3. Prevention of similar troubles based on customer complaint cases
[Backgrounds]
The room, where the trouble occurred, was an explosion-protective area. It had an air-conditioning system
operated by a once-through type outdoor air-conditioner.
The setting of the relative humidity of the room was raised to reduce the generation of static electricity.
Key factor 3
Note that under humidification at a lower temperature (the air is humidified at 15 or lower), the vapor absorption must be
longer than that under the humidification room temperature. If the air is humidified at a lower temperature, consider using
standpipe-equipped air-conditioners.
*See Engineering data: Selection of humidifiers.
3
3. Prevention of similar troubles based on customer complaint cases
Supply air is room air dew-point condition .( Supply air dew-point temperature control )
Setting dew-point temperature is 15 DP .
(1) Air temperature after pre-heating coil ; 16DB
(2) First stage humidifying ;
(3) Supply air is re-heated to 18DB ; t = 5
(4) Second stage humidifying ;
(23-60%)
(0-40%)
4
3. Prevention of similar troubles based on customer complaint cases
Supply air is room air dew-point condition .( Supply air dew-point temperature control )
Setting dew-point temperature is changed from 15 DP to 16 DP .
Action of Stopping same failure again
Key factor 1.
In case of using steam humidifying system , In case of room humidity setting rate changing ( Supply air dew-point rate changing )
It is required to be checked Air after humidifying is not over 85 % RH .
Humidifying to Air might not be unity / even , then 85 % RH condition is set .
(23-65%)
90%
(23-60%)
(0-40%)
5
3. Prevention of similar troubles based on customer complaint cases
Room air-conditioning load was increased , re-heating was no working , supply air temperature was changed from 18 to 16 DB .
HEPA filter was become wet , resistance was increased , air-conditioner running air volume was decreased down .
Supply air condition was saturate condition .
Action of Stopping same failure again
Key factor 2.
In factory / production , it is possible to be expanded production volume than primary design time condition .
It might be increased room air-conditioning heat load .
Then the actual supply air condition and supply air volume have to be measured and checked .
And it is required to be checked actual air volume due to air filter clogging .
(23-65%)
100%
(23-60%)
(0-40%)
6
3. Prevention of similar troubles based on customer complaint cases
In case of air temperature below 15 DB , In case of humidifying volume larger than 5g / m3 ( 0.005 kg / m3 ) .
Stand type steam humidifier and With angle type are available , have to be considered to be used .
The objective is to increase humidifying efficiency and humidifying expanding performance .
Refer Engineering data Humidifier selection
Stand Pipe humidifier system
Installation image
Steam pipe
Angle
Air Flow 45
,1500Pa()
8
3. Prevention of similar troubles based on customer complaint cases
9
3. Prevention of similar troubles based on customer complaint cases
Example ,
t : Temperature difference of room air and supply air , it is 45 Times of temperature allowance rate .
Example ,
25 1 t = 4 5 (K)
General air-conditioning system , allowance rate is around 2 K , so t = 10 (K) nearly .
10
3. Prevention of similar troubles based on customer complaint cases
45.2
0.0088
0.0013
11
3. Prevention of similar troubles based on customer complaint cases
e)
m
lu
vo
A
eO
ak
nt
(I
ad
Lo
49.6
A
O
45.2
39.9
0.0088
0.0081
0.0013
12
91.0
35.0
49.6
It is impossible to be changed air condition from 24.2 point to 18.2 point
45.2 directly by Cooling coil cooling & de-humidifying .
39.9
Outdoor Air Load
Room Load (TH) 0.0088
0.0013
24.2
18.2 23.0
13
91.0
49.6
45.2
39.9
0.0088
23 - 67 %
0.0013
14
91.0
35.0
In case of fixed temperature & humidity room , it is required to put de-humidifying capacity exactly .
It is poor calculation & design just on the desk , needed to be checked on the psychometric chart .
46.9
45.2
39.9
Outdoor Air Load
24.2
It is required t = 18.2 - 13.0 = 5.2 deg. C re-heating , from cooling coil outlet to supply air .
15
3. Prevention of similar troubles based on customer complaint cases
2. After you confirm the permissible temperature range and the permissible humidity range on the
psychrometric chart, select more strict ranges.
Consider the outlet air temperature difference corresponding to the permissible temperature difference.
3. You should consider equipment behaviors on the psychrometric charts to determine the equipment capacity.
* You should determine the equipment capacity by comparing the capability to reheat the air with that
necessary for heating air-conditioning.
16
3. Prevention of similar troubles based on customer complaint cases
Case 3 Deficient humidification in an office building
Recently, many office buildings have adopted multiple air-conditioning systems.
The reasons why such systems are adopted include advantages, such as separate operation and easy switching
between cooling and heating modes.
Multiple systems, however, frequently cause deficient humidification during the winter. More customers tend
to express requests to improve it. The following factors are possible causes.
3. Customers do not have sufficient knowledge of humidification, or the air-conditioners are not maintained
adequately.
*1: Do not raise the room temperature without reason. If the temperature rises, the relative humidity falls.
*2: Comply with instructions described in the manual, and maintain equipment and systems without fail.
17
3. Prevention of similar troubles based on customer complaint cases
Case 3 Deficient humidification in an office building
Example :
Building multi air-conditioning system with heat exchanger and humidifier .
Office room air-conditioning load is cooling side in winter also .
Humidifying
(2) Plotting ofis design
done after heat exchanger
calculation OA ,
result rates
Heat exchanger is with direct expansion coil type , but it is not heating running .
Humidifier
Necessary check & study items are ,
Separate heat exchanger line with air-conditioner indoor unit line .
Air-conditioner Set individual OA air-con. Line for OA treating and supply .
indoor unit Setting humidifier separately .
Just 35% RH only Humidifying is done on this point OA after heat exchanger
18
This is the end of the explanation of
Prevention of similar trouble based on customer complaint cases
for Understanding psychrometric charts
19