You are on page 1of 18

Wuhan Huaying Electric Power Tech & Science Co.,ltd whhy818@163.

com

HYRZ-902
Frequency Response Analyzer

WUHAN HUAYING ELECTRIC POWER TECH & SCIENCE CO.LTD


Add: 4F, Building 7, Optical Valley International Headquarters Industrial
Park, No.62, Optical Valley Road, Wuhan, China
Tel: +86-027-82845035
+86-027-82850969
Fax: +86-027-82210223
Web: www.hy-dl.cn/en
www.hy-dl.en.alibaba.com
Sales manager:Wang Shuyue
Cellphone: 86-15827280740
Skype:wangshuyue1991
Email:whhy818@163.com
whhytester@163.com
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

Directory
ONE, TESTER INTRODUCTION................................................................................................................................................... 2

TWO, TECHNIQUE CHARACTERISTICS.................................................................................................................................... 2

THREE, TECHNIQUE STANDARD............................................................................................................................................... 2

FOUR, HOW TO USE THE TESTER............................................................................................................................................. 3

FIVE,..................................................................................................................................................................................................... 7

HOW TO USE THE PC SOFTWARE..............................................................................................................................................10

1. THE INTRODUCTION OF THE PC SOFTWARE..........................................................................................................................11


2. USING PC TO CONTROL THE TEST........................................................................................................................................ 11
3. UPLOAD DATA........................................................................................................................................................................12
4. DATA ANALYSIS..................................................................................................................................................................... 13
5. CREATE WORD DOCUMENT AND PRINT CURVE..................................................................................................................... 13

SIX, NOTICE.................................................................................................................................................................................. 14

SEVEN, PART LIST....................................................................................................................................................................... 14

APPENDIX ONE THE USUAL WINDING TYPES OF THE TRANSFORMER........................................................................ 15

APPENDIX TWO THE STANDARD OF ANALYSIS................................................................................................................. 16

APPENDIX THREE INSTALL THE DRIVER............................................................................................................................. 17

1
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

One, Tester introduction

1The structure and reference of the transformer is fixed after been made, Therefor, the

frequency response of each winding will be almost the same normally.

2Some case such as cut off between circles or phases in experience, cut off or winding moved

for the pull of power in running, winding moved for hit in transportation, could change the

reference of the transformer ,of which the frequency response will be changed, we could

detect the deformation according to the frequency response curve.

3Our company has designed the winding deformation tester base on the idea and the

advanced technique. It could draw the frequency response curve accurately. Then we

compare the curves horizontally or vertically to detect the deformation of the transformer.

4The tester is conformed to the standard of DL/T911 2004.

Two, Technique characteristics

1 Using the advanced technical of DDS;

2 Using the high speed and advanced microprocessor to design;

3 Using double channels of AD chip of 16 bits;

4 With seven inch LCD touch screen of which the brightness can be adjusted;

5 With thermal printer of which the print thick can be adjusted;

6 It could store one hundred and twenty groups of data, which could be read to current

screen or upload to the PC;

2
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

7 With PC software using which we could upload data ,test, analyze data, print data, or create

word document;

8 Using USB2.0 to connect to the device

9 Tester dimension31cm X 15cm X 15cm

10 Weight4.0KG

Three, Technique standard

1Two different sweep modes Linear sweepSection sweep

Linear sweep 0.5KHZ-1MHZ interval 0.5KHZ 2000 dots

Section sweep50HZ-100HZ interval 2HZ 25 dots

100HZ-1KHZ interval 20HZ 45 dots

1KHZ -10KHZ interval 50HZ 180 dots

10KHZ-100KHZ interval 0.2KHZ 450 dots

100KHZ 500KHZ interval 0.5KHZ 800 dots

500KHZ 1000KHZ interval 1KHZ 500 dots

2Test range(-100dB - +20dB

3Test accuracy0.1dB

4Frequency accuracy<0.01%

5Signal input impedance>1M

6Signal output impedance50

7Repeat test99.5%

3
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

Four, How to use the tester

1. Fig.1 shows the top interface of the tester, the printer is in the left and the seven inch screen is

in the right, the print thick and brightness can be adjusted in Setting.

Fig. 1 tester interface

2. Fig.2 shows the left interface of the tester, the connect method refers to the Appendix

One ,USB2.0 is used to connect with PCThe tester driver need be installed if it is the first to use

USB2.0, The way of installing driver shows as appendix three. Fig.3 shows the right interface in

which we could see the power outlet and power switch.

Fig. 2 Left interface Fig. 3 Right interface

3. Power on the tester , the main interface

showing as Fig.4 will be showed firstly, The

4
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

conresponding interface will be showed when clicking one of the button.

Test----------------------------Fig.8

Saveed Data-----------------Fig.13

PC communication---------Fig.16

Format Memory------------Fig.7

Setting------------------------Fig.5

The Calibraton button which is used to Fig.4 Main interface

calibrate the tester for factory is invalid to user, Because the calibration is finished before we sell

it to you

4. The tester setting interface: Fig.5.

(1) The ID Number is fixed for read

(2) The keyboard showing as Fig.6 will popup if

click

the date frame, click Enter button to

return to Fig.5 when finished to set the date.

(3) Click the language frame to change the

tester language.

(4) Click the left of the brightness frame to decrease

the brightness and right to increase.

(5) Click the left of the print thick frame to Fig.5 Setting

decrease

the print thick and right to increase.

(6) The OK button must to be clicked to store the

5
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

setting data.

5. Keyboard interface : Fig.6.

(1)
1 ------delete button

(2)
2 ------space button

(3)
3 ------Enter button

(4)
4 ------char button

6. Format the memory: Fig.7.

(1) One hundred and twenty groups of data could be

stored mostly; Fig.6 Keyboard

(2) UsedThe total groups of the data

(3) UnusedThe empty data group

(4) Input characters ok to the frame to format

the memory

(5) After format, the data will be invalid, so

upload

the data to the PC before formatting.

7. Test setting: Fig.8

(1) There are four winding modes normally, see the

appendix one;

(2) HV/LV can mark the current test winding is

6
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

high voltage winding or low voltage Fig.7 Format memory

winding;

(3) Sweep modeLinear and Section, the interval of

the linear mode is 0.5KHZ, and the Section

mode

refer to the technique stand.

(4) Transformer NO.To differ the different test

transformers.

(5) Referenceshow the selected references

8. Test interface: Fig.9

There are only three buttons in the interface: start, stop, return.

Click start to begin to test after connecting the wires correctly, wait until finishing to test. Click

Fig. 8 Test setting


stop in the testing process to stop the current

test, if there is test data the test result interface showing as Fig.10 will be showed, if there is no

data, the test setting interface will be showed. There are three curves to the three phases to be

test.

9. Test result: Fig10

(1) The curves can be differed by the white

square box

(2) There are two way to show curves The Linear show indicates that the frequency is

distributed averagely in the X-axis. The


Fig.9 Test interface

Log show indicates that the logarithm of

7
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

frequency is distributed in averagely in the X-axis.

(3) Click Save to save the test data if the tester has unused memory, so check the memory

before test

is needed. If the memory is full, delete a group of data or format the memory.

(4) Click analyze to analyze the current data, and then view the result to detect the

deformation degree.

(5) Click print to print the curve and analyze result, if

printing before analyzing, the print result will


Fig.10 Test result
not include the analysis result.

(6) Click Data to view the dB value of each

frequency value.

(7) Click return to return to the main interface

10. Data Analysis interface: Fig.11

R(AB,BC): the ratio between A--input B--test and Binput Ctest. The deformation degree

has four levels according to the ratio: normal, slight, obvious and serious, the detect method

refers to the appendix two.

Fig.11 Data Analysis

11. View the dB value of each frequencyFig.12

(1) Total forty pages of data, the page is showed

in the page frame.

(2) Click<<to back to the first page

(3) Click>>to show the last page

8
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

(4) Click<to reduce the page number

(5) Click>to increase the page number

(6) Click page frame and input the page number

(7) Click<= to show the curve

12. Saved Data Interface: Fig13 Fig.12 the dB value of each FQCY

Click open and the select a group of data to open.

13. Data directoryFig.14

(1) All the saved data will be showed in the directory , Click the single button and the click OK

to open.

(2) Click PgUp and PgDn to decrease or increase the page number.

Fig.13 Saved Data Interface Fig.14 Data directory


(3) Click DEL and then pop up a dialog to ask you whether delete the selected data, if yes

button is clicked the data will be deleted, if no button is clicked the data will not be deleted.

9
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

14. Fig.15 Whether Delete Fig.16 PC Communication

PC Communication Interface: Fig.16

You could not upload data or test through the PC until enter this interface, if return is clicked,

the communication with PC will be over.

10
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

Five,

How to use the PC software

1. The introduction of the PC software

(1) The software runs only in the Microsoft .NET framework 4.0 of Windows XP or Windows 7 , it
will be confirmed that you are using the windows system above, after that, if you can not
use the software yet, The Microsoft .NET framework 4.0 need to be installed, the install file
is : dotNetFx40_Full_x86_x64.exe.

(2) The PC software is shown as Fig.17.

(3) In case of compare two groups of data vertically, the PC software has two buttons to open

data. They are

open and load.

(4) Click open or load ,and then select a CVS file to open, the frequency range of the two

groups of data must be the same, if not, a inquire dialog will pop up, if yes is clicked ,

the select data will be open and the other group of data will be invalid..

(5) NoticeThe name of the file whether upload or new is named automatically, for example,

the name of a file is: 0_Y_HV_2013-10-10 15@30_123456.CVS

0---0.5KHZ-1000KHZY modeHV---high voltage windingtest date ---2013-10-10

15:30the : is replaced by@ thanks to the file name can not include:, transformer

NO.---123456

(6) Click Reference to show the reference of the data, user can change the transformer

NO. , test member, or the test company, and then click save .

(7) Check the check box, the corresponding curve will be shown, else the curve will not be

shown.

11
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

(8) The number next to the check box is the dB value of current frequency, user could

change the color of the curve though double clicking the number.

(9) Drag the slipper or click the <- and ->button to change the frequency line, which

decides the current frequency and the dB value.

(10) Check the cursor line box to show the cursor line, else not show.

(11) Click the Linear or Log button to change the way of showing curve.

(12) Click the Zoom In or Zoom Out button to zoom in or zoom out the curve

horizontally or vertically.

Fig. 17 PC software interface

2. Using PC to control the test

(1) Power on the tester and enter into the PC Communication state, and then open the PC

software, if the PC software find the device ,of which the ID number will be shown in the

title.

(2) If failed to connect to the PC , connect the USB wire, reboot the device, and then let it enter

into the pc communication state, at last click connect of the PC software.

12
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

(3) New a empty file, fill the reference show as Fig.18, click save ,the file name is

automatically named.

(4) Click start after connect the test wires correctly, if stop button is clicked in testing, the

current test will be over, A new file can save three curves in the most, which is

corresponding to three phases. The test data is saved to the file automatically.

Fig.18 New File

3. Upload data

Let the tester enter into the PC communication firstly, and then click Upload button in

the PC software, at the bottom of which the progress of uploading data is shown, the

uploaded file is named automatically, notice: user must not change the name of the file,

else the file cannot be open.

4. Data Analysis

(1) Data analysis interface: Fig.19


(2) Set the analysis frequency rangethe
frequency range must set to be integers and the
first data is less than the second one.
(3) Click Analyze to show the analysis
result after setting the frequency range;
(4) ROA,OB: the ratio between Oinput A--test
And Oinput Btest.
(5) If two groups of data are open, it will calculate the

13
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

ratio between the two groups of data.

Fig. 19 Data analysis

5. Create Word document and print curve


The context of creating word document and printing is the same, the context include the

current showed curves and axis, and analysis result if data analysis is made. The save

directory could be chose by user.

Six, NOTICE
1. User must not use the tester immediately if the transformer is tested by Winding DC

resistance tester;

2. Check that whether the ground line is connected before test, the patch-connector must be

cut off.

3. You must not use other test wires instead of that of the tester.

4. The tester should be placed at the place that is dry and there is wind..

Seven, Part list


NO. Objects Amount
1 Tester 1
2 Power wire 1
3 Test wire 1
4 Ground wire 1
5 BNC connecter 1
6 Accessory bag 1
7 USB wireAA 1
8 Product CD 1
9 Fuse 0.5A 3

14
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

10 Print Paper 2
11 Product instruction 1
12 Survey report 1
13 Product certification 1

Appendix one The usual winding types of the transformer

The usual four winding types of the transformer are shown as Fig.20, Each transformer may have a different
winding type, so user could choose one of the types according to the label of the transformer.
1. Connect the test wires according to Fig.20, keep the color the same between wires and terminals;
2. The other terminals of the wires are connected to test clamps,the red one is connected to the red
clamp,and then to the test terminal of the transformer, the yellow and green wires are connected
to the yellow clamp though BNC,and then to the input terminal;
3. The black clamp is connected to the ground terminal of the transformer;
4. Start the test after the wires are connected correctly;

15
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com
Fig.20

Fig.21 Four winding modes

Appendix two The standard of analysis

The tester and the PC software analyze the deformation degree according to DLT/911 2004 the

standard shows as follows. Tester cannot select the analysis frequency range, but the PC software can

select to user.

Deformation degree The ratio R

Serious RLF<0.6

Obvious 0.6RLF<1.0 or RMF <0.6

Slight 1.0RLF<2.0 or 0.6RMF<1.0

16
Wuhan Huaying Electric Power Tech & Science Co.,Ltd whhy818@163.com

Normal RLF2.0 and RMF1.0 and RHF0.6

Note RLF is the ratio between 1KHZ and 100KHZ

RMF is the ratio between 100KHZ and 60KHZ

RHF is the ratio between 600KHZ and 1000KHZ

Appendix three Install the driver

1. Connect the USB wire well and power on the tester, Click

PC communication;

2. Choose yes, only this once and then click next step;

3. Choose from list or user local and then click next step;

4. Click next step again , click continue and click browse,

Choose the USB driver directory of the CD, click OK;

5. Click next step, then wait until finished.