Pump unit (the assembly consisting of a pump and a drive electric motor) in Ex design for
operation in a fire and explosion endangered area, Zone 1.
Technical characteristics of the pump:
Design: Horizontal - self-priming The pump pumps the fuel from the underground reservoir V = 50 m3 with height elevation - 3 m. The pump suction connection is made with a suction pipeline DN 40 length l = 36 m (with the suction basket, non-returnable flap, and filter) and laid underground at a depth 0,6 m. Capacity: Q = 0,00133 m3/sec Manometric head: H = 91 m Medium: Diesel fuel (D2) viscosity at 400 C - 2,84 mm2/S density at 150 C - 829 kg/m3 According to the constructive design, the pump must be horizontal with the suction and pressure flange positioned vertically up.
Technical characteristics of the drive electric motor:
low voltage three-phase asynchronous cage electric motor with copper winding of the stator for the drive of the oil pumps in Ex design, rated voltage 400 V 5%, 50 Hz, drive type S1 (permanent operation), winding insulation class F, increasing of the temperature - B Class, ambient temperature -200C...+400C, degree of mechanical protection IP 55, cooling mode IC411, type of construction B3, connection box on the upper side, stator insulation designed to operate with frequency regulated rpm control.