Professional Documents
Culture Documents
P/N 76-100016-001
PEGAsys
Intelligent Suppression-Control
and Fire-Alarm System
Installation, Operation,
and Maintenance Manual
UL Listing File No. S2422
Factory Mutual Approval J.I. No. OB2A6.AY
LISTED
Fire Systems
PEGAsys
Intelligent Suppression-Control
and Fire-Alarm System
Installation, Operation,
And Maintenance Manual
FOREWORD
This manual is intended to clearly and accurately reflect the PEGAsys Fire Alarm/Suppression Control System. This publication de-
scribes the operation, installation and maintenance of the PEGAsys Fire Alarm/Suppression Control System, P/Ns 76-100000-501 for
Single-Loop System and 76-100000-600 for Multi-Loop System.
i
(THIS PAGE IS INTENTIONALLY LEFT BLANK)
ii
TABLE OF CONTENTS
Forward ......................................................................................................................................................... i
Terms and Abbreviations ................................................................................................................................ i
Appendices ................................................................................................................................................... vi
List of Illustrations .......................................................................................................................................... vii
List of Tables ................................................................................................................................................. ix
Safety Summary ............................................................................................................................................ x
iii
TABLE OF CONTENTS (CONT.)
PARAGRAPH TITLE PAGE
iv
TABLE OF CONTENTS (CONT.)
PARAGRAPH TITLE PAGE
v
APPENDICES
APPENDIX TITLE PAGE
L REMOTE DISPLAY CONTROL MODULE AND REMOTE DISPLAY MODULE ............................................................... L-1
vi
LIST OF ILLUSTRATIONS
FIGURE TITLE PAGE
vii
LIST OF ILLUSTRATIONS (CONT.)
viii
LIST OF TABLES
ix
SAFETY SUMMARY
Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability:
Warning - Several different sources of power can be connected to this fire alarm control panel. Disconnect all sources of power
before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or intercon-
necting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure proper system operation, this product must be tested in
accordance with NFPA - 1996 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is
required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware
or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change,
up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0 to 49 C and at a relative humidity of 85% RH (non-condensing) @ 30C.
However, the useful life of the systems standby batteries and the electronic components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal
room temperature of 60-80F.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced
transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce suscepti-
bility. The use of overhead or outside aerial wiring is not recommended due to the increased susceptibility to nearby lightning
strikes. Consult with the Applications Engineering Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable
entries from the sides. Before making modifications, verify that they will not interfere with battery and printed circuit board location.
Do not over tighten screw terminals, over tightening may damage threads, resulting in reduced terminal contact pressure and difficult
with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that
static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the Instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to
the control panel and associated equipment. PEGAsys operation and reliability depend upon proper installation.
Fire Alarm System Limitations While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices,
and a fire alarm control with remote notification-capability can provide early warning of a developing fire. Such a system, however, does
not assure protection against property damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side
of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example,
may not sense a first floor or basement fire. Furthermore, all types of smoke detectors - both ionization and photoelectric types, have
sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in
bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with
matches, or arson.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors
or are located on another floor of a building.
A fire alarm system will not operate without electrical power. If AC power fails, the system will operate from standby batteries only for a
specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist.
x
Auxiliary Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily
disabled.
The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be
tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection
and testing should be scheduled monthly or as required by National and/or local fire codes. Adequate written records of all inspections
should be kept.
GENERAL SAFETY NOTICES The following must be observed to maintain personnel safety.
The following general safety notices supplement specific warnings and cautions appearing in the manual. The safety precautions in this
section must be understood and applied during operation and maintenance. This manual is to be used by trained distributors/technicians.
The entire manual should be read and fully understood prior to installation.
TEST EQUIPMENT
Make certain test equipment is in good operating condition. Do not touch live equipment or personnel working on live equipment while
holding a test meter. Some types of measuring devices should not be grounded; these devices should not be held when taking measure-
ments.
FIRST AID
Any injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention immediately.
GENERAL PRECAUTIONS
The following general safety precautions are to be observed at all times:
1. All electrical components associated with equipment shall be installed and grounded in accordance with NEC, NFPA and local
regulation requirements.
2. Special precautionary measures are essential to prevent applying power to equipment at any time maintenance work is in progress.
3. Before working on electrical equipment, use a voltmeter to ensure that system is not energized.
4. When working near electricity, do not use metal rules, flashlights, metallic pencils, or any other objects having exposed conductive
material.
5. When connecting a meter to terminals for measurement, use range higher than expected voltage.
xi
Intelligent Suppression Control/Fire Alarm System PEGAsys
CHAPTER 1
GENERAL INFORMATION
Loop Isolator
for Style 7
Display Reset Switch
System Status
SCROLL DRILL 6 7 8 9 0
76-100003-001
provide connections for up to 7 I/O module circuit board as-
semblies. The ML motherboard is mounted to standoffs on the
back of the main system enclosure. It distributes system 24
VDC power, CCM-RX/TX communications for up to 8 RX/TX
modules and I/O bus communications to the I/O modules. The
I/O bus communications are provided by a RJ-12 (flat phone
cable) style connection. A single RJ-12 connection connects
the ML motherboard to the CCM for RX/TX communications.
The 24 VDC is provided by the system power supply via a 2-
conductor wiring harness.
76-100002-001
Figure 1-11. City Tie Module
120 VA C , 1.9 A mp s
P.S . Inp ut (P e r Mo d ule )
220 VA C , .95 A mp s
CCM
S i g na l Outp ut: 24 V D C , 2 A mp s
Re le a se Outp ut: 24 V D C , 2 A mp s
Figure 1-19. Loop Isolator, Stand-Alone Re la y C o nta ct Ra ti ng : 1 A mp @ 30 V D C
Tro ub le Re la y Ra ti ng : 1 A mp @ 30 V D C
SHORT-2 SHORT-1
J1
R X T X M o d u le
Ma x. Vo lta g e : 26.4 V D C
LOOP ISOLATOR
DS2 DS1
Mi n. Vo lta g e : 19.0 V D C
RX/TX
Underwriters
R Laboratories Inc. R Ma x. Li ne C a p a ci ta nce : 1.0 uF
LISTED
REFER TO
Ma x. Li ne Re si sta nce : 26 Ohms
INSTALLATION MANUAL
Ma x. A d d re ssa b le
P/N 76-100016-001 255 p e r RX TX
FOR MODULE INSTALL. KIDDE-FENWAL, INC. D e vi ce s:
PROCEDURES ASHLAND, MA 01721
R elease M o d u le
S i g na l Outp ut 2 A mp s @ 24 V D C e a ch
C a p a b le o f re le a si ng
Re le a se Outp ut Typ e : so le no i d s (sup p re ssi o n
a nd sp ri nkle r)
S ig n al Au d ib le M o d u le
R elay M o d u le
Figure 1-21. Loop Isolator, 6" Detector Base Mount (4) Fo rm C C o nta cts,
C o nta ct Ra ti ng : 2 A mp s @ 30 V D C o r
1 A mp @ 120 VA C
C ity T ie M o d u le
Lo ca l E ne rg y S up e rvi so ry: 11 mA
CHAPTER 2
OPERATION
System Status
SCROLL DRILL 6 7 8 9 0
simulated LCD display readouts. The LCD display readouts c. Type in three or four digit password into keypad. Ensure a
will be used to aid users in the operation of the system. pound sign (#) appears for each key pressed.
NOTE: Use the default password, if a new password has not
2-2.2 Audible Device been set.
The Display Panel also contains an audible device which gen- d. ) key. Verify that the display reads:
Press the return (
erates two separate audible tones, one for alarms and one for
1:ISOLATE 2:LIST
troubles. This device sounds continuously when a new alarm
condition is received until the condition is acknowledged. It also 3:SET 4:TEST
sounds intermittently when a trouble, supervisory, or pre-alarm
condition is received until the condition is acknowledged.
Refer to Table 2-1 for complete description of controls and indi- The following step-by-step procedure is for initial power-up of
cators. the CCP.
a. Perform the installation check-out procedure in Chapter 7
of this manual.
b. Set the circuit breaker for the CCP power to ON. Verify that
2-3 SYSTEM SECURITY the display reads "Main Processor Power On" and that the
The PEGAsys system provides three distinct levels of program CPU ERROR indicator is lit. Ensure that the audible device
protection, as required by UL Standard 864. The user can only is buzzing continuously.
access the system by entering a valid password. Typical valid c. Press the display module reset switch. Verify that the CPU
passwords consist of three or four characters but may be up to ERROR indicator is extinguished and the audible device is
eight characters in length. silenced.
d. Verify that the display reads as follows:
2-3.1 Levels of Security
MAIN PROCESSOR
The three security levels are: Level One, Level Two, and Sys- POWER ON
tem Manufacturer. The highest security level is reserved for the
e. After ten seconds, verify that the display reads as follows:
system manufacturer. System owner is level one, system in-
staller is level two. Passwords consist of numeric characters (0 RXTX NON-MONITORING TROUBLE ON
- 9) which allows access from the integral keypad of the CCM. RXTX1
Alphanumeric characters can only be used with the PCS pro-
gram and if used they will lock out any possible entry using the NOTE: For multi-loop systems only. The above and below RX/
CCM keypad to gain entrance to the menus. TX messages will repeat themselves for each RX/TX
module installed in the system. The above message
If alphanumeric passwords are necessary for a particular appli- will be displayed while the system is initializing itself.
cation, it is recommended that the Level One password be nu- This initialization can take up to 90 seconds.
meric and the Level Two password be alphanumeric so as to
allow the user to retrieve system information (system informa- To clear the below RX/TX message use the AutoLearn
tion lists) and also prevent a user from changing any pro- function from the menu function or upload the
grammed system parameters. configuration from the PCS program. If using PCS
software, verify that the correct number of RX/TX loops
are enabled in the Loops Topic of the configuration file
2-3.2 Default Passwords
prior to uploading.
The PEGAsys system provides protection from unauthorized
entry to the system menus by utilizing two levels of default pass-
RX/TX 1 NOT REGISTERED ON
words, level one and level two. This feature provides two sepa- RX/TX LOOP 1
rate passwords which increases the security of the system. f. Verify that the POWER ON and TROUBLE indicators are
Default passwords are set when the system is shipped from lit.
Kidde. These default passwords are: g. Connect the backup batteries to the CCP in accordance to
Level One = 987 the procedure in Chapter 7.
Level Two = 1865 h. Press the ACKLDGE pushbutton. After approximately one
minute the display will momentarily read :
These default passwords are valid until other passwords are
RXTX NON-MONITORING TROUBLE OFF
programmed into the system.
i. Verify the display reads the incorrect time and date.
2-3.3 Entering Passwords j. Set time and date as follows:
The password entry procedure is listed below: (1) Press 0 (zero) key. Verify that the display reads:
LED FUNCTION
When illuminated, indicates that the system is receiving AC input power. When
POWER ON off, indicates an AC input power failure has occurred (trouble condition) and the
system has switched to a battery standby condition.
When illuminated, indicates a ground fault has been detected on the 24 VDC line
GROUND FAULT
by the power supply monitor. The LCD will display either + / -.
When illuminated, indicates a smoke or heat detector has sensed a level of smoke
PRE-ALARM
or heat which exceeds the pre-alarm setpoint.
When illuminated, indicates CCM software has failed. The system defaults to
CPU ERROR
Zone Alarm / General Signal status.
SILENCE When illuminated, indicates the Signal/Audible outputs have been silenced.
SWITCH FUNCTION
When pressed after an Alarm ON (Alarm OFF if input device is set for non-
latching) Trouble, supervisory, or pre-alarm ON condition has occured, it silences
the panel's audible buzzer. The "ALARM", "TROUBLE", "SUPERVISORY", or
ACKNOWLEDGE
"PRE-ALARM" LED indicator glows steady to indicate that the condition has
been acknowledged. Subsequent conditions will cause the panel to resound the
above sequence.
When pressed after acknowledging current Alarm, it silences the system signal
outputs which have been programmed as silenceable. The "SILENCE" indicator
SILENCE
illuminates to indicate that the signal outputs have been silenced. Pressing the
"SILENCE" switch does not effect the Relay Output status.
When pressed after all active alarms have been acknowledged and cleared, the
system:
Resets auxiliary 24 VDC outputs used to power 4 wire detectors
RESET Resets all latched alarm conditions.
Returns all relays to their normal state.
Displays "System Reset" on the visual display.
Turns the "ALARM" and "ZONE ALARM" indicators off.
When pressed during an active alarm, trouble, or supervisory condition, will cause
the LCD to scroll through the active event buffer(s). The Alarm condition will not
SCROLL
allow supervisory or troubles to be viewed. Supervisory condition will not allow
the troubles buffer to be viewed.
When pressed and held for five seconds, the system will activate all signal
DRILL
outputs which have been programmed for drill activation.
NUMERIC KEYPAD (1-0) Use to enter password and system information into the menu system.
BACKSPACE Use to exit the menu system and to correct wrong entries.
RETURN Used as the Enter key when using the menu system.
7:Voltages
6:Digital I/O
6:GlobalI/O 6:Assignments
7:Global
6:GlobalI/O 7:Voltages
Isolate I/O Module Signal Output Isolate/De-isolate a signal module output circuit by address 1-2-1 1/2/M
Isolate I/O Module Release Signal Output Isolate/De-isolate a release module signal output by address. 1-2-2 1/2/M
Isolate CCM Signal Output Isolate/De-isolate A CCM signal output 1-2-3 1/2/M
Isolate I/O Module Relay Output Isolate/De-isolate a I/O module relay output by address 1-3-1 1/2/M
Isolate CCM Relay Output Isolate/De-isolate CCM relay output 1-3-2 1/2/M
Isolate I/O Module Release Output Isolate/De-isolate an agent release output by output address 1-4-1 1/2/M
Isolate City Tie Output Isolate/De-isolate city tie module by output address 1-5 1/2/M
Isolate Digital Input/Output Isolate/De-isolate digital input/output by I/O address 1-6 1/2/M
Global Isolate Inputs Isolate/De-isolate all system input loop devices; I/O modules 1-7-1 2/M
Global Isolate Outputs Isolate/De-isolate all system output I/O modules 1-7-2 2/M
List Isolated Loop Devices List all Loop Devices which are isolated 2-1-1-1 1/2/M
List Isolated I/O Modules List all I/O modules which are isolated 2-1-2-1 1/2/M
List Isolated CCM outputs List all CCM outputs which are isolated 2-1-2-2 1/2/M
List Event History Lists a user selectable range of event history entries by
2-2-2 1/2/M
Buffer(Range of Events) date
List a Single Detector Displays a selected detectors real time smoke / heat level 2-3-1 1/2/M
List Active Alarm(s) List all active system alarm(s). 2-4-1 1/2/M
List Active Trouble Condition List all active system trouble conditions 2-4-3 1/2/M
List Loop Device Addresses List all loop devices registered into the system 2-6-1 1/2/M
List I/O Module Addresses List all I/O modules registered into the system 2-6-2 1/2/M
List PC Line Voltage Levels Lists PC line voltage levels at each specified loop device 2-7-1 1/2/M
Access
Function Description Formula
Level
Set System Time Allows user to set system time 3-1-1 1/2/M
Set System Date Allows user to set system date 3-1-2 1/2/M
Set Internal Printer Enable port for internal printer connection 3-2-1-1 1/2/M
Disable Internal Printer Disable port for internal printer connection 3-2-1-2 1/2/M
Set External Printer Enable port for external printer connection 3-2-2-1 1/2/M
Disable External Printer Disable port for external printer connection 3-2-2-2 1/2/M
Set Device Address Allows user to change device address. 3-3-1 2/M
Set Ionization Detector Allows user to adjust Ionization detector Prealarm and alarm
3-3-2-1 2/M
Sensitivity settings
Set Photoelectric Detector Allows user to adjust Photoelectric detector Prealarm and alarm
3-3-2-2 2/M
Sensitivity settings
Set Thermal Detector Allows user to adjust Thermal detector Prealarm and alarm
3-3-2-3 2/M
Sensitivity settings
Register Devices Allows user to register loop devices into system configuration 3-3-3 2/M
Blink Control Allows user to disable detector LED blinking 3-3-5 2/M
Set Day/Night Mode Allows user to enable detector for day function. 3-4-1-1 2/M
Set Day / Night Periods Allows user to set Day / Night periods 3-4-1-2 2/M
Activate Day Mode Allows user to activate Day mode 3-4-1-3 2/M
Set 1st level Password Allows user to set 1st level password 3-4-2-1 2/M
Set 2nd level Password Allows user to set 2nd level password. 3-4-2-2 2/M
Enable RTC Program Allows user to enable RTC program line to function 3-4-3-1 2/M
Disable RTC Program Allows user to disable RTC program line from functioning. 3-4-3-2 2/M
Set AutoLearn Mode Allows user to activate the AutoLearn Function 3-4-4 2/M
Allows user to set the alarm verification function and time period
Set Alarm Verification 3-4-5 2/M
for individual detectors or range of detectors.
Set PAS Function Allows user to set the positive alarm sequence for devices 3-4-6 2/M
Clear Event Log Allows user to clear event history buffer entries 3-4-7 2/M
Global Acknowledge Enable Enables the Global Acknowledge Feature 3-8-1 2/M
Global Acknowledge Disable Disnables the Global Acknowledge Feature 3-8-2 2/M
NOTES: 1. For installation in the state of California, Alarm Verification Time must not exceed 30 seconds.
2. 1 = LEVEL ONE, 2 = LEVEL TWO, M = MANUFACTURER LEVEL
Access
Function Description Formula
L evel
Lamp Test Enable user to test system LEDs functionality 4-1 1/2/M
Battery Test Allows user to activate a battery test to verify battery capacity 4-3 1/2/M
Enable Walk Test Allows user to specify a range of devices to Walk Test 4-4-1 2/M
Disable Walk Test Allows user to disable walk test mode 4-4-2
NOTE: 1. WARNING: The Alarm Simulation Test must be used with care. When activated the Alarm Simulation Test (AST)
processes pre-programmed outputs which are related to the activated (simulated) input device. Before using AST ensure
that any associated outputs are disconnected or isolated to prevent unexpected outputs (releases, signals or shutdowns).
2. 1 = LEVEL ONE, 2 = LEVEL TWO, M = MANUFACTURER LEVEL
The system enters trouble mode when it detects an abnormal NOTE: The system has the option to acknowledge both
condition which may prevent proper operation or display a supervisory and common troubles on a global basis.
prealarm condition. (Example: loss of communications with a The panel by default will require that each trouble be
smoke detector.) Refer to Appendix G for a complete list of acknowledged individually. However, if the installer
trouble conditions. wishes to enable this function it can be done by
accessing the "set" menu option using the CCM
2-6.4.1 TROUBLE MODE INDICATIONS keypad. Refer to Table 2-4 for more information on
stepping through the menus to enable and disable the
The following indicates the system is in its trouble mode of Global Acknowledge function. With global acknowledge
operation. a total of 30 troubles can be acknowledged at one time.
a. The yellow TROUBLE LED will be flashing at a 1 second
rate and there will be a pulsing panel buzzer at the CCP.
This audible signal is distinctively different than the alarm
audible signal. 2-7 PRINTING OPERATION
b. The 80 character display will cycle between all currently In addition to the LCD display, the PEGAsys system informa-
active troubles and prealarms. Example: tion can be viewed using the Printer port of the CCM. For de-
tailed information pertaining to connecting a RS-232 peripheral
device, see the Chapter 7, Paragraph 7-18.
When the printer port is enabled and a serial printer is attached
the system will print out all status change information and any
system information lists that the user would request from the
system using the integral keypad.
Serial-type annunciator devices may be connected to the printer
port to provide graphical LED annunciator type indications to
building occupants. Contact Kidde application engineering for
compatible annunciator vendors.
2-6.4.2 TROUBLE MODE USER ACTION
The following steps should be performed when the system is
set into the trouble mode of operation: 2-8 SYSTEM PROGRAMMING
a. To silence the trouble audible signal, all current trouble The PEGAsys fire alarm system incorporates two unique pro-
conditions must be acknowledged by pressing the gramming languages that are easy to understand and use.
ACKLDGE pushbutton. This will silence the system buzzer. These two versatile programming languages, Event Output
b. When all trouble conditions have been acknowledged, the Control (EOC) and Real Time Control (RTC), can accommo-
80-character display will read: XXX ACTIVE TROUBLES date most any fire alarm control logic application. Programming
REMAIN. XXX representing the total number of active the system is accomplished by a personal computer via a sys-
troubles. All current trouble conditions can be viewed on tem interface cable.
the display by pressing the scroll pushbutton.
The two programs are constructed by the system Engineer/In-
NOTE: The first 300 troubles (supervisory or common) on a staller using the PEGAsys Configuration Software (PCS) pro-
Single-Loop will be displayed only. Subsequent troubles gram which is Windows based. The PCS program allows the
or supervisories will not be displayed even if any or all user to configure, verify, upload, download, edit, retrieve, store
300 troubles clear. However, all of the active troubles and print the entire system configuration program. Refer to the
or supervisories will be processed and entered into the PCS users guide (P/N 76-014) for further details.
event buffer. For a complete listing of all troubles and
supervisories over the initial 300, access the event 2-8.1 EOC Programming
buffer using the event buffer using the CCM keypad.
The Event Output Control (EOC) program logically combines the
For the Multi-Loop the first 2100 troubles or
systems input devices with the system's output devices. The pro-
supervisories will be displayed. Subsequent troubles
gram consists of sequentially numbered lines of equations con-
or supervisories over the first 2100 will not be displayed
taining input addresses, output addresses and logic operators.
even if any or all 2100 troubles or supervisories clear.
When an input becomes true (Active), the system processes the
However, all troubles or supervisories regardless of the
EOC program and activates any associated outputs as pro-
total will be processed and entered into the event buffer. grammed.
For a complete listing of all active troubles and
supervisories, access the event buffer through the CCM
keypad.
EXAMPLE: Each line number of the RTC Program is automatically enabled when
entered into the system. Once a line number in the RTC Program
The simplest event output control (EOC) equation would be:
has been disabled using the procedure below, the line will be ignored
Input = Output by the RTC Program until enabled. To enable a line number which
has been previously disabled follow the below procedure selecting
A basic equation with one or more inputs would be : "ENABLE" in step b.
Input Operator Input = Output a. Access the PEGAsys system menus by:
The system normally processes the EOC from left to right. However, (1) Press 0 (zero) key. Verify that the display reads:
in equations with parenthesis the contents of the parenthesis are PLEASE ENTER PASSWORD
executed first. Refer to the PCS users guide (76-014) for further
(2) Type in the Level 1 or Level 2 password.
details.
b. Select the set RTC program by typing the function formula, 3-4-
3. Verify the display reads:
2-8.1.1 LISTING EOC PROGRAMMING
1:ENABLE 2:DISABLE
The system's Event Output Control (EOC) program can be listed
out using either the owner's or installer's menu functions. To list the c. Select the desired choice and press return. Verify the display
systems EOC programming: reads:
a. Access PEGAsys system menus by: RTC LINE NUMBER _ _ _
(1) Press 0 (zero) key. Verify that the display reads: d. Type the three digit line number and press the return key.
PLEASE ENTER PASSWORD e. You may continue with another RTC line or press backspace
(2) Type in the Level 1 or Level 2 password. key to cancel this function.
(3) Press the return () key. Verify that the display reads:
1:ISOLATE 2:LIST 2-8.3 Types of Inputs and Outputs
3:SET 4:TEST The PEGAsys has various input and output devices/modules which
b. Select the list EOC program by typing the function formula, 2-5- are discussed in the following paragraphs:
1.
2-8.3.1 SYSTEM INPUTS
The system will then list all lines of the Event Output Control pro-
gramming on the LCD and any attached printer. Devices which are classified as system inputs are smoke detectors,
heat detectors, and addressable contact monitors (alarm, trouble,
2-8.2 RTC Programming abort, waterflow, manual alarm, manual release, supervisory, and
normal). Refer to the PCS users (76-014) guide for further details.
The RTC program language permits outputs to be controlled by the
systems real time clock. Outputs may be programmed to occur on 2-8.3.2 REMOTE CONTROL UNIT (RCU)
an hour, day, week and month time control basis. Alarm and Prealarm
threshold levels of all or individual detectors can be increased or de- The RCU input and output devices, which are connected to the RX/
creased in sensitivity (within UL limits) under RTC control. The RTC TX loop(s), are specified in EOC programming by the devices four
programming also provides the ability to control RCU relays, I/O digit address.
module Relays and smoke detector pre alarm and alarm set points.
2-8.3.3 RX/TX LOOPS
The program consists of sequentially numbered lines each contain-
ing control object, control content, time, date and day of week. For The system specifies the RX/TX loop controller using its loop num-
further details refer to the PCS users guide. ber followed by three zeros (1000 for RX/TX 1) in single loop sys-
tems and (1000 - 8000) in multi-loop systems. The specifier (1000
2-8.2.1 LISTING RTC PROGRAMMING -8000) will appear in cases when trouble conditions are present on a
particular RX/TX loop controller (i.e., a PC Line Short on RX/TX 1 -
The RTC program can be listed out using either the owners or in- would be displayed as "RX/TX PC Line Short Loop 1").
stallers menu functions. To list the RTC programming:
RX/TX loop (zone) alarms occur if a loop device alarm initiates under
a. Access the PEGAsys system menus by: one of the following conditions:
(1) Press 0 (zero) key. Verify that the display reads:
Failed communications between the CCM and RX/TX module
PLEASE ENTER PASSWORD (Trouble Condition)
(2) Type in the Level 1 or Level 2 password. Failed RX/TX processor. (Trouble Condition)
(3) Press the return () key. Verify that the display reads:
Failed input circuit of RCU device.
1:ISOLATE 2:LIST
An alarmed input device on the RX/TX (in FailSoft mode) can only
3:SET 4:TEST activate EOC programming if the RX/TX zone is used as a pro-
b. Select the list RTC program by typing the function formula, 2-5- grammed input (ZA1=1000, ZA2=2000, ZA8 = 8000, etc.).
2.
The system will then list all lines of the Real Time Control program- 2-8.3.4 SYSTEM OUTPUTS
ming on the LCD and any attached printer. Devices which are classified as system outputs are CCM - sig-
nals and relays (programmable / non programmable); I/O mod-
2-8.2.2 ENABLE/DISABLE RTC PROGRAM LINE NUMBERS ules - signal outputs, relay outputs, agent release outputs, release
RY - Relay Output The system will then list all of the registered I/O module ad-
dresses on the LCD and any attached printer.
CT - City Tie Output
AR - Agent Release Output 2-8.6 Addressing RCUs
RS - Release Signal Output RCUs refer to all devices which connect and operate from the
RX/TX PC (power/communications) Line. These devices include
PS - Power Supply Monitor Module SmartOne smoke detectors, SmartOne heat detectors, addres-
NOTES: sable contact input monitors, and addressable output contact
modules.
1. The I/O modules vary in amount of inputs and outputs. Refer
to section one component description for thorough descrip- Each device has a three digit numeric address. This address is
tions of options. stored in the non-volatile EEPROM memory of the device. The
system address is defined by the CCM by these three digits
2. The PEGAsys system can support a total of 16 I/O modules and a fourth digit representing the RX/TX channel number.
for single loop and 23 I/O modules for multi-loop, 8 maximum of
any one type. There are three ways to address the RCU (Loop) devices.
The RCUs can be addressed using the Hand Held Pro-
3. Power supply monitors only need an address, they have no
grammer (P/N 74-200013-001). This optional unit provides
need for an output number.
a convenient means of addressing RCUs without using the
The I/O module address is set using the three dip switches con- CCM.
tained on each PCB assembly, each module uses different num- The user may address the devices individually on the sys-
bered switches for module address assignment. The address tem by performing the procedure listed below.
is set during the installation procedure by placing the switches
into the correct position. Refer to the appropriate figure in Ap- To address RCUs using the SET RCU Address menu function
pendix I for the particular module you are working with and the each unaddressed RCUs must be connected to the RX/TX PC
addressing matrix. For a functional description of each module, line one at a time. Perform the following steps for each RCU:
refer to Chapter 3. a. Access the PEGAsys system menus by:
The switches would be set for each type of module in order. For (1) Press 0 (zero) key. Verify that the display reads:
example signal modules would be addressed 1 -8 if there were PLEASE ENTER PASSWORD
eight in the system, relay modules would be addressed 1 - 8 if (2) Type in the Level 2 password.
(3) Press the return () key. Verify that the display reads:
1:ISOLATE 2:LIST tion would be to attach all pre addressed loop devices to the PC line
3:SET 4:TEST of the RX/TX module. Power up the system (if it is not already run-
ning). As the loop devices power up they will begin to communicate
b. Select the set RCU address function by typing the function with the RX/TX module. The CCM will recognize the loop devices as
formula, 3-3-1. Verify that the display reads: not being not registered and raise a trouble for each not registered
PRESENT LOOP DEVICE ADDRESS _ _ _ _ (TBL NR) device attached. When the register RCU function is en-
abled the CCM will prompt the user to enter a range of loop device
NOTE: All new addressable devices have an address of zero addresses to register as valid system devices. At the conclusion of
(000). the register function the CCM will display the total amount of devices
registered.
c. Enter the present RCU address and press return
pushbutton. The system will display the following: The AutoLearn function works much the same as the registration
function, where it will automatically enter the devices which it can
TARGET LOOP DEVICE ADDRESS _ _ _ _ identify on the PC line of the RX/TX as not being registered into
d. Enter the desired address for the RCU / Detector, press system configuration memory.
return. The system will now change the RCU address if During both the Autolearn and RCU Registration procedures the
different than previously noted. CCM will automatically register the loop devices into memory and
The 40 character owner location message cannot be entered also set each device to default settings (Sensitivity levels and
using the system keypad. The owners location message can Input reporting) for the particular device. The CCM will also set the
only be entered by use of the PCS program and uploaded into default operation of the CCM outputs (MP01, MP02, MP03 and
system memory. MP04). Any system alarm received after this time will cause all
the CCM outputs (MP01 - MP04) to activate.
2-8.7 Registering RCUs Optionally, if the I/O motherboard and I/O modules have been
installed, the PCS program will need to be used to configure the
Registration is where the device address is joined with the de- system for use with the I/O modules. Procedures for registering I/
vice information in the system's memory. Device information is O modules are provided in the PCS Users Guide (See Address-
comprised of; Device type, Device Messages and Device set- ing I/O Modules).
tings.
There are four ways to register the RCU (Loop) devices on to 2-8.7.1 DETECTOR REGISTRATION
the system. SmartOne smoke and heat detectors would be registered on to
The user may register the devices individually on the sys- the system in the same fashion as the RCUs explained in the
tem previous section. The only other information which requires se-
Register all pre-addressed RCUs at once using RCU (Loop lecting is detection devices application, the alarm and pre-alarm,
Devices) registration function levels and latching or non-latching. There are three specific ap-
plications for smoke detector use: Open Area, Open Area (High
Register all pre-addressed RCUs using the Autolearn func-
Air Flow) and Duct. The smoke and heat detectors pre-alarm and
tion, which sets all devices at default values and any sys-
alarm set points are adjusted only when necessary if the user
tem alarm input activates all system outputs. If pre-addressed
desires the set points to be different from the default values for
devices are used, multiple devices can be attached and reg-
each detector type.
istered to the system all at one time using either the Autolearn
or RCU Registration function. The detectors will use the default values unless otherwise pro-
RCUs can also be registered into the system by using the grammed. To adjust the set points for the detectors, refer to Chapter
PCS program. The installer would specify each RCU to be 5 Setting and Adjusting Smoke and Heat Detector Sensitivities.
connected to the system and then upload the system con- The 40 character owner location message cannot be entered
figuration file to the system and then the system would su- using the system keypad. The owners location message can
pervise each device specified. Refer to the PCS users guide only be entered by use of the PCS program and uploaded into
for further details on RCU registration. system memory.
Active input initiates an alarm at the central control PLEASE ENTER PASSWORD
panel and is latched in the EOC until the system is (2) Type in the Level 1 or Level 2 password.
reset after alarm has cleared. (3) Press the return () key. Verify that the display reads:
2: Trouble 1:ISOLATE 2:LIST
Active input initiates a trouble at the central control 3:SET 4:TEST
panel, but does not latch EOC programming and will b. Select the List RCU address function by typing the function
self restore upon deactivation. formula, 2-6-1. Verify that the display and any attached print-
3: Abort ers list all registered RCU addresses.
Active input initiates an abort condition at the central
control panel. This will delay agent release if count- 2-8.7.5 UN-REGISTERING RCUs
down has begun. It does not latch EOC program and The system provides the capability to remove a single device or
will self restore upon deactivation. There are 4 styles group of devices from the system configuration. This function
of abort available for the device. removes the device address from the system memory but leaves
4: Waterflow the address in the device intact. Performing this operation will
Active input initiates a waterflow alarm condition at the cause the system to generate a trouble NR (Not Registered) for
central control panel and is latched in EOC program any devices which remain connected to the RX/TX PC line.
until reset. Signal outputs will be inhibited from being si- Removal or disconnection of the device(s) from the PC line will
lenced. clear the trouble condition(s) on the system.
5: Manual Alarm This function would be used during a system retrofit where some
Active input initiates a manual alarm condition at the devices may be desired to be removed from the system tempo-
central control panel, latches in EOC program until rarily during a building renovation and then reattached after reno-
reset. vations are complete. This feature is very efficient because the
device maintains its address information which speeds device
6: Manual Release
reregistering after the renovations.
Active input initiates a manual release condition at the
central control panel, causes instant release of pro- To perform the device un-registering operation perform the fol-
grammed output, latches in EOC program until reset lowing:
7: Normal a. Access the PEGAsys system menus by:
Active input initiates a momentary display but does not (1) Press 0 (zero) key. Verify that the display reads:
latch in EOC program, self restores. PLEASE ENTER PASSWORD
8: Supervisory (2) Type in the Level 1 or Level 2 password.
Active input initiates a supervisory trouble at the cen- (3) Press the return () key. Verify that the display reads:
tral control panel, but does not latch the EOC, and will 1:ISOLATE 2:LIST
self-restore upon deactivation. 3:SET 4:TEST
The 40 character owner location message cannot be entered
b. Select the set RCU De-Registration function by typing the
using the system keypad. The owners location message can
function formula, 3-3-4. Verify that the display reads:
only be entered by use of the PCS program and uploaded into
system memory. DEVICE DE-REGISTRATION
DEVICE FROM_ _ _ _TO_ _ _ _
2-8.7.3 REMOTE RELAY REGISTRATION
c. Enter the desired RCU address(s) and press return. The
The addressable contact output device is registered in the display will read the following in response to verify the de-
same fashion as the previous RCU's. vice de-registration:
Contact Output RCUs can also be registered into the system DEVICE DE-REGISTRATION
by using the PCS program. The installer would specify each XX DEVICES DE-REGISTERED
Contact Output RCU to be connected to the system and then d. Verify that the display changes to the device menu after 5
upload the system configuration file to the system and then the seconds. The backspace key can be pressed to return to
system would supervise each device specified. Refer to the PCS the main menu.
users guide (76-014) for further details on RCU registration.
e. To reregister RCU devices, perform the procedure which is out-
The 40-character owner location message cannot be entered lined in the RCU registration paragraph in this chapter.
using the system keypad. The owners location message can
only be entered by use of the PCS program and uploaded into
system memory.
CHAPTER 3
FUNCTIONAL DESCRIPTION
Display
Module
Central
Control RX/TX CCM
Module Comm Receiver/ Power/Comm
Transmitter Line RCU's
24 VDC
Module (Field Devices)
I/O Bus (RX/TX)
AC Line
Power 24 VDC
Battery Supply
Backup I/O Bus I/O Bus
Optional Optional
I/O I/O Module
24 VDC 24 VDC
Motherboard
Display
Module
Central
Control
Module Receiver/
Power/Comm
Transmitter Line RCU's
24 VDC Module
(Field Devices)
I/O Bus (RX/TX)
AC Line Up to 8 RX/TX
Power RX/TX CCM
RX/TX CCM
Modules
Comm
Battery Supply I/O Bus
Comm
Backup
24 VDC Multi-Loop I/O 24 VDC Optional
RX/TX 24 VDC Motherboard I/O Bus I/O Module
24 VDC
See Note 1
Note 1: The trouble relay
SOUNDER 1 SOUNDER 2 VOLT FREE RELAYS V/F RELAY
REP 1
REP 2
A B A B 1 2 FAULT
- + - + - + - + NO NC C NO NC C NO NC C
JP2
PORT
JK5
I/O
Loop Controller
SUPPLY
EARTH
24V 5V 0V
FLT
5V 0V
24V
0V
PLG6
PLG3
PLG2
JK1
JK2
JK3
TB6
Zone 2
Loop Loop
Isolator Isolator
Zone 1 Zone 3
See Note
Loop Loop
76-100005-001
Isolator Isolator
RX/TX
1 2 3 4
RET
RET
24V
24V
LOOP ISOLATOR
Mounted to RX/TX
CPU Reset 74-200012-001
PC Line Normal
Loop Isolator RX/TX
CPU Reset for Style 7
(74-200012-001) Note: Each zone can consist of 30 loop devices
between loop isolators
PC Line Reset
STYLE 7 Signal Line Circuit
Loop Loop
Isolator Isolator
See Note
Zone 2
Loop Loop
Isolator Isolator
Note: Refer to jumper table on Dwg. 06-235371-002 in appendix I
1 1 2 3 4
RET
RET
24V
24V
2
LOOP ISOLATOR
3 Mounted to RX/TX
74-200012-001
4
RX/TX
NOTE: Adjacent loop isolators must be within 20ft. Of a device with wiring in conduit
to be in accordance with NFPA Style 7 requirements.
3-3.3 Power Supply/Charger Assembly, Rev. A The power supply/charger assembly is addressable and com-
municates with the CCM over the I/O bus.
This power supply assembly was provided with earlier systems.
Information is being provided for service purposes only. The The power supply/charger assembly provides terminal connec-
power supply/charger assembly, Figure 3-5 (P/N 76-100009- tions for an auxiliary power module. This module comes with 2
001) is comprised of a printed circuit board (PCB) mounted on different wiring harnesses, as follows:
a AC / DC switching power module. The switching power pro- P/N 76-100009-002 is supplied with a 36" harness that is
vides 4 amps of 24 VDC power from the 120 / 240 VAC input meant to connect a main power supply/charger assembly
power. The PCB assembly is a microprocessor based unit which to the auxiliary power module in the main cabinet.
provides the system with
P/N 76-100009-003 is supplied with an 8" harness to mount
Battery charging (up to 33 AH) and supervision Low Volt- a main power supply/charger assembly to an auxiliary power
age Battery cutoff at 19VDC module in a expansion enclosure.
AC power supervision The addition of an auxiliary power module to the main power
24 VDC supervision supply/charger assembly will provide an additional 4 amps of
Battery load test current and make the total available current of 8 amps for this
assembly. The system can support up to 8 main power supply/
24 VDC ground fault detection (+/-)
charger assemblies with the capability of adding an auxiliary
Trouble relay that transfers upon any power supply trouble power module to each one to provide a maximum available cur-
or power off condition (Relay shown in the unpowered state) rent of 64 amps. Each additional power supply/charger assem-
Auxiliary 24 VDC outputs (programmable for switched or bly (P/N 76-100009-001) would need to have a separate address
unswitched configurations) to operate in the system. The auxiliary power module would
share the same address as the main power supply/charger as-
The auxiliary 24 VDC outputs rated at 1 Amp each and can be
sembly that it is connected to. Refer to drawing number 06-
used to power 4 wire type detection devices such as smoke,
235443-003, in Appendix I, for further installation details.
flame and gas detectors which must be sized properly to stay
within output current limits.
3-3.5 Multi-Loop I/O Motherboard connection located on the motherboard and the loop number and
addresses assigned to the connected module. Refer to Drawing.
The multi-loop I/O motherboard assembly, P/N 76-100017-001, No. 06-235443-012, in Appendix I, for installation details.
is an assembly which can accept any combination of 9 mod-
ules consisting of up to 8 RX/TX modules and provide connec- Table 3-1. Multi-Loop I/O Motherboard Connectors
tions for up to 7 I/O module circuit board assemblies. The ML
motherboard is mounted to standoffs on the back of the main CONNECTOR LOOP ADDRESS
system enclosure. It distributes the system 24 VDC power, CCM-
RX/TX communications modules and I/O bus communications JP1 1 1001-1255
to the I/O modules. The I/O bus communications are provided
by a RJ-12 (flat phone cable) style connection. A single RJ-12
JP2 2 2001-2255
connection connects the ML motherboard to the CCM for RX/ JP3 3 3001-3255
TX communications. The 24 VDC is provided by the system
power supply via a 2 conductor wiring harness connected to a JP4 4 4001-4255
terminal block (TB9) is distributed through terminal blocks (TB1-
TB8) for connection on RX/TXs. The 24 VDC provided by the JP5 5 5001-5255
system power supply via 2 conductor wiring connected to ter-
minal block TB-11 is distributed through I/O bus slots for power- JP6 6 6001-6255
ing I/O modules.
JP7 7 7001-7255
The RX/TX module communicates to the CCM via the multiplexer
located on the motherboard. The CCM identifies each of the in- JP8 8 8001-8255
stalled RX/TX modules by the RS-232 connection on the
motherboard. The table below lists each RX/TX communication
2 STYLE "Z"
5
-
CIRCUIT 1
6
-
10K EOR
7
+
8
+
9
-
{
Reset Switch Module Address 10
CIRCUIT 3
Trouble LED Assignment -
10K EOR
11
76-100003-001
SIGNAL AUD
+
12
+
See Note 2
Auxiliary Power
{ 1 STYLE "Z" AND 2 STYLE "Y"
5
NotUsed -
CIRCUIT 1
TB1 6
-
10K EOR
7
Sounder Circuits 1-4 +
8
+
9
-
10
CIRCUIT 3
-
10K EOR 10K EOR CIRCUIT 4
11
+
12
+
3-3.7 Relay Output Module The auxiliary relays are rated for 2.0 Amp @ 30 VDC & 1.0 Amp
@ 120 VAC. Refer to Drawing. No. 06-235371-007, in Appen-
The PEGAsys panel has the capacity for a maximum of 8 Aux- dix I, for further installation details.
iliary Relay Output cards for up to 32 relays. Each Auxiliary
Relay Output card (shown in Figure 3-9) is equipped with 4 Each relay output can be individually programmed via the PCS
Form C, dry contact relay outputs. The ability to isolate an indi- program for operation. Relation between each relay output and
vidual relay output is accomplished through the system opera- its input source is defined by the panel EOC logic program. In
tor menu. Walk Test mode the relay output circuit(s) will not operate when
the input device(s) under test are activated.
76-100004-001
RELAY
Note: A maximum of 8 Relay Output Modules can be used on the system. Refer to paragraph 1-2.7, in Chapter 1, for other limitations.
Each card is equipped with supervised signaling outputs for 3 Kidde-Fenwal 895630
Style Y 24 VDC polarity reversing type indicating circuits. Each
signal circuit is supervised for open, short and ground fault con- FM Groups A, B, D, E, &
ditions. The ability for individual output isolation is provided Various Manufacturers G
through the system operator menu. Careful consideration of Sprinkler Solenoids
alarm strobe in-rush currents has been made.
Power for standby and alarm operation of release and signaling
The agent release output circuit is rated for 24 VDC control outputs shall derive from one of two sources; 1) primary supply up
devices. Each release output can supervise and activate up to to its capacity, or 2) auxiliary power supply input. Input of auxiliary
two (2) solenoid control heads. power is hardwired through terminals 1 & 2 on the modules termi-
Table 3-2 details all devices with which the agent release mod- nal block. Output circuits are Listed for use in Power Limited appli-
ule is approved for operation. cations. All signaling power is fully regulated.
Module Address
Reset Switch
Assignment
Trouble LED
76-100001-001
RELEASE
See Note 2
Auxiliary Power
1 }
Release Circuits
TB1
Signal Circuits
12
Note 1: Only a maximum of 8 of this type module can be used on the system.
Refer to paragraph 1-2.7, in Chapter 1, for other limitations.
2: W1 and W2 must be cut when the auxiliary power input is used.
3-3.9 City-Tie Module Reverse Polarity-Type Output: Unsupervised output for trip
circuit wiring only, current limited at 100 mA, 24 VDC.
The City Notification Card (Figure 3-11) provides connection and
operation for Local Energy, Shunt type Master Box and Reverse Reverse Polarity output circuits are listed for use in Power Lim-
Polarity styles of output. The output type is selected by choosing ited applications. Refer to Drawing. No. 06-235443-008 for fur-
which terminals terminate the field wiring. The module has an Am- ther installation details.
ber LED to signify disconnect status. The ability for individual out-
The City Tie Module will operate during PEGAsys' FailSoft
put isolate is provided through the system operator menu.
mode. Any system alarm will cause the output to transfer.
Local Energy-Type Output: Monitored output for trip circuit wir-
In Walk Test mode the city notification outputs shall be disabled.
ing and Master Box coil status (Set/Unset), current limited at
In addition, the output has provisions for manual disable or iso-
550 mA, 24 VDC. Monitored for open, short and ground fault.
late through the operator menu function. The initiation of a walk
Shunt-Type Output: Unsupervised contact rated at 5.0 Amp, test will institute a system trouble causing the city tie output to
24 VDC resistive. transfer to the trouble state.
76-100002-001
CITY TIE
Off (not blinking) Trouble condition A unique sensing chamber permits 360 heat entry and re-
sponse. Each detector is electronically addressable and can
The following three paragraphs describe each type of available be fully field programmed. Calibration, device address, pre-alarm
detector. A typical detector is shown in Figure 3-12. & alarm sensitivity set points and drift compensation algorithm
are stored in each detector's nonvolatile memory.
3-3.11 SmartOne Ionization Detectors
SmartOne Heat detectors have an unobtrusive low-profile look
The SmartOne Ionization smoke detectors provide true distrib- and are available using the following:
uted intelligence addressable microprocessor based smoke de- Model THD 7252 SmartOne Heat Detector:
tection to the PEGAsys system. Model CPD-7052 is a dual P/N 70-404001-100
chamber analog ionization type detector which senses both vis-
ible and invisible smoke. A unique sensing chamber permits 3-3.14 Addressable Contact Input Devices
360 smoke entry and response. Each detector is electronically
addressable and can be fully field programmed. Calibration, de- The PEGASYS Contact Monitor (P/N 70-407008-00X) allows
vice address, pre-alarm & alarm sensitivity set points and drift an installer the ability to interface typical NO/NC fire alarm de-
compensation algorithm are stored in each detectors non vola- vices, such as water flow and tamper switches to the PEGAsys
tile memory. system. The contact monitor is also used to interface to the
Manual Alarm, Manual Release and Abort Stations. The ad-
SmartOne Ionization detectors have an unobtrusive low profile dressable contact monitor device is programmable to report in
look and are available using the following: the following manners: Alarm (default), Trouble, Manual Alarm,
Model CPD 7052 SmartOne Ionization Detector: Waterflow Alarm, Manual Release, Abort, Supervisory and Nor-
P/N 70-402001-100 mal (Silent input). Its default setting is alarm when programmed
using the Autolearn function.
3-3.12 SmartOne Photoelectric Detectors
The unit includes a connection for an optional status LED which
The SmartOne Photoelectric smoke detectors provide true dis- allows the device to indicate its present operating status. In nor-
tributed intelligence addressable microprocessor based smoke mal standby mode the LED will flash every 9 seconds, in trouble
detection to the PEGAsys system. Model PSD-7152 is a ana- condition the LED will be extinguished, when activated the LED
log photoelectric type detector which responds to a broad range will flash every 2 seconds.
of smoldering and flaming type fires. A unique sensing cham- Addressable Contact Input Device (NO):
ber permits 360 smoke entry and response. Each detector is P/N 70-407008-001.
electronically addressable and can be fully field programmed.
Calibration, device address, pre-alarm & alarm sensitivity set Addressable Contact Input Device (NC):
points and drift compensation algorithm are stored in each P/N 70-407008-002.
detector's nonvolatile memory.
DATE OF MANUFACTURE:
ASHLAND, MA 01721
SmartOne
INSTRUCTIONS
SEE INSTALLATION
MODEL AO
06-235577-001
The single gang mount unit includes intrinsic status LEDs which
allows the device to indicate in which direction the short condi-
tion is being detected. In normal standby mode the LED will be
Figure 3-14. Addressable Relay Output Device extinguished, in activated condition the LED will be on continu-
ously.
3-3.16 Model DH-2000 Air Duct Housing Loop Isolator RX/TX mount:
P/N 74-200012-001
The DH-2000 air duct housing is designed for detecting par-
ticles of combustion in air handling systems. Upon smoke de- Loop Isolator Stand-alone (Single Gang):
tection the system can be programmed to control a variety of P/N 74-200012-002
devices like HVAC fans and power shut down preventing un- Loop Isolator 6 detector base mount:
necessary damage to the facility. P/N 74-200012-004
CHAPTER 4
MAINTENANCE PROCEDURE
d. Ensure the following LEDs are momentarily lit: 4-3.3 Battery Test
POWER ON ALARM This test allows the user to activate a battery test to verify bat-
TROUBLE SUPERVISORY tery capacity. The step-by-step procedure to perform the bat-
GROUND FAULT PREALARM tery test follows:
CPU ERROR SILENCE a. Access the PEGAsys system menus by:
(1) Press 0 (zero) key. Verify that the display reads:
4-3.2 Loop Device Test
PLEASE ENTER PASSWORD
The PEGAsys system provides a unique detector test function
(2) Type in the Level 1 or Level 2 password.
which allows a user to initiate a test of a detection device through
(3) Press the return () key. Verify that the display reads:
the use of the system menus and verify the detection device(s)
1:ISOLATE 2:LIST
3:SET 4:TEST
b. Press number 4 push-button, verify that the display reads: Heat Detectors:
1:LAMP TEST 2:LOOP DEVICES When testing SmartOne heat detectors use of a low powered
3:BATTERY TEST SCROLL for more heat gun is acceptable. Heat the detector for a minimum of ten
seconds. When a sufficient amount of heat has been detected
c. Press number 3 push-button, verify that the display reads:
by the detector, the control panel will respond with an alarm
BATTERY TEST indication. The status LED of the detector will flash at a 2 sec-
BATTERY TEST ON PS*_ _ ond rate during the alarm period. Take care during the heating
of the detector to avoid over heating the plastic housing. Main-
d. Enter the power supply address which the batteries are
tain a minimum of 1 foot between the detector and the heat gun
connected to. Verify the display reads:
nozzle. Use of open flame devices are not recommended as
BATTERY TEST discoloration of the plastic housing is likely and this is a poten-
TEST ACTIVATED ON PS(_ _) tially hazardous practice.
e. Upon the completion of the test the display will read:
4-3.4.2 WALK TEST PROCEDURE
TEST ON PS(_ _) COMPLETED
The step-by-step procedure to perform the walk test follows:
>_>_ _._V
a. Access the PEGAsys system menus by:
f. Verify that the voltage is within allowable tolerances.
(1) Press 0 (zero) key. Verify that the display reads:
4-3.4 Walk Test PLEASE ENTER PASSWORD
The PEGAsys system provides a one person walk test func- (2) Type in the Level-2 password.
tion. This allows the service person to enable a group of de- (3) Press the return () key. Verify that the display reads:
vices for walk test, then proceed through the installation 1:ISOLATE 2:LIST
activating the specified devices. The system will respond to each 3:SET 4:TEST
activation with a short burst of the programmed signal circuit.
b. Press number 4 push-button, verify that the display reads:
The related signal circuit will only be pulsed if it has been con-
figured for the Walk Test feature when defining it in the PCS 1:LAMP TEST 2:LOOP DEVICES
software. 3:BATTERY TEST SCROLL for more
During the system installation/configuration operation the in- c. Press the SCROLL push-button, verify that the display
staller would need to enable each signal circuit installed in the reads:
system for Walk Test, if desired. The systems signal outputs
4:WALK TEST 5:ALARM SIM TEST
default to walk test disabled. When walk test is activated and
carried out the system enters each activation with a time and d. Press number 4 push-button, verify that the display reads:
date stamp. The operator can then print out all walk test results 1:START WALK TEST 5:STOP WALK TEST
for review.
e. Press number 1 push-button, verify that the display reads:
The walk test feature can be deactivated two ways, the service
person can deactivate it through the user menus or the walk START DEVICE WALK TEST
test function will time out after 10 minutes of non activation en- WALK TEST STARTED ON LOOP( _ _)
suring system response if the service person is called away for f. After completion of the walk test, press number 2 push-
an extended period of time. button to disable the walk test mode.
NOTE: When the walk test is active the panel will annunciate
a trouble condition. 4-3.5 Alarm Simulation Test (AST)
The PEGAsys system provides a feature which allows the sys-
4-3.4.1 WALK TESTING DETECTORS tem installer/inspector to verify the actual output operation in
Place the system in walk test as described in Paragraph 4-3.4.2. relation to the input(s) which are programmed to activate the
To place a detector into alarm perform the applicable proce- output of interest. The service person would enable the AST
dure below: function for a particular input and the system would operate the
output(s) as it is programmed in the Event Output Control pro-
Smoke Detectors: gram. The system will respond with an alarm condition when
When testing SmartOne smoke detectors use a "punk-stick" or the AST feature is enabled. The user would have to disable the
"cotton wick" to generate smoke. Apply smoke to the detector AST when output operation has been verified.
for a minimum of 10 seconds. When a sufficient amount of WARNING
smoke has entered the device, the control panel will respond
with an alarm indication. The status LED of the detector will Any outputs which are controlling critical pro-
flash at a 2 second rate during the alarm period. Use of aerosol cesses or agent releasing should be physically dis-
smoke simulation product may be used if acceptable to the connected from the process or agent container to
Authority having Jurisdiction and if the product is used as di- avoid unwanted shutdowns and/or agent releases.
rected in the instructions. When the AST function is enabled the pre- pro-
grammed outputs for the activated input(s) will
activate.
CHAPTER 5
TROUBLESHOOTING AND CORRECTIVE MAINTENANCE
All service to panel must be done with panel pow- Central Control
ered down to prevent damage to panel compo- 3-3 3-3.1 5-4.2
Module
nents, personnel injury, or both
Receiver/Transmitt-
3-4 3-3.2 5-4.3
er Module RXTX
Addessable Relay
5-2.2 Power Checks 3-12 3-3.13 5-5.4
Output Device
Many faults on the system can be caused by problems with
power. Ensure battery and line voltages are checked prior to Air Duct Housing 3-13 3-3.14 See Manual
troubleshooting the system.
3-14 thru 3-
Loop Isolators 3-3.15
16
Style 6
Jumper Style 4 Style 6 W/Loop Style 7
Isolator
CHAPTER 6
PARTS LIST
6-1 INTRODUCTION
The PEGAsys system parts list, Table 6-1 provides a list of all
repair parts.
SYSTEMS
PEGAsys Control Unit (includes CCM with One RX/TX Module, One Power Supply/ 76-100000-501
Charger Assembly and Enclosure)
PEGAsys Multi-Loop Control Unit (includes CCM with One Multi-Loop 76-100000-600
Motherboard One RX/TX Module, One P.S./Charger Assembly and Enclosure)
MAIN SYSTEM COMPONENTS
Central Control Module (CCM), Single-loop 76-100008-501
Central Control Module (CCM), Multi-loop 76-100008-600
Power Supply/Charger Assembly, includes 4 Amp. P.S., Rev. C. 76-100009-010
RX/TX Module for Single Loop System 76-100005-001
RX/TX Module for Multi-Loop System 76-100005-002
Main Enclosure 76-100000-502
INPUT/OUTPUT MODULES
Agent Release Module 76-100001-001
Signal Output Module 76-100003-001
Relay Output Module 76-100004-001
City Tie Module 76-100002-001
I/O Motherboard for 8 Option Modules 76-100007-001
I/O Multi-Loop Motherboard for up to 8 RX/TX or 7 I/O modules 76-100017-001
POWER SUPPLIES
Power Supply Module, 4 Amp., including 36" Wiring Harness (for main cabinet) 76-100009-002
Power Supply Module, 4 Amp., including 8" Wiring Harness (for expansion cabinet) 76-100009-003
ADDITIONAL COMPONENTS
PEGAsys Expansion Enclosure (order backplane separately) 76-100000-505
Expansion Backplane, for Mounting Motherboard and 4 Power Supplies 76-100000-006
Expansion Backplane, for Mounting 8 Power Supplies 76-100000-007
Expansion Backplane, for Mounting two I/O Motherboards 76-100000-008
Battery Enclosure for Additional Batteries 76-100010-001
Battery 12V, 17AH 06-115915-046
Battery 12V, 33AH 89-100052-001
CHAPTER 7
INSTALLATION
7-1 INTRODUCTION
This chapter provides information necessary to install the PE-
GAsys system. Installation consists of installing a complete sys-
tem. The procedures in this chapter should be accomplished
by technicians familiar with fire alarm system installation and
the requirements of relevant NFPA regulations.
7-3 INSTALLATION PROCEDURE FOR CENTRAL Figure 7-1. CCP Installation Drawing
CONTROL PANEL With the enclosure held by the top two screws place the bottom
The PEGAsys Central Control Panel enclosure is 28 inches high two mounting screws in place. Tighten the screws. Reinstall the
x 18 inches wide x 5 inches deep. It is designed to be surface enclosure door at this time. Care must be taken when installing
or semi-flush mounted using No. 10 or inch hardware. The the door to ensure that the hinge pins are lined up correctly.
type of hardware to be used is at the discretion of the installer
but must be in accordance with good electrical and safety prac-
tices.
7-4 INSTALLATION PROCEDURE FOR
Figure 7-1 shows the enclosures mounting hole layout. The EXPANSION ENCLOSURES
lower set of mounting holes should typically be 44 inches from
the floor in order that the display panel is at a convenient view- The expansion enclosure (P/N 76-100000-505) uses a back
ing height. plate installed in the enclosure to meet various system compo-
nent requirements. The expansion enclosure maintains the
To facilitate mounting the enclosure to its wall position, remove
same outside dimensions as the main system enclosure. There
the enclosures front door. Be sure to disconnect the ground
are three versions of the backplate:
wire before removing the door.
An I/O module cardcage with mounting provisions for up to
To remove the front door, open the door approximately 90 from 4 power supplies
its closed position and lift it up enough to allow the doors hinge
pins to clear their mating hinge sockets located on the left side Mounting provisions for up to eight power supplies
of the Central Control Panel. Two motherboard cardcages for mounting up to 16 I/O mod-
ules in the expansion enclosure.
Place the mounting screws in to the top two holes in the wall.
Leave approximately 1/4 of both screws exposed. Carefully The optional I/O motherboard and I/O modules must be installed
place the two key holes over the screws in the wall. Ensure the prior to the system being powered up. The I/O bus (communi-
enclosure has its door hinge sockets located to the left as you cations) and 24 VDC power are attached to connectors located
face the enclosure. Allow the enclosure to gently come to rest on the I/O Motherboard.
on the screws. Tighten the screws. NOTE: The I/O Bus (RS-485) wiring must be enclosed in
raceway from the main enclosure for a maximum run
of 20 feet, with expansion enclosures located in the
same room as the main enclosure.
Figure 7-2, shows the expansion backplate which provides
mounting for 4 power supplies and one I/O motherboard. Fig-
W2 W3
NO
NC
C
B
A
W4
N
DS1
1
S2
S1
AC OUT
L
N
2
L
1
2
1
2
G
AC IN
N
L
24V
S3
DC IN 1
RET
SHR
RET
AUX 1 AUX 2
24V
RET
R
24V
TB8 TB9
W1
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
W2 W3
NO
NC
C
B
A
W4
N
DS1
1
S2
S1
AC OUT
L
N
2
L
1
2
1
2
G
AC IN
N
L
24V
S3
DC IN 1
RET
SHR
RET
AUX 1 AUX 2
24V
RET
R
24V
TB8 TB9
W1
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
= Back Plate Mounting Studs (7 Locations) 7-5 INSTALLATION PROCEDURE FOR I/O
MOTHERBOARD
Figure 7-2. Back Plate, I/O Motherboard & 4 P.S.
The following paragraph provides the step-by-step procedure
to install a I/O motherboard into a single loop configured sys-
MOTHER BD CCM RS485 KIDDE-FENWAL, INC. ASHLAND, MA 01721
TBL RELAY
tem.
06-129562-001
W2 W3
NO
NC
C
B
A
W4
N
DS1
1
S2
S1
AC OUT
L
N
2
1
2
G
AC IN
N
L
24V
S3
DC IN 1
RET
SHR
RET
AUX 1 AUX 2
24V
sure.
RET
R
24V
TB8 TB9
W1
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
W2 W3
NO
NC
C
B
A
W4
N
DS1
1
S2
S1
AC OUT
L
N
the motherboard.
2
L
1
2
1
2
G
AC IN
N
L
24V
S3
DC IN 1
RET
SHR
RET
AUX 1 AUX 2
24V
RET
R
24V
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
nal TB1.
MOTHER BD CCM RS485 KIDDE-FENWAL, INC. ASHLAND, MA 01721
TBL RELAY
W2 W3
NO
NC
C
B
A
W4
1
S2
S1
AC OUT
L
N
2
L
1
2
1
2
G
AC IN
N
L
24V
S3
DC IN 1
RET
SHR
RET
AUX 1 AUX 2
24V
RET
R
24V
TB8 TB9
W1
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
W2 W3
NO
NC
C
B
A
W4
N
DS1
1
S2
S1
AC OUT
L
N
2
L
1
2
1
2
G
AC IN
24V
S3
DC IN 1
RET
SHR
RET
AUX 1 AUX 2
24V
RET
R
24V
TB8 TB9
W1
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
7-7.2 Relay Output Module e. Set jumpers in accordance with Drawing No. 06-235443-
003 (located in the back of this manual).
The following paragraph provides the step-by-step procedure
to install a relay output module into the PEGAsys system. f. Install module in the desired position on the back plate of
the main or extension enclosure.
a. Remove the relay output module from packing and inspect
g. Insert and tighten the four mounting screws/nuts into the
for physical damage.
four corners of the mounting plate.
b. Set address switches. Refer to Drawing No. 06-235443-
007 in Appendix I for address switch settings. 7-7.7 Power Supply/Charger Assembly, Expansion
c. Install module onto the motherboard. Ensure the connec- Enclosure
tor mates properly.
The following paragraph provides the step-by-step procedure
d. Insert and tighten mounting screws. Refer to appropriate to install a power supply/charger assembly into the expansion
Figure 5-1 or 5-2. enclosure.
7-7.3 Agent Release Module a. Remove the power supply/charger assembly from packing
and inspect for physical damage.
The following paragraph provides the step-by-step procedure
b. Set address switches. Refer to Drawing No. 06-235443-
to install a agent release module into the PEGAsys system.
003 in Appendix I for address switch settings.
a. Remove the agent release module from packing and c. Identify module revision by referring to Figures 3-5 and 3-
inspect for physical damage. 6.
b. Set address switches. Refer to drawing 06-235443- d. Ensure the wiring connections between the switching power
005 in Appendix I for address switch settings. supply (Aux. Power Supply) and monitor module (Main
Power Supply) are accomplished in accordance with the
c. Set switches S3 & S4 for solenoid or initiator activa- appropriate Figure, Figure 7-8 or 7-9.
tion (refer to drawing 06-235443-005 in the back of the
WHT
manual for switch settings). BLK/WHT
RET
SPV
24V
N L N L G N L
attribute ? attribute ? attribute ? attribute ? attribute ?
attribute ?
DC IN 2
RET BLK
RET BLK
attribute ?
7-7.4 City-Tie Output Module MAIN POWER SUPPLY
(76-100009-001)
The following paragraph provides the step-by-step procedure
to install a city tie output module into the PEGAsys system.
a. Remove the agent release module from packing and in-
spect for physical damage.
b. Set module configuration. Refer to drawing 06-235443-008
in Appendix I.
c. Install module on the motherboard. Ensure the connector
mates properly.
d. Insert and tighten mounting screws. Refer to appropriate AUXILIARY POWER SUPPLY
(76-100009-002) WHT
Figure 5-1 or 5-2. BLK/WHT
BLK
RED
RED
The following paragraph provides the step-by-step procedure ORN
AC OUT AC IN DC IN 1 DC IN 2
SHARE
1 2
RET
SPV
RET
SPV
24V
24V
N L N L L N G
attribute ? attribute ? attribute ? attribute ? attribute ? attribute ? attribute ?
Aux. Power
Function M ain Supply
Su p p l y
BLK
Aux. Power Supply Function M ain Supply
BLK
VIO
RED
RED White AC input (Neutral) TB13 (N)
ORN
Figure 7-7. Power Supply/Charger (Rev C), Wiring Diagram Black DC Output (Neg.) TB8 (Ret)
e. Set jumpers in accordance with drawing 06-235443-003
Violet Supervision TB8 (SPV)
(located in the back of this manual).
f. Install module in the desired position on the back plate of Orange Share TB9 (SHR)
the expansion enclosure.
N
1
AC OUT
attribute ?
WHT
N
2
BLK/WHT
attribute ?
L
G
N
L
(76-100009-001) 24V
(76-100009-003)
attribute ?
DC IN 1
RET
SPV
attribute ?
attribute ? attribute ?
RET
RET
24V
SHARE
DC IN 2
ORN
RED
RED
BLK
BLK
Figure 7-8. Power Supply/Charger (Rev A), Wiring Diagram for Expansion Enclosure
N
1
AC OUT
attribute ?
attribute ?
WHT
N
2
BLK/WHT
attribute ?
attribute ?
L
L
N
G
ORN
(76-100009-010) 24V
(76-100009-003)
attribute ?
attribute ?
RED
DC IN 1
RET
SPV
RED
attribute ?
BLK
attribute ?
SHARE
BLK
24V
VIO
attribute ?
attribute ?
DC IN 2
RET
SPV
attribute ?
attribute ?
Figure 7-9. Power Supply/Charger (Rev C), Wiring Diagram for Expansion Enclosure
The connection cable to an external power supply trouble indi- 1:IONIZATION 2:PHOTOELECTRIC
cating device is to be run through a conduit from the indicating 3:THERMAL (<) to return
device to the Central Control Panel. The conduit must be at- c. Select the desired detector style which is to have its sensi-
tached to any convenient Central Control Panel enclosure knock- tivity adjusted. After type selection, the system display:
out. Connect cable to TB1 on the Central Control Panels power
supply PCB as shown in Figure 3-6. SET DETECTOR SENSITIVITY
DETECTORS FROM _ _ _ _ TO _ _ _ _
NOTE: The user would enter the address range of the
detectors to be adjusted. The range can be from 1 to
7-13 DETECTOR INSTALLATION 255. The system will adjust the sensitivity of all the
Refer to the SmartOne Smoke and Heat Detector Installation specified type of detectors which were previously
Sheet (74-212) for installation instructions. Also, refer to Chap- chosen (Ion, Photo or Heat) within the range.
ter 2, Paragraph 2-8.6 for setting addresses and registering d. Press the return pushbutton and the display will read:
RCUs.
SET DETECTOR SENSITIVITY
PREALARM _._ (0.2 -3.0 / FT)
Setting the sensitivity of SmartOne ionization and photoelectric Device Open Area High Velocity
smoke detectors and heat detectors is accomplished by setting Ionization 0.5 - 1.5%/FT 0.5 -1.0 %/FT
the threshold alarm and pre-alarm smoke density levels. The
SmartOne smoke detectors (Ionization and Photoelectric) were Photoelectric 0.2 - 3.5 %/FT 0.2 - 2.0 %/FT
previously programmed for a device application during the reg- Device 50-FT spacing 70-FT Spacing
istration process.
Thermal 80 - 155 F 80 - 145 F
The smoke detectors have specific sensitivities for particular
applications. There are 3 applications which represent the ma-
jority of detector use: Open Area, Open Area (High AirFlow) e. This prompt asks the user for the Pre-alarm level for the
and Duct. detector(s) to be set. Key in the desired pre alarm level
and press the return key. After pressing return the display
The sensitivity adjustment is accomplished in one of two ways:
will read:
1. Smoke & Heat Detector Configuration. During the SET DETECTOR SENSITIVITY
process of configuring the system using the PCS program, the
ALARM _._ (0.5 -3.0 / FT)
operator selects the application of the detector and adjusts the
settings of the alarm and pre-alarm values within the range for
the application chosen, or accept the default values for the ap-
TOLERANCE RANGE
plication.
2. Level Setting Operation. This procedure is selected Device Open Area High Velocity
from the menus. This method is generally used for systems Ionization 0.5 - 1.5%/FT 0.5 -1.0 %/FT
which have been installed and operational for a period of time.
It should only be used if there is a need to change the sensitiv- Photoelectric 0.5 - 3.5 %/FT 0.5 - 2.0 %/FT
ity of the device.
APPENDIX A
POWER SUPPLY REQUIREMENTS
AuxiliaryPower
Supply or ( ) X 1.9 =
Module
NOTE: Each main power supply and power supply module added to the system would increase the AC requirement
by 1.9 Amps (max.)
Table A-2: AC Branch Circuit Requirements (220 VAC)
AuxiliaryPower
( ) X 0.95 =
supply
NOTE: Each main power supply and power supply module added to the system would increase the AC requirement
by 0.95 Amps (max.)
NOTE: Use Table A3 (Standby or non-alarm) to determine main system power supply and any installed auxiliary power module
standby current requirements.
Maximum
Standby Module /
Module / Device Standby
Current(Amps) System
Current (Amps)
Central Control Module 0.070 X 1 = 0.070
RXTX module 0.035 X =
Power supply Monitor 0.060 X =
Auxiliary Output 1, Max 1.5A (See
X =
Notes 1 & 2)
Auxiliary Output 2, Max 1.5A (See
X =
Notes 1 & 2)
Multi-Loop Mother Board 0.035 X =
Signal Audible Output Module 0.025 X =
Relay Output Module 0.010 X =
City Tie Output Module 0.030 X =
Agent Release Output Module 0.065 X =
FIELD DEVICES X =
Ionization Detector 0.000400 X =
Photoelectric Detector 0.000405 X =
Addressable Contact Input 0.000310 X =
Addressable Contact Output 0.000330 X =
Loop Isolators 0.001 X =
Sum Column for
Standby Load = Amps
(Notes 2)
NOTE: 1. Auxiliary Outputs and each must be considered for total standby alarm loading of the system power supply.
2. Use of auxiliary 24 VDC outputs of during standby operation must not cause the calculated standby current of the
system to exceed its rated maximum as defined in the Table A-6.
NOTE: 1. Central Control Module (CCM) Alarm condition power requirements must be evaluated for loading of the signaling
devices. Each signal circuit can provide up to 2 amps of 24 VDC power for signaling device use.
2. Auxiliary Outputs would have to be considered for total alarm loading of the system power supply.
3. Each Signal output modules alarm condition power requirements must be evaluated for loading of the signaling
devices. Each signal circuit can provide up to 2 amps of 24 VDC power for signaling device use. There are a total of 4
signal circuits per module.
4. Each Agent Release module contains three signaling circuits which must be evaluated for loading. Each signal circuit
will provide up to 2 amps of 24 VDC power for signaling device use. There are a total of 3 signal circuits per module.
5. When using constant power solenoids, the current draw of the solenoid must be added in the calculation. Momentary
solenoids and initiators are negligible in there current draws and do not need to be added into the total calculation.
Total AH Required
(Original AH required + =
Derating Factor)
NOTE: 1. Main system enclosure can house up to (2) 33 AH batteries (P/N 89-100052-001). If an auxiliary power module is added to the
system the batteries must be moved to a separate battery box or secondary enclosure, if used.
2. NFPA 72 - 1996 Protected Premises or Proprietary fire alarm systems require 24 hours of standby power followed by 5
minutes alarm activation.
3. NFPA 72 - 1996 Auxiliary or Remote Station require 60 hours of standby power followed by 5 minutes alarm activation.
4. NFPA 72 - 1996 allow 4 hours of standby battery capacity if there is an automatic starting engine driven generator.
5. NFPA 12, 12A, 12B require 24 hours of standby and five minutes of alarm activation.
6. Factory Mutual requires Pre-action and Deluge systems to have 90 hours of battery standby and 10 minutes of alarm activation.
12 Ah (4 hours) 2.5
17 Ah (4 hours) 3.6
Auxiliary
(0) X 1.9 = 0
Power Supply
Main Power Supply Loading Examples: This example is based on the same system as above. Refer to Paragraph
A-2 for additional information.
Standby or Non-Alarm Power Requirement Calculation
Maximum
Standby Module /
Module / Device Standby
Current(Amps) System
Current (Amps)
Central Control Module 0.070 X 1 = 0.070
RXTX module 0.035 X 2 = 0.070
Power supply Monitor 0.060 X 1 = 0.060
Auxiliary Output 1, Max 1.5A X =
Auxiliary Output 2, Max 1.5A X =
Multi-Loop Mother Board 0.035 X 1 = 0.035
Signal Audible Output Module 0.025 X 2 = 0.050
Relay Output Module 0.010 X 1 = 0.010
City Tie Output Module 0.030 X =
Agent Release Output Module 0.065 X 1 = 0.065
FIELD DEVICES
Ionization Detector 0.000400 X 10 = 0.004
Photoelectric Detector 0.000400 X 20 = 0.008
Heat Detector 0.000400 10 0.004
Addressable Contact Input 0.000310 X 6 = 0.0024
Addressable Contact Output 0.000330 X 4 = 0.0016
Loop Isolators 0.001 X =
Sum Column for
Standby Load
= 0.380 Amps
Battery Size Requirement Calculation Example: This example is based on the same system as above. Refer to Paragraph A-4
for additional information.
Total AH Required
(Original total AH
= 10.24
required + Derating
Factor)
APPENDIX B
SYSTEM EXPANSION
SHR
RET
24V
N L N L G N L
The system will support up to 16 I/O modules for single loop and DS1 SHR
TB9
DC IN 2
24V
TBL RELAY
NO RET
TB8
C RET
NC
W1
module. The system power supply monitor module can super-
F1
ASHLAND, MA 01721
W2 W3
KIDDE PEGAsys
TP4
vise two power supply units (4 amps each for a total of 8 amps
+
BAT
RS485 KIDDE-FENWAL, INC.
-
S3
TP3
2
S1
1
SYSTEM POWER
R RET
24V
MOTHER BD CCM
The following diagrams will demonstrate the available ways of
R RET
24V
RET
RET
RET
24V
24V
06-129562-001 AUX 1 AUX 2
Figure B-1 shows the single loop PEGAsys system (P/N 76-
100000-501). This includes the Central Control Module (CCM),
Receiver/Transmitter (RX/TX) module, Power Supply/Charger
assembly and the system enclosure. The basic system can be
expanded as shown in the following sections
AC OUT AC IN DC IN 1
1 2
SHR
RET
24V
N L N L G N L
DS1 SHR
TB9
DC IN 2
24V
TBL RELAY
NO RET
TB8
C RET
NC
W1
F1
ASHLAND, MA 01721
W2 W3
KIDDE PEGAsys
TP4
+
BAT
RS485 KIDDE-FENWAL, INC.
-
S3
TP3
2
S1
1
W4
2
S2
1
A
B 24V
SYSTEM POWER
R RET
24V
MOTHER BD CCM
R RET
24V
RET
RET
RET
24V
24V
AC OUT AC IN DC IN 1
1 2
SHR
RET
24V
N L N L G N L
06-129562-001
W2 W3
NO
NC
C
B
A
DS1 SHR
AC OUT AC IN DC IN 1
TB9
DC IN 2
24V
1 2
SHR
RET
24V
W4
N L N L G N L
TBL RELAY
NO
N
RET
DS1
TB8
1
S2
S1
AC OUT
C
L
RET
N
NC
2
L
1
2
1
2
G
AC IN
N
L
SHR
W1
DS1
F1
24V
TB9
S3
DC IN 1
DC IN 2
RET
24V
ASHLAND, MA 01721
W2 W3
SHR
TBL RELAY
NO RET
RET
AUX 1 AUX 2
TB8
24V
C RET
KIDDE PEGAsys RET
R
TP4
24V
NC TB8 TB9
W1
+
BAT
RS485 KIDDE-FENWAL, INC.
-
S3 TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
TP3
BAT F1
SYSTEM POWER DC IN 2
2
S1
1
W1
F1
W4
2
S2
1
ASHLAND, MA 01721
A
W2 W3
B 24V
SYSTEM POWER
R RET MOTHER BD CCM RS485 KIDDE-FENWAL, INC. ASHLAND, MA 01721
TBL RELAY
06-129562-001
W2 W3
24V
MOTHER BD CCM
NO
NC
KIDDE PEGAsys
C
B
A
R RET
TP4
24V
W4
N
RET
DS1
1
S2
S1
AC OUT
L
+
N
BAT
RS485 KIDDE-FENWAL, INC.
2
-
L
1
2
1
2
G
S3
AC IN
RET
N
RET
24V
24V
TP3
L
06-129562-001 AUX 1 AUX 2
2 24V
S3
DC IN 1
S1 RET
1
SHR
RET
W4
AUX 1 AUX 2
2 24V
S2
1 RET
R
24V
TB8 TB9
W1
B 24V
SYSTEM POWER
R RET TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
24V
MOTHER BD CCM
R RET
24V
RET
RET
RET
24V
24V
06-129562-001 AUX 1 AUX 2
AC OUT AC IN DC IN 1
1 2
SHR
RET
24V
N L N L G N L
06-129562-001
W2 W3
NO
NC
C
SHR
B
A
DS1
TB9
DC IN 2
24V
TBL RELAY
NO RET
W4
TB8
N
DS1
C
1
RET
S2
S1
AC OUT
L
NC
N
2
L
1
2
1
2
G
AC IN
N
used to charge a common set of batteries. All other power
W1
F1
L
24V
S3
DC IN 1
ASHLAND, MA 01721
RET
W2 W3
SHR
RET
AUX 1 AUX 2
KIDDE PEGAsys
24V
TP4
RET
R
24V
+ TB8 TB9
BAT
RS485 KIDDE-FENWAL, INC.
W1
-
S3
TP3
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
supply/charger assemblies could be connected to the com-
2 F1
S1 BAT DC IN 2
1 SYSTEM POWER
W4
2
S2
1
A
B 24V
SYSTEM POWER
R RET
MOTHER BD CCM
MOTHER BD CCM TBL RELAY
06-129562-001
W2 W3
R
NO
RET
NC
C
B
A
24V
RET
W4
N
DS1
1
S2
S1
AC OUT
L
N
2
L
1
2
1
2
RET
RET
24V
G
24V
AC IN
06-129562-001
N
AUX 1 AUX 2
L
24V
S3
DC IN 1
RET
SHR
RET
AUX 1 AUX 2
24V
R
24V
TB8 TB9
W1
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
06-129562-001
W2 W3
NO
NC
C
B
A
W4
N
DS1
1
S2
S1
AC OUT
L
N
2
L
1
2
1
2
G
AC IN
N
ing capacity of the main power supply.
L
24V
S3
DC IN 1
RET
SHR
RET
AUX 1 AUX 2
24V
RET
R
24V
TB8 TB9
W1
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
06-129562-001
W2 W3
NO
NC
C
B
A
W4
N
DS1
1
S2
S1
AC OUT
L
N
2
L
1
2
1
2
G
AC IN
N
L
24V
S3
DC IN 1
RET
SHR
RET
AUX 1 AUX 2
24V
RET
R
24V
TB8 TB9
W1
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
AC OUT AC IN DC IN 1
1 2
SHR
RET
24V
N L N L G N L
W2 W3
NC
C
B
A
NO
NC
C
SHR
B
A
DS1
TB9
DC IN 2
24V
W4
TBL RELAY
NO
N
RET
W4
DS1
TB8
1
S2
S1
N
AC OUT
DS1
C
L
1
RET
S2
S1
AC OUT
L
N
NC
2
N
L
2
L
1
2
1
2
G
AC IN
1
2
1
2
G
N
AC IN
N
L
W1
F1
24V
L
S3
DC IN 1
24V
RET
S3
DC IN 1
ASHLAND, MA 01721
RET
W2 W3
SHR
RET SHR
AUX 1 AUX 2
RET
AUX 1 AUX 2
24V
R
TP4
24V
RET
R
W1
-
S3 TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
TP3
F1 TP3 TP4
RET
BAT
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
SYSTEM POWER DC IN 2
2 F1
S1 BAT DC IN 2
1 SYSTEM POWER
W4
2
S2
1
A
B 24V
SYSTEM POWER
W2 W3
24V RS485 KIDDE-FENWAL, INC. ASHLAND, MA 01721
MOTHER BD CCM
06-129562-001
C
B
A
W2 W3
R
NO
RET
NC
C
B
A
24V
W4
RET
DS1
W4
S2
S1
AC OUT
L
N
DS1
1
S2
S1
AC OUT
N
L
2
L
N
2
1
2
1
2
L
AC IN
1
2
1
2
RET
N
RET
24V
G
24V
AC IN
L
06-129562-001
N
AUX 1 AUX 2
24V
S3
DC IN 1
RET 24V
S3
DC IN 1
SHR RET
RET
AUX 1 AUX 2
SHR
24V
RET
AUX 1 AUX 2
RET
24V
R
24V RET
TB8 TB9
R
W1 24V
TB8 TB9
W1
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2 TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
W2 W3
NO
NC
C
B
A
W4
N
DS1
1
S2
S1
AC OUT
L
N
2
L
1
2
1
2
G
AC IN
N
L
24V
S3
DC IN 1
RET
SHR
RET
AUX 1 AUX 2
24V
RET
R
24V
TB8 TB9
W1
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
W2 W3
NO
NC
C
B
A
W4
N
DS1
1
S2
S1
AC OUT
L
N
2
L
1
2
1
2
G
AC IN
N
L
24V
S3
DC IN 1
RET
SHR
RET
AUX 1 AUX 2
24V
RET
R
24V
TB8 TB9
W1
TP3 TP4
RET
RET
24V
SHR
RET
24V
RET
24V
RET
24V
-
+
BAT F1
SYSTEM POWER DC IN 2
APPENDIX C
RELEASING APPLICATIONS
The PEGAsys system can be used for agent release, leasing. For complete details refer to the PCS users guide.
pre-action, sprinkler and deluge sprinkler control applications. The following features are supported for releasing functions,
When used with UL listed, compatible actuating and initiating with which the system will be compatible.
devices, the PEGAsys system meets the requirements of the
following standards:
NFPA 12 CO2 Extinguishing Systems (High Pressure)
C-2 ABORT
NFPA 12A HALON 1301 Extinguishing Systems
The abort function is a feature which manually stops a discharge
NFPA 13 Sprinkler Systems time delay. The PEGAsys supports four styles of aborts, as listed
in Table C-1.
NFPA 15 Water Spray Systems
NFPA 16 Foam-Water Deluge and Foam-Water Spray
Systems
NFPA 17 Dry-Chemical Extinguishing Systems
C-3 DELAY
NFPA 17A Wet-Chemical Extinguishing Systems The time delay period is an installer programmable value which
begins to count down after alarm activation of an initiating
NFPA 2001 Clean-Agent Fire Extinguishing Systems device(s) which is protecting the protected area and mapped to
the agent-release output. The time delay can be programmed
for activation after one or two alarm occurrences.
C-1 PROGRAMMING
The PEGAsys system can support up to nine independently
C-4 SOAK
controlled releasing outputs (AR1 - AR8 and MP1), which are
used to control releasing functions. AR1 - AR8 are the agent The soak function is used to automatically shut off the releas-
release I/O modules, which are inserted into the I/O motherboard ing solenoid at a predetermined time after the mapped inputs
and MP1 is the CCM releasing output, which is optionally pro- activate them. It may be programmed as a 10 minute or 15 minute
grammable to be a signal release output. The PCS program is soak period. This soak function is for use in NFPA 16 applica-
used to program the system for all functions including the re- tions only.
Underwriter Laboratories Delay timer continues to count down upon abort activation, and stops at 10
(UL)(Complies with UL second mark until release of abort switch. Upon release of abort switch,
864) timer resumes the countdown starting at 10 seconds.
Industrial Risk Insurers Functions in similar manner to the UL-type abort, with the only exception
(IRI)(Complies with UL that the abort will only function if held prior to the receipt of the second
864) alarm.
Operation of the abort switch, once an alarm exists, changes the delay timer
to the selected delay plus an additional 90 seconds. The timer will not start
New York City
as long as the abort switch is held. Release of the abort switch continues
the countdown from the initial value plus the 90 seconds additional delay.
Once the delay timer has started, operation of the abort switch restores the
Local Jurisdiction timer to its original value. The delay timer will not start as long as the abort
switch is held. Release of the abort switch continues the countdown.
NOTE: The abort function will not work if a time delay value is not entered in the EOC programming for the hazard. Maximum
allowable delay is 60 seconds as allowed by UL864. The abort input is not intended to be used for a service disconnect.
(+) (+)
PC Line PC Line
(-) (-)
In Out
PUSH / HOLD
Remote LED
(Optional)
.
10K ohms
P/N 06-129025-003
8 7 6 5 4 3 2 1
(+) (-) (+) (-) A B (+) (-)
PC PC PC PC SW SW LED LED
DATE OF MANUFACTURE:
FOR SERVICE SEND TO:
SmartOne TM
KIDDE-FENWAL, INC.
CAT. NO. 70-407008-001
ASHLAND, MA 01721
MODEL AI, N/O
INSTRUCTIONS
SEE INSTALLATION
06-235578-001
NOTE: The 10-K ohm resistor must be connected across the abort station contacts for supervision.
Failure to install this resistor will result in a "Trouble Open" message for that monitor.
(+) (+)
PC Line PC Line FIRE FIRE
(-) (-)
In Out ALARM ALARM
Remote LED
(Optional) PUSH
.
10K ohms
8 7 6 5 4 3 2 1
P/N 06-129025-003
PULL
(+) (-) (+) (-) A B (+) (-)
PC PC PC PC SW SW LED LED
ALL TERMINALS ARE POWER LIMITED
MAX. INSTALL. TEMP. 120F
DATE OF MANUFACTURE:
FOR SERVICE SEND TO:
SmartOne TM
KIDDE-FENWAL, INC.
CAT. NO. 70-407008-001
ASHLAND, MA 01721
MODEL AI, N/O
INSTRUCTIONS
SEE INSTALLATION
06-235578-001
APPENDIX D
APPENDIX E
FACTORY MUTUAL SPRINKLER REQUIREMENTS
FOR
PRE-ACTION AND DELUGE TYPE SPRINKLER SYSTEMS
APPENDIX F
GLOSSARY
Internal Identifier Symb ol s th at are u sed to n ame or id en tify a comb in ation of in p u ts.(For
(I001 - I255) examp l e 1001 + 1004= I001).
An op tion al assemb l y, l ocated in th e Cen tral Con trol Pan el , th at h as th e
cap acity for eig h t Ou tp u t Mod u l es. Typ ical Ou tp u t Mod u l es are Rel ay, Sig n al
I/O M otherboard
Au d ib l e, Ag en t Rel ease, Dig ital In p u t or Ou tp u t an d In tel l ig en t In terface
Mod u l e.
A set of b ran ch es formin g a cl osed cu rren t p ath p rovid ed th at th e omission of
Loop
an y b ran ch el imin ates th e cl osed p ath .
A d evice wh ich p rovid es p rotection ag ain st wire to wire sh ort con d ition s on th e
Loop Isolators
RX/TX PC l in e. Con forms to (NFPA Styl e 7.0)
M ulti drop Line Lin e or circu it in tercon n ectin g several d evices from a cen tral p oin t.
M ultiplex Th e u se of on e tru n k or p air of wires to commu n icate with on e or more d evices.
(Per NFPA-72) Th e PEGAsys al l ows 255 d evices to commu n icate on on e tru n k.
Smart d evices or smoke d etectors may b e ord ered with an op tion al rel ay th at
Optional Relay can con trol extern al d evices su ch as el evators an d n on -emerg en cy p rocess
con trol .
Ou tp u t Mod u l es, l ocated in th e Cen tral Con trol Pan el en cl osu re, p rovid e real
Output M odule worl d ou tp u t cap ab il ity from th e Cen tral Con trol Mod u l e. Typ ical mod u l es are:
Rel ay an d Sig n al Au d ib l e.
Memory l ocation s th at are p rog rammab l e b y th e own er to store a 40 ch aracter
Owner Locations
al p h an u meric d escrip tion of th e l ocation of th e fire d etection d evice.
Power an d commu n ication wires orig in atin g from th e RX/TX Mod u l e. Al so
PC Line
cal l ed Sig n al Lin e Circu it (SLC).
An Ou tp u t Mod u l e l ocated in th e Cen tral Con trol Pan el en cl osu re th at
in terfaces with au xil iary eq u ip men t. Each mod u l e con tain s fou r in d ivid u al
Relay Output M odule
p rog rammab l e SPDT 2 Amp 24 VDC rel ays. A total of eig h t Rel ay Ou tp u t
Mod u l es may b e u sed in th e system for a total of 32 circu its.
An ad d ressab l e or smart fiel d d evice th at p rovid es a rel ay con tact to con trol a
Relay Output RCU
d evice su ch as a fan . Typ ical l y mou n ts in a 4 in ch sq u are el ectrical b ox.
Remote Control Unit
An ad d ressab l e or smart fiel d d evice.
(RCU)
Th e Receiver / Tran smitter mod u l e is l ocated in th e Cen tral Con trol
RX/TX M odule Pan el en cl osu re an d fu n ction s as a d ata tran smission in terface b etween th e
Cen tral Con trol Mod u l e an d remote con trol u n its - (RCUs).
An ou tp u t mod u l e, l ocated in th e Cen tral Con trol Pan el en cl osu re, th at
Signal Audible Output p rovid es fou r Styl e Z or Styl e Y, 24 V, 2 Amp p ol arized sig n al circu its. Al l
M odule circu its are su p ervised for an op en or sh ort con d ition . A maximu m of eig h t
mod u l es with 32 circu its may b e in stal l ed in th e PEGAsys system.
Smart smoke d etectors (ion ization or p h otoel ectric) measu re smoke l evel every
9 secon d s with in th eir smoke sen sin g ch amb er. After in itail l y d etectin g smoke
Smart SmokeDetector th e d etector en ters an al ert state wh ere it measu res smoke con cen tration every
2 secon d s. If th e d etector d etects smoke th ree ou t of fou r samp l es, it sen d s a
p re-al arm or al arm statu s to th e Cen tral Con trol Pan el .
A d evice with th e featu res of an ad d ressab l e d evice b u t ad d ition al l y h as th e
comp u tin g p ower to make al arm d ecision s b ased on stored cal ib ration an d
Smart Device en viron men tal d ata, an d con d ition of th e d etector. Al so th e d evice tran smits
an d receives an al og val u es. Examp l es wou l d b e p h otoel ectric or ion ization
d etectors.
A d evice with ou t th e el ectron ics n ecessary to tie d irectl y to th e mu l tip l ex tru n k.
Standard Fire Alarm
It req u ires an ad d ressab l e in p u t or ad d ressab l e ou tp u t d evice to in terface with
Device
th e PEGAsys system. (ie..con ven tion al smoke an d h eat d etectors)
A code on the display that identifies an RCUs status. There are eight field
State programmable states a RCU may be programmed to: Alarm, Trouble, Abort,
Manual Alarm, Manual Release, WaterFlow, Supervisory and Normal.
Provides primary and secondary system power. Stand-by batteries, provide DC
System Power
voltage to the Power Supply in the event of an AC power failure. The stand-by
Supply
batteries are located in the Central Control Panel enclosure.
T-TAP See Multi drop Line. Only allowable in Style 4 configuration.
Trouble Relay A non programmable relay which operates during any system trouble condition.
A message on LCD display that identifies the type of device reporting. The
Type
message identifies Smoke & Heat detectors and Input and Output RCU devices.
Variable Identifier See Internal Identifier (I001-I255).
This timer senses abnormality in the Central Control Modules CPU. If the CPU is
M odule Watch Dog
operating normally, it periodically resets the timer. If the timer is not reset, it times
Timer
out and indicates a CPU error.
%/FT Percent of smoke obscuration per foot of light.
APPENDIX G
DISPLAY ABBREVIATIONS
APPENDIX H
INDEX
Subject Page Paragraph
A
Accessing the System Menus .......................................................................... 2-4 ................................................... 2-5.2
Active Alarm Mode ............................................................................................ 2-5 ................................................... 2-6.2
Active Supervisory Trouble Mode ..................................................................... 2-10 ................................................. 2-6.3
Active Trouble Mode ......................................................................................... 2-11 ................................................. 2-6.4
Addressable Contact Input Device Installation .................................................. 7-11 ................................................. 7-15
Addressable Contact Input Devices ................................................................. 1-5, 3-11 .......................................... 1-2.11,3-3.14
Addressable Contact Monitor Registration ....................................................... 2-14 ................................................. 2-8.7.2
Addressable Relay Output Device Installation .................................................. 7-11 ................................................. 7-16
Addressable Relay Output Devices .................................................................. 1-5, 3-12 .......................................... 1-2.12, 3-3.15
Addressing I/O Modules ................................................................................... 2-13 ................................................. 2-8.4
Addressing RCUs ............................................................................................. 2-13 ................................................. 2-8.6
Agent Release Module ...................................................................................... 3-9, 7-4 ........................................... 3-3.8, 7-7.3
Agent Release Output Module .......................................................................... 1-4 ................................................... 1-2.7.3
Alarm Mode Indications .................................................................................... 2-5 ................................................... 2-6.2.1
Alarm Mode User Action ................................................................................... 2-5 ................................................... 2-6.2.2
Alarm Simulation Test (AST) ............................................................................ 4-2 ................................................... 4-3.5
Arming Release Circuits .................................................................................. 4-3 ................................................... 4-4.2
AST Procedure ................................................................................................. 4-3 ................................................... 4-3.5.1
Audible Device .................................................................................................. 2-2 ................................................... 2-2.2
B
Basic Motherboard ........................................................................................... 1-2 ................................................... 1-2.5
Batteries ........................................................................................................... 7-6 ................................................... 7-9.2
Battery Enclosure ............................................................................................. 7-6 ................................................... 7-9.1
Battery Test ...................................................................................................... 4-1 ................................................... 4-3.3
C
Central Control Module (CCM) .......................................................................... 1-1, 3-2, 5-2 .................................... 1-2.1, 3-3.1, 5-4.2
City Tie Module ................................................................................................. 1-4, 3-10 .......................................... 1-2.7.4, 3-3.9
City Tie Output Module ..................................................................................... 7-4 ................................................... 7-7.4
Component Description .................................................................................... 1-1 ................................................... 1-2
Connecting a Printer ......................................................................................... 7-11 ................................................. 7-18.2
Connecting a Terminal or Personal Computer .................................................. 7-11 ................................................. 7-18.1
Connecting AC Power ...................................................................................... 7-6 ................................................... 7-8
Connection of Peripherals ................................................................................ 7-11 ................................................. 7-18
Control and Indicator Description ..................................................................... 2-2 ................................................... 2-2.3
Control and Indicators ...................................................................................... 2-1 ................................................... 2-2
D
Default Passwords ........................................................................................... 2-2 ................................................... 2-3.2
Detector Installation .......................................................................................... 7-10 ................................................. 7-13
Detector Registration ....................................................................................... 2-14 ................................................. 2-8.7.1
Disarming and Rearming Release Circuits ...................................................... 4-3 ................................................... 4-4
Disarming Release Circuits ............................................................................. 4-3 ................................................... 4-4.1
Display Control Card (DCC) .............................................................................2-12 ................................................. 2-8.3.3
Display Module ................................................................................................. 1-1 ................................................... 1-2.2
INDEX (Cont.)
E
Enable/Disable RTC Program Line Numbers ................................................... 2-12 ................................................. 2-8.2.2
Entering Passwords ......................................................................................... 2-2 ................................................... 2-3.3
EOC Programming .......................................................................................... 2-11 ................................................. 2-8.1
Exiting the System Menus ................................................................................ 2-4 ................................................... 2-5.3
External Power Failure Indicator Connection .................................................... 7-10 ................................................. 7-12
F
Field Device Connection to RX/TX Module ....................................................... 7-7 ................................................... 7-10
Field Devices .................................................................................................... 3-11, 5-3 .......................................... 3-3.10, 5-4.4
Functional Descriptions .................................................................................... 3-2 ................................................... 3-3
I
Input/Output Modules ........................................................................................ 1-3 ................................................... 1-2.7
Install and Connect DC Power ......................................................................... 7-6 ................................................... 7-9
Installation Checkout ........................................................................................ 7-11 ................................................. 7-17
Installation Procedure for Central Control Panel ............................................... 7-1 ................................................... 7-3
Installation Procedure for Expansion Enclosures ............................................. 7-1 ................................................... 7-4
Installation Procedure for I/O Motherboard ....................................................... 7-2 ................................................... 7-5
Installation Procedure for RX/TX Module .......................................................... 7-2 ................................................... 7-6
Installation Procedure for I/O Module ................................................................ 7-3 ................................................... 7-7
Intelligent Loop Devices .................................................................................... 1-4 ................................................... 1-2.9
Isolate Menu Function ....................................................................................... 2-4 ................................................... 2-5.4.1
L
Lamp Test ......................................................................................................... 4-1 ................................................... 4-3.1
LCD Display ..................................................................................................... 2-1 ................................................... 2-2.1
Levels of Security ............................................................................................. 2-2 ................................................... 2-3.1
List Menu Function ........................................................................................... 2-4 ................................................... 2-5.4.2
Listing all Registered RCUs .............................................................................2-15 ................................................. 2-8.7.4
Listing EOC Programming ...............................................................................2-12 ................................................. 2-8.1.1
Listing I/O Module Assignment ......................................................................... 2-13 ................................................. 2-8.5.1
Listing RTC Programming ................................................................................2-12 ................................................. 2-8.2.1
Loop Device Test .............................................................................................. 4-1 ................................................... 4-3.2
Loop Isolator Devices ....................................................................................... 1-6 ................................................... 1-2.14
Loop Isolator Devices ....................................................................................... 3-12 ................................................. 3-3.17
M
Maintenance Procedures ................................................................................. 4-1 ................................................... 4-3
Materials Required for Installation ..................................................................... 7-1 ................................................... 7-2
Menu Functions ................................................................................................ 2-4 ................................................... 2-5.4
Menu Structure ................................................................................................. 2-4 ................................................... 2-5.1
Mode of Operation ............................................................................................ 2-1 ................................................... 2-1.1
Model DH-2000 Air Duct Housing ..................................................................... 1-5, 3-12 .......................................... 1-2.13, 3-3.16
Modes of Operation .......................................................................................... 2-5 ................................................... 2-6
Multi-Loop Motherboard .................................................................................... 1-3, 3-6 ........................................... 1-2.6, 3-3.5
INDEX (Cont.)
N
Normal Standby Mode ...................................................................................... 2-5 ................................................... 2-6.1
O
Output Signal Connection ................................................................................. 7-9 ................................................... 7-11
Overall Block Diagram Description .................................................................. 3-1 ................................................... 3-2
P
Parts List .......................................................................................................... 6-1 ................................................... 6
Power-Down Procedure ................................................................................... 4-3 ................................................... 4-5.1
Power-Down System ....................................................................................... 4-3 ................................................... 4-5
Power-Up Procedure ........................................................................................ 4-4 ................................................... 4-6.1
Power-Up System ............................................................................................ 4-4 ................................................... 4-6
Power Checks .................................................................................................. 5-1 ................................................... 5-2.2
Power Supply Communication Connections .................................................... 7-6 ................................................... 7-7.7
Power Supply/Charger Assembly ..................................................................... 1-2, 7-4 ........................................... 1-2.4, 7-7.5
Power Supply/Charger Assembly, Expansion Enclosure ................................. 7-4 ................................................... 7-7.6
Power Supply/Charger Assembly, Revision A .................................................. 3-4 ................................................... 3-3.3
Power Supply/Charger Assembly, Revision C .................................................. 3-5 ................................................... 3-3.4
Printing Operation ............................................................................................. 2-11 ................................................. 2-7
R
Receiver/Transmitter (RX/TX) Module .............................................................. 1-2, 3-3 ........................................... 1-2.3, 3-3.2
Registering I/O Module Assignments ............................................................... 2-13 ................................................. 2-8.5
Registering RCUs ............................................................................................2-14 ................................................. 2-8.7
Relay Output Module ........................................................................................ 1-3, 3-8, 7-4 .................................... 1-2.7.2, 3-3.7,
.................................................................................................................................................................................. 7-7.2
Remote Control Unit (RCU) ............................................................................. 2-12 ................................................ 2-8.3.2
Remote Relay Registration .............................................................................. 2-15 ................................................ 2-8.7.3
Removal and Replacement ............................................................................. 5-2 .................................................. 5-4
Required Tools ................................................................................................ 5-2 .................................................. 5-4.1
RTC Programming ........................................................................................... 2-12 ................................................ 2-8.2
RX/TX Loops .................................................................................................... 2-13 ................................................ 2-8.3.4
RX/TX Module ................................................................................................. 5-2 .................................................. 5-4.3
S
Scheduled Maintenance .................................................................................. 4-1 .................................................. 4-2
Set Menu Function .......................................................................................... 2-4 .................................................. 2-5.4.3
Setting and Adjusting Smoke & Heat Detector Sensitivities ........................... 7-10 ................................................ 7-14
Setting and Adjusting Smoke & Heat Detector Sensitivity Procedure ............ 7-10 ................................................ 7-14.1
Signal Audible Output Module ......................................................................... 7-3 .................................................. 7-7.1
Signal Output Module ...................................................................................... 1-3, 3-7 ........................................... 1-2.7.1, 3-3.6
SmartOne Detector Bases ............................................................................... 1-5 .................................................. 1-2.10
SmartOne Heat Detectors ............................................................................... 1-5, 3-11 ......................................... 1-2.9.3, 3-3.13
SmartOne Ionization Detectors ........................................................................ 1-4, 3-11 ......................................... 1-2.9.1, 3-3.11
SmartOne Photoelectric Detectors .................................................................. 1-5, 3-11 ......................................... 1-2.9.2, 3-3.12
Standard Fault Isolation Techniques ............................................................... 5-1 .................................................. 5-2
Standby Batteries ............................................................................................ 1-4 .................................................. 1-2.8
Supervisory Trouble Mode Indication .............................................................. 2-10 ................................................ 2-6.3.1
INDEX (Cont.)
T
Test Menu Function .......................................................................................... 2-4 ................................................... 2-5.4.4
Trouble Mode Indications .................................................................................. 2-11 ................................................. 2-6.4.1
Trouble Mode User Action ................................................................................. 2-11 ................................................. 2-6.4.2
Troubleshooting ................................................................................................ 5-1 ................................................... 5-3
Troubleshooting and Corrective Maintenance ................................................... 5-1 ................................................... 5
Types of Inputs and Outputs .............................................................................2-12 ................................................. 2-8.3
U
Un-registering RCUs ........................................................................................ 2-15 ................................................. 2-8.7.5
V
Visual Inspection .............................................................................................. 5-1 ................................................... 5-2.1
W
Walk Test .......................................................................................................... 4-2 ................................................... 4-3.4
Walk Test Procedure ........................................................................................ 4-2 ................................................... 4-3.4.2
Walk Testing Detectors .................................................................................... 4-2 ................................................... 4-3.4.1
Wiring the RX/TX PC Line ................................................................................ 7-7 ................................................... 7-10.1
APPENDIX I
SYSTEM DRAWINGS
This appendix provides installation diagrams and instructions for various PEGAsys system modules.
PEGAsys
SOUNDER 1 SOUNDER 2 VOLT FREE RELAYS V/F RELAY
REP 1
REP 2
A B A B 1 2 FAULT
- + - + - + - + NO NC C NO NC C NO NC C
DISPLAY ASSEMBLY
SEE NOTE 1
JP1
SW1
SEE NOTE 1
IC1
JP2
PORT
JK5
I/O
TO I/O MODULES AN
BT1 POWER SUPPLIES
RX/TX
PORT
JK2 JK3 JK4
I-2
JK1 PLG2
TB6
1 TO RX/TX
LOOP
SUPPLY
CONTROLLER
EARTH
DISP PRINT P.C. 24V 5V 0V
FLT
5V 0V
FLT
PLG1
24V
0V
PORT PORT PORT DISPLAY
TO REMOTE PC
FOR PROGRAMMING
PROCESSOR
1 of 4
SHEET
AD
REVISION
06-235443-001
DRAWING No.
(PEGAsys)
Display & Control Assembly
Installation Wiring Diagram CCM/
TITLE
SW1
PLG2
PLG6
PLG3
PLG1
PLG2
TB6
JK1
JK2
JK3
76-100016-001
890181
2. SOUNDER/RELEASE CIRCUITS ARE RATED AT 24VDC, 2A POWER LIMITED.
SUPERVISORY CURRENT - 2.4mA/CIRCUIT 899175
895630
3. ALL RELAY OUTPUTS (VOLT/FREE RELAYS AND V/F RELAY) ARE RATED 897494
AT 30VDC, 1A.
486500
4. SIGNAL OUTPUT REQUIRE THE USE OF END OF LINE RESISTOR (EOR) - 486500-01
10K, 0.5W; NOT SUPPLIED WITH PANEL. FM GROUPS
AVAILABLE AS PART NO. 06-129520-001 (KIT OF 50). SPRINKLER
5. IF MP01 IS CONFIGURED AS A RELEASING OUTPUT, SOLENOIDS
A 220 OHM (5W MIN.) RESISTOR COULD BE USED TO SIMULATE A,B,D,E,G
THE CIRCUIT IF NO SOLENOID IS CONNECTED.
CAUTION: DO NOT USE RESISTOR IF SOLENOID IS CONNECTED. 9. FOR SPECIFIC SIGNAL DEVICE INFORMATION
REFER TO FENWAL DATA SHEETS
6. TO GUARANTEE THE REQUIRED VOLTAGE AT THE RELEASING DEVICE, THE 75.XXX
FOLLOWING TABLE SHALL BE USED.
PEGAsys
August 1999
PEGAsys Intelligent Suppression Control/Fire Alarm System
TITLE
Installation Wiring Diagram CCM/
Display & Control Assembly
(PEGAsys)
DRAWING No.
06-235443-001
REVISION
AD
SHEET
3 of 4
TITLE
Installation Wiring Diagram CCM/
Display & Control Assembly
(PEGAsys)
DRAWING No.
06-235443-001
REVISION
AD
SHEET
4 of 4
August 1999
24 VDC
PEGAsys
FROM POWER
RET SUPPLY NOTES:
MODULE (BLK) SMART DETECTORS USED:
1. SMART DEVICES MAY UTILIZE T-TAP WIRING METHOD IN PRODUCT NO'S. 70-401001-000 70-402001-100
RS232 PORT
FOR COMMUNICATION STYLE 4 CONFIGURATION ONLY. 70-401004-000 71-402001-100
WITH CCM. 2. MAXIMUM OF 255 LOOP DEVICES PER RX/TX 71-401001-000 70-404001-100
LOOP. ANY COMBINATION OF DEVICE TYPE 71-401004-000 70-403001-XXX
IS ACCEPTABLE.
3. MAXIMUM 20 LOOP ISOLATORS EXCLUDING ONE ON RX/TX CONTACT INPUT DEVICES:
CAN BE INSTALLED ON PC LINE. NO MORE THAN 30 LOOP
PRODUCT NO'S. 70-407002-00X
DEVICES BETWEEN TWO ADJACENT LOOP ISOLATORS.
70-407003-001
STYLE 6 (4-WIRE) PC LINE CONFIGURATION IS RECOMMENDED
70-407004-001
TO FULLY UTILIZE LOOP ISOLATION FUNCTION. 70-407008-001
J1 4. ARRANGEMENTS FOR PC LINE WIRING 70-407008-002
J2
JUMPER STYLE 4 STYLE 6 STYLE 6 w/LOOP ISO. STYLE 7 RELAY OUTPUT DEVICES:
SEE NOTE 4 W1 & W2 OPEN SHORTED SHORTED SHORTED PRODUCT NO.'S 70-408002-000
W1 W2 70-408003-000
JP2 IN IN OPEN OUT 70-408004-001
RX/TX
ISOLATORS, THE RXTX MODULE REQUIRES THE USE ELECT. BOX 74-200012-002
OF ONE (1) P/N 74-200012-001 ISOLATOR MODULE BASE MOUNT 74-200012-004
RX/TX TO OPERATE IN THE STYLE 7 CONFIGURATION.
76-100005-001
4.2- WHEN LOOP ISOLATOR USED: ANALASER INTERFACE MODULE
PLUG IN THE LOOP ISOLATOR (RXTX) 74-200012-001 PRODUCT NO. 89-100081-001
AND INTERCONNECT IT USING FLEX CABLES TO J3 ON
CPU RESET LED1
RXTX. MAKE SURE THAT UNEVEN PINS ARE
PC LINE NORMAL LED2 INTERCONNECTED.
LOOP ISOLATOR
RX/TX
5. MAXIMUM OF ONE #12 AWG WIRE PER TERMINAL.
CPU RESET SW1
(OPTIONAL)
SHORT-1
SIGNALING LINE CIRCUIT CHARACTERISTICS
PC LINE RESET SW2 LOOP ISOLATOR
I-6
KIDDE-FENWAL, INC.
ASHLAND, MA 01721
74-200012-001 MAX VOLTAGE: 26.4 VDC
1
MIN. VOLTAGE: 19.0 VDC
T1 T1 MAX. LINE CAPACITANCE: 1.0 uF
SHORT-2
J3
MAX. LINE RESISTANCE: 26.0 OHMS
1 2 3 4
MAX. NUMBER OF RCU'S: 255
JP3 JP2 MAX. RIPPLE VOLTAGE: 100 mV RMS
12
J3
LED 1 - RED LED INDICATES RXTX RESET WHEN ON.
LED 2 - GREEN LED INDICATES NORMAL OPERATION OF RXTX PC LINE
TRANSMITTER WHEN BLINKING.
SEE NOTE 4 SW 1 - CPU RESET.
SW 2 - PC LINE REST / DISCONNECT 24V FROM TERM. 2 & 3.
RX/TX ASSEMBLY
74-200005-001
AC
1 of 2
TITLE
SHEET
REVISION
(PEGAsys)
DRAWING No.
06-235443-002
Installation Wiring Diagram
Receiver/Transmitter Module
76-100016-001
Intelligent Suppression Control/Fire Alarm System
Intelligent Suppression Control/Fire Alarm System PEGAsys
TITLE
Installation Wiring Diagram
Receiver/Transmitter Module
(PEGAsys)
DRAWING No.
06-235443-002
REVISION
AC
SHEET
2 of 2
TITLE
Installation Wiring Diagram
Power Supply
(PEGAsys)
DRAWING No.
06-235443-003
REVISION
XC
SHEET
1 of 1
TITLE
Installation Wiring Diagram
Power Supply
(PEGAsys)
DRAWING No.
06-235443-003
REVISION
AC
SHEET
1 of 2
BLK/WHT
WHT
ORN
RED
RED
BLK
BLK
VIO
VIO
BLK
DC IN 2
RET
ORN
24V
SHARE
SPV
DC IN 1
RET
BLK/WHT
24V
G
AC IN
N
WHT
L
L
2
AC OUT
N
L
1
N
TITLE
Installation Wiring Diagram
Power Supply
(PEGAsys)
DRAWING No.
06-235443-003
REVISION
AC
SHEET
2 of 2
TITLE
Installation Wiring Diagram
Release Module
(PEGAsys)
DRAWING No.
06-235443-005
REVISION
AD
SHEET
1 of 3
August 1999
SINGLE SOLENOID TWO SOLENOIDS
SINGLE TB1 DAUL TB1 TB1 TB1
PEGAsys
1 1 1 1
CONTROL HEAD CONTROL HEAD
L
S 2
2 3 2 2 2 AUXILARY POWER
S
L + + + + CONNECTION
L
3 3 3 3
S 1 TB1
CKT #1 CKT #1 L CKT #1 +24V
- - - - 1
2 4 2 4 4 4
3 S 3 S
S L
+ + + +
5 5 5 5 2
L RET.
CKT #2 CKT #2 CKT #2 NOTE:
1 - 1 - - - JUMPERS W1 & W2 TO BE REMOVED
6 6 6 6
WHEN AUXILARY POWER USED.
NOTES:
NOTES:
1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ".
1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ".
2. MAXIMUM CIRCUIT WIRING RESISTANCE
2. MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 0.6 OHMS. IS TO BE 0.7 OHMS.
SOLENOID PART NO. 899175 SOLENOID PART NO. 486500, 486500-01 SIGNAL CIRCUITS
(U.L. LISTED)
S L 2 S L 2 2 2 8
S + S L
BLK + BLK + RED + +
BLU 3 BLU 3 3 RED
3 9
L -
I-12
CKT #1 CKT #2 10K EOR
YEL - YEL - - BLK -
WHT 4 WHT 4 4 4 10
S
+ S L
+ + + +
BLK
5 BLU 5 5 RED
5 11
SOLENOID -
SAFETY FUSE CKT #2 CKT #2 10K EOR
- YEL - BLK - BLK -
6 WHT 6 6 6 12
+
S L
S L NOTES:
1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ".
NOTES: 2. MAXIMUM CIRCUIT WIRING RESISTANCE
1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ". IS TO BE 6.0 OHMS.
AD
2 of 3
TITLE
SHEET
REVISION
(PEGAsys)
DRAWING No.
06-235443-005
Release Module
Installation Wiring Diagram
76-100016-001
Intelligent Suppression Control/Fire Alarm System
76-100016-001
FM GROUP SPRINKLER SOLENOIDS
S L S L
+ + + +
5 5 5 5
CKT #2 CKT #2 CKT #2
- - - -
6 6 6 6
NOTES:
NOTES:
1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ".
1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ".
2. MAXIMUM CIRCUIT WIRING RESISTANCE
2. MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 2.3 OHMS. IS TO BE 1.5 OHMS.
I-13
GROUP E,G
(U.L. LISTED)
L
2 2
S
+ +
3 3
L CKT #1
- -
S
4 4
AD
+ +
5 5
3 of 3
TITLE
CKT #2
- -
SHEET
6 6
S L
REVISION
(PEGAsys)
NOTES:
1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ".
2. MAXIMUM CIRCUIT WIRING RESISTANCE
DRAWING No.
06-235371-005
Release Module
IS TO BE 2.5 OHMS.
August 1999
PEGAsys
August 1999
PEGAsys
NOTES:
1 2 1 2 1 2
TROUBLE LED MODULE ADDRESS ASSIGNMENT
4. MODULE ADDRESS ASSIGNMENT
76-100003-001
SIG. AUD.
SEE NOTE 5 MODULE SWITCH POSITION
ADDRESS SW2,2 SW1,1 SW1,2
1 ON ON ON
2 ON ON OFF
3 ON OFF ON
4 ON OFF OFF
5 OFF ON ON
6 OFF ON OFF
I-14
1
POWER 8 OFF OFF OFF
NOT USED
5. EITHER SOUNDER OUTPUT (2) MAY BE CONFIGURED
FOR EITHER 2 STYLE "Y" OR 1 STYLE "Z", USING
TB1 JUMPER AND DIP SWITCH SETTINGS SHOWN ON SHEETS 2 & 3.
SOUNDER SEE NOTE 8 6. FOR SPECIFIC SIGNAL DEVICE INFORMATION
CIRCUITS
REFER TO FENWAL DATA SHEETS 75.XXX
1-4
ONLY POLARIZED SIGNALLING DEVICES TO BE USED.
5 5
- -
L S L S CIRCUIT 1 L S L S CIRCUIT 1
6 6
10K 10K - 10K 10K -
CIRCUIT 2 CIRCUIT 2
EOR EOR EOR EOR
7 7
+ +
8 8
+ +
9 9
- -
L S L S CIRCUIT 3 CIRCUIT 3
10 10
10K 10K - 10K -
CIRCUIT 4 L S
EOR EOR EOR
11 11
+ +
12 12
+ +
TB1
+24VDC
1
AUXILIARY
2 of 3
SHEET
AC
REVISION
06-235443-006
DRAWING No.
(PEGAsys)
Signal Audible Module
Installation Wiring Diagram
TITLE
POWER RET
2
PEGAsys
August 1999
2 STYLE "Z" 1 STYLE "Z" AND 2 STYLE "Y"
August 1999
PEGAsys
TB1 TB1
L S
5 5
- -
CIRCUIT 1 CIRCUIT 1
6 6
10K - 10K -
L S EOR EOR
7 7
+ +
8 8
+ +
9 9
- -
CIRCUIT 3 L S L S CIRCUIT 3
10 10K 10K 10
10K - -
L S EOR EOR EOR CIRCUIT 4
11 11
+ +
12 12
+ +
I-16
RELAY
76-10004-001
TITLE
Installation Wiring Diagram
Relay Output Module
(PEGAsys)
DRAWING No.
06-235443-007
REVISION
AB
SHEET
1 of 1
CITY TIE
76-100002-001
TITLE
Installation Wiring Diagram
City Tie Module
(PEGAsys)
DRAWING No.
06-235443-008
REVISION
AB
SHEET
1 of 2
TITLE
Installation Wiring Diagram
City Tie Module
(PEGAsys)
DRAWING No.
06-235443-008
REVISION
AB
SHEET
2 of 2
PEGAsys
I/O MOTHER BOARD
J9
J1 J2 J3 J4 J5 J6 J7 J8 RS-485
Rv2
R1 JP1
Rv1
COM. TBL.
COM. ALM.
SIG. GND
485A
C 485B
Tb1
RET
NOTE: 1. USE RED WIRES FOR +24VDC AND BLACK FOR RET.
1. POWER CONNECTIONS:1.
2). 24VDC POWER TO RX/TX MODULES (J1) FROM TB5 OR TB6 ON POWER SUPPLY.
3). TERMINAL TB1 CAN BE USED TO BRING POWER TO I/O MODULES IN THE AUXILIARY BOX.
2. COMMUNICATIONS:
I-20
1). J9 CONNECTS TO CCM PORT AND PROVIDES I/O MODULES WITH RS485 COMMUNICATIONS.
2). J1 THROUGH J8 TO BE USED TO PLUG IN I/O MODULES AND SUPPLY THEM WITH +24VDC
POWER AND RS485 COMMUNICATIONS.
3). RS232 COMMUNICATIONS FOR RX/TX MODULE TO BE PROVIDED THROUGH PHONE CABLE
PLUGGED INTO "RX/TX" PORT ON CCM.
TO POWER SUPPLY
TO CCM I/O PORT
TO CCM RX/TX PORT
/TX E
RXDUL
MO
LE
O DU
I/O
M
TITLE
Installation Wiring Diagram
Basic I/0 Motherboard
(PEGAsys)
DRAWING No.
06-235443-011
REVISION
AB
SHEET
2 of 2
RS232
August 1999
RET
PEGAsys
+24V
RET
+24V
RET
+24V
RET
+24V
RET
+24V
RET
+24V
RET
+24V
RET
+24V
RET
+24V RS485
COM. TBL.
COM. ALM.
SIG. GND
485A
485B
RET
I/O
MODULES
+24V
KIDDE-FENWAL, INC.
ASHLAND, MA 01721
NOTE: 1. USE RED WIRES FOR +24VDC AND BLACK FOR RET.
1. POWER CONNECTIONS:1.
I-22
2). TB1 THROUGH TB8 TO BE USED TO CONNECT 24VDC POWER TO RX/TX MODULES (J1).
3). TERMINAL TB9 CAN BE USED TO BRING POWER TO I/O MODULES IN THE AUXILIARY BOX.
2. COMMUNICATIONS:
1). JP0 CONNECTS TO CCM MODULE AND SUPPLIES RS232 COMMUNICATION FOR RX/TX MODULES.
3). JP9 CONNECTS TO CCM PORT AND PROVIDES I/O MODULES WITH RS485 COMMUNICATIONS.
4). J1 THROUGH J7 TO BE USED TO PLUG IN I/O MODULES AND SUPPLY THEM WITH +24VDC
POWER AND RS485 COMMUNICATIONS.
AB
5). TB10 TO BE USED TO INTERCONNECT TO AUXILIARY PANELS' MOTHER BOARD AND POWER
SUPPLIES TO PROVIDE RS485 COMMUNICATIONS.
1 of 2
TITLE
SHEET
REVISION
(PEGAsys)
DRAWING No.
06-235443-012
Multi-Loop I/0 Motherboard
Installation Wiring Diagram
76-100016-001
Intelligent Suppression Control/Fire Alarm System
Intelligent Suppression Control/Fire Alarm System PEGAsys
/TX E
RXDUL
M O
E L
DU
I/O
MO
TITLE
Installation Wiring Diagram
Multi-Loop I/0 Motherboard
(PEGAsys)
DRAWING No.
06-235443-012
REVISION
AB
SHEET
2 of 2
August 1999
TO REMOVE WIRING DIAGRAM FOR CONNECTION TO SMART
BROWN CONTACT DETECTOR MULTIPLEX TRUNK CIRCUIT AND
PEGAsys
I-24
EOL 8. REFER TO SYSTEM OPERATION MANUAL FOR APPLICATION
OF ADDRESSABLE CONTACT INPUT DEVICE.
BB
1 of 1
TITLE
SHEET
REVISION
DRAWING No.
06-234563-003
NO/NC (Obsolete)
Installation Wiring Diagram
Addressable Contact Input Device
76-100016-001
Intelligent Suppression Control/Fire Alarm System
BROWN ( N/C )
ORANGE ( COM ) SEE NOTE 2
76-100016-001
N.C.
N.O.
NOTES
I-25
6. REFER TO SYSTEM OPERATION MANUAL FOR APPLICATION
OF ADDRESSABLE RELAY OUTPUT
RD BK
BA
1 of 1
TITLE
SHEET
(Obsolete)
REVISION
DRAWING No.
06-234563-001
Installation Wiring Diagram
Addressable Relay Output Device
August 1999
PEGAsys
August 1999
PEGAsys
Typical N.O. Initiating
Devices
NOTES
DATE OF MANUFACTURE:
FOR SERVICE SEND TO:
SmartOne TM
KIDDE-FENWAL, INC.
CAT. NO. 70-407008-001
INSTRUCTIONS
EOL
SEE INSTALLATION
06-235578-001
PC PC PC PC SW SW LED LED
annunciator (if used) must be located in
the same room as the AI.
AI, N/O AI, N/C
11. Use Listed 10K Ohm end-of-line resistor,
P/N 06-129025-003.
76-100016-001
76-100016-001
supervised.
7 6 5 4 3 2 1
N/C (+) (-) (+) (-)
N/O COM
PC PC PC PC
TERMINALS 5-7 ARE POWER LIMITED
TERMINALS 1-4 ARE POWER LIMITED
MAX. INSTALL. TEMP. 120F
DATE OF MANUFACTURE:
TM
ASHLAND, MA 01721
SmartOne
INSTRUCTIONS
SEE INSTALLATION
MODEL AO
06-235577-001
PEGAsys
August 1999
PEGAsys Intelligent Suppression Control/Fire Alarm System
APPENDIX J
PEGAsys NETWORK INTERFACE CARD
CR2 K2 CR1 K1
K3
C27 Network group number: 0 to 32
1
R23
U13
Processing of network RESET messages:
RV11
U11
Enabled/Disabled
RV12
K4 R46
R45 C12 GND
RV6 RV8 RV2 TP1 Processing of network SILENCE messages:
RV10
+5
RV4 RV9 RV3 C20 U2
1 TP2
I1 Enabled/Disabled
C23
R10 Y1
R24
TP3
E8
+ N1
Logging all events: Enabled/Disabled.
C13 TP4
N2
R25
U7 C4
R6
R5
R3
R4
E7
E3
E6
E5
E2
E4
C3
+
TP5
1 I2
TP6
R14
C5
R22 1
U3 Central Station
C2
U18 R36
R2
R41
R40
U20
1 U4 J-2.1.1 NETWORK STYLE
1 U21 C16 1 1
U19 1
R44 R12
U14
R19
Both of the two independent data channels can be enabled (Style
C1
R33
R15
Q4
C9 1
C8
R1
1
U17
C22
U10 U9
R34
7), or either one of the channels can be disabled (Style 4). These
Q3
R7
U15
U8 data channels transmit network information from one node to
Q1 1 1 1 1
the next, or bi-directionally if nodes are connected on either
+
R42
3. SET
1. TIME:DATE
2. PRINTER
3. DEVICES
4. PROGRAMMING
5. DCC's
7. CLEAR EVENTS
7. NETWORK
9.CLR RMT EVENTS REMOVE QUEUED EVENTS RECIEVED FROM NODE #___
If a node is in a non-zero group, it will accept button pushes and events from remote nodes if configured as shown
below:
If a node is in group 0, it will accept button pushes and events from remote nodes if configured as shown below:
membrane keypad. In addition, the menu provides the ability to gram. The ACKNOWLEDGE function will be automatic, the
add or remove individual or groups of nodes to/from the net- SILENCE and RESET functions must be enabled in PE-
work. The additions to the PEGAsys menu structure are dia- GAsys Configuration Software (PCS), or by using the
gramed in Figure J-2. panels membrane keypad and LCD display panel.
A node in a different non-zero network group configured to
J-2.3 Configuring Networking Options via PCS log all groups will process network message(s) from any
node in the entire network, depending on its own installed
Configuration of all CCM parameters, including network param-
program. ACKNOWLEDGE is automatic, however SI-
eters, can be accomplished using PCS. The software will ini-
LENCE and RESET functions must be enabled in PEGA-
tially use default values, with networking Style set to None
sys Configuration Software (PCS), or by using the panels
until changed by an operator.
membrane keypad and LCD display panel.
See the PEGAsys Configuration Software (PCS) Program User's A node in network group zero, the default group, will not be
Guide (76-014) for details. recognized by any other nodes in network group zero for
functions other than receiving messages unless it is con-
J-2.4 Configuring Networking Options figured to log all groups in PEGAsys Configuration Soft-
via a Dumb Terminal ware (PCS).
Control panel configuration can be performed through use of Refer to Table J-1 for a summary of these relationships.
the system menus using a dumb terminal attached to the se- Nodes can be added or deleted from network only via Net-
rial PC Port. The software will initially use default values, with work Menu.
networking style set to None until changed by an operator.
NOTE: Menus cannot be accessed with an alarm
condition in effect.
J-4 FUNCTIONAL DESCRIPTION
This section describes the hardware used to implement the
PEGAsys Network:
J-3 OPERATION
Central Control Module (CCM) CPU Board
Networked PEGAsys panels may be configured to communi- Network Interface Card (NIC)
cate differently depending on
Network Wiring
Whether they are assigned to network group 0 or to groups
1 through 32, J-4.1 Central Control Module CPU Board
Whether they are communicating with other
The CCM board is a slightly modified version of the original
panels in their local group,
CPU board designed so that the NIC will plug in as a daughter
Or with panels in a remote group. board. This modification has no effect on normal operation of
Table J-1 sets forth these relationships. In more detail, how- the PEGAsys panel or system.
ever:
J-4.2 Network Interface Card (NIC)
A node which receives the network message from another
node in the same non-zero group, will process the network The NIC contains the hardware necessary for data-communi-
message appropriately, depending on its own installed pro- cation between network nodes. The channel is an EIA-485 bus
line. Each node uses one (1) NIC. The NIC performs the follow- without power will not participate in networking, this pass-through
ing functions: function allows all other network nodes to function normally while
Dual Channel Support providing the proper trouble indications.
Note B Channel 1
RTS Rx Tx
Note A
1/2 NETWORK INTERFACE CARD (NIC) B2NA2 B1NA1 B2IA2 B1IA1 B2NA2 B1NA1 B2IA2 B1IA1
To CCM CPU
nels. Under normal operation with Style 7, network communi- Note A: Attach the shields on the 'N' side of the network line to the grounding screw on the CCM.
Note B: The shields on the 'I' side of the network line are to be cut short and left floating.
cation is divided between the two channels. In case of a short Note C: All circuits are supervised and power limited.
J-4.2.2 MESSAGING
When a node wishes to transmit over a network channel, the J-5 MAINTENANCE AND/OR REPLACEMENT
data is written to the NIC which sends the signals out to the bus No maintenance is required. In the event of failure, the module
for receipt by remote NICs. While a node is not transmitting should be returned to the factory for repair or replacement.
data, the NIC reads the bus data traffic, and converts it to a
form readable by the nodes software. Data communication will
be configured on the NICs UART as 8 bits, no parity, 1 stop bit
(8-N-1), and 9600 baud. The NIC will either transmit locally pro-
duced data or receive and retransmit bus activity as a repeater.
LONG SCREW
AND SPACER
THROUGH HERE
INSERT PLASTIC
STANDOFFS HERE
DISPLAY PORT
I/O PORT
PRINT PORT
PORT
Rx/Tx PORT
I/O
P.C. PORT
PORT
RX/TX
APPENDIX K
ADDRESSABLE SIGNAL/SOUNDER MODULE
AUDIO
MODE
P1=1&2 FM
S1=3 ON APPROVED K-5 MAINTENANCE OR REPLACEMENT
The ASM is shipped from the factory as an assembled compo-
Figure K-1. ASM Front Panel nent and is not field serviceable. Little or no maintenance is re-
quired.
Testing is accomplished through the testing capabilities of the
PEGAsys panel. See Chapter 5, Troubleshooting and Corrective
K-2 ADDRESSING AND REGISTRATION Maintenance, for particulars. In the event of a failure, the module
should be replaced.
As with any SmartOne loop device, addressing is through the
Kidde hand-held programmer (P/N 74-200013-001) or the PEGA- For replacement, follow the instructions in the ASM Installation
sys control panel menu/keypad as described in Chapter 2 of this Data Sheet.
manual.
Module-programmable parameters include owners-location mes-
sage, non-silenceable (waterflow), walk test, drill mode and si-
lence. The programming process is described in PEGAsys
Configuration Software (PCS) Program Users Guide, 76-014, (P/
N 06-235766-001).
Addressing and programming the module's registration into the
PEGAsys system is described in Paragraph 2-8 (and sub-para-
graphs) of this manual. Registration of the module at the PEGA-
sys panel is mandatory to ensure proper operation.
CAUTION
Exposing more than 1/4 of wire may cause a ground
fault. Exposing less than 1/4 of wire may result in a
faulty connection.
Refer to the National Electrical Code for proper box specifica-
tions. ASM volume is 8.94 cubic-inches.
Refer to the RX/TX specifications in the chapters on Operation,
and Functional Description for addressable-loop wiring specifica-
tions.
Power/Communication (PC) line wiring is power limited and su-
pervised. For power-limited circuits, use Type FPL, FPLR, or FPLP
cable per Article 760 of the National Electrical Code (NEC).
The note located on the module's product label (ALL OTHERS-
POWER LIMITED) must be removed if the module is connected
to a non-power limited supply source.
If the auxiliary notification appliance power source is not power
limited, the output circuit, auxiliary input circuit, and the trouble
circuit are non-power limited. Otherwise, all three circuits are
power limited.
Supervision of audio to ASM must be provided by the audio equip-
ment. Power limited or non-power limited amplifier outputs are
available.
APPENDIX L
REMOTE DISPLAY CONTROL MODULE
AND REMOTE DISPLAY MODULE
as the maximum quantity for each module is not exceeded. The
L-1 INTRODUCTION RDCM, in addition to emulation of the PEGAsys LEDs and LCD
displays, provides remote access to the system and, if pro-
This manual contains the information necessary to support the grammed, the PEGAsys network panel(s) and menu options
PEGAsys Remote Display Control Module (RDCM)(Figure L-1), via this emulation of the PEGAsys front panel function and nu-
P/N 76-300000-502, and Remote Display Module (RDM)(Figure meric keys.
L-2), P/N 76-300000-501. Both modules function as remote ad-
dressable adjuncts to the PEGAsys and mimic the main control Remote power is required and can be provided by the control
panels LCD and LED front displays. Additionally, the RDCM con- panel PSU or a separate supply UL listed for fire alarm applica-
tains system control switches and a tactile response numeric key- tion. In each instance, remote power is supervised by the RDCM
pad. These controls match the PEGAsys layout. The RDM does and RDM with failure displayed locally and at the control panel.
not permit operation of the control features (operation is read only). The units also contain a buzzer with sequencing that follows
The RDCM is key and password secured with the password needed the buzzer contained in the control panel.
being the one used on the associated PEGAsys panel.
Either the PEGAsys control panel or one RDCM can be pro-
grammed as the master unit to control the system under alarm
or fault conditions. Operation of an alternate (non-master) unit
will grant that module exclusive control over the system for 30
System Status Display seconds. Under these conditions, attempts to input from an-
other module will prompt a lockout display message on the mod-
AC POWER SYSTEM TROUBLE SYSTEM
ACKNOWLEDGE
SILENCE ule attempting the interrupt. This acts to prevent conflicting
ALARM
PRE-ALARM
SUPERVISORY
SILENCE
SYSTEM
RESET
SCROLL inputs. Under all circumstances, the master will be granted im-
mediate system control.
1 2 3 4 5
R 6 7 8 9 0
L-2.1 Operator Interface
All operator interfaces are contained in the front panel assem-
bly. Operator inputs are passed to the PEGAsys for processing.
Figure L-1. RDCM Front Panel
The RDCM operator-interface function keys are:
Acknowledge: Acknowledge alarms/troubles and silence
all local buzzers.
System Status Display Silence: Silence signal/audibles after Acknowledge.
Reset: Reset latched alarm conditions.
AC POWER SYSTEM TROUBLE
alarm condition.
CPU fail: Mounted on main PCB and available to the in- L-3 OPERATION
staller only. Indicates RDCM/RDM processor has failed to Before proceeding with operations, please become totally fa-
initialize. miliar with PEGAsys Fire Alarm/Suppression Control System
LED colors used to represent indications are: manual, especially the sections on Active Alarm Mode, Active
Supervisory Trouble Mode, and Active Trouble Mode. Please
Red: Alarm.
note differences between latching and non-latching Active Alarm
Green: Power-on. Modes.
Yellow: CPU failure, trouble, silence, supervisory and pre-
For RX/TX loop input devices. To set either latching or non-
alarm.
latching, please refer to the PEGAsys Configuration Software
The RDM functions as read only. Therefore, it has a scroll key, (PCS) manual, PCS Operations chapter.
but does not provide the other function keys nor an operable
keypad. The following example is for latching alarm mode (for these
examples, assume the device to be manual release, address
1004).
L-2.2 Interconnection
In Normal Standby Mode, the display will show:
The RDCM and RDM operate on a shared RS-485 bus which
supports wire runs of up to 4000 ft. from the PEGAsys control SYSTEM STATUS NORMAL 10:00AM 06-08-99
panel. The primary RS-485 bus from the PEGAsys will support PEGASYS
up to 15 RDCMs and 16 RDMs in any combination not exceed-
In practice, the actual local time and date will be presented.
ing maximum of each module.
When a RX/TX loop device goes into active alarm, the display
L-2.3 Addressing will show:
Address selection is via setting of the 16-way, 4-bit hexadeci- 1004 ALARM ON - MANUAL RELEASE
mal coded rotary switch, SW1, mounted on the printed circuit Default or user text
board. See Figure L-4.
L-3.1 Switch Functions
Table L-1. Address Switch Settings
The switch functions are listed in sequence of use:
Switch RDM/RDCM Switch RDM/RDCM
Setting Address Setting Address L-3.1.1 ACKNOWLEDGE
1 RDM or RDCM 01 9 RDM or RDCM 09 All ALARM ON, ALARM OFF, TROUBLE ON/OFF, or SUPER-
VISORY ON/OFF messages must be acknowledged by opera-
2 RDM or RDCM 02 A RDM or RDCM 10 tion of this switch. Multiple alarms must be individually
acknowledged, all other multiple inputs will default to individual
3 RDM or RDCM 03 B RDM or RDCM 11 acknowledge, but may be programmed to global acknowledge
by accessing the SET" menu from the PEGAsys or any RDCM.
4 RDM or RDCM 04 C RDM or RDCM 12
The RDCM will pass the acknowledge input to the PEGAsys
5 RDM or RDCM 05 D RDM or RDCM 13 causing its LED to go from a pulsing to a steady mode, and the
buzzer to silence.
6 RDM or RDCM 06 E RDM or RDCM 14
The PEGAsys sends a global command to silence all remote
7 RDM or RDCM 07 F RDM or RDCM 15 RDCM/RDM buzzers.
8 RDM or RDCM 08 0 RDM 16 The PEGAsys sends out a global lockout command to all other
RDCMs. This gives the calling device exclusive control over the
system for 30 seconds. Under these conditions, attempts to in-
put from another module will prompt a lockout display message
(See Paragraph L-3.1.2 for example) on the module attempting
the interrupt to prevent conflicting inputs. Under all circum-
(The default or user text is that entered at the associated PE- The PEGAsys sends out a global lockout command to all other
GAsys panel. This message cannot be changed from the RDCMs. This gives the calling device exclusive control over the
RDCM.) system for 30 seconds and displays the following message:
Then the display will show how many active alarms are still SYSTEM RESET
present in the system (if any), and subsequently display how If there are no further key entries at the calling device (address
many active trouble conditions are still present in the system (if 02), and no further system events are detected, all modules
any). For example: and the PEGAsys will display the system default message:
001 SYSTEM STATUS NORMAL 10:00AM 03-08-99
ACTIVE ALARMS REMAINING PEGASYS
Again in the case of multiple alarms (either On or Off), each In practice, the actual local time and date will be presented.
event must be acknowledged separately. In the case of mul-
tiple troubles, actuation of the acknowledge input may be sepa- In the event of an RDCM's microprocessor going into fault con-
rate or programmed to global acknowledge. A maximum of 32 dition, actuation of hardware switch S3 located behind the dis-
trouble message can be displayed/scrolled at any one time. play membrane will cause a hardware reset of the
microprocessor.
For non-latching sequence, each ALARM OFF will display and
must be acknowledged. L-3.1.4 SCROLL
1004 ALARM OFF - MANUAL RELEASE When the Scroll key is pressed during any active system event,
Default or user text the following will result:
In the event of loss of communications between the RDCM and The PEGAsys sends out a global lockout command to all other
the PEGAsys on the RS-485 bus, the local buzzer will sound RDCM(s). This gives the calling device (address 02) exclusive
and the trouble LED will light. control over the system as described in reset above.
L-3.1.2 SILENCE NOTE: The RDM scroll key does not provide the global lock-
out command.
When all alarm and trouble conditions have been acknowledged,
operation of the silence switch will have the following results: The PEGAsys, RDCMs and RDMs will then be updated by the
next event in the buffer.
The RDCM will pass the silence input to the PEGAsys causing
all outputs programmed for silence to de-energize. When a Scroll key is actuated at any RDCM, RDM or the PE-
GAsys, the resulting scroll display is sent globally to the sys-
The PEGAsys sends out a global lockout command to all other tem.
RDCM(s). This gives the calling device exclusive control over
LED Test Feature: With no active inputs, press and hold
the system for 30 seconds. For these examples, assume RDCM
the scroll key for 2 seconds. All LEDs will light for 5 sec-
address 02. If another (non-master) module attempts an inter-
onds.
rupt, the following lockout message will display for 5 seconds:
System Information Entry Keys: To enter passwords and
RDCM 02
gain access the PEGAsys menu functions, the relevant keys
IN CONTROL are:
NOTE: RDCM 02 is the default. This message can be cus- Numeric 0-9: Enters password and system function infor-
tomized in PCS. Please refer to the PEGAsys Con- mation.
figuration Software (PCS) Program Manual Enter: Enter information into the system menu.
After the 30 second control period, any other module can pro- Delete: Exit system menu and correct wrong entries.
vide system inputs (unless a module programmed as system To enter the password, press the 0 key. The RDCM opens the
master assumes control). password entry menu and displays:
After all active alarms and troubles have been cleared, input Each key entry will then display the # character:
devices programmed to the latching sequence will show: PLEASE ENTER PASSWORD
XXX ####
ALARMS ACTIVE If the password entry is incorrect, the display will become:
Input devices programmed to the non-latching sequence will PASSWORD ENTRY FAILED
show: The RDCM will request another password entry request, and, if
correct, the PEGAsys will send the 30 second global lockout
If during the password entry sequence any key other than the Input voltage 24 VDC nominal
numeric key (except Delete) is pressed before the Enter key,
the PEGAsys will update the RDCM with the default display. Supervisory current 64 mA nominal
.409
12.000
5.875
9.500
DS1
SW3
.
ND
OU
GR
RTH
EA
SIS/
AS
CH
TO
LE
D SH
IELD
ED
CAB
HARDWARE FOR
TW
ISTE
GND. CONNECTION
CONNECTOR
LY
PP
SU
R
WE FM
PO RO
VED
APP
UL
R
INSTRUCTION LABEL
.
NO
R.
SE
APPENDIX M
ADDRESSABLE ALARMLINE MODULE
TM
APPENDIX N
NETWORKABLE CENTRAL CONTROL MODULE (NCCM)
play the current time and date on the system LCD and provides
N-1 INTRODUCTION basic information for real-time operations.
The Networkable Central Control Module (NCCM), shown in Internal diagnostics enhance the troubleshooting ability of the
Figure N-1, is the heart of the PEGAsys system and is com- system. Examples include: microprocessor failure, memory fail-
posed of two printed circuit board assemblies; the display con- ure, RS-232 port troubles, etc. Network diagnostics are sepa-
trol module (DCM), and the CCM printed circuit board. The rately controlled and report to appropriate panels.
NCCM is available in two versions, P/N 76-100008-501 for
Two individually programmable signal output circuits (MP1 &
single-loop systems and P/N 76-100008-600 for multi-loop sys-
MP2) provided are used primarily for signaling devices (horns,
tems.
bells, strobes) and deliver up to 2.0 amps of 24 VDC power.
The MP1 output can be optionally programmed for releasing
applications using solenoid-actuated suppression equipment
(agent and sprinkler).
System Status Display
Two individually programmable relay outputs (MP3 & MP4) are
AC POWER SYSTEM TROUBLE SYSTEM
SILENCE
provided on the NCCM for controlling building functions during
alarm occurrences. Relays are Form C, 1 Amp @ 30 VDC rated.
ACKNOWLEDGE
ALARM SUPERVISORY
SYSTEM
SCROLL
PRE-ALARM SILENCE RESET
All four NCCM outputs can be programmed via EOC to activate
1 2 3 4 5
from either panel or, if provided, network inputs.
R 6 7 8 9 0
APPENDIX O
CENTRAL STATION OPERATION
NO NC C NO NC C
Volt Free Fault Relay
Relay 2
(Use this report to indicate deficiencies, user remarks and recommendations relating to the publication. Fold on dotted line, tape and mail to
KIDDE-FENWAL, Inc., 400 Main Street, Ashland, MA 01721, Attn. Documentation Manager or FAX to 508-881-8920)
DATE:
7. USER EVALUATION
12. ADDRESS
220423
FOLD
Place
Stamp
Here
KIDDE-FENWAL, Inc.
400 Main Street
Ashland, MA 01721
FOLD
220423
LIMITED WARRANTY STATEMENT
Kidde-Fenwal, Inc. represents that this product is free from defects in material and workmanship, and will repair or replace any
product or part thereof which proves to be defective in workmanship or material for a period of twelve (12) months from the date
of purchase but not to exceed eighteen (18) months after shipment by the manufacturer. For a full description of Kidde-
Fenwals LIMITED WARRANTY which, among other things, limits the duration of warranties of MERCHANTABILITY and FIT-
NESS FOR A PARTICULAR PURPOSE and EXCLUDES liability for CONSEQUENTIAL DAMAGES, please read the entire
LIMITED WARRANTY on the Kidde-Fenwal Quotation, Acceptance of Order, and/or Original Invoice which will become part of
your sales agreement. Please contact Kidde-Fenwal directly for a return material authorization (RMA) number before returning
material to the factory at Ashland, Massachusetts, shipment prepaid. Kidde-Fenwal will repair or replace and ship prepaid.
Kidde-Fenwal Inc.
400 Main Street These instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection with
Ashland, MA 01721 installation, operation and maintenance. All specifications subject to change without
(508) 881-2000 notice. Should further information be desired or should particular problems arise which are
76-100016-001 Rev. BB 1998 Kidde-Fenwal Inc. Printed in USA