You are on page 1of 6

1

Investigations into the Influence of Generator


Design on Rating of Circuit Breakers in a High
Voltage Transmission Network
J. D. F. McDonald, Member, IEEE, and T. K. Saha, Senior Member, IEEE

effectiveness of any changes to network configuration. This is


Abstract--This paper examines the impact of the network particularly pertinent when considering augmentation or
modification produced by the replacement of an existing replacement of existing generation capacity with generators of
conventional generator with a high voltage directly connected new or innovative design, such as PowerformerTM, the high
generator on the adequacy of existing circuit breakers distributed
voltage generator developed by ABB in 1997 [3].
throughout a high voltage transmission network. The
significance of generator design changes is assessed by comparing
the critical fault types producing maximal circuit breaker current
through each breaker in the original and modified networks. In
the majority of cases the impact of even significant generator
design changes on the nature of these critical fault types is
restricted mainly to breakers in the immediate vicinity of the
generator of interest. Finally, analytical expressions quantifying
the influence of generator design on the current flows produced
by faults through circuit breakers distributed network-wide are
developed to clarify the results obtained from simulation.

Index TermsCircuit Breakers, IEEE Standards, Fig. 1.Comparison of PowerformerTM and conventional generator [3]
PowerformerTM, power system faults, power generator planning
PowerformerTM is able to generate electricity at
I. NOMENCLATURE transmission voltage levels and can inject power directly into
m bus at which generator of interest connected to network the transmission network without need for a step-up
k bus at which fault occurs transformer. Previous studies indicate that the fault current
l bus at remote end of line under consideration (amperes) produced by a three-phase fault at the terminals of
the directly connected generator will be significantly reduced
II. INTRODUCTION when compared with the corresponding fault at the terminals
of the conventional generator while remaining comparable to
C ircuit breakers form an integral part of the protective
system for an electric power system. As stated in [1],
satisfactory network behaviour is maintained under fault
the fault levels produced by a fault on the HV terminals of the
generator step-up (GSU) transformer [3].
conditions through quick isolation of the faulted portion of the This paper, however, examines the impact of generator
network, minimization of the available short circuit current design on the fault types producing maximal current through a
and reducing the duration and extent of the outages by circuit breaker under fault conditions, thus determining the
providing alternate circuits and automatic transfers. These critical fault type of each breaker. This critical fault type
objectives can be obtained only through correct selection and can then be used in a formal breaker rating process, e.g. IEEE
operations of circuit breakers throughout the network. Std C37.010 1999 [4], leading to a thorough assessment of the
Any modification to network configuration may impact impact of the replacement of an existing conventional
upon the adequacy of existing interrupting equipment. Given generator and its (GSU) transformer by a directly connected
the considerable capital investment that must be allocated to generator of varying sub-transient reactance on the adequacy
these devices [2], the cost of any required breaker alterations of existing network breakers.
or augmentation must be included in assessing of the cost As well as considering the variation in critical fault types
determined by simulation of different network configurations,
This work was supported by an Australian Research Council S.P.I.R.T. this paper also presents the derivation of an analytical
Grant along with the generous contributions of the affiliated industry partners. technique for quantifying the potential impact of generator
J. D. F. McDonald and T. K. Saha are with the School of Information design variations upon the different fault types. This technique
Technology and Electrical Engineering, University of Queensland, St Lucia,
Queensland, Australia, 4072 (e-mail: jdm@itee.uq.edu.au,
is then used to provide further insight into results obtained
saha@itee.uq.edu.au). using conventional simulation procedures.

0-7803-7990-X/03/$17.00C2003 IEEE
2

III. CIRCUIT BREAKER RATING PROCEDURES Line flow 1 current Line-out fault current
The principal function of a circuit breaker as defined in [4] Line flow 2 current Line-end fault current
is to carry load current and interrupt short-circuit current. The The different line currents are illustrated in Fig. 8 while the
time-dependent nature of power system short circuit behaviour line-out and line-end fault are assumed to correspond to their
means that these parameters can only be determined accurately standard definitions.
by a dynamic stability study. A satisfactory estimate of fault Different network configurations are required to calculate
behaviour can be determined through use of industry standards
each fault type, ensuring that the values of E X , X R and the
such as the IEEE C37 standards or IEC 60909 international
standards. The standard techniques represent a compromise consequent ac and dc decrement multiplying factors will also
between solution accuracy and simulation simplicity [2] differ, depending upon the critical fault type determined at a
providing a conservative estimate of the parameters required specific breaker location. It then can be assumed that a change
for breaker application. The scope of this study was limited to in the critical fault type of a given breaker is potentially
the IEEE C37 standards, given their comparatively less indicative of a change to breaker rating as calculated using
complicated and perhaps more efficient solution procedure. [5] IEEE Std C37.010 1999. Determining the number of circuit
breakers whose critical fault type is affected by a network
A. IEEE Standards modification will provide an assessment of the suitability of
The IEEE Standards C37.04 1999 [6], C37.06 -1997 [7] existing circuit breakers for use in the altered network.
and C37.010 1999 [4] outline clearly the procedure for
relating specific network conditions to required breaker ratings B. Simulation Procedure
allowing selection of suitable breakers for each application. In order to assess the influence of generator design on
This investigation was confined to a consideration of only the circuit breaker ratings an extensive fault study was completed
short circuit current and related capabilities. The short circuit on 600 bus transmission network modeling the transmission
capabilities of a circuit breaker rated according to these system used in Queensland, Australia. It was assumed that
standards is characterized by its rated short circuit current. every line was equipped with a breaker connected at each end
This is defined in [6] as: the symmetrical component of while each generator was also protected by a generator circuit
short-circuit in rms amperes to which all required short- breaker. This configuration represents more breakers than
circuit capabilities are related. By determining the impact of would be used in a realistic system but provides a clearer
generator design on this parameter, the influence on illustration of the regional impact of generator design changes.
parameters such as symmetrical or asymmetrical interrupting The replacement of six different generators was considered,
capability or rated closing and latching current carrying although results for only three different generators locations
capability is also addressed. will be detailed. Figure 2 illustrates the comparison between
1) Short circuit current calculation the combinations of the sub-transient reactances of the
The IEEE Standard C37.010 1999 outlines two methods conventional generators with short circuit impedances of
for calculating the rated short circuit current. The basis of their GSU transformers to the sub-transient reactance of the
both methods is the calculation of the fault current E X , where analogous directly connected generators.

E represents the pre-fault voltage and X the equivalent Connection of PowerformerTM - fault impedance change
Generator
Generator / transformer impedance [ p.u. ]

network reactance at the fault point. Depending upon the level


0.4 Transformer 0.4 PowerformerTM fault impedance [ p.u. ]
of accuracy required, this estimate either can be used directly Powerformer
TM

or modified to account for ac and dc decrements. The required


modifier depends upon the closeness of the fault to significant 0.3 0.3

generation and the X R ratio at the fault point.


0.2 0.2

IV. ASSESSMENT OF INFLUENCE OF GENERATOR DESIGNS ON


CRITICAL FAULT TYPES
0.1 0.1

A. Relationship of Critical Fault Types and Breaker Ratings


A limitation of the procedure outlined in C37.010 1999 0
Tarong Collinsville Swanbank
0
[4] stems from the lack of consistency between the fault
currents produced by bus faults and the actual line currents
Fig. 2. Comparison of conventional generator / PowerformerTM fault
that must be interrupted by the circuit breakers [8]. Maximum impedances
breaker current is also dependent upon the breaker
arrangements used in the network. Without specifying The relationship illustrated is representative of that
precisely the network-wide breaker locations maximal breaker expected between the fault impedance of a conventional
current must be calculated by comparing at each breaker generator and a corresponding high voltage directly connected
location the different fault current line flows as designated by generator. The sub-transient reactance of the directly
3

connected generator usually will be similar to or slightly lower These results highlight the limited number of breakers at
than the total fault impedance of the conventional generator which the critical fault type will be affected by the change in
and GSU transformer replaced. generator configuration. At Collinsville a slight variation in
The most important step in the procedure was the the system in-feed to the breaker connected at what was
comparison at all breaker locations of the magnitude of fault formerly the GSU transformer high voltage terminals increases
currents produced by each of the four fault types. The the significance of the line-out fault marginally. The
maximum fault current at each point defined the critical fault magnitude of this variation however is not overly significant.
type that should be used to rate a specific breaker. This 1) Conventional generator circuit breakers
process was completed on the original network along with The two breakers affected by the change in design of the
each of the modified network configurations considered. Swanbank generator are the conventional generator circuit
breaker and a circuit breaker on the low voltage terminal of the
C. Test Cases
original step-up transformer. The identity of these breakers
The impact of changes to generator design on breaker rating has been retained in the directly connected system although in
is examined by simulating the following test cases. a realistic network these breakers would be removed or
1) Case 1 replaced as a result of the radical change to generator terminal
In the first case, the conventional generator and GSU fault current (amperes) produced in the modified network.
transformer was replaced with a directly connected generator The fault current produced by an earth fault on the directly
with fault impedance equal to the total fault impedance of the connected generator terminal would also exceed the
conventional generator and transformer replaced. This shows permissible levels for a generator circuit breaker rated
the impact of replacing a conventional low voltage high according to IEEE Std C37.013-1997. [9]
current generator with a high voltage low current generator. Perhaps it is more appropriate to note the lack of change to
2) Case 2 the rating of the breaker formerly at the high voltage terminal
The second scenario involved replacing the conventional of the GSU transformer that would become the generator
generator and GSU transformer with a realistically designed circuit breaker in the directly connected system.
high voltage directly connected generator. The specific
generator impedances used are illustrated in Fig. 2. B. Case 2
3) Case 3 TABLE II
In this case a short circuit was substituted for the CRITICAL FAULTS TYPES CONVENTIONAL GENERATOR REPLACED WITH
REALISTIC POWERFORMERTM.
conventional generator, with GSU transformer impedance left
unchanged. This configuration illustrates both the maximum Fault Type Tarong Collinsville Swanbank
impact of changes to the conventional generator design in Line flow 1 1 1
conjunction with illustrating the replacement of a conventional Line flow 2 1 1 1
Line out 1
generator and GSU transformer with a directly connected Line end
generator of comparatively low fault impedance.
4) Case 4 The results of Table II again emphasize the limited change
For the final test case, the conventional generator and to critical fault types produced by the introduction of a more
transformer were replaced by a directly connected generator of realistically designed directly connected generator.
negligible fault impedance. Although this is not a realistic Although the fault in-feeds of the directly connected
scenario, the results obtained illustrate the greatest impact of generators were more pronounced than that of Case 1, the
directly connected generator design on fault behaviour. proximity of the generator to the meshed transmission system
ensured that the rating of breakers attached to the high voltage
V. SYSTEM RESULTS generator terminals and surrounding lines would be dominated
The results listed in Tables I III include the number of by the system contribution. At these points critical fault types
breakers who critical fault types have been changed by each were unaffected by the different high voltage generator design.
alteration of generator design. The italicised and bolded C. Case 3
columns represent the critical fault types of the affected TABLE III
breakers in the original and modified networks respectively. CHANGE IN CIRCUIT BREAKER CRITICAL FAULTS CONVENTIONAL
GENERATOR REMOVED.
A. Case 1
TABLE I Fault Type Tarong Collinsville Swanbank
CRITICAL FAULTS TYPES CONVENTIONAL GENERATOR REPLACED WITH Line flow 1 1 2 1 2
POWERFORMERTM. Line flow 2 1 1 1 1
Line out 1
Fault Type Tarong Collinsville Swanbank Line end 1
Line flow 1 1 1
Line flow 2 1 1 1 As highlighted previously, the interpretation of the results
Line out 1 obtained in this case will depend on the manner in which the
Line end
reduction in conventional generator fault impedance is viewed.
4

If the network modification is viewed as a reduction in fault Collinsville - Variation in Critical Fault Types
10
impedance of the existing conventional generator then it would Modified Network

Number of Breakers Rated by Fault Type


9 Original Network
appear that the influence of the conventional generator on
8
circuit breaker ratings is fairly limited. The majority of change
is confined to breakers located near the generator terminals 7

with the variation in critical fault type due mainly to the 6

increased significance of generator fault in-feeds. 5


If this network change however is considered as the 4
replacement of a conventional generator and GSU transformer 3
with a directly connected generator of reduced sub-transient
2
reactance then it would appear that even this large change to
1
generator design does not lead to a comparably large change to
0
the critical fault types of breakers in the modified network. As Line Flow 1 Line Flow 2 Line Out Line End
Critical Fault Types
highlighted above, the breakers where change is most
pronounced are those at the terminals of the LV generator. Fig. 4. Change in critical fault types Conventional generator at Collinsville
These breakers would be removed in the directly connected replaced with S/C directly connected generator
configuration. More importantly, the appreciable increase in
The significant impact on critical fault types was observed
generator fault contribution still does not affect the breakers
mainly for breakers located on lines relatively near to the
connected at what was originally the HV terminal of the GSU
directly connected generator. The change in critical fault type
transformer, as they remain controlled by system fed faults.
was often due to the increased fault current in-feed from the
The large change to generator design however did highlight
directly connected generator. In several cases however the
the significant regional influence of both conventional and
breakers affected were not geographically close to the
directly connected generators on network fault behaviour. The
generator. In these cases it appeared that the increased line-
generator design variation at both Tarong and Collinsville lead
flows in the modified network placed a greater significance on
to changes in the critical fault types of breakers over 150 km
line flow rather than line-out or line-end faults.
away from the generator terminals, although the actual change
to the short circuit current ratings was limited to around 2%.
VI. ANALYTICAL ASSESSMENT OF INFLUENCE OF GENERATOR
D. Case 4 DESIGN ON FAULT CURRENTS
The final change to generator design considered represents Although the results obtained suggest that impact of the
the most significant network modification that could be replacement of a conventional generator with a directly
produced by the introduction of a directly connected generator. connected generator is relatively limited, a more analytical
While these results obtained are somewhat un-realistic the approach is required to determine the specific network
trends illustrate the expected impact of replacing the existing conditions that control this phenomenon. Of particular
conventional generator/transformer by a directly connected consequence would be the identification of those system
generator with very low fault impedance. configurations where even small changes in generator design
As can be seen in Fig. 3 and Fig. 4, the introduction of the would place pressure on the adequacy of existing breakers.
low impedance directly connected generator produces a In earlier work by the authors [10, 11] analytical
change in critical fault types at a number of breaker locations. expressions were defined that illustrate the degree of influence
that the design of either a single conventional or directly
connected generator exerts upon the bus fault currents
Tarong - Variation in Critical Fault Types
6
Modified network
produced at points throughout a high voltage transmission
Original network network. Similar expressions could also be obtained that
Number of Breakers Rated by Fault Type

5
quantify the influence of generator design upon the fault
quantities needed for circuit breaker rating including the line
4
currents produced under fault conditions and the line out or
line end fault currents.
3
Simple expressions can be developed for the impact of
2
generator design on line currents. This is confirmed in the brief
derivation of the required equations in the attached appendix.
1 It was not possible to derive similar concise equations for
lineout and lineend faults currents. Instead the system
0 modifications required for calculating these fault currents were
Line Flow 1 Line Flow 2 Line Out Line End
Critical Fault Types first applied to the network from which the influence of the
generator of interest had been completely removed. It was
Fig. 3. Change in critical fault types Conventional generator at Tarong
replaced with S/C directly connected generator then possible to obtain numerical solutions to the equation:
5

I (fk ) =
Vk {(ZG + ZT ) + Z mm } (1) on the breakers critical fault types.
Z kk Z km Z mk
( ZG + ZT ) + Z mm
Range of break points - PowerformerTM at Collinsville
Z kk
Line End
This characterizes the influence of generator design on line-
end and line out fault currents. The validity of this approach
Line Out
was verified by comparing the maximum potential variation in
the line-out and line-end fault currents calculated from
manipulation of equation (1), as using a method described in Line Flow 2

[10], with the ratio of the fault currents determined from


simulation of the test system with the fault impedance of the Line Flow 1
generator of interest either very large or else approximately
equal to zero. The comparison is shown in Fig. 5
Bus Fault

Comparison of simulated and predicted variation in fault current


550 0 0.02 0.04 0.06 0.08 0.1
Break Point Positions [ p.u. ]
Line end fault
500 Line out fault
Fig. 6. Break points ranges PowerformerTM at Collinsville
Simulated variation in fault current [%]

450

400 Range of break points - PowerformerTM at Tarong


350 Line End

300

250 Line Out

200

150 Line Flow 2

100

50 Line Flow 1

0
0 100 200 300 400 500
Predicted variation in fault current [%] Bus Fault

0 0.01 0.02 0.03 0.04 0.05


Fig. 5. Comparison of predicted and simulated line-out/line-end fault currents Break Point Positions [ p.u. ]

A. Comparison with analytical results Fig. 7. Break points ranges PowerformerTM at Tarong
A logical application of the analytical technique is
identification of the range of generator designs leading to In [10, 11] a proportional relationship between break point
significant change to network fault behaviour. From an separation and fault parameter sensitivity was also highlighted.
analogy with control systems theory it would be expected that The larger range of break points for the line flow currents
the major change in network response would be produced by shown in Fig. 6. and Fig. 7. then suggests that these parameters
generator designs varying between the relevant break points could be more sensitive to generator design than the other fault
determined for each different fault parameter. These ranges of parameters This postulate is supported by the increase in the
these break points for the connection of high voltage generator number of breakers rated by line flow currents rather than line-
at either Collinsville or Tarong are shown in Fig. 6 and Fig. 7. end or line-out fault current in network containing a low
The proximity of the break points to the origin is quite impedance directly connected generator.
obvious especially for a directly connected generator at
Tarong. This implies that significant variation in network fault VII. CONCLUSIONS
behaviour would not be expected unless the fault impedance of The most important finding of the investigation is the
generator of interest was also quite small, an interpretation relatively limited impact produced by the replacement of a
consistent with the results obtained previously. Consequently conventional generator with a directly connected generator on
the relatively minor change in generator fault impedance the critical fault types governing circuit breaker ratings in a
produced by the inclusion of a realistic directly connected realistic power system. This suggests that very few
generator such as PowerformerTM would be unlikely to modifications will be required to breaker capacity to allow the
produce significant changes to the critical fault types of the inclusion of a high voltage generator into an existing system
network breakers. Significant impact would be produced only where the original breakers have been rated according to
if the break points were widely separated, as would be the case C37.010 1999. Even large changes to generator design
in a network that was both relatively un-meshed and contained appear to have an impact on only a limited number of
little additional generating capacity. In this case the inclusion breakers, although the location of the affected breakers will
of a directly connected generator could have a marked impact not necessarily be confined to the direct vicinity of the
6

generator under consideration. Z lm Z mk Z km Z mk



Z G + Z mm
These results also highlight the effectiveness of the (Vk )(Zline + Zlk Z kk ) Z line + Z lk Z kk
analytical technique to predict accurately the potential impact = (4)
of generator design variation on fault parameters such as line-
I line 2
( )
Z line Z kk + Z f

Z km Z mk

Z G + Z mm
out and line-end fault currents. The analytical method also Z kk + Z f

appears to provide a logical explanation for the numerical
results obtained, allowing identification of system
configurations that are highly sensitive to generator design. IX. REFERENCES
Finally, although this investigation suggests that the design [1] IEEE recommended practice for protection and coordination of
of a single directly connected generator would have only a industrial and commercial power systems: IEEE Standard 242-2001,
2001.
limited impact on critical fault types required for short circuit
[2] IEEE recommended practice for industrial and commercial power
current rating calculations, this represents only one aspect of systems analysis: IEEE Standard 399-1997, 1998.
the circuit breaker rating process. Properties such as switching [3] M. Leijon, K. N. Srivastava, B. Franken, and B. Berggren, "Generators
capability or transient recovery voltage have not been Connected Directly to High Voltage Network," presented at 3rd
International R&D Conference of Central Board of Irrigation and Power,
addressed. Future work however will concentrate on the CBIP, Aurangabad, India, 2000.
remaining facets of the circuit breaker short circuit rating [4] IEEE Application guide for AC high-voltage circuit breakers rated on a
procedure including consideration of single line-to-ground symmetrical current basis: IEEE Standard C37.010-1999, 2000.
[5] A. Berizzi, S. Massucco, A. Silvestri, and D. Zaninelli, "Short-circuit
faults and a more detailed treatment of AC and DC decrement. current calculation: a comparison between methods of IEC and ANSI
standards using dynamic simulation as reference," IEEE Transactions
VIII. APPENDIX on Industry Applications, vol. 30, pp. 1099-106, 1994.
[6] IEEE Standard Rating Structure for AC High-Voltage Circuit Breaker.
New York: IEEE Standard C37.04-1999, 1999.
A. Generator influence on line flow fault currents
[7] AC high-voltage circuit breakers rated on a symmetrical current basis-
preferred ratings and related required capabilities: ANSI C37.06-
1997, 1997.
[8] T. C. Nguyen, S. Chan, R. Bailey, and T. Nguyen, "Auto-check circuit
breaker interrupting capabilities," IEEE-Computer-Applications-in-
Power, vol. 15, pp. 24-8, 2002.
[9] IEEE standard for AC high-voltage generator circuit breakers rated on
Fig. 8. Breaker line flow fault currents a symmetrical current basis: IEEE Standard C37.013-1997, 1997.
[10] J. D. F. McDonald and T. K. Saha, "A Sensitivity Method for Assessing
the Impact of Generator/Transformer Impedance upon Power System
1) Line flow 1 Fault Behaviour," IEEE/PES Transmission and Distribution Conference
The current through the line between bus l and the fault bus and Exhibition 2002: Asia Pacific Conference Proceedings, vol. 1,
k, shown as Iline1, can be determined by: 2002.
[11] J. D. F. McDonald and T. K. Saha, "Development of a Technique for
I line1 =
dVl dVk
=
( ) ( )
I f Zlk , new I f Z kk , new
(2) Calculation of the Influence of Generator Design on Power System
Zline Zline Balanced Fault Behaviour," 2002 IEEE PES Summer Meeting
Proceedings, 2002.
where Zlk,new, Zkk,new, represent elements of the impedance
matrix incorporating the impact of generator design. The X. BIOGRAPHIES
impact of generator design can also be represented by John McDonald (M2001) was born in Brisbane,
expressing (2) in terms of both impedance matrix elements Queensland, Australia, on October 21, 1977. He
obtained a BE (Hons Elec)/BA (Chinese) from the
describing a network from which the influence of the generator University of Queensland in 1999 and at present he
has been completely removed along with the fault impedance is completing for his PhD investigation at the
of the generator of interest. University of Queensland entitled Investigations
into the design of PowerformerTM for optimal
Z lm Z mk Z km Z mk generator and system performance under fault

Z G + Z mm
conditions. His fields of interest include power

( Vk )(Zlk Z kk ) Zlk Z kk systems analysis, system fault performance and
= (3)
I line1
(
Z line Z kk + Z f )

Z km Z mk

equipment condition monitoring.

Z G + Z mm
Z kk + Z f Tapan Kumar Saha was born in Bangladesh and
came to Australia in 1989. Dr Saha is a Senior
Lecturer in the School of Information Technology and
where Vk is the pre-fault voltage at bus k. Electrical Engineering, University of Queensland,
This expression is analogous to those relationships defined Australia. Previously he taught at the Bangladesh
in [10, 11], suggesting that the impact of the generator fault University of Engineering and Technology, Dhaka,
Bangladesh for three and a half years and at James
impedance on Iline1, the current through the breaker, will be Cook University, Townsville, Australia for two and a
controlled by the location of break points extracted from (3). half years. He is a senior member of the IEEE and a
2) Line flow 1 Chartered Professional Engineer of the Institute of
Engineers, Australia. His research interests include
A similar derivation can be completed for line flow 2. power systems, power quality, high voltage and insulation Engineering.

You might also like