HVAC GENERAL NOTES DIFFUSER SCHEDULE

NECK MODULE FRAME MANUFACTURER


SYMBOL CFM SIZE SIZE TYPE PATTERN DAMPER MATERIAL SERVICE FINISH & MODEL NO. NOTES

I. GENERAL REQUIREMENTS: 3. ALL MAIN DUCTWORK (SUPPLY, RETURN, EXHAUST, OUTSIDE AIR) SHALL BE
GALVANIZED SHEET METAL CONSTRUCTED IN ACCORDANCE WITH SMACNA A AS NOTED AS NOTED 24x24 LAY-IN PLAQUE NO STEEL SUPPLY NOTE 2 TITUS OMNI 1,2,3
1. MECHANICAL CONTRACTOR IS TO FURNISH AND PAY FOR ALL LABOR, MATERIAL, STANDARDS. RUNOUTS FROM MAIN/BRANCH DUCTS MAY BE FLEXIBLE DUCT john l. harvey
EQUIPMENT, PERMITS & FEES REQUIRED FOR THE COMPLETE INSTALLATION OF ALL CONFORMING TO THE REQUIREMENTS OF UL 181 FOR CLASS 1 FLEXIBLE AIR DUCTS. B AS NOTED N/A 24x24 LAY-IN PERF. NO STEEL RETURN NOTE 2 TITUS PAR 1,2,3 Architecture + Design, Inc.
SYSTEMS IN THIS SECTION OF WORK. MAX. LENGTH OF FLEX PER RUNOUT TO BE 6'-0" UNLESS SHOWN OTHERWISE.
TITUS 350FL
C N/A N/A SEE PLAN LAY-IN PERF. NO STEEL RETURN NOTE 2 1,2,3 2128 Old Forest Drive
2. ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH NC MECHANICAL CODES 4. ALL SUPPLY AND RETURN DUCTWORK AND PLENUMS SHALL BE INSULATED.
INSULATION OF DUCTWORK IN UNCONDITIONED SPACE SHALL BE MINIMUM R-5 PER Hillsborough, NC 27278
AND ALL OTHER APPLICABLE CODES. MC IS TO COORDINATE W/ G.C. IN REGARDS NOTES:
2012 NCECC. INSULATION OF DUCTWORK OUTSIDE BUILDING THERMAL ENVELOPE office: (919) 883-1966
TO PROJECT TIMELINE, WORK HOURS, AS WELL AS ANY BONDING OR INSURANCE
(I.E. ROOF, ATTIC, CRAWLSPACE) SPACE SHALL BE MINIMUM R-8 PER 2012 NCECC. cell: (919) 323-1473
REQUIREMENTS. GENERAL - MC RESPONSIBLE FOR VERIFYING QTY, COLOR & FRAME TYPE 2. FINISH TO MATCH / BE ABLE MATCH CEILING OR WALL OR DOOR.
email:
OF DIFFUSERS/GRILLES BEFORE ORDERING. PROVIDE SQR TO RND 3. FACTORY INSULATION BACKING ON GRILLES EXPOSED TO NON-CONDITIONED AREAS.
5. CONCEALED SHEET METAL SUPPLY & RETURN DUCT MAY BE EXTERNALLY INSULATED info@harveyarchitecture.com
3. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED COMPLETE WITH ALL TRANSTIONS & PLENUMS AS NECESSARY. ALTERNATELY, FIELD SUPPLY AND INSTALL.
ACCESSORIES, HANGERS, SUPPORTS, CONTROLS, ETC FOR A FULLY FUNCTIONING WITH MINERAL FIBER BOARD OR BLANKET OR MAY BE INTERNALLY INSULATED WITH
ACOUSTICAL DUCT LINER. EXPOSED SPIRAL DUCTWORK DOES NOT REQUIRE 1. DIFFUSER DESIGNATIONS ON PLANS AS FOLLOWS: www.harveyarchitecture.com
SYSTEM REGARDLESS OF PRESENCE ON PLANS.
INSULATION UNLESS OTHERWISE NOTED (WHEN INSTALLED IN CONDITIONED SPACE). DIFFUSER OR
4. ALL EQUIPMENT, MATERIALS AND INSTALLATION SHALL BE GUARANTEED TO BE FREE NECK SIZE. DIFFUSER TYPE
8x4
6. ALL MAIN DUCTWORK (INCLUDING EXHAUST) TO BE SEALED ACCORDING TO 2012 A AS NOTED ABOVE
OF DEFECTS FOR A PERIOD OF ONE (1) YEAR AFTER FINAL ACCEPTANCE OF WORK 75
OR IN ACCORDANCE WITH THE MANUFACTURER'S STANDARD GUARANTEE, IF NCECC AND AT A MINIMUM INCLUDE SEALING OF ALL DUCT SEAMS W/ AIR QUANTITY
LONGER. ALL COMPRESSORS ARE TO INCLUDE FIVE (5) YEAR WARRANTY. EXISTING NON-HARDENING MASTIC. SEALING BY TAPE ALONE NOT ALLOWED.
EQUIPMENT IS EXCLUDED FROM WARRANTY REQUIREMENT.
7. ALL DAMPERS TO INCLUDE SET SCREW OR SIMILAR FEATURE FOR LOCKING IN EXISTING FAN POWERED BOX SCHEDULE MECHANICAL LEGEND
5. THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL LOCATION AND POSITION.
GENERAL DATA AIR FLOW HEAT ELECTRICAL DATA
ARRANGEMENT OF ALL MATERIALS AND EQUIPMENT. THE DRAWINGS SHALL BE
FOLLOWED AS CLOSELY AS BUILDING CONSTRUCTION AND ALL OTHER WORK WILL
PERMIT. IV. COORDINATION:
UNIT
TAG
AREA
SERVED
MANUF.
MODEL
INLET
DIA (")
MIN.
CFM
MAX
CFM
ELEC
(KW)
#
STAGES
VOLTAGE
(V/PH)
MCA MOCP
(A) (A)
NOTES
18x14 RECTANGULAR DUCT
maple
ENGINEERING, pllc
EXISTING DUCTWORK 1405 HILLSBOROUGH ST
REDD-1 RALEIGH, NC 27605 LIC.#: P-0990
6. DO NO SCALE DRAWINGS FOR MEASUREMENT. 1. THE MECHANICAL CONTRACTOR SHALL COORDINATE CLOSELY WITH ALL OTHER FB-1 OFFICE 8 300 650 3.5 1 208/1 25 25 1,2,3 P:919-341-4247 F:919-890-3797
NRFHE 500-08
TRADES TO AVOID CONFLICT AND ENSURE OTHER TRADES PROVIDE MEASURES TO FLEX/RIGID ROUND DUCT plumbing mechanical electrical
7. ALL DUCT DIMENSIONS SHOWN ARE INTERIOR DUCT DIMENSIONS. ACCOMMODATE MECHANICAL WORK (I.E. ACCESS DOORS, SLAB/WALL/ROOF NOTES
OPENINGS, ELECTRICAL CONNECTIONS, ETC). 1. EXISTING FAN BOX IS DUCTED TO 15 TON RTU. ENSURE BOX IS IN GOOD WORKING ORDER. BALANCE TO AIRFLOW SHOWN.
SUPPLY TAP WITH VOLUME DAMPER
8. BEFORE BID MC IS RESPONSIBLE FOR CLARIFYING W/ G.C. ANY CONFUSION IN 2. CONTROLLED BY EXISTING SPACE THERMOSTAT.
REGARDS TO RESPONSIBILITY OF WORK TO BE PERFORMED OR MATERIALS TO BE 2. MECHANICAL CONTRACTOR SHALL VERIFY LOCATION OF ALL PENETRATIONS FOR
PROVIDED. THE SUBMITTAL OF THE BID BY THE CONTRACTOR WILL BE HELD AS RELIEF HOODS, OUTSIDE AIR HOODS, LOUVERS, AND WALL CAPS WITH ARCHITECT & 3. REPLACE FILTER ON UNIT. SUPPLY DIFFUSER/GRILLE OR RISER
PROOF THAT THE CONTRACTOR UNDERSTANDS THOROUGHLY AND COMPLETELY OWNER PRIOR TO INSTALLATION.
THE SCOPE OF THE WORK INVOLVED, AND HAS INCLUDED ON THE BID ALL THE RETURN REGISTER/GRILLE OR RISER
NECESSARY ITEMS TO CARRY OUT THIS SECTION OF WORK. 3. LOCATE CEILING DIFFUSERS IN ACCORDANCE WITH ARCHITECTURAL REFLECTED TAGGED NOTES - THIS SHEET CONNECT TO EXISTING.
CEILING PLANS (IF PROVIDED).
9. ALL EXISTING EQUIPMENT AND SYSTEMS ARE ASSUMED BY ENGINEER TO BE IN GOOD
1 MOVE EXISTING THERMOSTAT TO LOCATION SHOWN. THERMOSTAT
WORKING ORDER. BEFORE BEGINNING WORK M.C. IS TO ENSURE ANY EQUIPMENT & V. EXECUTION:
SYSTEMS TO REMAIN ARE PROPERLY FUNCTIONING. NOTIFY G.C. IMMEDIATELY IF 2 RETURN AIR GRILLE TO BE HIGH ON WALL AND MATCH
PROBLEMS ARE DISCOVERED. 1/21/14
1. M.C. TO FOLLOW MANUFACTURER'S INSTRUCTIONS WHEN INSTALLING MECHANICAL EXISTING AREA GRILLES.
EQUIPMENT. ENSURE REQUIRED MAINTENANCE ACCESS AND CLEARANCES ARE
10. ALL QUESTIONS MUST BE SUBMITTED IN RFI FORMAT TO THE ARCHITECT AND MUST BE 3 EXISTING FAN BOX IS FED FROM MAIN TRUNK
MAINTAINED. IF CONFLICT EXISTS BETWEEN THESE PLANS AND MFG INSTRUCTIONS
ADDRESSED BY THE APPROPRIATE DESIGNER OF RECORD PROIR TO BECOMING A DUCTWORK IN THIS AREA.
CONTACT ENGINEER.
PROPOSED CHANGE ORDER. 4 EXISTING BUILDING PLENUM RETURN IN MAIN SPACE.
2. SEAL ALL PENETRATIONS OF RATED WALLS, CEILING, FLOORS IN ACCORDANCE W/
11. UPON COMPLETION OF WORK M.C. IS TO PROVIDE OWNER W/ COMPLETE BOUND APPROPRIATE U.L. PENETRATION DETAIL. 5 RIGID RETURN DUCT SHALL BE INTERNALLY INSULATED.
SET OF ALL EQUIPMENT OPERATION & MAINTENANCE MANUALS. PACKAGE IS ALSO
4
TO INCLUDE AND WARRANTY & GUARANTEE INFORMATION. 3. INSTALL ALL CONTROL DEVICES, INCLUDING THERMOSTATS AND SWITCHES, 4'-0" 6 RETURN BOOT FOR NOISE, SEE DETAIL.
ABOVE FINISHED FLOOR.
12. M.C. IS TO PROVIDE TRAINING TO OWNER OR OWNER'S REPRESENTATIVE IN
REGARDS TO OPERATION, FUNCTION, AND MAINTENANCE OF ALL MECHANICAL 4. INDEPENDENT CERTIFIED TEST AND BALANCE CONTRACTOR SHALL BALANCE SYSTEM
EQUIPMENT, CONTROLS, ETC. TO AIR QUANTITIES INDICATED ON PLANS AND IN ACCORDANCE W/ 2012 NCECC
AREAS SHOWN FOR CLARITY, NOT IN SCOPE.
SEC. 503.2.9. M.C. TO PROVIDE OWNER'S REPRESENTATIVE & ENGINEER WITH
II. DIVISION OF WORK: COMPLETE BALANCE REPORT. MC RESPONSIBLE FOR PROVIDING ANY DAMPERS, 2
VALVES, PORTS, ETC. NECESSARY FOR A COMPLETE SYSTEM BALANCE. 3 C 18X14
-
1. ALL LOW VOLTAGE WIRING RELATED TO MECHANICAL EQUIPMENT AND SYSTEMS IS
THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR (ANY LOW VOLTAGE FIRE 5. PENETRATIONS OF NON-RATED WALLS, PARTITIONS AND FLOOR OF COMBUSTIBLE
ALARM WIRING TO BE BY E.C.). ALL HIGH VOLTAGE CONNECTIONS TO CONSTRUCTION SHALL BE FIRESTOPPED WITH MATERIALS EQUIVALENT TO TWO
MECHANICAL EQUIPMENT, TO BE PROVIDED AND INSTALLED BY E.C. (SEE INCHES OF WOOD. FIRESTOPPING SHALL COMPLY WITH ASTM E-814.
EQUIPMENT SCHEDULE FOR DISCONNECT RESPONSIBILITY).
6. ANY NOTCHING, DRILLING, BORING OR OTHER ALTERATION TO BUILDING
2. G.C. TO BE RESPONSIBLE FOR PROVIDING AND INSTALLING ANY ACCESS DOORS STRUCTURE SHALL BE PERFORMED IN A CODE APPROVED METHOD AND NOT
FB-1
Office
(WALL, FLOOR, CEILING) RELATED TO MECHANICAL SYSTEM. M.C. RESPONSIBLE FOR THREATEN THE INTEGRITY OF THE BUILDING STRUCTURE.
COMMUNICATING TO G.C. SIZE AND LOCATION OF REQ'D ACCESS DOOR(S).
7. SUPPORT ALL DUCTWORK AND PIPING IN ACCORDANCE W/ 2012 NC MECHANICAL

14X10
3. MECHANICAL CONTRACTOR IS TO EMPLOY THE SERVICES OF THE G.C. FOR CUTTING CODE. ANY SUSPENDED MATERIALS SHALL BE DIRECTLY SUPPORTED BY THE BUILDING
AND PATCHING OF WALLS, FLOORS & CEILINGS RELATED TO THE INSTALLATION OF STRUCTURE.
MECHANICAL EQUIPMENT & SYSTEMS.
8. DUCT ACCESS DOORS TO BE PROVIDED AT ALL FIRE, RADIATION & SMOKE A 175

10X10
4. G.C. RESPONSIBLE FOR PAINTING OF ANY EXPOSED DUCT, PIPING, GRILLES, ETC. DAMPERS, SMOKE DETECTORS, CLEANOUTS AND ANY OTHER CODE REQUIRED
A 100
M.C. RESPONSIBLE FOR CLEANING AND PREPARING ITEMS FOR PAINT, COORDINATE LOCATIONS.
W/ G.C.
9. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL 2
III. MATERIALS: MECHANICAL EQUIPMENT FROM FOREIGN MATERIAL DURING CONSTRUCTION
(PAINT, SPACKLE, ETC.). UPON COMPLETION OF WORK THE MECHANICAL
1. ALL MATERIALS SHALL BE NEW UNLESS OTHERWISE SHOWN OR SPECIFIED. CONTRACTOR SHALL CLEAN, WASH, ETC ALL ITEMS AND EQUIPMENT WITHIN HIS C 18X14
-
SCOPE OF WORK AND LEAVE ALL ITEMS BRIGHT AND CLEAN.
2. PROVIDE HANGERS & SUPPORTS APPROVED FOR USE BY 2012 NC MECHANICAL B 22x22
-
CODE. 6

Conference B 22x22
-

6 Office

1 A 175
6
B 22x22
-

B 22x22
-
6

A 200 Revisions
No. / Description / Date

SUPPLY AIR DUCT. VOLUME DAMPER WITH


3/8" LOCKING QUADRANT
Reception
AND END BEARING.
ROUND SHEET (WHERE ACCESIBLE)
METAL DUCT. 22x14 DUCT
FLEX DUCT N.
" MI
DIAMETER "D" 18
W
LO
AI RF
ACCOUSTICAL This sheet is formatted for a
DUCT LINER 24" x 36" print. If this print
does not measure that -
refer to the graphic scale.
RETURN 6" MIN.
REDUCER OR
AIR GRILLE
Sheet Title:
FLARED SHOULDER & SQUARE TO ROUND
SPIN IN COLLAR W/ CIRCULAR CLAMP TRANSITION MECHANICAL
TYP. (IF NECESSARY)
INTEGRAL SCOOP. PLAN, NOTES, +
FINISHED SCHEDULES
CEILING SURFACE DIFFUSER/GRILLE
(COORD. FRAME TYPE)
NOTES:
1. PROVIDE INSULATED REGISTER BOOT/PLENUM BOX IF NECESSARY.
AIR FLOW

2. RETURN APPLICATION IS SIMILAR. ALL ELBOWS IN RETURN APPLICATION Date: JAN. 21, 2014
TO BE INSULATED SHEET METAL (NO FLEX ELBOWS).
Project: ZYY-1401

MECHANICAL PLAN Sheet Number:


3
DIFFUSER DETAIL
2
SOUND BOOT DETAIL 1 SCALE: 1/4" = 1'-0"
NO SCALE NO SCALE
M1