) = 89'1 Btu / (hr - ft) or 85.6 W/m
R'=
2kL
of pipe wall.
purposes only to
for distribution on a not_for-profit basis for testing or instrutional
Excerpts from this work may be reprodued by instructors r rnslioi f this ork beyond ht permited
hu, "., uJo|i"a. ny oher reprucin
Students enollod in courses fbr h'ih the textbook : ''
^' '1-"4' "'
L- Q.nl;n-" n ^.'
'
6- 70-42 - =3,4488tu / hr; q/L = 34.488tu/(hr-ft)
' 8.12 x 1O-'
orq=1.01 kW; 9=33
L
1W/m
R'g =
=4.98x10-3 C/W
2 (1.4) 100
5-35 Moisturewillmovetowardtheinside.Locatethevapor
insulation'
retardent on the outer side of the
retardent is placed on the
The insulation will beome wet if the
plywood would probably \/arp
inside or left out entirely and the
and rot.
_F1
Uo = O'o71 Btu /( rr - ft2
purposes only to
basis for esting or instructiona'
reproduced by insructors for distribution n a no-for-prol yt.pern:ted
Excerps rom his \rk lnay be
students enrolled in courses fo ^: lh.
j:*tbook has *9,i'"l'Ji."o"'i,-:';;;;;;;;;;;"ii"111i117; ,:y::'::'|"*o
90
or 2-
tdp=37F<65F-ocondensationexpected
(c)Since|z=lS.3Fismuchlessthanthedewpoint,condensation
would ocur'
Place vapor retardent at the location of interface
1'
+(U** +U'P+rhcp)to',ti=72F;
*c __UrAtt, to = 1o F
(UtAt + U** + U'P + rhc, )
'1'5l0'8 =1'88
ssume 1.5 in. of wood floor, Pine; Rwoo =
rr -a'R*
"*_Rw v =0.68+(6/15)+ O'17 =1'25',U* = O'80
only to
basis fo 1e^sting or lnstructional purposes
Excrpts from this work may be rproduced
by instructors for distribution on a not-for-pofrt his ork beyond ht permited
'
of
-'", "* t.d. ,-ny otlr", ,rproEu.in r rnslio
students enolled in courses fr whih the textbo"t "J"p
91
(c) lf room air leaks into the air space for the case of no roof deck
insulation (b) there could be some condensation since t6p = 50
tl = ti _
_ to) = 22_ = 3.98 C or 39 F
ft,' ffir'+17)
tdp = 9.5 C, Assuming room air can diffuse into the air space,
condensation likely will form on the concrete block surface.
Therefore, place vapor retardant on inside surface of gypsum
board. Use foil backed retardent. Retardent must not touch
concrete blocks!
purposS ony to
Exerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instrutional
;;#;;;;ln o'l
_
rL6=
_(4.4+15.4)70+(2 x 0.8 x o) + (15.a x o)
" (2 x 1.08) + 15.4 + 14.4 + 5.4 -S5.8F
1
Ut = ; Rf = (2 x 0.92) + (1 5/0.8) + 2.1 = 5.82
&
Carpet and Fibrous pad assumed, Ur = 0.172 Btu/ (hr - ft2 - F)
ltrti
+( U** + Ubf f )tg
tb=
U11 + U** *Urr
l'b-_(0.172x400
r, x72) + (.1G4 x 80 x 7 + 0.029 x 4OO)1a.6
to = 30.3 F or -0.95 C
Exerpts from this work may be reproduced by instructors for distribution on a not-for-profit
basis for testing or instrutional purposes only to
students enrolled in courses fr whih the textbook has ben adopted. ny oher reproucion
or rnslii qf his ork beyond h nermied
by Seins 07 r ! 08 n! n." t o7A t r;lDs <}-t-^ .^^',-]-Ll t 1: ^^...'- -
basis fr
Excerpts frm this work may be reprodued
by instructr9 jor distribution on a not-for-prrt
textbook has been
enrlled in ourses for whih the
testing or instructinal purposes on1y to studes Sections ]07 or
of this work beyond tht permitted by
adopted. ny other reproduction or trns,ltion is unlwfu'
0B f the ]976 Unitei Sttes Copyright
ct withut the permission of the copyright owner
John
should be'ddressed ti the Peimission Deprtment'
Requests fr permissioln or furthir"infrmtion
iiria son, nr, ] 1 ] Rier Street, Hoboken' NJ 07030'
CHAPTER 6
6-1
Wind
Direction, deg.
CCW from N
6 140 0.0
(a) Pendleton, OR 11
-2 13 290 0.0
(b) Milwaukee, Wl
4 10 0.0
(c) Anchorage, L -9
12 340 0.003
(d) Norfolk, VA 24
18 I 360 .0
(e) lbuquerque, NM
20 0.003
(f) Charleston, SC 28 7
6-2
possible condensation on inside
Design relative humidity is determined by
(which is the maximum dew-
of glass. Find glass surface temperature
poi;t temperature of the inside air allowed)'
tr=
Uti + to (Cr - U)
cl
Design or
lndoor Outdoor tr=
City oF oF oF Max.
T, , top,
RH-%
(a) Caribou, ME 72 -10 35.5 26.2
6-3
Assume that the weather strip does not change the convetive heat loss.
From Figure 6-2, Cp = 0.3. Using Eq. (6-7b) with the air density of 0 'F,
the pressure difference due to wind is
P* = 0'037in'wg
I
Now Q, = rh cr(t1 - to) = v cp(t; - tr)
Q,r-8,, 64.t-20.5
-At-4, - 64.r
Q,, Qt = 0.68
6-4
ry]
s) _ 53.6P
P., =
_*
z.( .okg
t i/-s'
(a) From Table 6-2, K = 1 for tight-fitting.
Then, from Fig. 6-1, Q/L = 0.60 L/m-s
Q = 0.60 x (0.9 + 2'0) x2 = 3l8_L
ssuming that the wind speed and wind direction are the Same as the
given conditions for the bank at Rapid City, SD, the heating load (at -20'6
(: * . o
(' .#l r r,
* }r)rr,
_
1_zo.o1)" c= 393.tW
a, =
)
+ 1
6-5
From Figure 6-2, C = 0.52' Using Eq. (6-7b) with the standard air density,
the pressure difference due to wind is
r2
s#) (zz-en- l
p _
\-
o'sz (o o
(
#)' ( o.rnro :n:
r,
b^_f) lbflft')
^\
z.| z.17':::-_!-
lbf _s'z)
|
P' = 0't35in'wg
b-b
(b) For Bitlings, MT, design conditionS are to = -7oF, t= 72"F, = 28o/o.
From Table 6-3, K = 0.66 for conventional urtain wall.
6-7
6-7 (Cont.)
only to
instuctors fo dlstribution on a not-for-profit
basis for testing o instructional puoses
xcerpts tiom this wk may be reproduced by ork beyond hct permied
students enolled in ourses t. *-'}, the
textbook has been uaot,i 'ny ornr, ,rprort|uron'o''trnston-ths
per-ission of he cpyright oner is unfu'
by Sectins 1 07 or ] 08 o7 n' to:ii'inir-d Ses Cpyrgh' ''i"rii'i"''
'i"
9V
70oF
For Charleston, WV: to = 1 1oF' ti =
q, = (897 x ll \ 'z)(o'z4)(70-11) = 65'25 Btu/hr
q. = (897 x 60/1 1'72)(1060)(O'OO5 - O OOO) = 24'338 Btu/hr
q = q" + 9. = 89,363 Btu/hr
6-8
pressure difference due
(a) Assuming standard sea level air density, the
to the wind sPeed of 20 m/s is
(
o.o,urt\'(zo*pt *1.461L:\ /
fi,J =o 197in,water
,,_ |.9/+ tbfl
UUWindward: P*=O197xO25=ooo:
Windward Leeward
puoses only to
basis fr testing r instructional
by instrutos fo distribution on a not-for-profit h permtted
Excerpts tiom this work may^b reprodued
the textbook *' 119iJ]1'^"'i";:i:j!i::;:;:;:':""":jfi,':i:,i{:x:x#,.beyond
students enrolled n couSes tor whih
;}i::j;fii,Z'i'"f!"in:ii'ini,a s**, copy,ign,'a;,\iiio"i'', i,.'i-n of he coyrigh owner is unlwful
& r *--,-,
100
(b)
6-8 (Cont.)
.*
& \d
tl
R. ilt. lrate
Foor
Exfiltration _ Wind\/ard Sides, from 14th to 2oth
Leeward Sides, from 2nd to 2Oth Floor
(c) 1rt floor, lnfiltration on all sides - through doors, walls and fixed
windows
Then,totalinfiltration(neglectingtrafficeffect)is
Qtot = 154 + 1O + 356 31 =
+ 551 cfm'
6-9
[Note:t=70-(-11)=81oFisinconsistentwithProblem6-8where
to be minor]
t = 40"F was used; however, an
error is assumed
6-10
windows, doors,
Transmission heat loss (negtecting infiltration) through
walls, and roofs can be determined by Eq. 5-19 as:
q = UA(t -to)
Doors: A 2=243ft2',
= (3 x 6.75)1
From Table 5-8, U = O'28 Btu/(hr - ft2 - 'F);
(assume panel with metal storm door)
q = 0 28 (243)(70 - (-4)) = 5,035 Btu/hr
can be determined
Transmission heat loss through the slat-on-grade floor
bY Eq 5-23 as:
Q = U'P(ti -to)
heat losses;
Finally, total transmission heat loss is the sum of all
6-1 1
(0 5[ 0.0765y\-
fr' )
LP, -
z.(nllbry__s2
_
lbf
P* = 0.058 in. water
pressurization' thus
For a low-rise building, neglect stack effect and
P1 = 0.058 in. water
and doors'
From TabIes 6-'1 and 6-2, = 1 for tight-fitting windows
From Fig. 6-1, Q/L = O.'13 cfm/ft'
L" = [(3 x 3) + (2 x a)]x3 + (3+6.75)x2x3 = 109'5
ft
Qr= ('zx60/12'15)(16OX.O5_0.00)=372Btulhr
Qt= Q, + Qr. = 1,617 Btu/hr
6-12
6-13
oF; ti 70"F
Memphis, TN; to = 21 =
R*= 0.92+ 1.55 + 0.99 + 1.77 +0.17 = 5.4 (Tables 5-1 a'5-2a)
U* = 115.4 = O.'185 Btu/(hr - ft2 - 'F)
Us = 0.81 Btu/(hr - f( - "F) (Table 5-5a)
s = 6xax3 = 54 ft2
n* = (40xl O)-54 = 346 ft2
q,= 0.185 x 346 x (70 - 21) = 3,136 Btu/hr
qs = 0.81 x 54 x (70 - 211= 2,143 Btu/hr
Qtotrl = 5z auk!
6-14
6-15
6-16
(a) q=9s
vs
(i' - iu)
puoses only to
for distibution on a not-for-profit basis for testing or instructional
Excets from this work may be reprodued by instuctrs f ork beyond th permited
udo|ted ' Any other repriuctn or trnstion his
students enolled in ourses tbl which the textbook t-'as b"en oner is unlcnful'
cpyrigh
by Secins 07 or ] 08 7 *e l ol i ined Stotn, Copyrght
Act ithou tie permisiion of he
105
.^= q":-=:-_
(280'00)(14.6)
_
19(S
_21.8)60 =^251
v! cfm
i._iu 2.7
(b) q = rh cp(t, -
9
t..) =
vs
cp(ts - tr)
. q, (250,00)(14.6)
Q' = ;r== (O24X1 15_7O) =
5'633 cfm
6-17
SHF = 4st
Q./(9. + ") = 33, ooo
-100'999
(1 - oo, ooo)
===,
= -3.O3
1
EetS frm this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instrutional puoses ony to
students enolled in ourses for whih the textbok has been adopted. ny other reproduction or trnslion of this work beynd ht
permied
by Secions 107 or ] 08 of the 97 6 Unied Sttes Cpyright c ,ithout the permission f he copyrigh oner is unlnful.
106
t
ffi
p
n
i
Excerpts frm this work may be reprodued by instrutors for distribution on a not-for-profit basis for tSting or instructional puoses only to
studentsenlledinoursesforwhichthetextbookhasbeenadopted. nyotherreproductionortrnsltionfthisorkbeyondthpermitted
] 07 or 108 of he 976 [Jnited SteS Cpyright ct ihout the permission of the copyright oner i3 unlful.
by Sections
Exets from this work may be reproduced by instrutrs for distribution n a not-for-profit basis for
testing or instructional purposes only to students enrled in courses for which the textbook has been
adopted. ny ther reproduction r trnsltion fthis wrk beyond tht permitted by Sections ]07 or 0B
of the 976 United Sttes Cpyright ct without the permissin f the copyright owner is unlwful.
Requests for permission or further informtion should be ddressed to the Permission Deprtment, Jhn
Wiley & Sns, nc, ] ] Rier Street, Hoboken, NJ 07030'
Chapter 7
7-1
First, find longitude from Table B-1a
Then, convert Daylight Saving Time to Local Standard Time using Eq. 7-5
7-2
our angle (negative for morning and positive for afternoon) can be
determined by
7-4
/= 33.0 deg. N
From Eq. 7-8; sin(B) : os(/). os(ft). os() + sin(/). sin() = 0.593
= 36'37 deg'
- os sin / os h
"oo
^^^ __ sin cos /
= O.751
From Eq. 7-11; cos
north)
= 41.33 deg. (clockwise from
. sincos/
os="
_ossin lcosh
=-0'751
From q'7-11;
from north)
= 138.67 deg. (ctockwise
7-6
Maximumsolaraltitudeangle,willoccuratsolarnoon,h=0
]09-
For north latitude, / is positive and greater than |rrr| so we need largest
positive value of .
From Table 7-2, 'u" = 23'45 deg. and hence '", = 73.70 deg.
Therefore, maximum solar altitude angle occurs at solar noon on June 21.
For north latitude, / is positive and greater than |rrr| so we need largest
positive value of .
From Table 7-2, 'u"= 23.45 deg. and hence 'u"= 70.68 deg.
Therefore, maximum solar altitude angle occurs at solar noon on June 21.
For south latitude, / is negative and |/| is greater than l'u"l So \/e need
largest negative rralue of .
From Tabe 7-2, 'u, = -23'45 deg. and hence '", = 79.50 deg.
Therefore, maximum solar altitude angle occurs at solar noon on Dec 21.
7-7
Longitude'. Lt= 100 deg. W
Excerpts from this orktnay be reproduced by instrutors for distibution on a not-fr-profit basis for testing or
instrutional puoses nly to
l . _-__t!^lj.-^^''-^^^ ''^'^-^).'^1:^'"^-|-^aclntinnnfthj.srkbeondhDermied
110
Using Eq. 7-6, LSf = 15.50 - (100-90).4 /60+ '13.8/60 = 15.063 Hr or 3:04
pm.
7-8
= 39.92 deg.
7-9
XetS from this work may be reproduced by lnstrutors for distribution n a not-for-profit basis fr testing or instructional purposos only to
studerrts enroled in curses for whih the tcxtbook has been adopted. ny her reroductio or r1fisin f his work beyond ht ermited
Equation of ime: oT = -6.2 min
7-10
For Philadelphia, PA on July 21,
Longitude'' L= 75.25 deg. W
Latitude: / = 39.88 deg. N
Equation of Time: oT = -6.2 min
Declination: = 20.6 deg.
Eastern Daylight Savings Time: EDSI = 10:30 am
xerpts from this work may be reprodued by instrutors for distribution on a not-for-profit basis fr testing or instrutional puoses nly to
students enrol]ed in courses for which the textbook has been adopted. nyl other renro,l1ft;h ^v lf.l^i^,^ ^{lL]d 'l^yL o1'^') t1nt ^trmtted
112
Using q' 7-11 to find solar azimuth; = 114.30 deg. (clockwise from north)
(a) Using q' 7-13c to calculate angle of incidence for a horizontal surface,
(b) For vertical surface facing southeast, Surface Tilt; = 90 deg., and
Surface azimuth; = 135 deg. (clockwise from north)'
(c) For inclined surface faing south, Surface Tilt; = (90-40) = 50 deg.,
and Surface azimuth', = 180 deg. (clockwise from north)'
7-11
7-12
7-13
For Calibou, M on July 21,
Exerpts from this work may be reprodued by instrutors f,or distribution n a not-or-profit basls for testing or
instructional puoses only to .
students enrolled in courses for which the texook has been adpted. ny other rerlu"',--:':::':::!*::::]'-g:,od hl permted
113
Using q'7-11 to find solar azimuth; __ 230.2 de9. (clockwise from north)
7-14
Given lnformation:
Date: June 21
Longitude' Lt= 96'0 deg' W
Latitude: / = 36.0 deg. N
quation of ime: oT = -1 .4 min
Declination: = 23.45 deg.
puoses only to
Eerpts fiom this wrk may be reprdued by instrutors for distribution on a not-for-profit basis or testing or instructional -
f his wrk beyond h permited
students enrolled in ourses fb whih the textbook has been adopted. ny ther rerucion r rJ'lsalion
114
7-15
Given lnformation:
Date: lar 21
Latitude: / = 56.0 deg. N
Equation of Time: o = -7'5 min
Declination: = 0.0 deg.
Solar Parameters; = ao.g Btu/hr-ft2 or 1164\Nlm', B = 0'149'
and C = 0.109
Local Solar Time: LSf = 12:00 Pm
Surface Tilt; = 90 deg'
Surface Azimuth, S; = 180 deg' (clockwise from north)
Clearness number; CN = 0'95
Diffuse Reflectance from Sno\/; n = 0'7
puoses ony to
distribution on a not-for_profit basis for testing or instrutional
Excerpts from this work may b reprodued by instructors for rnstion of his rk befrr] .hot nermiti
has been adopted. thei ,eroucion or
students enrolled in courses for which the textbok 'qn
115
Using q' 7-11 to find solar azimuth; = 180.0 deg. (clockwise from north)
G^: PrF'r(sln+C)G'o
7-16
Given lnformation:
Date: Aug 2'1
Latitude: I = 32.0 deg. N
Equation of Time: oT = -2'4 min
Declination: = 12.3 deg.
Solar Parameters; = 350.9 Btu/hr-ft2 or 1107 \llm2, B = 0'182,
and C = 0.134
Local Solar Time: LSf = 10:00 am
Surface Tilt; = 45 deg.
Surface azimuth, SW; / = 225 deg. (clockwise from north)
Diffuse Reflectance from ground; n = 0.3
Exerpts from this wrk may be reprodued by instrutors for distribution on a not-for-pofit basis for testing or instructional puoses only to
students enrolled in ourses for which the textbok has been adopted. ny her renrdcin or trnstion f thi't yk hcn] thl nPrmitt/]
116
Using q.7-11 to find solar azimuth; = 118.7 deg. (clockwise from north)
7-17
The following results are determined from a computer program employing
equations in the book from Eqs. 7-6 to 7-26'
Following tables summarize input and output data calculated for southwest-
facing vertical window at32 deg. N latitude, 90 deg. W longitude, for all
daylght hours of a clear day on July 21with ground reflectance of 0.2 and
clearness number of 1.
lnput Data
Longitude 90 deg
Standard Meridian 90 deg
EOT -6.2 min
Latitude 32 deg
Declination 20.6 deg
Surf Azimuth 225 deg
Surf Tilt 90 deg
A 346.4 Btu/hr-ft2
B 0,186
c 0,138
cN1
RoG 0'2
Output Data
cDsr LsI o . o
Gruo* Go* Ga* G* G,* "
h, ,. , , ,
7.00 5.90 -91.55 9.50 71.57
153.43 151.90 112.19 O.OO 6.97 3.40 10.37
8.00 6.90 -76.55 21.78 78.63 146.37 140.64 209.84 o.OO 13.03 10.68 23.71
9.00 7.90 -61.55 34.38 85.69 139.31 128.74 249.18 o.OO 15.47 17.51 32.98
10.00 8.90 -46.55 47.09 93.60 131.40 116.76 268.71 o.OO 16.69 23.39 40.07
11.00 9.90 -31.55 59.65 104.24 120.76 104.98 279.23 o.OO 17.34 27.g5 45.2s
12.00 10.90 -16.55 71.33 123.59 101.41 93.63 284.65 o.OO 20.57 30.90 51.46
13.00 1 .90 -1.55 78.52 172.69 52.31 83.01 286.52 34.88 24.03
1
32.03 90.94
14.00 12.90 13.45 73.44 229.79 4.79 73.4s 285.30 81.05 27.54 91.28 139.87
15.00 13.90 28.45 62.18 252.83 27.83 65.62 280.70 115.85 30.36 28.70 174.91
16.00 14.90 43.45 49.71 264.52 39.52 60.08 271.44 135.41 31.69 24.45 1g1.54
17.00 15.90 58.45 37.00 272.79 47.79 57.55 254.30 136.46 30.69 18.81 185.97
18.00 16.90 73.45 24.37 279.93 54.93 58.44 220.69 115.51 26.33 12.15 153.99
19.00 17.90 88.45 12.00 286.94 61.94 62.60 141.60 65.16 1s.97 4.90 86.03
*Unit
of lrradiation is Btu/hr-ft,
7-18
Using the developed program, following tables summarize input and output
data caculated for south-facing Surface tilted at 45 deg. on Apr 21 in
Louisville, KY.
lnput Data
Longitude 85.73 deg
Standard Meridian 90 deg
Eo 1.1 min
Latitude 38.18 deg
Declination 1.6
1 deg
Surf zimuth 180 deg
Surf Tit 45 deg
A 358.2 Btu/hr-ft2
B 0.1 64
c 0.12
CN 1
RHOG 0.2
Output Data
o
tSI h, '. ," ,"," Gruo* JD G* ^*
JR ^*
ra
1.0 -165.0 -38.3 18.8 161.2 164.4 0.0 0.0 0.0 0.0 0.0
2.0 -150.0 -32.9 35.7 144.3 150.0 0.0 0.0 0.0 0.0 0.0
3.0 -'135.0 -24.8 49.8 130.2 135.4 0.0 0. 0.0 0.0 0.0
Exerpts from this work may be reprodued by instructors for distributin on a not-for_profit basis for testing or instrutional purposes
only to
students enrolled in courses for whih the textbok has been adnted. nll nthy
"o^.^)"
118
7-19
Using the developed program,.following tables
summarize input and output
data calcuated for an east-facing windw, 3
ft. wide by 5 ft. high, with no
set bak on a clea r Jul21 day in-Boise, lD.
nput Data
Longitude 116.22 deg
Standard Meridian 120 deg
oT -6.2 min
Latitude 43.57 deg
Declination 20.6 deg
Surf Azimuth 90 deg
Surf Titt 90 deg
A 346.4 Btu/hr-ft2
B .'186
c 0.1 38
CN 1
RHOG 0.2
Output Data
LSr h, o ,. o Guo* Go"
,' ," , G* GR* Gt* e
5.0 -,105.0 3.8 25.3 21.5 19.5
6.0 -90.0
65.0 25.0 3.6 0.4 23.5 352.4
14.0 74.8 15.2 20.6 160.9 .150.6 27.4 6.'1 184.1 2761 .3
7.0 -75.0 24.7 84.4 5.6 25.3 222.0 200.7 36.8 12.3 249.9 3747.9
8.0 -60.0 35.6 94.8 4.8 35.8 251.6 203.9 38.5 18.1 260.6 3908.9
9.0 -45.0 46.2 106.9 16,9 48.6 267.7 177.2 36.1 23.0 236.3 3544.7
10.0 -30.0 56.1 123.0 33.0 62.1 276.8 129.6 31.4 26.8 187.8 2817.2
1 1.0 -15.0 63.8 146.7 56.7 76.0 281.6 68.2 26.2 29.2 123.6 18s3.6
12.0 0.0 67.0 18.0 90.0 90.0 283.0 0.0 21.5 30.0 51.4 771.7
13.0 15.0 63.8 213.3 123.3 104.0 281.6 0.0 17 .5 29.2 46.6 699.7
14.0 30.0 56.1 237.0 147.0 117 '9 276.8 .0 17 '2 26.8 44.0 659.8
15.0 45.0 46.2 253.1 163.1 131.4 267.7 0.0 16.6 23.0 39.7 594.8
16.0 60.0 35.6 265.2 175.2 144.2 251.6 0.0 .15.6
18.1 33.7 505.9
17 .0 75.0 24.7 275.6 .185.6
154.7 222.0 0.0 13.8 12.3 26.1 391.9
18.0 90.0 14.0 285.2 195.2 159.4 160.9 0.0 10.0 6.1 16.1 241.6
19.0 105.0 3.8 295.0 205.0 154.7 21.5 0.0 1.3 0.4 1.8 26.7
*Unit
of lrradiation is Btu/hr-ft2
oE
is the rate at which solar energy strike the window in Btu/hr
7 -20
Given lnformation:
Latitude: l= 32.47 deg. N
Surface azimuth, S; z-= 180 deg. (clockwise from north)
Windowwidth;W=4ft.
Windowheight; H=6ft.
Setbackdistance; b=1 ft.
(a) On April2l
Declination: = 12.3 deg.
Local Solar ime: LSr= 9:00 am
Using q' 7-1'1 to find solar azimuth; = 106'27 deg. (clockwise from north)
4'
x.erpts from- this work may be reproduced by instructors 1br distribution on a not-or-profit basis for testing or instructional puoses only t
students enrol1ed in courses fbr which the textbook has been adopted. ny other reprducion or rnsl.tii of his wrk beyni th permied
bySections]07r]08ofhe976UniedlqaeC-apyrighcw,ihouheDern&1!!Mf1hecwlrjsh1 oue-r j'9g!!-g+&!. ."!:'.''' a
'-7
120
,h =W * H _ (W
- x) * (H _ y) = 22'52 ft2
7-20 (Cont.)
(b) On July 21
Declination: = 20.6 deg.
Local Solar Time. LSl. = 12:00 pm
Using q.7-11 to find solar azimuth; = 180.0 deg. (clockwise from north)
(c) On Sep 21
Declination: = 0.0 deg.
Local Solar Time: LSl. = 5:00 9m
Excerpts from this work may be reprduced by instrutors for dlstribution on a not-for_profit basis for testing or instrutiona] puoses only to .
studentsenrolledincoursesforwhihthetextbokhasbeenadopted. nyotherreproducionortrnsionfthisrkbeyondthpermted
by Secions 07 or ]08 ofhe 976 [JnitedSesCnriqhl '| \ithn1t th hovh'i'Ci' n{tho '^---:not '1lv'-
;a ''"^''t\'1
121
7 -20 (Cont.)
7-21
Given: Problem 7-20 with a tong 2 ft overhang located 2ft above the top of
the window.
For this problem, bo for overhang is the sum of the overhang depth and the
setback; hene, bo = /+] = 3 ft.
lo=botanlcosy_!o-.
where 1rr-, is the distance of the overhang above the window. Therefore,
o = (3 ft.)*tan(43.82)/cos
(73'73) - 2 _ 8'27 ft'
7 -22
setback'
Given. Problem 7-2owith 6 in. setback instead of 1 ft'
is 59'1%'
Therefore, the percentage of the window that is shaded
(c)UsingEqs.T-28to7-3Otocalculateshadeddimensions,
,h =W *
H _(W _.)* (H _ y) = 21'27 ft2
7 -23
on December 21, Declination: = -23'45 deg. Using the same procedure
as described in Problem 7-20, the following table summarizes the
calculated data.
7 -24
This problem is similar to ProblemT-21 but the overhang depth is 3 ft
instead of 2ft. Since the window in ProblemT-21 is completely shaded
in
7 -25
7 -26
7 -27
Eqs'
First, we need to know angle of incidence and solar irradiation. Using
problem),
7-8 to 7-26 (or a computeiprogr developed for previous
Then, the area of the glazing and of the frame is calculated to be 12'44
ft2
From Table 7-3, solar heat gain coefficients for the glazing system lD 21c
are
From able 5-6, the U-value for the fixed, double glazed window having
aluminum frame with thermal break utilizing metal spacers is 1.13 Btu/hr-
ft2-'F.
From Table 7-1, solar absorptance of the aluminum frame (assuming the
window is not a nev/ one) is 0.8.
ssuming the window with no setback (Ar,u'" = Aru), the SHGC for the
frame can be calculated using Eq' 7-31 as:
7 -28
glazing
From Table 7-3, the glazing transmittance and absorptances for the
system lD 21c are
puoses only to
Excerpts from this work may be reprodued by instructors for
distribution on a not-for-prfit basis for testing or instrutional
has .", uJopt". ny oher reprouction or rnsti of hs wrk beyond h permitted
students enrl]ed in ourses for whih the tx;book
125
7 -28 (Cont.)
Using Eq. 7-36, total solar heat gain absorbed by the glazing is
From Table 5-5a, the U-value for the center of glass is 0.42 Btu/hr-ft2-"F.
Then, the inward flowing fraction for glazing layer 1 can be calculated by:
Nt=0.42 14.0=0.105
The conductance from the inner pane to the outdoor air can be calculated
by:
,11
flo'2=
1 1=-1 1 =o'59Btu/hr-ft2-'F
U hi 0.42 .46
Then, the inward flowing fraction for glazing layer 2 can be calculated by:
Exerpts 1iom this work rnay be reprodued by instrutors for distribution on a not-for-profit basis for testing or instructional
puoses only to
students enrolled in ourses fbr which the textbok has been adoted' ny oher reproduction r lrnsltin of his wrk beyond th
permitted
126
7-28 (Cont.)
Using Eq. 7-39 and the SHGGr calculated from the previous problem, the
solar irradiation absorbed by the frame is
Using q' 7-40, the total absorbed solar heat gain of the fenestration
system is
7 -29
From Table 7-4, lAC for a lighted-color Venetian blind installed on a
residential double-pane window is 0.66.
Q suc = '226-2'56-220'9)
+ [0.548*12.44*163.4 + 0.52* 12.44*57 .5]*0.66
= 1108.48 Btu/hr.
7 -30
From Table 7-6, for a ighted-color Venetian blind, shade transmittance,
reflectance, and absorptance are 0.05, 0.55, and 0.40, respectivey.
7-30 (Cont.)
Qrroo = 0.05*1130.91 = 56.55 Btu/hr.
7-31
From Table 7-3, solar heat gain coefficients for the glazing system lD 5b
are
7 -32
From Table 7-3, the glazing transmittance and absorptances for the glazing
system lD 5b are
Using Eq. 7-36, total solar heat gain absorbed by the glazing is
Q llc'g = [1 63.4*(0.1924+0'12) + 57.5-(0. 1 9+0. 1 1)1-12.44
-===
7 -32 (Cont.)
= 849.60 Btu/hr.
ho,z=t\ =T-]
1 = 0.88 Btu/hr-ft2-"F
(]_ O55 - 1-46
hen' the nward flowing fraction for gtazing
layer 2 canbe calcutated by:
/vz=0.55/0.gg=0.625
Qwc = 1448'64
+ 212J6 = 1661'4 Btu/hr'