15728:2008
ICS 91.100.30
12&23<,1*:,7+287%6,3(50,66,21(;&(37$63(50,77('%<&23<5,*+7/$:
PD CEN/TR 15728:2008
National foreword
BSI 2008
ICS 91.100.30
English Version
Conception et utilisation d'inserts pour le levage et la Bemessung und Verwendung von Transportankern fr
manutention du bton prfabriqu - lments Betonfertigteile
This Technical Report was approved by CEN on 2 March 2008. It has been drawn up by the Technical Committee CEN/TC 229.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
2008 CEN All rights of exploitation in any form and by any means reserved Ref. No. CEN/TR 15728:2008: E
worldwide for CEN national Members.
CEN/TR 15728:2008
Contents Page
Foreword..............................................................................................................................................................3
1 Scope ......................................................................................................................................................4
1.1 Scope / General......................................................................................................................................4
1.2 Types of inserts for lifting and handling .............................................................................................4
1.3 Minimum dimensions ............................................................................................................................4
2 Normative references ............................................................................................................................5
3 Definitions and symbols .......................................................................................................................5
3.1 Definitions ..............................................................................................................................................5
3.2 Symbols ..................................................................................................................................................7
4 General design principles.....................................................................................................................8
4.1 General principles..................................................................................................................................8
4.2 Partial factors .........................................................................................................................................8
5 Actions on inserts..................................................................................................................................9
5.1 Actions....................................................................................................................................................9
5.2 Effect of lifting procedures on load directions...................................................................................9
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
2
CEN/TR 15728:2008
Foreword
This document (CEN/TR 15728:2008) has been prepared by Technical Committee CEN/TC 229 Precast concrete
products, the secretariat of which is held by AFNOR.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights.
CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
To ensure the performance of the precast concrete products, lifting and handling should be taken into account in
the design of the product.
Inserts are used for lifting and handling of precast elements. They should meet an appropriate degree of reliability.
They should sustain all actions and influences likely to occur during execution and use.
This Technical Report deals with all lifting inserts cast into precast concrete elements i.e. lifting parts developed
and produced at the precasting plant as well as lifting inserts as part of a system supplied by a manufacturer of
lifting systems. The intent of this document is to give information to precast product designers.
The failure of inserts for lifting and handling could cause risk to human life and/or lead to considerable economic
consequences. Therefore inserts for lifting and handling should be selected and installed properly by skilled
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
personnel.
This Technical Report based on current practices gives recommendations for correct choice and design of lifting
inserts according to the lifting capacity of their part embedded in the concrete. It is based on EN 1992-1-1
(Eurocode 2) and on published suppliers data.
In the Technical Report numerical values for partial safety factors are recommended as basic values that provide
an acceptable level of reliability. They have been selected assuming that an appropriate level of workmanship and
of quality management (Factory Production Control) applies. They may be applied in the absence of national
regulations.
3
CEN/TR 15728:2008
1 Scope
This Technical Report provides recommendations for the choice and use of cast-in steel lifting inserts, hereafter
called 'inserts' for the handling of precast concrete elements. They are intended for use only during transient
situations for lifting and handling, and not for the service life of the structure. The choice of insert is made according
to the lifting capacity of their part embedded in the concrete, or may be limited by the capacity of the insert itself
and the corresponding key declared by the insert manufacturer. The report covers commonly used applications
(walls/beams/columns and solid slabs and pipes) and the range of these applications is further limited to prevent
other types of failure than concrete breakout failure (cone failure), failure of supplementary reinforcement or failure
in the steel insert. A basic supposition is that the concrete is demonstrably uncracked during all lifting situations.
The limitation in scope is used to obtain simple design models. Further information may be found in [1].
The recommended safety levels are intended for short-term-handling and transient situations.
This Technical Report applies only to precast concrete elements made of normal weight concrete and
manufactured in a factory environment and under a factory production control (FPC) system (in accordance with
EN 13369:2004, clause 6.3) covering the insert embedment.
The design of the insert itself (for inserts manufactured by insert suppliers).
The lifting key that hooks on to the embedded lifting insert as a component between the insert and the lifting
machinery (crane, excavator), nor its compliance with the embedded insert. These components, when
brought to the market separately, are covered by the Machinery Directive (98/37/EC).
This Technical Report applies to the embedment of lifting inserts made by the precaster for his own use as well as
lifting inserts forming part of lifting systems brought to the market by a lifting system supplier, see tables 8.3 and
8.6. Devices made by the precaster may consist of smooth bars, prestressing strands and steel wire ropes. The
system devices may be e.g. internal threaded inserts, flat steel inserts and headed inserts.
Lifting loops of ribbed bars are not covered, nor wire ropes of less than 6 mm.
This Technical Report applies in general to inserts with a minimum nominal diameter of 6 mm or the corresponding
cross section. In general, the minimum anchorage depth should be la = 40 mm.
4
CEN/TR 15728:2008
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated references,
only the edition cited applies. For undated references, the latest edition of the referenced document (including any
amendments) applies.
EN 1992-1-1:2004, Eurocode 2: Design of concrete structures Part 1-1 : General rules and rules for buildings.
EN 10025-2:2004, Hot rolled products of structural steels Part 2: Technical delivery conditions for non-alloy
structural steels.
)
EN 10138-3, Prestressing steels Part 3 : Strand 1 .
EN 12385-4:2002, Steel wire ropes Safety Part 4 : Stranded ropes for general lifting applications.
EN 13414-1:2003, Steel wire rope slings Safety Part 1 : Slings for general lifting service.
CEN/TR 14862:2004, Precast concrete products Full-scale testing requirements in standards on precast
concrete products.
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
3.1 Definitions
3.1.1
concrete breakout failure
concrete cone separated from the base material by loading the insert
3.1.2
concrete breakout resistance
the resistance corresponding to a concrete cone surrounding the insert or group of inserts separating from the
member
3.1.3
edge distance
the distance from the edge of the concrete surface to the centre of the nearest insert
5
CEN/TR 15728:2008
3.1.4
anchorage length
for cast-in headed insert bolts and splayed inserts, the anchorage length, la , is illustrated in Figure 1
3.1.5
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
embedment depth
distance from the concrete surface to the farthest point of insert, measured perpendicular to the concrete surface
3.1.6
factory Production Control (FPC)
a quality system satisfying the requirements in EN 13369, clause 6.3
3.1.7
headed insert
a steel insert with a head for anchorage installed before placing concrete
3.1.8
insert
a steel unit cast into concrete and used for lifting of precast elements
3.1.9
insert loading
axial, shear or combined - Loads applied to the insert
3.1.10
insert resistance
load capacity (characteristic value) of the part of the insert embedded in the concrete (different from maximum
working load of the insert see 3.1.13). In this report, the wording characteristic resistance is sometimes used
3.1.11
lifting key
lifting tool to couple to the embedded insert
3.1.12
lifting system
system of lifting key and appropriate insert
3.1.13
maximum working load
maximum load guaranteed by the supplier before steel failure, reduced by application of the relevant safety
coefficient and marked on a lifting key or system (from Directive 98/37/EC, 4.1.1)
6
CEN/TR 15728:2008
3.1.14
precaster
producer of precast concrete elements in a factory environment
3.1.15
pullout failure
a failure mode in which the insert pulls out of the concrete without a steel failure and without a concrete breakout
failure
3.1.16
side-face blow-out resistance
the resistance of inserts with deeper embedment but thinner side cover corresponding to concrete spalling on the
side face around the embedded head while no major breakout occurs at the top concrete surface
3.1.17
insert steel failure
failure mode characterised by fracture of one of the steel insert parts
3.1.18
minimum reinforcement
reinforcement required by EN 1992-1-1 or in national annex (Nationally Determined Parameter)
3.1.19
supplementary reinforcement
reinforcement designed to resist the full load in case of a concrete failure
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
3.1.20
complementary reinforcement
reinforcement provided to avoid brittle failure
3.1.21
supplier
manufacturer of lifting inserts brought to the market or its authorized distributor
3.2 Symbols
qadh adhesion
7
CEN/TR 15728:2008
3.2.3 Inserts
Notation and symbols frequently used in this technical report are given below. Further particular notation and
symbols are given in the text.
The inserts load capacity for lifting and handling should be calculated and/or tested according to the principles and
design models given in this document. Embedment conditions for lifting and handling, which do not conform to
these principles or design models, should be tested according to the recommendations given in Annex A and
evaluated in accordance with EN 1990.
Actions should be obtained from the relevant parts of EN 1991-1 where applicable.
Q = 1,5 (partial factor for live load, i.e. adhesion, friction and dynamic actions).
In the absence of National provisions the partial factors given in Tables 1 and 2 are recommended.
Recommended values of the partial factors s for characteristic resistance of steel based on characteristic ultimate
values (Ruk, fuk) are given in Table 1. For solid steel loops, steel wire ropes and prestressing strands the partial
factor s is based on the characteristic resistance of the loop including effects of the lifting hook.
8
CEN/TR 15728:2008
Recommended values of the partial factor c for failures in the load transfer between the insert and the concrete
are given in Table 2. These values assume that an FPC system is used to control that concrete is uncracked in the
vicinity of the insert.
5 Actions on inserts
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
5.1 Actions
The forces acting on an insert should be calculated for all relevant loading situations taking into account the product
properties, the position of the inserts, condition of the form, lifting equipment, number and length of the ropes,
chains or straps and the static system. In some cases it might be necessary to take into account the deformations
of the precast element during lifting and handling.
Inserts for lifting and handling may be subjected to loads acting in different directions during operation. As
examples information on slabs and wall elements are given.
The lifting equipment should allow statically determinate load distribution to the inserts (see Figure 2). To ensure
that all inserts carry their required part of the load, sliding or rolling couplings between the lifting wires or chains
should be used when there are more than two lifting points. In a statically indeterminate system the load distribution
on the inserts depends in most cases on the unknown stiffness of the ropes and the position of the insert
(see Figure 3). Therefore only the statically determinate part of a system should be used in calculating the actions
on the inserts.
9
CEN/TR 15728:2008
a) b)
10
CEN/TR 15728:2008
Depending on the equipment used during lifting the inserts may be subjected to combined parallel and transverse
shear load (Figure 5a), combined tension and parallel shear loads (Figure 5b), transverse shear loads (Figure 5c)
or axial tensile loads (Figure 5d).
a) b) c) d)
Key
a) Combined parallel and transverse shear load
b) Combined tension and parallel shear load
c) Transverse shear load
d) Axial load
Shear loads acting on inserts may be assumed to act without a lever arm, if the design of the inserts and its key
avoids significant concrete crushing in front of the insert during loading. If this condition is not satisfied the lever
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
arm should be taken as the actual distance between the shear force and the concrete surface plus half the nominal
diameter of the insert.
Adhesion and form friction will occur when the precast element is removed from the formwork. The values should
be taken from National provisions. In the absence of National provisions the values for the combined effect of
adhesion and form friction qadh given in Table 3 may be considered. General values for form friction are difficult to
assess and friction should be avoided as far as possible.
For some types of uneven form surfaces (structured matrixes, reliefs, structured timber etc.) the forces may be
much larger than given in the table, and should be considered separately. The forces may be zero if the concrete
does not come in contact with the form at all, for example if the concrete is poured on a layer of bricks that has
been laid out on the form bottom. Large vertical form surfaces may create extensive friction forces due to
undulations in the form. Prestressed components will usually have a camber caused by the prestressing force, and
will therefore have lower friction against the vertical sides of the form.
Ed = G G + Q qadh A f
with
11
CEN/TR 15728:2008
G and Q are partial safety factors for permanent and variable actions respectively.
During lifting and handling the precast elements and the lifting devices are subjected to dynamic actions. The
magnitude of the dynamic actions depends on the type of lifting machinery. Dynamic effects should be taken into
account by the dynamic coefficient dyn given in National regulations. In the absence of National Regulations the
values of Table 4 may be considered. Other dynamic influences than covered by Table 4 should be based on
special provisions or engineering judgement.
x) In precasting factories and if special provisions are made at the building site
lower values may be appropriate.
The actions, Ed, for lifting situations should be determined from Equation (5.3):
Ed = G G + ( dyn 1) Q G
6 Choice of inserts
Having determined the actions on the insert for all relevant load combinations the task remains to choose an
appropriate insert and relevant reinforcement.
The insert load capacity depends on the field of application. The designer has three options in choosing the
appropriate lifting arrangement :
1) The recommendations given by the insert suppliers may be used directly. This option is further described
in clause 7;
3) Tests may be carried out specific to the intended application as outlined in clause 9.
12
CEN/TR 15728:2008
1) The method is certified by an accredited third party in accordance with a relevant ETAG;
2) The method is certified by an accredited third party in accordance with a CEN product standard;
3) The method is certified by an accredited third party based on tests according to Annex A;
The suppliers declaration of the product should state the method chosen. If the supplier cannot satisfy either of
these conditions, or if the intended application falls outside the range of validity for the design methods
recommended by the supplier, the designer should choose one of the options in clause 8 or clause 9.
NOTE Suppliers catalogues may disclaim the responsibility for the use of the data. Consequently, such catalogues should
not be used as a recommendation.
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
13
CEN/TR 15728:2008
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Key
1)
The application of the insert is fully within the limits stated in the catalogue of an insert supplier or manufacturer. These
limits include weight, concrete strength, edge distance, dimensions of the concrete member, local reinforcement and mode of
lifting.
2)
To verify the design model of chapter 8 for a certain type of insert it might be necessary to perform tests according to Annex
A. The reinforcement provided to transfer loads from the insert into the element should be designed according to National
provisions. Reinforcement for other purposes such as flexural or shear capacity of the precast element in use would not
normally be considered in this.
3)
Specific testing is intended to justify the capacity in a particular situation. As an example, this might include inserts for tunnel
segments or bridge beams. It does not provide information for a wide range of applications.
For most common applications, present practice and available general information concerning the load capacity of
inserts can be combined into a design model. This model is described in further details in sections 8.3 8.4. The
14
CEN/TR 15728:2008
model is not universally applicable. Limitations on the range of validity are used to exclude situations where other
types of failure than concrete breakout failure (cone failure), failure of supplementary reinforcement or steel failure
in the insert can occur. Within the indicated limited range of validity the model yields results that are very close to
present practice. The limitations on the range of applicability are the following:
1) Field of application
a) walls and other linear elements (such as beams and columns), where the insert is typically long
compared to the edge distance (the smallest distance from the insert to a concrete surface parallel to
the insert) and where the concrete in the vicinity of the insert is uncracked.
b) slabs and pipes, where the edge distance is large while the possible length of the insert is limited by
the thickness of the element and where the concrete in the vicinity of the insert is uncracked.
This section covers the use of some common types of inserts in these two situations, cp tables 7
and 10.
Minimum reinforcement is typically provided according to EN 1992-1-1. Although provided for other
reasons the reinforcement may also act as a safeguard against failure in case cracking should
unexpectedly take place in the concrete around the insert. If minimum reinforcement is not provided
complementary reinforcement should be provided. If the minimum reinforcement is left out the risk of
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
The presence of complementary reinforcement also makes it possible to postpone the development of a
breakout failure so that the capacity of the insert becomes somewhat larger than in unreinforced concrete,
see e.g. ref. [2].
Supplementary reinforcement is designed specifically to transfer the full load on the insert to the concrete
element as a whole. The suggested models for design of the supplementary reinforcement are in
accordance with the rules given in EN 1992-1-1.
Where no other indication of minimum concrete compressive strength is given, it is assumed that the
concrete strength (at the time of lifting) is at least 15 MPa measured on cubes, side length 150 mm
(or 12 MPa measured on cylinders).
It is assumed that the precaster applies a Factory Production Control system according to the
requirements in EN 13369, clause 6. It is furthermore assumed that the inspection scheme for finished
product inspection includes a check that no harmful cracking has occurred in the neighbourhood of the
inserts at the time of delivery.
The validity of the calculation model outside the range covered by the graphs is not sufficiently known and
therefore the graphs should not be extrapolated.
15
CEN/TR 15728:2008
6) Safety factors.
To facilitate the use of nationally determined partial factors the capacity values given in this chapter could
be used as characteristic values.
16
CEN/TR 15728:2008
All these standard lifting systems consist of an insert embedded in the concrete element and a matching unit (key)
that connects to the insert (Figure 7). The crane hook or hook of a lifting sling attaches to the key. The combination
of components from different systems is prohibited.
Threaded lifting devices and corresponding keys should be marked with a colour corresponding to their diameter.
The colours given in Table 5 are recommended.
Table 5 Recommended colour identification codes of lifting systems for threaded lifting systems
Diameter Colour
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Rd 12 orange
Rd 16 red
Rd 20 light-green
Rd 24 dark-grey
Rd 30 dark-green
Rd 36 light-blue
Rd 42 silver-grey
Rd 52 yellow
For other than threaded systems, the following method of marking is possible.
The marking consists of a System ID and an Insert ID (Table 6). It should be fixed directly to the cast-in part and
the lifting key.
System ID Insert ID
Producer System Specification
Lifting key P S
Insert P S X
The System-ID consists of the identification of the producer P (minimum two letters or logo) and the producers
name for the system S.
In many cases different types of cast-in-inserts belong to the same system. Therefore the insert has to be marked
with an Insert-ID containing additional information such as the specification by the supplier X and the length of the
anchor Y. It should be visible after pouring the concrete. It is recommended to mark the insert directly with its length
or to use a length identification code (capital letter or colour).
17
CEN/TR 15728:2008
In addition to the commercially available inserts the precasters may produce their own lifting loops from smooth
bars, prestressing strands or steel wire ropes. Necessary information on the handling of the element, e.g. lifting
hook dimensions, shall be given in erection specifications.
Lifting loops should only be used if the lifting angle is approximately the same in all lifting and handling situations.
Furthermore, the lifting angle should be kept within the limits indicated in Figure 14.
Figure 13 Lifting loops made of smooth bar, strand or steel wire rope (Type g) inserts)
Examples of the inserts are shown in Figure 13 and they should conform to the following specifications:
Smooth bars
The material for smooth bar lifting loops should be at least equivalent to EN 10025-2, S235J2+N. During
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
operation the minimum bending diameter of the smooth bar should not be less than 5 bar diameters. The size
of the lifting hook may require a larger bending diameter.
Strands
The shape of the strands may be adapted to the various types of elements. Prestressing strands that have
been deformed before shaping should not be used. Bending of the strands during stocking or turning of
elements should be avoided.
The bending diameter of the strand loop (illustrated by the curvature of the sleeve in Figure 13) should be
equal to or less than twice the diameter of the lifting hook (the diameter is 2s in the figure in Table 8). The
bending diameter of the strand loop must be larger than the diameter of the lifting hook. The strand diameter
should not exceed 13 mm and the bending radius should be at least 50 mm.
Bundling of maximum four strands may be used only when provided with a steel sleeve bent together with the
strands, see Figure 13.
To take into account effects of lifting hook diameter and different load distribution to the strands within a
bundle, capacity reduction factors are given in Tables 8 and 9.
Only steel wire ropes, which comply with EN 12385-4 and 13414-1 should be used.
2 2
Steel and fibre cores are allowed. The rope grade should be 1770 N/mm or 1960 N/mm . However, in
2
calculations only a value of 1770 N/mm should be considered.
To ensure sufficient flexibility of a rope the steel wire ropes should consist at least of the following number of
wires:
The bending diameter of the steel wire rope should not be less than 2 rope diameters.
18
CEN/TR 15728:2008
To ensure sufficient bond steel wire ropes must be cleaned. The ends of the lifting loop made of a steel wire
rope should be ferrule-secured or split. Split ends should not be taken into account in the design, but a
ferrule-secured end will provide some extra anchorage.
The loading angle, , (angle between the direction of the force and the axis of the insert) should not exceed
30, (see Figure 14). The effect from on the distribution of the force to the legs of the loop should be
considered.
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
a)
b)
19
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
CEN/TR 15728:2008
Table 7 Design summary for inserts under inclined tensile loading in walls and linear elements
Anchor type
a) b) c)
g)
Basic steel capacity Choose an insert with sufficient steel Choose an insert and associated rebar both Choose an insert with sufficient steel Choose an insert with sufficient steel
resistance based on supplier declaration with sufficient steel resistance based on resistance based on supplier declaration resistance based on supplier
supplier declaration, see Figure 21 declaration
Wall thickness Prevent blow-out failure by using Figure 16 Ensure that wall thickness is sufficient to obtain normal anchorage conditions: wall thickness larger than 7 times bar diameter
(straight bars) or 11 times bar diameter (other than straight bars). If smaller thickness: the embedment length shall be increased.
Amount of complementary
reinforcement Prevent brittle failure due to concrete cracking, see Figure 17
Anchorage length for axial load Determine required anchorage length Determine required anchorage length for Determine required anchorage length for Determine required anchorage length
corresponding to concrete cone capacity bent rebar, see Figure 22. hooked rebar, Figure 22. Check that for strand or hooked bar, Figure 22.
from Figure 18. necessary anchorage length determined
from Figure 17 is smaller
Supplementary hairpin If concrete cone capacity is too small or if None for tension None for tension None for tension
reinforcement (replaces shear load component: determine required
complementary reinforcement) reinforcement to carry the whole anchor
load, see Figure 19, 20 and 22
Supplementary diagonal pull Choose reinforcement arrangement and Choose reinforcement arrangement and Choose reinforcement arrangement and Not used. Insert to be tilted according
reinforcement, see Figure 23 amount amount amount to load direction
Capacity reduction due to shear 20% for loading angle 300 <<600 20% for loading angle 300 <<600 30% for loading angle 300 <<450 Loading angle < 300
in wall plane provided suitable key 15% per 100 loading angle
20
CEN/TR 15728:2008
The choice of an appropriate insert for a wall application would typically involve:
Selection of an insert, suitable for the load direction and with sufficient resistance of the insert itself;
Compensation for the possible reduction in capacity due to shear load component.
These items are summarised in Table 7 and further dealt with in the following sections.
All commercially available inserts should be marketed together with a declaration stating the expected
characteristic resistance of the insert corresponding to a failure in the steel. The value should cover the transfer of
load from the key or lifting hook to the insert and any type of possible failure within the insert itself (e.g. welding).
The value may be given as a combination of the maximum working load and a safety factor.
For type g) inserts (usually produced by the precaster) the precaster should evaluate the available characteristic
resistance with due respect to the key or lifting hook to be used. An estimate can be made by ordinary vectorial
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
For lifting loops made of strands the influence of the lifting hook and the bundling of strands with a sleeve should
be taken into account by the factors k1 and k2:
N Rk , s = k1 k 2 As f uk
The reduction factors k1 and k2 to consider the influence of the diameter of the lifting hook and bundled strands are
given in Table 8 and 9.
In the case when a steel sleeve is used for a single strand loop, factor k1 may be increased by 25%, however
k1 1,0.
Table 8 Influence of the lifting hook, capacity reduction factors for lifting loops made of strands
Diameter 2s [mm] k1
25 or 60 0,65
50 0,8
75 0,9
Number of strands 2 3 4
k2 0,90 0,85 0,75
21
CEN/TR 15728:2008
The thickness of the wall shall be sufficient to avoid failure modes that cannot be counteracted effectively by
reinforcement.
Type a) inserts
For type a) inserts a side-face blow-out failure may occur at the built-in end of the insert, see Figure 15.
The risk of a blow-out failure depends primarily on the anchor force, the concrete strength and the edge distance.
The strength may be found from the following expression, [1]:
N Rk = 11,4 c (d h2 d 2 ) f ck [N]
4
For inserts with a head diameter, dh [mm], larger than 2,4 times the shaft diameter, d [mm], (dh 2,4d) this may on
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
k
N Rk = k 3 c hef4 f ck
[N]
2
where c [mm] is the edge distance, fck [N/mm ] is the concrete strength and
The curves given in Figure 16 are based on this latter expression assuming that the insert is placed in the middle of
the wall. If not, the wall thickness should be assumed to be twice the smallest edge distance. The diagram also
assumes that partial safety factors for steel and concrete are the same. If the partial safety factor to be used is
smaller for steel than for concrete (blow-out), the next higher insert dimension may be required.
The other insert types transfer their load to the concrete primarily by bond stresses. The anchorage length
necessary to develop the full resistance of the insert depends on the concrete cover when this cover is small.
The wall thickness needed to make the anchorage length independent of the thickness is taken from EN 1992-1-1,
clause 8.4.4. For ordinary rebars the wall thickness should be at least 7 times the bar diameter for straight bars
and 11 times the bar diameter for other than straight bars. See also clause 8.3.4.
22
CEN/TR 15728:2008
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Key
Y Characteristic axial resistance, kN
X Wall thickness, mm
Blow-out failure
--- Insert steel failure
Figure 16 Required wall thickness to avoid side-face blow-out failure for inserts of type a) with
dh > 2,4 d and fuk = 500 Mpa
23
CEN/TR 15728:2008
According to EN 1992-1-1 most wall elements will have minimum mesh reinforcement (one or two layers). Minimum
reinforcement is presently a Nationally Determined Parameter. Beams and other linear elements will also normally
have minimum shear reinforcement in the region of the insert. In case of unexpected cracking of the concrete
around the insert this reinforcement already provided will often be sufficient as complementary reinforcement to
avoid accidental failure, although the unexpected cracking may render the element unsuited for its purpose. It
should be checked, however, that the design load can be carried by the complementary reinforcement without
yielding (partial resistance factor, s = 1).
N Rk = As f yk cs
The reinforcement As should be positioned within a maximum distance from the insert of 0,75 la, and proper
anchorage lengths should be provided on both sides of the potential crack. For small embedment depths these
requirements may not be easily satisfied. Alternatively, a few extra hairpins may be placed next to the insert with
maximum distance between hairpins = 50 mm. The graphs in Figure 17 may be used to determine the required
amount of reinforcement (either hairpins or mesh reinforcement) for a given characteristic insert resistance and
anchorage length (for c = 1,5).
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Key
Y Characteristic insert resistance, kN
X Anchorage length, mm
1 Mesh
2 Hairpins
Figure 17 Complementary reinforcement required to ensure ductile failure (fyk=400 MPa, accidental
design situation, c = 1,5 and s = 1,0)
The rebars used with inserts of type b) and c) are usually so long that a cone failure is very unlikely (anchorage
failure, see 8.3.4, or steel failure is likely). A check of the complementary reinforcement is therefore not required in
these cases.
The insert should have sufficient anchorage length, so that the full load on the anchor can be transferred to the
concrete. Insufficient anchorage length is likely to result in a cone failure for anchors of type a) while the other types
are more likely to be pulled out of the concrete (anchorage failure).
24
CEN/TR 15728:2008
The anchorage length, la [mm], required to develop a certain force, Nrk, for type a) inserts may be determined
2
based on the following calculation model for fck [N/mm ]:
N Rk = k 3 c l ka4 f ck [N]
c
c = k2 + 1
k1 l a
where
k1 = 1,75
k 2 = 0,16
k3 = 6,1
k 4 = 1,7
Although the calculation model does not explicitly refer to reinforcement it should not be used unless the minimum
reinforcement described in 8.3.3 is provided. Furthermore the range of validity is limited to la 350 mm and
NRk 300 kN. The head diameter should be dh > 2,4d to avoid a pull-out failure.
The calculation model yields up to 20% higher results than a similar model given in ref [1] for inserts in unreinforced
concrete. The difference is due to the effect of the complementary reinforcement. As described in ref [2] the
breakout failure is initiated at working load level by a crack formed at the head of the insert. This crack increases in
length as the load is increased. The presence of complementary reinforcement will slow down the propagation of
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Results from the calculation model are given in diagrams in Figure 18. A required characteristic insert resistance
and an available wall thickness determines the required anchorage length for the insert (the insert should of course
have the required steel strength). The region to the left of the curved lines in the diagrams signify a possible failure
by side-face blow-out which means that the wall thickness is not sufficient, see Figure 16.
If the application is outside the range of validity for Figure 18 or if the required anchorage length for some reason
cannot be accommodated a supplementary reinforcement should be used.
25
CEN/TR 15728:2008
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Key
Y Characteristic axial resistance with complementary, kN
X Wall thickness, mm
1 Possible Blow-out see Figure 16
Figure 18 Required anchorage length corresponding to concrete cone failure for type a) inserts
with dh>2,4d, when complementary reinforcement is provided. For inserts with yield strength higher than
600 MPa dh 2,5d is needed for fck = 15 MPa.
26
CEN/TR 15728:2008
counteracted by this reinforcement close to the insert. The hairpins serve as a load distributor within the concrete
member. In case of splitting of the concrete the crack width is kept small.
Key
1 Insert stirrup
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
The amount of hairpin reinforcement is given by the diagram in Figure 20. The diagram is based on the assumption
that the whole anchor force should be transferred to the element through the hairpin reinforcement (no concrete
contribution). It also means that the complementary reinforcement defined above to prevent a brittle failure is not
needed when the supplementary hairpins are provided.
Nd s
As =
f yk
The hairpins should be located as close as possible to the insert, and they should at least be located within a
distance from the insert of no more than 75% of the length of the insert. The hairpins should be properly anchored
on both sides of the potential cone failure surface. The anchorage length for the open ends of the hairpins can be
found from diagram in Figure 22. The anchorage of the closed ends of the hairpins should be checked with
accepted methods of calculation and the use of sound engineering judgement. The length of the hairpins should be
the sum of the anchorage length of the open end and the length of the insert. The anchorage of the closed ends of
the hairpins needs not to be checked if the insert embedment depth is more than 300 mm and the maximum
distance between the hairpins is 50 mm.
27
CEN/TR 15728:2008
Key
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Figure 20 Supplementary reinforcement, 2-leg stirrups anchored on both sides of potential crack,
see Figure 19
The required anchorage length for anchors of type b), c) and g) is determined on the basis of EN 1992-1-1,
clause 8.4.2 and clause 8.10.2. Results are given in Figure 22 for rebars and strands assuming good bond
conditions. If good bond conditions cannot be expected the anchorage lengths should be increased by 40 %.
For some inserts of type c) the length of the insert may be sufficiently short to facilitate a cone failure. In such cases
a supplementary reinforcement can be used as for type a) inserts. Otherwise, no improvement in axial load
capacity is obtained by supplementary reinforcement.
28
CEN/TR 15728:2008
Key
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
29
CEN/TR 15728:2008
Key
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Figure 22 Anchorage lengths for bonded reinforcement with diameter = d and cover = cd for good bond
conditions. If bond conditions are not good, the anchorage length values should be multiplied by 1,4.
A shear component of the insert force will introduce two possible negative effects on the insert capacity: a shear
failure in the anchor itself and a failure in the concrete due to the contact pressure between the top of the insert and
the concrete.
Both these effects may be counteracted by the design of the insert and its corresponding key. Type a) and b)
inserts typically have keys transmitting the shear component of the anchor load directly to the concrete, thus
introducing very limited shear stresses in the anchor steel. The capacity of anchor type c) will be reduced as a
consequence of the shear stresses in the steel. Anchor types g) may be mounted with an inclination, so that the
direction of the force on the insert may be kept within the limits indicated in Figure 14.
If the lifting angle becomes larger than 30 type a) inserts should be supplied with the hairpin reinforcement
described in 8.3.4, so that reliance on complementary reinforcement only is not accepted. Furthermore, the shear
force transfer to the concrete calls for supplementary reinforcement, consisting of horizontal hairpins (angled pull
links), see Figure 23. The hairpins surround the insert close to the top surface and as they are intended to take up
the shear load on the insert, they should point in the opposite direction of the load. The amount of supplementary
reinforcement should be sufficient to resist the whole shear load component in tension.
If these reinforcement requirements are met, type a) and b) inserts can be expected to have a reduction in tensile
load capacity of 20 % of the tension load capacity for loading angles between 30 and 60.
30
CEN/TR 15728:2008
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Key
1 Mesh reinforcement Q
2 Edge reinforcement
3 Length of slot-in link L1
4 Slot-in link (positioned as closely to anchor as possible)
5 Angled pull reinforcement as close as possible to recess
6 Additional reinforcement for pull
Type c) inserts.
For type c) inserts a suitable key must be used to obtain any shear resistance and even then the shear resistance
of the insert itself cannot be greater than about 50 % of the insert steel resistance in tension. If supplementary
reinforcement is provided according to the same rules as for type a) and b) inserts, the reduction of the insert
0 0
tension load capacity can be expected to be 30 % for loading angles between 30 and 45 .
Type g) inserts
The load direction should be kept within 30, see Figure 14. Furthermore the opening angle should not
exceed 60. It should be recalled that the insert might be placed with the axis at an angle to the surface of the wall
top.
The reduction in insert load capacity can be expected to be 15 % per 10 loading angle.
31
CEN/TR 15728:2008
The choice of inserts to be loaded with a transversal shear force component, see Figure 5c), is rather complicated,
mainly because the local stresses introduced by the transfer of load from the insert to the concrete are augmented
by the global stresses from bending moments in the wall. Generally, the transversal shear should be kept as small
as possible, the edge distance should be as large as possible and supplementary tilting reinforcement should be
provided, e.g. according to Figure 24. Further information may be found in [1].
Key
1 Additional reinforcement
2 Radial reinforcement
3 Transverse pull
Figure 24 Examples of lifting inserts in a wall with supplementary tilting reinforcement for transverse
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Since the thickness of the slab or pipe wall is the limiting factor, the relevant types of inserts are short and provided
with some sort of head, plate or similar anchorage device designed to activate as large a concrete cone as
possible. Some of the insert types and their corresponding keys are designed to transfer shear components of the
insert load directly to the concrete, see also 8.2.1.
The full insert load capacity is obtained only if the edge distances are large enough to allow the cone to develop
fully and independently of the edge distance. This is likely to be the case if the edge distance is at least 1,5 times
the length of the insert. Smaller edge distances will reduce the load capacity.
Since the function in many cases is based on the cone resistance it is essential that a complementary
reinforcement be provided to avoid brittle failure. Figure 25 illustrates a possible arrangement with the
reinforcement on top of the insert head. The figure shows the amount of reinforcement needed to obtain ductile
failure for a certain needed tensile resistance of the insert. The required anchorage length is dealt with in
section 8.4.3.
32
CEN/TR 15728:2008
Key
Y Characteristic axial resistance, kN
X Diameter of complementary rebars in slabs, mm
Figure 25 Arrangement of complementary reinforcement in slabs and pipes for fyk=500 MPa. Required
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
length of rebars is app. 30 50 times bar diameter (highest value for larger diameter)
The insert may in some cases be placed so that the main reinforcement in the slab or pipe can provide the same
function. In that case a separate complementary reinforcement is not needed.
33
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
CEN/TR 15728:2008
Table 10 Design summary for inserts under inclined tensile loading in slabs and pipes
Anchor type
d) f)
e)
Distance to edge
Edge distance at least 1,5 times length of insert
Required anchorage length Determine required anchorage Determine required anchorage length corresponding to
length corresponding to concrete concrete cone capacity from Figure 26
cone capacity from Figure 26
Capacity reduction due to shear 20% for loading angle 30 <<60 20% for loading angle 30 <<60 30% for load angle 30 -45
component
34
CEN/TR 15728:2008
Assuming that the reinforcement requirements in section 8.3.4 are satisfied, the necessary anchorage length
to obtain a given capacity for type d) and e) inserts can be found from Figure 26. The curves correspond to a
cone failure according to the calculation model given in section 8.3.4., assuming that edge distance is larger
than 1,5 times anchorage length. Again the complementary reinforcement delay the crack development
compared to an unreinforced situation which explains an increased strength compared to values in ref [1]. It
should be noted that the same range of validity as given in section 8.3.4 apply (i.e. NRk < 300 kN).
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Key
Y Characteristic resistance with complementary reinforcement, kN
X Anchorage length, mm
Figure 26 Anchorage length needed in slabs and pipes to obtain required characteristic resistance.
Edge distances larger than 1,5 times anchorage length
For very short anchors (typically type g) inserts with embedment length smaller than 75 mm in shallow slabs
reliance on the cone resistance should not be used. Instead a reinforcement designed to carry the whole
anchor load should be arranged according to Figure 27.
Key
1 Main reinforcement (surface)
35
CEN/TR 15728:2008
The applications dealt with in clause 8.4 will not have shear loads pointing towards the edge.
For anchor types that are used with a key designed to transfer shear forces directly to the concrete, the load
capacities given in section 8.4.3 for tension loads can be used for a loading angle smaller than 45.
For other types of anchors the load capacity should be reduced by 30% for loading angles between 30
and 45.
In the first case the precaster wants to check that a design based on supplier information or on the
recommendations in chapter 8 is valid for a specific application. Strong prior knowledge can be assumed
and that may reduce the necessary testing program to 2-5 tests. EN 1990, Annex D.8.4 provides the
basis as described in Annex A.5.2 and A.6.2.1.
In the second case the precaster wants to verify a design that may be outside the range for which
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
available information is valid. The insert to be applied may be new or it may be used outside the
stipulated limits. In this case the necessary testing program is likely to be somewhat larger, because the
strength of prior knowledge is somewhat debatable. EN 1990, Annex D.8.2 provides the basis as
described in Annex A.5.2 and A.6.2.2.
In the third case the precaster wants to utilise an insert for which no prior knowledge is available. The
necessary testing program is likely to be large. EN 1990, Annex D.7.2 provides the basis as described in
Annex A.5.3 and A.6.3.
10.1 General
The precaster should make sure, that the choice and design of the lifting arrangement is documented. The
documentation should include:
The following technical information should be available for any kind of insert, whether produced by the
precaster or delivered by a supplier (see Annex B):
General description of the lifting system, including material properties, sketches main dimensions, main
uses, instructions for use, limits of use, etc.;
36
CEN/TR 15728:2008
when design values are determined by calculation, verification of the validity of the design method for
the insert dimensions and that the design method covers the assumed lifting and handling situations;
when the design values are determined by testing, verification that the test method represents the
lifting conditions in practice;
when the design values are determined by testing or calculation assisted by testing, both verifications
mentioned above and the evaluation of the test results;
NOTE For lifting systems put on the market by a lifting systems supplier contractual information should be available
e.g. in brochures. Only contractual documents should be used (often commercial brochures are not contractual). For other
lifting inserts the information should be available as part of the precaster's technical documentation.
The design of the lifting inserts for a specific concrete product should be documented in the precaster's
technical documentation. Normally this will be part of the general design of the product, and the result shown
on the production drawings. The following should be included:
description of the lifting insert, e.g. type, size, length and corresponding key;
assumptions for lifting operations used in design, e.g. dynamic factors, loading angles, form friction and
adhesion provided by the precaster (see Section 7);
handling instructions.
The following information should be available at the precast plant and on site for each type of precast element:
37
CEN/TR 15728:2008
any measures for protection, if necessary (this does not have anything to do with lifting and handling,
except to prevent ice forming in lifting recesses);
In certain cases it might be necessary additionally to include a description of the required compensation
devices (see Fig. 5.1), the transport and erection procedures and to indicate the centre of gravity.
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
38
CEN/TR 15728:2008
Annex A
(informative)
A.1 Objectives
A.1.1 General
The design process for a specific lifting application can often be based on calculation models as described in
this report. In some cases, however, the precaster may need to verify the load capacity of inserts used under
various conditions by testing. Depending on the situation, the objectives of the test programme may vary. The
aim, however, is to obtain a sound and uniform basis for the design.
This Annex describes the planning, execution and evaluation of such test programs to support design of
inserts. The annex is not intended to cover the full testing program needed to support a declaration valid for a
range of applications.
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
The objective of these tests is to provide reliable information on the resistance properties of a particular insert
for a limited area of application. The insert might be produced by a precaster for his own use or it might be an
insert as part of a system.
The testing program limited to the special application may intend to confirm an existing design model, it may
intend to develop a special design procedure or it may intend to determine a resistance value for the insert.
Prior know-ledge should be used as far as possible, but the effect of prior knowledge depends on the
circumstances.
Testing conditions should reflect the conditions within the intended range of application and this should be
documented.
A lifting insert should be tested depending on the field of its application. For example, a distinction between
lifting of slabs and pipes on one side and walls and linear concrete elements such as beams and columns on
the other side is generally appropriate.
arrangement of insert(s) within concrete member (distance between inserts, edge distance, etc.);
39
CEN/TR 15728:2008
reinforcement.
Depending on the area of application, typical test specimen may be arranged as shown in Table A.1 and
Figures A.1 to A.3.
In addition the steel resistance should be tested (if included in the calculation model).
Figure A.1 Example of a test set-up for inserts under tension load and combined tension and shear
load
40
CEN/TR 15728:2008
Key
1 Jack
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
2 Pipe
3 Insert
Figure A.2 Example of a test set-up for inserts under tension load in a pipe
a) b)
Key
1 Polystyrene
2 Edge distance
Figure A.3 Examples of test set-ups for inserts under tension load and shear load in a wall
41
CEN/TR 15728:2008
a) b)
The specimen should be representative for the concrete product, i.e. cured and kept as the product and tested
such that properties can be established for the relevant lifting situations. The precise history of the specimen
should be known i.e. age, production, curing method, storage, etc.
Typically testing is performed at early age of the concrete. It should be noted that the tensile strength of the
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
concrete develops slower than the compressive strength during the first days of hardening. Furthermore, it
should be considered that temperatures due to heat of hydration may yield strength development of the test
specimen different from that of the corresponding cubes or cylinders stored together with the specimen.
The testing samples should be representative of the production of the manufacturer as applied to the precast
concrete element.
The lifting inserts should be installed in accordance with the intended use.
The lifting inserts to be tested should be unambiguously identified by comparison with relevant specifications
and drawings.
After the concrete specimen has been installed, the lifting insert should be connected to the test rig by means
of the lifting key intended for use in practice. If the lifting insert is part of a lifting system, the lifting insert
should be tested with the appropriate lifting key. In other cases the smallest high strength hook intended to be
used should be used in the tests.
The test rig should be placed such that an unrestricted concrete failure is possible. The clearance ls between
insert and support of the test set-up on the specimen to avoid an influence on the concrete break-out
resistance should be at least:
in case of inserts under tension loading in general the clearance between outer perimeter of the insert
and support of the test set-up l s 1,5 hef ;
42
CEN/TR 15728:2008
in case of inserts under tension loading where other than concrete break-out failures are to be studied,
the distance between support and insert may be reduced to a value of half of the insert length and the
directly connected rebars;
In a combined tension and shear test the load may be applied by either one jack acting at the specified angle
to the lifting insert axis or by two jacks under servo control applying simultaneously an axial tension load and a
shear load, respectively. During the test the intended angle of load application should be kept constant with a
tolerance of 2 degrees.
The insert should be loaded to failure unless the resistance of the insert is determined by attributes.
The load shall be applied to the specimen according to the following procedure:
Speed of loading shall not exceed 10% of expected ultimate load per minute. In case of manual recording
of test data the time includes actual time used to increase the load from one level to the next and the time
spent at each load level to record displacements and to make other observations;
The loading history should start with one loading-unloading step to a small load value (5% of expected
ultimate load to settle the set-up);
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
The loading history shall contain 5 loading-unloading sequences to service load level each sequence
consisting of 5 load steps (if the stiffness or permanent deflections are part of the objectives).
A.4 Measurements
Tests should be carried out using measuring equipment for load and displacement having traceable
calibration.
The load application equipment should be designed to avoid sudden increase in load especially at the
beginning of the test. The measuring error of load and displacement should not exceed 3 % of measured
values at ultimate load in each test.
Displacements should be recorded continuously (e.g. by means of displacement electrical transducers) with a
measuring error not greater than 0,1 mm.
The displacements of the insert relative to the concrete surface at a distance of > 1.5 la in case of tension
loading and > 1,5c1 in case of shear loading from the insert should be measured in the direction of the load
application.
A.5.1 General
The need for testing arises when prior knowledge is insufficient. It means that the need may vary from almost
nothing to infinity depending on the situation. And it means that there may be more than one good solution to
a given problem.
Prior knowledge may be hard core evidence like original results of earlier traceable tests. It may be
state-of-the-art evaluations of test results from other sources (like the present report or design
recommendations from suppliers of inserts). It may even be experience from previous successful use of an
43
CEN/TR 15728:2008
insert. From a statistical point of view the use of these various types of prior knowledge is not necessarily
unambiguous and thus the need for testing is always debatable. Furthermore, it may well be more economical
to compensate for uncertain design rules by over-sizing the inserts instead of doing more testing. The
following recommendations should therefore be considered as guide lines for good practice rather than legal
minimum requirements.
The precaster will often have a certain prior knowledge about the resistance properties of an insert to be used
in a certain application. The aim of testing is to fill in the remaining gaps. The typical situations would be in a
range between the following two examples:
The validity of an earlier initial type testing (ITT) is to be checked. Strong prior knowledge can be claimed
and the rules given in EN 1990, Annex D.8.4 may be used requiring only a few tests;
The precaster intends to use a home made insert for a limited range of applications. The insert may or
may not be covered by the type descriptions in clause 8. For the initial type testing (ITT) the precaster
assumes that the load capacity of the insert within the application range may be calculated according to a
certain calculation model. Tests are then used to verify that the assumed calculation model can be used
or how the model may be improved. EN 1990, Annex D.8.2 describes the procedure and an example on
the use of the procedure is given in TR 14862:2004.
The term prior knowledge is by nature a flexible concept. Furthermore, some of the descriptions given in
EN 1990 may be interpretable so that different designers may reach different results from these procedures. It
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
is therefore important that a clear and fair limitation on the range of applicability of the resulting calculation
model is given.
A.5.3.1 Determination of properties for one insert used for specific applications
This possibility may be used successfully for ITT when an insert is to be used in a very narrow range of
applications. A number of tests may be used to determine the mean value and the deviation of the resistance.
The characteristic resistance may then be found using ordinary statistical methods as described in EN 1990,
Annex D.7.2. Prior knowledge is not needed in this case:
The tests may be performed for only the most unfavourable situation within the range of applications in
order to obtain a characteristic resistance that may then be used for the whole range;
Tests may also be performed for several situations which each represent the most unfavourable case of a
group of situations within the range of applications;
In any case the testing should cover at least the most unfavourable combination of the intended lifting and
handling conditions, e.g. lowest concrete strength or loading direction with the lowest expected ultimate
resistance.
The method may utilise prior knowledge on the coefficient of variation, but if a larger range of applications
should be covered, it would often be more economical to develop a design model according to clause A.5.2.
The evaluation of the test results should follow the procedures given in EN 1990, Annex D. The characteristic
resistance is defined as the 5 %-fractile of the ultimate loads measured in a test series at a confidence level
44
CEN/TR 15728:2008
of 75 %. In general, a normal distribution and an unknown standard deviation of the population should be
assumed.
The aim of testing is normally to obtain an estimate for the characteristic resistance. The assessment will be
different, however, depending on the testing program chosen in clause A.5. If a program according to A.5.2 is
chosen, the result is a calculation model which predicts the characteristic resistance for a (limited) range of
situations. If no prior knowledge is used the result will be a number (clause A.5.3.1) valid for one insert in one
application.
If a calculation model is known from previous tests (including an upper bound value for the coefficient of
variation) a few more tests may be used to estimate the characteristic resistance, Rk. According to EN 1990,
Annex D.8.4 the following estimate may be used, provided that each additional test result deviates less
than 10 % from the mean value of the additional results:
k
Rk =
n Ri
1 1
Ri
n Ri 0,1
n Ri
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
where
When testing is used to verify a calculation model the test result to be assessed is the ratio between
measured and calculated values (using measured values of all parameters entering the calculation model).
Ideally, this ratio should be 1,0. If the scatter on this ratio is large or even systematic the model should be
modified so that the scatter is reduced. Details about the assessment may be found in EN 1990, Annex D.8.2
and in TR 14862:2004.
If the test program does not utilise prior knowledge (test program according to clause A.5.3.1), the test results
to be evaluated are the measured values. Rules for the evaluation are given in EN 1990, Annex D.7.2. A
normal distribution and an unknown standard deviation of the population may normally be assumed.
NOTE The number of tests should be large enough to establish a stable coefficient of variation of the ultimate load.
45
CEN/TR 15728:2008
Date of tests.
Type of test (e.g. tension, shear, oblique tension, short-term or repeated load test).
Number of tests.
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Date of manufacture.
Dimensions of control specimens, and/or cores (if applicable) measured value of compression strength at
the time of testing (individual results and average value).
Information on the positioning of the insert (e.g. placed on the uncast face or cast face of the test
member).
Distances of inserts from edges of test member and between adjacent inserts.
Depth of anchorage.
46
CEN/TR 15728:2008
Parameters of load application (e.g. rate of increase of load, size of load increase steps, etc.).
Ultimate load.
Radius (maximum radius, minimum radius) and height of a concrete cone produced in the test (where
applicable).
47
CEN/TR 15728:2008
Annex B
(informative)
a) Short description of the lifting anchor system and its components including the connection between key
and lifting inserts.
Storage;
assembly in formwork;
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
c) General specification:
corrosion behaviour;
load directions;
e) Restrictions;
a) Available types, dimensions and sizes and their marking in figures and tables
b) Materials
c) Information on which keys can be used, e.g. colour code for threaded systems
48
CEN/TR 15728:2008
f) Load table, dependent of the type of key used, showing at least the insert load capacity for the minimum
concrete strength in different directions
g) Required supplementary reinforcement, shape, amount, diameter, length, depending on the lifting
conditions
h) Minimum dimensions of the concrete elements, spacing between anchors, edge distance, panel
thickness, concrete cover
j) Restrictions
The operation instruction has to fulfil the European Machinery Directive 98/37/EC. The following information
should be given:
producer;
fabrication number;
year of production;
d) Materials
lifetime definition;
49
CEN/TR 15728:2008
description of checking;
c) Materials
closing of openings;
cleaning threads;
f) Restrictions
50
CEN/TR 15728:2008
Bibliography
)
[1] Design of fastenings for use in concrete, CEN TS 2 .
[2] Eligehausen, R.; Malle, R.; Silva, J.F.: Anchorage in Concrete Construction, Ernst & Sohn,
Berlin, 2006.
[3] Directive 98/37/EC, of the European Parliament and of the Council of 22 June 1998 on the
approximation of the laws of the Member States relating to machinery, Official Journal of the European
Communities, L 207, Vol. 41, July 1998.
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
51
PD CEN/TR
15728:2008
British Standards Institution (BSI)
BSI is the independent national body responsible for preparing
British Standards. It presents the UK view on standards in Europe and at the
international level. It is incorporated by Royal Charter.
Revisions
British Standards are updated by amendment or revision. Users of
British Standards should make sure that they possess the latest amendments or
editions.
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: +44 (0)20 8996 9000 Fax: +44 (0)20 8996 7400
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services.
Tel: +44 (0)20 8996 9001 Fax: +44 (0)20 8996 7001
Email: orders@bsigroup.com
You may also buy directly using a debit/credit card from the BSI Shop on the
Website http://www.bsigroup.com/shop.
Licensed copy:Benaim Group, 17/01/2009, Uncontrolled Copy, BSI
Information on standards
BSI provides a wide range of information on national, European and
international standards through its Library and its Technical Help to Exporters
Service. Various BSI electronic information services are also available which give
details on all its products and services. Contact the Information Centre.
Tel: +44 (0)20 8996 7111 Fax: +44 (0)20 8996 7048
Email: info@bsigroup.com
Subscribing members of BSI are kept up to date with standards developments
and receive substantial discounts on the purchase price of standards. For details
of these and other benefits contact Membership Administration.
Tel: +44 (0)20 8996 7002 Fax: +44 (0)20 8996 7001
Email: membership@bsigroup.com
Information regarding online access to British Standards via British Standards
Online can be found at http://www.bsigroup.com/BSOL.
Further information about BSI is available on the BSI website at
http://www.bsigroup.com.
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means electronic, photocopying, recording or otherwise without prior written
BSI Group Headquarters
permission from BSI.
389 Chiswick High Road,
This does not preclude the free use, in the course of implementing the standard,
London W4 4AL, UK of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
Tel +44 (0)20 8996 9001
written permission of BSI must be obtained.
Fax +44 (0)20 8996 7001
Details and advice can be obtained from the Copyright & Licensing Manager.
www.bsigroup.com/standards Tel: +44 (0)20 8996 7070 Email: copyright@bsigroup.com