24kV to 36kV
3AH4
24kV 36 kV
Central legend
General: :
Siemens 3AH4 vacuum circuit-breakers (V- 3AH4 ,
breaker) are of the triple-pole indoor type for high , 120,000
switching frequency up to a service life of at least 24kV 36kV.
120,000 mechanical operating cycles. The rated
voltage ranges between 24 and 36kV.
- 1/1 -
Basic type
Rated voltage
3 A H 4 2 6 6 - 6
(See catalog HG 11 for selection and ordering data of the ( 11)
respective circuit-breaker)
Rating plate
4266 2Q 4266 2Q
32444557 32444557
24 2500 24 2500
40 40
125 68 125 68
Fig.1/1 .1/1
Rating plate
Note: In the event of any queries state the type : (2), (4),
designation(2), designation code(4) and the serial (3).
number(3). - 1/2 -
Load current A
1250A 2
2000A 4
2500A 5
-1/3 -
- (11)
U UW Us ISC tth Ima D.C. PA MLFB
1st to 7th place
1250A 2000A 2500A 1 7
(kV) (kV) (kV) (kA) (s) (kA) (%) (mm)
2 4 6
24 125 50 40 3 100 36 275 EU 3AH4 266-6
36 170 70 31.5 3 80 36 350 EK 3AH4 305-2*
EK 3AH4 305-4*
EK 3AH4 305-6*
40 3 100 36 350 EU 3AH4 306-6*
* Us to 85kV on request; UW to 185 kV on request; * 85kV; 185Kv;
Note: available :
1. Rated voltage (maximum permissible system voltage) at 50 to 1. ( ) 50-60Hz
60Hz.
2. Rated lightning impulse withstand voltage (peak value) 2. ( )
3. Rated power frequency withstand voltage (RMS value) 3. ( )
4. Rated short-circuit current 4.
5. Rated short-circuit duration 5.
6. Type designation 6.
7. Rated normal current 7.
8. Rated short-circuit making current 8.
9. DC component of rated short-circuit breaking current 9.
10. Pole center distance 10.
11. Switching duties U= Rapid load transfer 11. U=
K= rapid auto-reclosure +U K= +U
E= electrical operating energy E=
Fig.1/4 electrical data for 3AH4 vacuum circuit-breaker .1/4 3AH4
- 1/5 -
ms >15
shortest pulse duration of breaker tripping signal for 1st shunt release/1 .
shortest pulse duration of breaker tripping signal for 2nd and 3rd shunt release
ms >10
/2 3 .
Fig.1/5 operating times/ .1/5
*) 8RL74, G
The supply voltage may deviate from the rated value by -15% +10% .
-15% to +10%.
- 1/6 -
Breaking capacity/
AC 40 to 60 Hz/ 40~60Hz DC/
Voltage Operational current Voltage Operational current/
I (A)
U (V) I (A) U (V) Resistive load/ Inductive load/
(T=20ms)
<230V 10 24 10 10
48 10 9
60 9 7
110 5 4
220 2.5 2
Fig.1/7 Breaking capacity of 3SV92 auxiliary switch
.1/7 3SV92
1
) Can be ordered on request, retrofitting possible. 1) , .
-1/8-
Mechanical interlocking1) 1
Operating mechanism of disconnectors can be fitted )
with a mechanical switchgear interlocking facility. The .
disconnector and the associated circuit-breaker are in .
this case interlocked mechanically.
The sensing parts check the switch position of the
circuit-breaker and prevent if from closing mechanically , ,
and electrically if the associated disconnector is not in
a position to allow safe operation. On the other hand, , . ,
the disconnector is prevented from being operated , .
when the circuit-breaker is closed.
- 2/1 -
51.1
Tightening torque/
=10Nm
- 2/2 -
- 2/3 -
- 2/4 -
- 2/5 -
On the pole plate (15.) and mechanism housing (60.) (15.) (60.) 14 -
there are a total of 14 fixing holes - to suit the various ( .3/1).
types of installation (Fig.3/1).
Note: :
Silver-plated parts must not be bolted together with .
aluminium bars.
Use the appropriate M12 nuts and bolts of strength 8 M12 ,
class 8 and corresponding spring elements and plain .
washers.
Control leads
Vacuum circuit-breaker of standard design are 64 X0 (68.7.1).
2
provided with a 64-pole low-voltage plug connector X0 1.5mm
(68.7.1). The corresponding plug for external , .(
connection is designed for crimp connection of control Harting 09 99 000 0110 09 99
2 2
leads with a nominal section area of 1.5mm . Use only 000 0111) ).
crimping tools (e.g. Harting crimp tongs 09 99 000 01
2
10 with positioning sleeve 09 99 000 0111) ).
Earthing
Fig.3/2 0
.3/2
Circuit documents
The wiring and connection of circuit-breaker is shown
in the circuit diagram supplied, depending on the ,
particular model and complement. .
Release "off"
-Y6 -Y5
-Y7
Motor drive Closing and anti- 1st shunt Switch closing spring charged signal
pumping device release tripping signal
HA Manual tripping/
Fig.3/3 V circuit-breaker 3AH4 with manual and electrical HE Manual closing/
closing with 64-way plug connector K1 Anti-pumping contactor
.3/3 , 64
3AH4
M1 Motor operating mechanism/
P Energy store/
R1 Resistor/
Tripping via S1 Auxiliary switch/
Tripping via NC NC contact S21, S22 Position switches (cut-out motor after
contact
System wiring charging)
( )
S3 Position switches
(open when closing spring charged )
( )
Breaker wiring
S41, S42 Position switches (signals charged state)
( )
S6, S7 Position switches (for switch tripped signal)
( )
X0 Low-voltage plug connector
Release "off"
"
-Y6 -Y5
-Y7
-Y7
Motor drive Closing and anti- 1st shunt 1st CT operated Switch Closing spring charged signal
closing pumping device release release tripping signal
Fig.3/5 V circuit-breaker 3AH3 with electrical manual closing with 64- HA Manual tripping/
way plug connector HE Manual closing/
Example for extended fitting with Y4 and varistor circuit for DC K1 Anti-pumping contactor
.3/5 64 3AH4
Y4
M1 Motor operating mechanism/
P Energy store/
Resistor/
S1 Auxiliary switch/
S21, S22 Position switch (cut-out motor after charging)
With this model, the auxiliary switch terminals are wired to the plug connector as illustrated
( )
S3 Position switch
(opens when closing spring charged )
Auxiliary switch standard Auxiliary switch extended
( )
S41, S42 Position switches (signals charged state)
( )
S6, S7 Position switches (for switch tripped signal)
( )
X0 Low-voltage plug connector
! WARNING !
This equipment contains hazardous voltages ,
and mechanical parts which move at high .
speed and may be control remotely.
In particular: :
Do not remove the cover (60.1). Do not reach (60.1).
inside any openings in the operating mecha- .
nism. Dot not touch pole assemblies(19.) (19.) (48.).
and operating rods (48.).
Commissioning
! CAUTION !
The V-breaker may be operated only with the ,
original hand crank (50.), in order to avoid (50.).
injures as a result of the motor suddenly
starting up.
4. Charge the closing spring (62.) with the hand crank (50.) 6. (50.) (62.) ( .4/1),
(see Fig.4/1), press the close push-button (53.) and (53.), , (54.) .
after closing, trip the breaker by pressing the open
push-button (54.).
- 4/1 -
6. Check the auxiliary switch S1 (68.) and position switches 6. 3AH3 , S1 (68.)
(50.4.1) electrically in both end positions by actuating the (50.4.1) .
3AH3 vacuum circuit-breaker.
Closing
Tripping
Safety measure
! DANGER !
Maintenance, repair and subsequent conver- ,
sion work may be carried out only by specially .
trained personnel in accordance with the
operating instructions and/or special
conversion instructions. Training and
information sessions for personnel can be
provided by the competent Siemens
department
before starting any work on V-breakers, ,
reference must be made to the local safety , (DIN VDE 0105/07.83
regulations for high-voltage switchgear, e.g. 9 , 1 ).
the five safety rules (DIN VDE 0105/07.83 ( "
Part 1, item 9). Switch off the power supply " ),
and then close and open the V-breaker by .
hand ( V-breaker in open state "closing spring
discharged" indication visible), in order to
Servicing
- 5/1 -
10,000
30,000
60,000
1. Circuit-breaker/
1.1 Clean insulating components Warm water, X See note 1)/ 1)
and breaker external parts household
/ detergent
/
Grease bearings and sliding X See Figs. 5/2 and 5/3/ 5/2 5/3
1.2
surfaces as shown in Figs.5/2 Isoflex Topas L32 Note 2/ 2)
switching operations/ Shell Tellus Oil 32 Note 3/ 3)
5/2
5/3 3 5
5/5
Fig.5/1/ 5/1
Notes:
:
1) If the 3AH4 vacuum circuit breaker is used in
1) 3AH4 ( ,
unfavourable indoor conditions (strong, frequent
), , ( )
moisture condition, dust-laden air etc.), we recommend
.
that the insulating parts and, if necessary, the external
breaker parts be regularly cleaned at frequent intervals.
2) Joints and bearings which can not be dismantled must
2)
not be treated with a cleaning agent prior to
.
reapplication of anticorrosive.
-5/2-
Order No
180 g Klber-Isoflex topas L32 3AX1133-3A
and 50 g SHELL Tellus Oil 32 180 g Klber-Isoflex topas L32 3AX1133-3A
and 50 g SHELL Tellus Oil 32
180 g Klber-Isoflex topas L32 3AX1133-3H
180 g Klber-Isoflex topas L32 3AX1133-3H
50 g SHELL Tellus Oil 32 3AX1133-2G
50 g SHELL Tellus Oil 32 3AX1133-2G
1kg SHELL Tellus Oil 32 3AX1133-2D
1kg SHELL Tellus Oil 32 3AX1133-2D
1kg Klber-Isoflex Topas L32 3AX1133-3E
1kg Klber-Isoflex Topas L32 3AX1133-3E
4) The hardware elements used on all replaced parts must
also be renewed (spring washers, SL fuse, splints, etc.). 4) ( , )
Key to parts
a Crank pin for pushbutton
operating a
b Lever bearing
c Cam contour b
d ON latching c
e Diverting auxiliary switch d
f Auxiliary switch e
g Opening spring guide f
h Diverting auxiliary switch g
j Switching shaft bearing h
k OFF latching j
l Cam for OFF latching k
m Stop l
p Opening spring bearing m
p
- 5/4 -
Rated voltage Rated short-circuit breaking current Load characteristic number at rated normal current
A hand crank 3AX 1530-2B for charging the closing spring 3AX 1530-2B :
can be supplied as an accessory:
Owing to the fact that all parts of this breaker type have been ,
optimized to the last the normal service life, it is not possible ,
to recommend particular spare parts for keeping in stock. .
-5/5-