You are on page 1of 23
VOLUME 4 SCHEMATIC PLANS AND TECHNICAL REQUIREMENTS OF A 100-BED HOSPITAL 4.4 NURSING Service Facility aul Hospital DEPARTMENT DATA SHEET Department of Health HEALTH INFRASTRUCTURE, Tertiary, 100-Bed SERVICE Updated Reference: Department: Reference Sheet Number May 1991 WARD NURSE STATION AND SERVICE GROUP 41008-NU-DDS01 LAYOUT PER DEPARTMENT SHOWING ROOMS AND SPACE COMPONENTS. 2100 2100, 3) 13300 mm 4200 1400. 1000. aac: a aa ol CLEAN A] onty smut ORRIOOR TREATMENT ROOM fal edu 10. ‘AN Seale 1:100 me 44nd Hosptial Department of Health RES UATAISHEST HEALTH INFRASTRUCTURE Tetiary 100-8e Reo | Department bom Til Updated Reference a Roe Reference Sheet Number: Peay 1002 NPATIAARDS NS NURSE STATION TOE NU RDSOTA FUNCTIONAL DESIGN REQUIREMENTS: This aciviy space provides facies needed forthe following ore ee quantiry | REMARKS actviies ACCESSORY CHECKLIST 8. Nurse makes plan other acites ane determine her snerty acts, Nurse makes oper imeniony of resources, ie. supplies, drugs ete. to detemine requsitons tebe made Nuts prepares fe admission ofa patent 6. Nurse erters rar of patient in the admission book, ward sirectery 8 cet work | , Nutse makes phone cals to coordinate with otherunts | ofthe hospat | Nutse eterains queries Eom vistors ofpaient Nurse vcmas ana reper patent cae ates, FURN TURE AND, . QUANTITY REMARKS People involved FIXTURE CHECKLIST Ecienth aie +s cil crete em 1 Nursing Attendant ‘Chair, rack , | | eremeey | ee ‘ADDITIONAL EQUIPNENT ANO. ENGINEERING TERMINALS | QUANTITY | REMARKS Planning Relations: a Close t Nursing Wards. | Outet,telerone 1 1 aajacdi to Utity area anc Linen Rooms: Outlet 104, 2F, 240V, duplex 2 ‘grounding type ©. ose to Treatment Room. parallel stots ‘Smoke detector 1 Outlet inereom 1 4Antan Hospital, Terliay, 100-Bed ROOM DATA SHEET Department of Health HEALTH INFRASTRUCTURE SERVICE Department INPATIENT NURSING 4.414.168 ENVIRONMENTAL CCNOITONS | DESGN DATA ENVIRONMENTAL CONOMIONS DESIGNDATA Outdoor au temperature (deg.C) ave, local slaton temp reading |! General thumination (LUA) | 730 | Mecranical ventiation | Task ilumination (LUX) NA | Nome (eum thesperson) 278 Colour rendering essential DESIRAALE unnsenssayy in af | Eee Fon = ee decid i ii Sere a ‘Acceptable sound ievel (db) | 50 ‘SAFETY iy Se ee % Saale ee od es ae eee || = — Access limit atmedeine siatt ay Hosptat ROOM DATA SHEET Deparment of Health HEALTH INFRASTRUCTURE Teitiary, 100-Bed Sener | = ] : Department 3 Updated Reference: Room Tue Reference Sheet Number: ay 1982 De NURSE STATION TOOE-NU-ROSOTE TECHNICAL DESIGN DATA: LAYOUT OF ROOM AND SPACE COMPONENTS: DIRECT SERVICES DESIGN DATA Seale 1:100 mts. Dispos hospital atid waste tyne A S = 5 6000 m_ - Hot water reared a ik | 1500, 3000, 1500 ole water requred at sik & talot ues Drainage read at sik, oi, bdues & fr al 8 cos na g* ‘Compressed ait NA 3 g steam NA 8 5 others DIRECT DEMANCS ON FLOOR ANO WALL | Loading Na key Spitaae SLIGHT soccastonal requent | 1 Superwsing Nunes evbiie 6 Bulain board, 690x600 2 Counter, £00%m high, wih 200mm 7 Sbol Foot tae light: MEDIUM: heavy | dep shelves ard cabnets below 8 Chat eck ees 3 Desk, 75041200 9 Dirty tity area [Wuieerecie a, {Wilibung cabot SONG dap 10° Chan uity wee 5 Ghat, upg, sacking 11 Work Ace Impacss NA Aprasion na SPACE DEMANDS (Toe Minimum Space Requindin eam) 1260, Easy mointenance ESSENTHLdeuratc rvecesay | Space ompenans | Minimum Space RemizediCamponent ‘ibraton tee eer DESIRABLE unecessary Werk Area 2458qm eet sets 1, open een Tevet s15sam, Wineows nil REGULATIONS AND NOTES: Interna glazing nil AAAAAC 419 Hospital Department of Health ROBWPATA SHEET HEALTH INFRASTRUCTURE Tertiary, 100-Bed SERVICE Undated Reference INPATIENT NURSING Boom Tite Reference Sheet Number May 1062 WARDS UTILITY AREA TOoSNU ROSODA FUNCTIONAL DESIGN REQUIREMENTS: This actwily space provides facilities needed for the following po rete pheacd QUANTITY REMARKS: aciviies ACCESSORY CHECKLIST 2. Nurse performs clean-up related acivies in order SSniin counter with anessoecis ' to mantan order end hygiene inthe Nurse Staton baud knee at abe contre b. Nurse stores and ratraves ward sugplis. © Nurse maintains hospital equipment utize in the Modizino sinkin counter with 1 ward a1ea, gocsenedk epeut | FURNITURE AND rxTUREcHEGKST | QUANTITY | REMARKS Peoste invoived Courter 960mm high with | yk Nuiee {abinets below i Nussng Abendant ‘ial hung cabne, 330mm deep 1 Nuss ANE Aocked wal cabinet with inner Tooter naretc compartment aise ght ADDITIONAL EQUIPMENT AND ENGINEERING TERMINALS | QUANTITY | REMARKS Planning Relationships: ‘Qutet. 108, 28, 240 2 groundina tee, 3 Adjacent te Nurse Staton parallel slots ‘Out 188, 2P, 240. single 1 grounding tyce Tandem slots 2.48 200 Hospial Deparment of Heat ROCM BATA SHEET HEALTH INFRASTRUCTURE Tentery, 100-860 SERVICE Deparment ree NATE ARDS NS UTE AREA rete NU abseze TECHNICAL DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA ENMROWENTALCENGMONS| ———DESIGNOATA | AR LIGHTING ANO VISUAL Ouioer ar temperate dog) | ae, cal stn tmp. reading || Caneraiuniatn LUX) s00 ein Terperate 6.6) mosphere Ngntominaton (Lux) Na | Mechanics ventiaton Tek iliaton LUX) NA lure (eum -person NM Color encerag eset ‘DESIRABLE umacseery vey nt) Mm ‘Standby ght scat ‘DESIRABLE ocesny — Emergency ight [srt cee urease ena. 4 ayia eset dere UNNECESSARY wet i) nA View out ese DESIRABLE reecssary | scout tation na Privacy seid DESIRABLE rece idy RH) na Bch out essere, UNNECESSARY ano on (TA) ona | souNo | eco soured evel) A | sarery Speech pany cst OESRARE uns || acestle osu a ualtytichcannet be tenalimpadt | Maximum tampertue (eg. 6) NA tpertee Domest ot water at sii snk Moxinam operat (fo ©) 70 deca it nurshg sit [ Frersk LOW: meu: nigh Onerraks na 444.248 mI Hosoital Department of Health ROOM DATA SHEET HEALTH INFRASTRUCTURE Tertiary, 100-Bed SERVICE Department “ Undated Reference Room Tite: Reference Sheet Number May 1992 INERTIENT NURSING UTILITY AREA 100B-NU-ROSOZC WAROS. TECHNICAL DESIGN DATA LAYOUT OF ROOM AND SPACE COMPONENTS: DIRECT SERVICES DESIGN DATA Seale 1:100 mis. Depeeal hospital sod waste ype ‘A Hot water required al sik Gold water requred at sink Drainage provide at sik ote na Compressed at ma Steam NA Oihers OIRECT DEMANDS ON FLOOR AND WALL 7 Ke Loading na. ~ 1 Medicine shkin counter 4 Sinkin counter with gooseneck Srilage saht: OCCASIONAL :tecuert|| with gooseneck spout spout and knee or elbow 2 Locked wal cabinet with conta! Foottrafic light: MEDIUM: heavy ||” innertocker narcotic 5 allnurg civ, Storm oop compartment ane nse ight 6 Diy uty area wea! trae ma 3 Gounter, 8COmmhigh, wth 7 Clean utity area cabinets below bnpacts 1A Abrasion wa || space DEMANDS (TotaMinimum Space Requiced in sam): 6:0 Easy mainlerance ESSENTIAL desinbieumeessay || Space Cemponenis | Ninimim Space Required/Gompenent oration tee ESSENTIAL desrabe wrecesay |] Clean \niy Area sissam Door sets 1 open to creation ity Unity Area 318sam. Windows | ctear soar conte! REGULATIONS AND NOTES: Internat lazing fil 4AA2AC aan Tertiary, 100-Bed ae westReono | REYES Department of Health HEALTH INFRASTRUCTURE _ SERVICE Reference Sheet Number: 1008-NU-RDSOBA [FUNCTIONAL DESIGN REQUIREMENTS This actvty speoe provides facilites needed for the following aatnviies Clezn Linen Room 3. Storage of Clean Linen, ®. Issuance of Giean Linen, Soiled Linen Room 4, Transt storage of sles ten. ecole involved Nursing 1 1x Nursing Atendant EQUIPMENT AND ACCESSORY CHECKLIST QUANTITY | REMARKS Lines hamper Exhaust fen Boar chser 1 | stoic ine Roce | FURNITURE AND FIXTURE CHECKLIST | guawmiry | REMARKS Linen clase, 6Otmm doer ADDITIONAL EQUPMENT AND ENGINEERING TERMINALS | QUANTITY | REMARKS Planning Relationship. 2 Adjacent to Nurse Station ef Inpatient Nursing Wards Close to Inpatient Nursing Wards. 444340 ane ues aaa, EE seamipageet wesgrages | weARER Rone: | feasts | Paani Se | xr LIGHTING AND VISUAL Seema women 5 oo ce 5 a Yea ae aes! ee a most = nn aemommcon - mse aitieeeataeseel| var [sl icons ana es ae rsneempesont i rr oe ciate ‘Cooling load (TR) NM aes aaaemenen macmenaes a sina mane | enceemite| a — re rs aes] om | = — | [nea aaa ie é 4.4.4.3.48 bod Hospital Tertiary, 100-803 ROOM DATA SHEET Dapartment of Health HEALTH INFRASTRUCTURE eg geeree | meni RRons | eens | MMGRENRRRE DIRECT SERVICES DESIGN DATA Seale 1:100mis. ona co Diana NA i on “ a = " 5 5 ais AND WALL DIRECT DEMANDS ON FLOOR esa Sige ws | Feats FoR MEDIUM heaw |] ey Bane m 1 trent eon dee 3. Cling mounted hast fn 2 Kanara 4 orator | pets wa — sa ‘SPACE DEMANDS (TotalMnimum Saace Respite in sqm): 630, | nay meinveranse ESQENTIAL; debate: unnasezesn score DESTUBLE | rreesay | ‘Space Components | Minimum Space ReguredComponent | ration ree ‘Gkean Lnen Room 345sam, Door sets oramayy access door || SoledLiren Rear 3.4534m Wingows al ||_ REGULATIONS AN NOTES: i Internal glazing nil BAC BE Hospital Department of Health ROOM DATA SKEET HEALTH INFRASTRUCTURE Tertiay, 100-Bed SERVICE Updates Ret nex ENTRURSine eam Ties Reterence Sheet Number ated Relerence: er Peay 1992 WARDS TREATMENT ROOM 1008-NU-ROSO4A FUNCTIONAL DESIGN REQUIREMENTS: ‘This activity sp900 provides faciities needed for the folowing Acco eeecusr [QUANTITY | REMARKS: activites Instrument and seruo sink wit 4 ‘a. Patient anives on foot. in wheelchair or on a stretcher trolley tom ward, bb Transfer cf patient rom wheelchair or streicher troley ‘gooseneck spout snd spray aad knee control te examining table Eearanng tant A Physician or nurse administers necessary medical, artis oe ‘surgcal and first-aid treatment to patient. Seo 4 rast wcopmcie 1 URATERE AA QUANTITY | REMARKS FIXTURE GHEGKUIST People Involved Instrument abe 6003900 1 Physician Maye table 1 Nuise Footstol + Nursing Attendant Irigitor stand 1 Patient Dressing cart ‘Aijustatle sto! (Counter, Sco high wth cabinets Belew Wialcatinet 1 1 [ADDITIONAL EQUIPMENT AND ENGINEERING TERMINALS | QUANTITY | REMARKS Planning Relationships ark SRS : aL: Aajpcertiv Nupe station: uta, 108, 2, 240, due 4 around pe 1b Chase te Waras, paral siots ‘Outlet, 158, 29; 240 1 grounding type, ‘tandem slots Nurse call station, emargancy ‘ 4.41418 31 sesarsraee | wentERSONG | saelPRoow | SRE ENVIRONMENTAL CORDTIONS DESIGN DATA ENVIRONVENTAL CONDITIONS DESIGN ATA = vane Ave es = [nance ener 8 S | ‘Voluene (2u.mJnr-persan) W275 ‘Colour rendering ESSENTIAL Gesrable \anecessary [senna | sean aM aie on fe vn [sn ss ro ro et CR ‘ai san ho Ss 8 * ay es eh we Sooling!oad (TR) 1 aoa ventana 2 [ae — | is eat re ee erated Domestichot water: aoe ‘Acaess limit [ medical stat & patient | || omer is NA 441418 Hy Hospital ROOM DATA SHEET Department of Health HEALTH INFRASTRUCTURE Tertiary, 100-Bod SERVICE i Deparment Updated Reference: Room Title: Reference Sheet Number: thay 28 INPATERTNURSING | TREATMENT Room SEND RN TECHNICAL DESIGN DATA, LAYOUT OF ROOM AND SPAGE COMPONENTS: RECT SERVICES DESIGN DATA sues ‘saa an Sawa ook a rvr'eoer*re=e® Hotter | reg ole co water require Se & tet ies orainage prove oe dan ane “Ga rove gis an sxcton al | compressed a WA Steam | NA Others ‘Y nurses" cali (to Nurse Stabor) | DIRECT DEMANDS ON FLOOR AND WALL Loading NA Sailace SUGHT: oozasonal frequent Foot tatfe ght MEDIUM: heavy Wree! tte ght: MEDIUM: heaxy | mpacs NA Abrasion NA avy mantenancs ESSENTIAL ceerble umocaesiny Key 1 Waste receptacle 2 rigor stand 2 Gombinaton scrub sik and 9 View bor instumert sikwigooseneck 10 Dressing cart spout & spray & knee contol 11 Examining ight 3 Counter, 906mm tigh wih 12 Mayotable cabinets below 13 Instrument table, 600%800 4 Wat cabinet 14 Adjustable stoo! 3 Bulletin board 15 Gramining ble 6 Nurses cal station 1 Foststoo! 7 ‘Kick bucket 17 Intercom, watt mourtes rata tee ESSENTAL cearate umensery || _S°ACE DEMANDS (ol Minmum Spee Requdin aqan} 1585, Dove et examina isbe.wneeknar || SpaceCampnents, | _nmun specs RequreaCempenert | ‘teicher access ‘Treatmest Room 1260sem, | [_ Windows clea, solar contiol, privacy | Toilet 336sam, | cont REGULATIONS ANDNOTES: Internal glazing nil Provide tat proof shades 444 AAC Ay ] Department af Health ROOM DATA SHEET Hospi HEALTH INFRASTRUCTURE Tera, 100-Bed ae Department : | Updated Retorance ef Room Tit Reference She! Number re May 1992 INPATIENTNURSING |! EQUIPMENT STORAGE “OOBNU-RDSOSA WARDS FUNCTIONAL DESIGN REQUIREMENTS: ty space provides facies forthe fotos EQUIPMENT AND Te tty op ides facies needed forhefolowing || gc cEQUPMENTAND | quanriry | REMARKS ‘8. Storage of hesptal equigment nol in usa, ‘2g. oxygen tank, ete 1, Storage of clearing of msintenance equipment Soicliwtn FURNITURE AND, People Involved RURNITURE AND | quantity | REMARKS 1x Nursing Attendant Opan stating, 1 x Hospital Mantenance Stafl Planning Relationships: | 8, Close to Treatment Room [ADDITIONAL EQUIPMENT AND be, Close ty Nurse Station ENGINEERING TERMINALS | QUANTITY | REMARKS AAASAR aa Hospital Tr Department of Health ROOM DATA SHEET - Depanment |_wmgrser | west | ai Mane | MRD ENVIRONMENTAL CONDITIONS ESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA | { AR | Ligure ano visual | Quidaor airtemperature (deg C) | ave local station temp. reading | General iimination (LUX) 50 ‘Mechanical ventiavien - iT Task ilumnation (LUX! NA “Velocity ene) | NA ‘Standby light ‘essentia OFSIRABLE unnecassary Exmaust (ps!) NA Dayhgtt a essential’ desiabla, UNNECESSARY | Init (ps | NA View out essen desiatle: UNNECESSARY | a SOUND, | sarery ‘Acceptable sound level (do) | #0 ‘Accessible hot surface: WA 4.44518 209 Hospital - Deparment of Health sess wows ROOM DATA SHEET veronngrcne remacaaes | aR REARS | cour Eténace | SMSSSENERBSHE™ | TECHNICAL DESIGN DATA | LAYOUT OF ROOM AND SPACE COMPONENTS: sinect seavees DESIGN OATA Sea 100 mis Dipl | Na owt 5 cat was ss orenigs rr [os mn 1900 am, cones a ws —_ i= Suen - £8 Oe, | na ig REST DEMANDS ON FLOOR ANO WAL = toatng |] te we te sptaye we | retvane our nesen eb | tere metinstenn ly ‘Waee) eee Ms 1 Open shehing, 600mm deep | Impacts light, MEDIUM: heavy —— | sea UGiT: medium hana || smeEDRIMNDS Tasttnmum see Rages ineam) 984 enyinveuiaaee inst Seton ieee | Seestcieaeie | mine Release Vibration free -essentia DESIRABLE: unnevessary || Equpment Storage 2.40 sqm, | ower cay weit || ans cen sa f dons a REGULATIONS ADNOTES) a a | 4445.16 99) Hospital Department of Health ee HEALTH INFRASTRUCTURE ‘Tentary, 100-Bed SERVICE | Deparment, Updated Reference: INPATIENT NURSING Room Tile Reference Sheet Number May 1992 WARDS TYPICAL 2-BED WARD 1008 NU-ROSOSA FUNCTIONAL DESIGN REQUIREMENTS: EQUIPMENT AND This acy snace srovdes facies needed tothefolowna || nccesgony creexist | QUANTITY | REMARKS a. Patient may arrive an foct, Ina wheelchair or ona sretcner roy, Transfer of patient to a hospital bed from a wheelchair ora stretcher trolley and vice versa Patient urdressesiaresses 1 the vicinity of hospital bed, with or without assistance, Patient takes meals in bed or siting area. Patient recelves visitors Patient stores cothing and other personal belongings, Patient cequies prvacy Use of tilt ane bath Use of monitaring/diagnestis equoment Bhysicaans and nurse check on patiant Hand washing and other cieamup actives FURNITURE AND aati | qe People Involved FOSTURE CHECKLIST | 2 x Patients ‘Adjustable hospital bod 2 2x Vistors Queroes table 2 4x Resident Physician (Chair, uoriht stacking 2 1 Nurse of Nursing Aide Footstool 2 = ‘Beaside cabinet. SCOx600 2 Planting Relationships: [ADDITIONAL EQUIPMENT AND ENGINEERING TERMINALS | QUANTITY | REMARKS 8 Close to Nuse Staton Distant fo Outpatient Department Rail, eutan, wiedow : Close te Medical Surgical Servecas |) Rai cutan, cubicle 2 Cutlet, 104, 28, 2400, dunton 5 aroundieg type, parallel sts Bodiam 2 fourescent, 200 with ight ght with pendant ten “This sctviy soace provides facitine needed for he delivery of || util, 184, 2°, 240V. single: 1 grounding tyes, ‘Gene'siPationt Care tandem slots Nurse Caf Station, normal 2 Nurse Cal Station, emergency | + ‘Smoke detector 1 AN nan a an | Hospital Department of Health REOMIONEA SHEST HEALTH INFRASTRUCTURE Tertiary, 100-8ed SERVICE 5 Undated Reference INPAPENT NURSING Room Tite: Reference Sheat Number May 1992 WARDS TYPICAL 2-BED WARD 1008-NU-ROSOSE TECHNICAL DESIGN DATA ENVIRONWENTALCONOTTONS | DESIGN OTA ENVRONWENTAL ONDTIONS]| __—_ESKN DATA aR LIGHTING AND VISUAL | ont a wane ope} | ihc aston oa | is uc au 0 | repay, % nti LUX) ® | ethan vraon Task tuninaon (UX) 00 \olane (cum pen 129 lo eg eset DESRABLE ovens | olay (matey 909 Stancby ight ESSENTIAL :desratle unnecessary freiare istic at ser DESRABLE urecaty Exhaus! (psi) NA | Daylight essential: DESIRABLE -unrecessary wt) nA ewaut swt: DESRABLE- ures ‘st aon 39% men || Prey stl OESRABLE-wrewpay | Humiaey oF s Block ou essential sesrable UNNECESSARY ‘coking oad (TR) 1 eT E = ss SRT [eminem AAIAB aa — Deparror af Roath ROOMAOATA SHEET HEALTH INFRASTRUCTURE Tortry, 100-824 Sees | i Department: Update Reference on Reference Sheet Nunber 1 es IWPATIRTRERSING | ryoicROFLEBinan | SEE Sieose TEGHNIGAL DESIGN DATA LAYOUT OF ROOM AND SPACE COMPONENTS RECT SERVICES DESIGN DATA Saab 1100 mts r 3000 wm [ror owas eta 20 ‘00, 1600 Rain Se ee : ES nom old water ‘¢ toi tures|| 00 | cova [at oy Stites) | UE Eee - [age oglnintieti, [ute 8 opt 3] es [ue crpranangues |e SR | on coimicssne ma ita | seneeeecer | eer g [seam ss eee gl =e al se un att mga] ur a oe * ee g DIRECT DEMANDS ON FLOOR AND WALL Loading NA spllace SLIGHT ozasina:Hoxvent Fest tte ight: MEDIUM = Hey | ke secton 1 Rate nx na vires! taste gh: MEDIUM: heavy ||? Nu cra ein ii Bes ange at wipes Bs 12 Suen ost 13 Suter bee baat ta abason Na 4a, WHO oxy mantonnce ESSENTIAL eae vray SECTION avon tee ESSENTIAL date rece Door ets ad, stetorertoley wnedtoar || SPACE DEMANDS (lot nnmim Space Requedin gm) 1886 | | access Space Components | Minimum Space RequredConponent | Lwin clear sla cont, pracy Wardavea e090 contol “Tolet ard Bath 3.05 am, | nena lang ai | 442.40 ond Hospital Department of Heath ROOM DATA SHEET HEALTH INFRASTRUCTURE Tertiary, 100 Bed vice |. Department: Updates Reference Rear Tite Reference Sheet Number May 1082 INPATIENARD NS | TYPICAL 4-8E0 WaRD 1100B-NU-RDSO7A FUNCTIONAL DESIGN REQUIREMENTS, ‘his activty Space provides facities needed for the following sctities 2 Patient may arrive on foot in @ wheelchair of on & serene! tale ‘9, Transfer of patet toa hospital ved torn a wheetznair ora strelcher troley and wce versa. allen unaresseaiaresses in tne vicinity of nospial bed, with or without assistance Patient takes meat n bed or in sting area, Patient eceives vistors Patient stores clthing and oer personal belongngs Patent requires privacy Use of toll and bath Use ef monitering/diagnostic equipment Physcians and nurses check on patients Hang washng and other clean-up activites People Imowved Patiems vistors Resident Physioan 4 1 1x Nurse or Nursing Ade Planning Relationships 4: Close to Nurse Station 1 Disiany fo Outpaten: Deparmane € Clase to Medical/Surgical Services || This setity space crovides facies needed for te delivery of |) Nurse Call Staion, rormal Goneral Patent Care EQUIPMENT AND acceesenrcneckuier _CUANTITY | REMARKS | FURNITURE AND rietunecnecxust | QUANTITY | REMARKS ‘Agustabe rasoital bes 4 Overbed table 4 hai. ugh, stacking 4 | Footsioot 4 Bedside catine, 500x600 ‘ Lavatory 1 ADDITONAL EQUIPMENT AND ENGINEERING TERMINALS | QUANTITY | RENARKS Ral, curtain window 1 Ral, cura, eubele 4 Oust, 108, 2R, 2404, Duplex | 10 ‘| grounding ype paralel sles Bei ight wight amp 4 | tuceseer, 200, | vith ight ight | sy pera sen Outle, 15A, 2, 2407, Single 2 | srouncing type tandem slats 4 | with pendant Nuse Gat Staion, emergeney | 1 ‘| swrien 44340 Hospital ROOM DATA SHEET Department of Health HEALTH INFRASTRUCTURE wmegaraeeen | we ER | amt Twn | aa aa TECHNICAL DESIGN DATA: - | | Room Temperature (deg C) cod ‘Night slurmination (LUX) 3 | nectar venlon | sat numinaton (Lux) soo | “Volume {éu mfr, -persan) ALTE ‘Colour rendering essential DESIRABLE Unnecessary a dees se is mon rn Humidity (RH) 0 || black out essential: desirable UNNECESSARY ‘Cooling toae (TR) 2 - - eee ie DESIABLE unm | Aces et sce Na say ye cama be temo | _asmam temperate (9 ©) Na tolerated: | Domestic hot water at favatony | sim tneprse ag 6) % | | posesstit medical sta 8 patents Frerise LOW = mesium high Otner risks Na 4.43.18 gay Hospital Department ef Health ROSMIDATAIRHEST HEALTH INFRASTRUCTURE Tartiary, 100-Bed ‘SERVICE Undated Reference Department. Reom Title Reference Sheet Number May 1050 INPATIENTNURSING | Typical 4BED WARD erpoce get Nu TECHNICAL DESIGN DATA: LAYOUT OF ROOM AND SPACE COMPONENTS: DIRECT SERVICES DESIGN DATA 6000 Sab 1100 mis Disposal hoseital solid waste type ! AE 1400. 230 tne a8 Hot water requred a lavaery Cold water regi atlavatery & tote tures 8 Drainage roq(s at lav. 10: fie. Bf a as oxygen outlet reuired Compressed ar NA g 3 Stearn NA 3) 8 others suction outlet required § DIRECT DEMANDS ON FLOOR AND WALL Loss essing - NA iad Spiga SUGHT-poxasonal fequent | + Adjuabiohosp.bee 4 Badléecatinet & Cutan androd |] 2 cal, uprg stacking § Bad igh 9 Nurse cal ene) Fost wate ght MEDIUM: neavy | 3 Husecallstaion 6 Cvebestabie 10 Nurse cal dome ig 7 Fonttod = 11 Lavabry Whee! attic Yont: MEDIUM: neavy impacts NA fe 1 Adjustable hospital bed Abrasion Na Easy maintenance ESSENTIAL wine use| 5 Bed light 3 Nurses! cal station 4 Bedside cabinet vitration te ESSENTIAL! dosratie eet jeraton fee wowees |) 4 Suction outlet Door sets bad stetonertroley whesichair || 12 Svetion outlet backer sec uven access ‘SPACE DEMANDS (ots! Ninimem Space Requtedin sqm.) 28.56 Windows clea, solar contl, privacy || Space Components | Minimum Space Requied Component contol WardArea sqm | Internal clazing fi | Tellet and Bath 3qm AABAC 295

You might also like