You are on page 1of 15

534 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO.

3, MAY/JUNE 1998

Instrumentation, Measurement Techniques, and


Analytical Tools in Power Quality Studies
Ronald H. Simpson, Senior Member, IEEE

AbstractThe proper choice of instrumentation, measurement of short- and long-term transient phenomenon, such as voltage
techniques, and analytical tools is vital to the successful imple- dips, impulses, sags, and surges.
mentation of any power quality study. Whether the desired result Dips and impulses are transient voltage waveforms super-
is the determination of harmonic distortion levels, a harmonic
filter design, or transient waveform analysis, the proper choice imposed on the nominal waveform with duration generally
of instrument, measurement technique, and analytical tools can measured in subcycles. In contrast, longer term variations in
make the difference between a well-engineered solution to a voltage, such as sags and surges, are generally measured as
complex problem and an expensive failure. This paper reviews variations to the rms value of voltage and are characterized by
the points of consideration for power quality instrumentation,
longer time intervals, which are usually measured in duration
a description of appropriate measurement techniques, and a
discussion of analytical methods. of cycles or even seconds.
It should be noted, however, that in certain types of phenom-
Index Terms Harmonic distortion, instrumentation, power
ena, the distinction between harmonic distortion and transient
quality.
phenomena becomes less clear [1]. Specifically, transformer
energization current is normally considered to be a transient
I. DEFINITIONS phenomenon. However, transformer energization currents are
rich in second and third harmonics and have been known to
D IPS and impulses are transient voltage waveforms su-
perimposed on the nominal waveform with duration
generally measured in subcycles.
precipitate the failure of installed harmonic filter capacitor
banks with parallel resonance near one of these frequencies.
Harmonic distortion is distortion occurring in a sinusoidal In addition, the third harmonic component of the energizing
voltage or current waveform which is modeled as a sum- current has been known to cause the trip of ground overcurrent
mation of sinusoidal waveforms at integral multiples of the relays in situations where long third harmonic energizing
fundamental frequency. currents resulted from wye-grounded primary windings, weak
Distortion factor or total harmonic distortion (THD) is the sources (high impedance), and resultant long energization
square root of the sum of the squares of the amplitudes of all times. An example of this type of phenomenon is discussed
harmonics divided by the square of the fundamental expressed later in this paper.
as a percent: The abilities of various instruments to adequately measure
disturbances falling into either of the two main categories
of harmonic distortion or transient phenomena is dependent
on the manufacturers specifications for that instrument. The
THD
vital components of the specification of an instrument concern
sampling rates, type and amount of information captured to
Sags and surges are generally measured as variations to the characterize an event, analog input circuitry design, probe
rms value of voltage and are characterized by longer time accuracy, and analytical methods employed by the measuring
intervals which are usually measured in duration of cycles or device to determine harmonic content and other aspects of the
even seconds. captured data.
Correct application of the measuring instrument is required
II. INTRODUCTION in order to obtain meaningful results in the form of useful
Power quality concerns for industrial power distribution data for further analysis. Limitations inherent in available
systems generally fall into two categories. The one which instrument transformers and possible alternatives to these
has received most of the attention in the industrial technical devices should be considered in light of the desired result. The
literature is the problem of harmonic distortion and harmonic ease with which the instrument and associated software allows
filter design. However, a second area of concern is in the area scanning and inspection of the measured data base greatly
impacts the amount of work required to obtain useful data for
Paper PID 9723, presented at the 1997 IEEE Pulp and Paper Industry
Conference, Cincinnati, OH, June 1420, and approved for publication in analysis in some cases. In addition, the ability of the instrument
the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS by the Pulp and Paper to provide harmonic and transient data as sample points from
Industry Committee of the IEEE Industry Applications Society. Manuscript a waveform or harmonic amplitudes and phase angles in an
released for publication September 2, 1997.
The author is with GE Company, Duluth, GA 30096 USA. ASCII text file greatly impacts the ease or accuracy of further
Publisher Item Identifier S 0093-9994(98)03623-8. analysis in some cases.
00939994/98$10.00 1998 IEEE
SIMPSON: POWER QUALITY STUDIES 535

Analytical techniques employed in evaluating the collected where is the frequency of the sideband harmonic, is
data are a key element in determining the source of system the inverter running frequency, and is the ac system base
problems or disturbances. The characterization of a disturbance frequency.
event in sufficient detail to allow effective analysis is essential The previously mentioned spectrum analyzer or dynamic
to the successful mediation of the problem. Completely erro- signal analyzer which has been used by the author is on
neous conclusions can result from inadequate modeling of the the low end of the spectrum analyzer offerings and has the
event in the analytical phase of the study. capability of providing spectrum analysis up to 100 kHz. This
device employs a swept-tuned superheterodyne receiver which
operates as a frequency-selective, peak responding voltmeter
III. INSTRUMENTATION
calibrated to display the rms value of a sinewave [3]. The
Until relatively recently, instrumentation vendors generally instrument does not perform a fast Fourier transform (FFT), as
provided two separate and distinct types of power distribution virtually all the commercially available industrial instruments
system monitors. The first type is the power demand analyzer. do.
This type is used to determine such things as kilovoltampere, This device will only gather data on one phase at a time
kilowatt, and kilovar demand; power factor; voltage sags and in a three-phase system. In addition, this device provides only
swells; and harmonic distortion of the voltage and current magnitude information concerning the harmonic frequencies
waveforms. The second type of monitor usually offered for and does not supply relative phase angle. As will be discussed
power system metering was the transient waveform analyzer later in this paper, this limitation precludes the use of this in-
or disturbance analyzer. This device generally looks at dips, strument as a primary power quality tool for the measurement
impulses, waveshape faults, and noise and, in later models, of harmonic distortion. Referencing all current phase-angle
also contains harmonic distortion measurements. information relative to a common vector (conventionally the
A-phase voltage) is critical to the proper analysis of harmonic
A. Spectrum Analyzers current distortion with respect to harmonic filter design and
Due to the lack of availability of industrial power monitor- assessment of responsibility for limitation of harmonic dis-
ing instrumentation in the early period of harmonic distortion tortion levels at points of common coupling with respect to
studies, a spectrum analyzer or dynamic signal analyzer was IEEE Std. 519 [5].
often used to gather harmonic distortion information. These The dynamic signal analyzer also does not record surges,
devices were designed for laboratory or desktop applications sags, or power demand. Its sole advantage turns out to be
and had both good and bad qualities with respect to their the ability to detect and record noninteger harmonics (a
ability to gather meaningful data in an industrial environment. contradiction in terms, since harmonics are defined as integer
The strength of these instruments is that they provide a multiples of the fundamental frequency) [2], as stated above
spectrum which contains both integer and noninteger multiples and in (1).
of the fundamental frequency which might be present in the The instrument has the capability of measuring noninteger
waveform. As a result of this advantage, the dynamic signal harmonics with a 7.5-Hz resolution over a 3-kHz span (400
analyzer has the ability to detect problems indiscernible to lines/span or 0.25% resolution). None of the industrial power
later instruments used to take these measurements. quality instruments come close to this level of resolution, since
Virtually all of the instruments designed to take measure- they all provide only multiples of the fundamental. This is a
ments of harmonic distortion in industrial plants provide only 60-Hz resolution, or about 1/10th as good as the spectrum
integer multiples of the fundamental waveform. In the vast analyzer for the 3-kHz span.
majority of cases, this is sufficient for the purpose. However, In addition to the other limitations, the input voltage limit to
there are certain cases where noninteger multiples of the fun- the dynamic signal analyzer is very small, typically 42-V peak.
damental can be present in the spectrum of the current and/or This is due to the fact that the dynamic signal analyzers were
voltage waveform. One such case is in the area of arc furnaces. designed for desktop use in electronic circuitry applications.
When the molten metal level in the crucible is low, these This limitation requires that the user supply a voltage divider
devices will produce noninteger multiples of the fundamental, network to lower the instrument transformer secondary voltage
although usually of substantially lower magnitude than the or the system low-voltage bus voltage to within the 42-V peak
integer harmonics. (30-V rms) limit.
In addition to arc furnaces, noninteger multiples of the A current probe which will provide a linear conversion
fundamental frequency can also be produced by reflection of measured current to a voltage input for the instrument
from ac variable-frequency-drive inverters. The reflection is is required for industrial applications. The manufacturer did
back across the dc link to the converter and into the ac not supply industrial probes for this instrument, due to the
power system [2]. These frequencies are actually integer intended desktop electronic circuit application. Probes had to
multiples of the fundamental inverter running frequency of be purchased from other vendors or designed and constructed
the load-commutated synchronous motor drive examined in by the user.
[2]. The resulting noninteger frequencies appear as sideband
B. Instrument Probes
pairs according to the following equation:
With all of the instruments designed specifically for power
(1) quality measurements, the manufacturer of the instrument
536 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 3, MAY/JUNE 1998

TABLE I distortion in the industrial plant system without some safety


COMPARISON OF INTELLIGENT AND NONINTELLIGENT CURRENT PROBES margin for future increases, which are sure to come.

C. Harmonic Filter Design Guidelines


As a result of the general unpredictability of increases in
harmonic distortion with time, it would be inadvisable to
specify the harmonic voltage capability of a harmonic filter
capacitor bank, or the harmonic current rating of the tuning
supplies both current and voltage probes. Some manufactur- reactor, based on present values of in-plant current harmonic
ers will provide so-called intelligent current probes. These distortion only. A healthy safety margin of 1.52 the existing
intelligent current probes are said by the manufacturers to current harmonic distortion level is advisable and practical for
compensate for individual current probe characteristics and, most cases.
in combination with environmental probes, compensate for Certain critical aspects of the design, such as the voltage
ambient temperature. rating of the capacitor banks relative to the system nominal
Table I compares some specifications by two manufacturers voltage and system voltage regulation, will determine how
for their respective instruments current probes. One manufac- much safety margin can be obtained.
turer uses the intelligent current probes and one does not. As a general rule of thumb, the harmonic current rating
The intelligent current probes generally yield 0.5%1.0% of the tuning reactor should be based on either predictions
better accuracy than the nonintelligent probes, dependent on based on known distortion characteristics of the present load
rated current range. However, the manufacturer of Brand Y can plus anticipated system expansions, or an extrapolation of the
supply 1.0% accuracy probes on request if desired or needed. measured harmonic current distortion profile from the known
However, the stated accuracy for the nonintelligent probes existing level. These harmonic profiles should be adjusted to a
seems adequate for most applications. The recommended con- level which is equivalent to the voltage rating of the capacitors.
servative nature of harmonic filter design and the uncertainties The 10% overvoltage capability of the capacitor bank, as
associated with harmonic distortion measurements in general specified in ANSI Std. 18, should be incorporated in the
far exceed the 2.0% inaccuracy in the measured current data. extrapolation and resultant specification of the tuning reactor,
One great disadvantage of the intelligent probes is that thereby creating a design wherein the components are specified
they typically cannot be calibrated with the instrument with and rated to the same level of harmonic current distortion.
which they are used, although they can be calibrated with However, it is inadvisable to utilize the 10% overvoltage
other instruments offered by the vendor. On three occasions, rating of the capacitors, as specified in ANSI Std. 18, for the
when the author has rented an instrument which employs the initial duty of the harmonic filter. This overvoltage capability
intelligent probes, the intelligent probes were found to be should be used as a safety margin where possible.
out of calibration.
The out of calibration condition of the current probes
was discovered only after the author was in the field at the D. Sample Rates
customers site ready to take measurements. Although the The rise-time threshold that a particular instrument can
author can easily produce a test waveform to test the 5-A record is determined by the Nyquist Criteria, which states
probes in the office with a test circuit fed by a wall outlet, that the highest frequency information that can be obtained
no such waveform can be produced for the 40-A, 150-A, or with a given sample rate is one-half the sample rate [3]. With
higher ampere-rated probes. a 1.85-MHz sample rate, the highest frequency component that
In cases where the higher ampere-rated probes were found can be detected is approximately 900 kHz. The inverse of this
to be out of calibration, the instrument either had to be returned number equates to a 1.1- s period.
to the rental agency for recalibration, thereby losing at least Any recorded disturbance of a duration equal to or greater
one days time, or incomplete measurements were taken. than 1.1 s will be recorded, but the rate of rise (rise time) and
The harmonic distortion which is in the industrial sys- the associated frequency content will be lost if the rise time
tem changes with the future addition of nonlinear loads. is less than 1.1 s. However, few of the transient waveforms
The harmonic distortion which is present on the utility line encountered in industrial plants will have rise times faster than
changes with nonlinear load additions to other industrial and this threshold. One exception to this is converter SCR firing
commercial facilities on the system. Since most utilities are transients.
not presently enforcing the limitations on harmonic distortion IEEE Std. 1100 (the Emerald Book) [8] provides a table
at the point of common coupling, as designated by IEEE of frequency spectra of five common, standard surge voltage
Std. 519, it is quite possible to have a harmonic filter in waveforms specified in ANSI C62.41 [9]. Figs. 415 from this
the industrial plant fail or be overloaded as a result of a standard and the associated discussion shows that most of the
neighboring industrial plants harmonic pollution. One such commonly utilized surge spectra have relatively large voltage
case history is reviewed in this paper. or current components between dc and 100 kHz.
It would, therefore, seem foolhardy to design a harmonic The exception to this rule is the electrically fast transient
filter that could only handle the present levels of harmonic (EFT) waveform, which has significant spectral content over
SIMPSON: POWER QUALITY STUDIES 537

100 kHz. This test waveform has 5 1.5-ns rise time, with harmonic distortion information can be exported in ASCII text
50 15-ns duration burst of 5 1-kHz pulses. format or Excel Spreadsheet format. The harmonic information
It is vitally important to have an instrument which will includes harmonic order, amplitude (typically rms), and phase
characterize high-frequency (fast rise time) waveforms to the angle in the exported formats, aiding additional analysis.
extent that such things as rise time, polarity of the first peak
of the impulse, and general wave shape can be determined. F. Software
A good characterization of a transient phenomenon with
Windows-compatible analysis software packages are avail-
some indication of frequency content can mean the difference
able for some instruments, either from a separate company or
between a successful power quality study and a failure.
from the instrument vendor. The software program reads the
Several distinct types of transient over voltage phenom-
recorded data files generated by the instrument and analyzes,
ena can be distinguished if sample rates of approximately 2
categorizes, and summarizes all desired data. The presentation
MHz or higher are used. With a 2-MHz or higher sample
of the analysis is in final report form, which includes possible
rate, it is possible to distinguish lightning surges, inductive
sources of the voltage transients and typical solutions. A
impedance switching, surge suppresser clipping, electronic
harmonic spectrum is also given by some instruments for the
load pickup, gas discharge surge arrester operation, switch or
initial voltage and current waveforms seen by the instrument
contact bounce, loose wiring, static discharge, and capacitor
upon installation, or any other waveform recorded by the
switching events which can have transients with characteristic
instrument.
frequencies up to 10 kHz.
In one instrument, impulses are stored in a disk partition
The sampling rate for all of the devices specifically designed
which holds 6000 impulses. Impulses are assigned a quality
for power quality measurements is comparable when taking
number which is derived by multiplying the peak voltage by
measurements of power demand, harmonics, surges, and sags.
the duration of the first excursion. This quality number
The sampling rate of all of the instruments when performing
grades the impulse and ranks them by grade. When the
these type measurements varies from 5 to 8 kHz.
partition eventually fills, incoming impulses are compared to
This would result in a minimum 2.5-kHz and a maximum
the smallest previously recorded impulse. The larger of the two
4-kHz frequency capture. The resulting rise time capture is
impulses under comparison is then recorded and the smaller
from 400 to 250 s rise time. However, it is not possible
one is discarded.
to characterize many transient disturbances (as opposed to
The peak voltage and time of occurrence of the discarded
power quality or power demand measurements) with sufficient
waveform is saved, however. This insures that only the worst
detail to determine the source with this low sample rate. A
case impulses are stored graphically. Waveshape faults are
sample rate over 1 MHz is required for some types of transient
detected by comparing the total harmonic distortion from one
measurements.
cycle to the next and grading them in similar fashion to the
E. Harmonic Distortion Data impulses. RMS faults are graded by comparison of rms values.
The best power quality instruments will generate an ASCII
text file which can be used for harmonic analysis for any G. Impulse Recordings
waveform captured by the instrument. The ASCII text file The limitation of at least one instrument for transient
will generally be in one of two forms. One file is in the waveform recording is in the way that it measures and records
form of sample points from the recorded waveform. In order impulses. This instrument uses a sample-and-hold circuit uti-
to do harmonic analysis with the sample points, the user lizing stored charge on a capacitor to determine the magnitude
must perform an FFT on the sampled data and generate a of the impulse waveform. No details on rise time or frequency
suitable harmonic vector file. Some vendors software will content is available. In addition, no characteristics of the wave-
automatically supply 1024 points from the captured waveform form which might help determine the source of a given impulse
to satisfy the FFT criteria that the number of points must be or transient are provided. As a result, this instrument may not
a power of 2. provide the detailed information on transient waveforms that
A second type of ASCII text file is a file containing is needed to define the source of the problem.
harmonic number, magnitude, and phase angle which could In another instrument, a 250-kbyte circular buffer can hold
be used directly in harmonic current flow analysis. However, over 300 impulses of 100- s duration. It takes a maximum
at least one vendor provides this data in a picture format which of 2 s to write impulse data from the buffer to memory,
cannot be directly used for analysis. The data contained in the during which time the buffer can accept no other impulse data.
picture must be entered by hand into an ASCII text file for This results in a 2- s recovery time between impulses. If the
analysis. This introduces time delays, increases the probability duration and peak voltage information of successive impulses
of errors, and increases the cost of the analysis. are the same, algorithms within the instrument will command
All of the most popular power quality instruments take har- the logic to stop impulse capture until the impulses change.
monic measurements to at least the thirty-third harmonic. This Most instruments employed to take measurements of transients
is sufficient for the vast majority of applications. Most instru- will typically fill the memory with repetitive impulses before
ments measure and store trending information at user-defined any other impulses can be recorded.
intervals on power quantities such as watts, vars, power factor, Most instruments require some threshold setting to specify
and harmonic distortion. With the leading instruments, the the minimum impulse which will trigger the capture circuit
538 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 3, MAY/JUNE 1998

of the instrument. In at least one instrument, however, no will provide data on integer harmonics of the voltage and
threshold settings are required to trigger the disturbance or current with phase-angle information for all three phases and
event recordings. The default threshold is 5%7% change of neutral (if present).
amplitude. The digital signal processor (DSP) filters the in- However, as previously stated, in addition to the industrial
coming signal and sends it to the appropriate circuit, dependent power quality instruments, the dynamic signal analyzer should
on whether the frequency content is greater than or less than be used in those situations where so-called noninteger har-
4 kHz. A 10-b 4-MHz AD converter converts the analog monics are suspected to be present at critical frequencies.
signal to a digital signal with 12-V resolution. The thresholds Critical frequencies would include the parallel resonance of
are set at the third least significant bit for impulse recordings existing or planned harmonic filter banks or capacitor banks.
on the phase conductors, which is 48-V peak. Display range In order to adequately model a harmonic distortion problem,
settings are unnecessary due to the 10-b AD converter that all feeders in a given substation should be measured for
is used. harmonic content. This is normally done at the medium-
voltage substations, since capacitor banks and harmonic filters
H. Controllers are most often applied at the medium-voltage level. The
amplitude and phase-angle information for both current and
For the newest models on the market, the instrument is set
voltage harmonics on all three phases and neutral (if present
up, and data is downloaded from the instrument, using a sep-
in low-voltage system measurements) should be measured.
arate controller. The minimum requirement for the controller
The measurements should be taken as closely together
is a standard portable 486DXS PC with 4-Mbyte RAM and
in time as possible. In general, at least in process industry
120-Mbyte hard disk. External voltage and current connections
applications, it is usually not necessary to rent or buy multiple
are made to the monitor with one fan-out connector. Reverse
power quality instruments in order to provide simultaneous
polarity and phase rotation of the probes can be accomplished
readings on more than one feeder of a substation.
with software without having to reconnect the instrument. This
However, the readings should be taken at a time when the
can be very important in applications where the instrument is
substation is at or near the peak load, if possible. The error
being connected to an energized circuit and exposure to these
introduced by noncoincidental measurements of the various
circuits needs to be minimized.
feeders is usually small enough to have little effect on the
In addition, the setup and analysis software from the leading
resulting analysis for most industrial sites. The error introduced
vendors are Windows-based software packages, which are
by noncoincidental measurements can be calculated, as will
fairly easy to learn for experienced Windows users. The soft-
ware is supplied free of charge by one instrument vendor. The be demonstrated later.
author has generated ASCII files from disturbance recordings Standard instrument transformers provided with medium-
made by the author and performed FFT calculations using voltage switchgear will generally provide sufficiently good
these files. An example of this type of analysis appears later frequency response for the frequencies of interest in harmonic
in this paper. analysis (usually less than or equal to 3 kHz). Current trans-
It is possible to perform FFTs over multiple cycles using formers normally supplied with this equipment will provide
ASCII data point files generated by this software if the accuracy to within 3% for input currents up to 10 kHz.
waveform amplitude does not vary significantly. This, in turn, IEEE Std. 519 [5] states that voltage transformers normally
allows a harmonic spectrum to be generated which contains supplied with this equipment will provide accuracy to within
noninteger frequencies below the fundamental, although not of 3% for input voltages up to 5 kHz. Shielded conductors are
sufficient resolution to compare to the dynamic signal analyzer. recommended for the current probes.
The captured transient disturbance data is plotted with re- B. Transient Waveforms
spect to the Computer Business Equipment Manufacturers As-
sociation (CBEMA) standard envelope in the best instruments. In contrast to harmonic measurements, standard instrument
This envelope was incorporated into the CBEMA guideline transformers may not be adequate for the measurement of
after its inclusion in IEEE Std. 446 (Orange Book) [4]. transient waveforms. This is due to the much higher frequency
Work is currently under way to include short-time voltage content found in this type of phenomenon as compared to the
disturbances in ANSI C84.1 [6]. The short-time disturbances relatively low frequencies associated with harmonic distortion.
were removed from ANSI C84.1 in 1982. However, some The distributed capacitance of instrument transformers, as well
instruments still allow the choice of plotting disturbances with as power transformers, will shunt an increasing amount of
respect to this ANSI standard envelope. the waveform energy through the parasitic capacitance of the
transformer as the frequencies of the waveform increase.
Fig. 1 shows that the distributed capacitance of the trans-
IV. MEASUREMENT TECHNIQUES
former forms a capacitive voltage divider which shunts the
inductive coupling circuit. From this drawing, it can be seen
A. Harmonic Distortion that the ratio of secondary to primary voltage is dependent on
All of the best industrial power quality instruments will the frequency of the impressed waveform, with energy from
provide adequate measurements of harmonic distortion of the the higher frequencies being shunted by the capacitive circuit
voltage and current waveforms in an industrial facility if and energy from the lower frequencies being inductively
integer harmonics only need to be measured. These devices coupled per (2).
SIMPSON: POWER QUALITY STUDIES 539

capacitance in the system overhead line, cable, power trans-


formers, instrumentation transformers, and instrument probes.
These losses are experienced by the circuit being measured,
as well as the instrument taking the measurements. However,
the instrument has an additional significant loss of accuracy
in the probes.
In certain cases, the ability of electronic components or
surge-suppressive devices to withstand the high-frequency
transients generated by converters or drives may be in ques-
tion. None of the commercially available power quality in-
struments can model in detail the high-frequency transients
Fig. 1. Capacitive coupling circuit of transformer. generated by converters.
The so-called ring and notching transients generated by con-
verters have rise times down to the nanosecond range. These
transients are periodic and can, therefore, be measured with
a high-frequency spectrum analyzer or storage oscilloscope
(gigahertz range). However, although these type transients are
periodic, the amplitude of the transient may vary by as much
as a 2 : 1 ratio from one cycle to the next.

V. ANALYTICAL TECHNIQUES

A. Harmonic Current Vector Summation


As previously stated, relative phase-angle information is
vital to the proper modeling of harmonic distortion phe-
nomena. The following example demonstrates the importance
of this type of information in determining the source of
harmonic distortion. This, in turn, allows the engineer to
assign responsibility for compliance with IEEE Std. 519 [5]
restrictions on the point of common coupling (PCC) between
utilities and industrial plants.
The data picture in Fig. 2 gives the current harmonic
distortion to the fiftieth harmonic. The main circuit breaker for
a substation with seven feeders was metered. The instrument
was programmed to provide harmonic data in rms amps of
Fig. 2. Phase A current spectrum for main circuit breaker. primary current. This was done in order to collect data in a
form which could be directly used by a harmonic analysis
program without multiplying by instrument transformer ratios.
Recordings of transient-type phenomena with high-
The THD number is in amps and not percent, which can be
frequency components (approximately >10 kHz1 MHz)
confusing, since the definition of THD [5] is in percent as
made with the use of:
follows:
transformer inductive coupling ratio:

transformer capacitive coupling ratio: THD (3)


(2)
The harmonic currents measured for the example substation
instrument transformers will not provide a fully accurate rep- for the main circuit breaker and circuit breakers A1A7 are
resentation of the transient waveform. Some of the frequency listed in Fig. 3. Only the significant harmonics are listed
(rise time) and amplitude information will be sacrificed. ( , odd harmonics). Circuit Breaker A1 is the
Therefore, if detailed information on rate of rise or ampli- feeder which serves the fifth and seventh harmonic filters
tude must be obtained in order to evaluate specifications for installed in this substation. The harmonic current amplitudes
medium-voltage surge suppressive devices or medium-voltage have been rounded off to the nearest amp by the instruments
insulation ratings, a capacitor/resistor voltage divider should be software.
considered for direct connection to the medium-voltage bus. The harmonic analysis program written to analyze the
If the failure of electronic components is being investigated, harmonic data is written in symbolic processor software.
the transient measurements should be taken in the low-voltage This software does computations in radians. Therefore, the
circuit where the failures occur. At this point in the system, harmonic data was converted from degrees to radians. The
the energy loss in the transient waveform is due to parasitic phasor representation of the recorded harmonic currents is
540 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 3, MAY/JUNE 1998

MAINA READPRN(MAINA) CBA1 READPRN(CBA1) CBA2 READPRIN(CBA2)

MAINA CBA1 CBA2

CBA3 READPRN(CBA3) CBA4 READPRN(CBA4) CBA5 READPRIN(CBA5)

CBA3 CBA4 CBA5

CBA6 READPRN(CBA6) CBA7 READPRN(CBA4)

CBA6 CBA7

Fig. 3. Recordings of harmonic current vectors.

calculated in (4)(7): The sum of all the feeder currents is shown in

LOADA12 CBA1 CBA1 LOADA LOADA12 LOADa34


LOADA567 (7)
CBA2 CBA2
(4) Fig. 4 is a plot of the fundamental component of the sum
LOADA34 CBA3 CBA3 of all the feeder currents [Load(A )] and the current through
the main [CABMAN( )]. Note that for the fundamental
CBA4 CBA4 due to the default origin of matrices in this software package
being 0. Also note that the error in the summation appears
(5) very small, since the sum of all the feeder load currents is
LOADA567 CBA5 CBA5 very nearly equal to the main current.
Fig. 5 is a plot of the fifth harmonic vectors from each
CBA6 CBA6 feeder and the main. Note that the fifth harmonic current
injected into the substation from the feeders is characterized by
CBA7 CBA7 wide variation in the relative phase angle. This property of the
(6) captured fifth harmonic data will result in the fifth harmonic
SIMPSON: POWER QUALITY STUDIES 541

Fig. 4. The fundamental.

component being largely canceled out when the vector sum of which is the error in the harmonic measurements due to the
the feeder fifth harmonic currents is calculated in (7). noncoincidental nature of the measurements and the accuracy
The current from the main circuit breaker is of the CTs at various loadings. Equation (13) checks the
calculation:
CBMAINA MAINA MAINA
CHECK LOADA1 LOADA CBMAINA
(8)
ERROR CHECK (13)
where and .
An instrument which measures only harmonic amplitude Note that if harmonic amplitude only information were gath-
would not allow this type of analysis to be implemented. ered on the feeders, the arithmetic sum would be
The harmonic current from Circuit Breaker A2 is
LOADA2 CBA2 CBA2
(9) SUM CBA2 CBA3 CBA4 CBA5
CBA6 CBA7 SUM (14)
The fifth harmonic current into the harmonic filters is
while the magnitude of the vector sum is
LOADA1 CBA1 CBA1
(10) LOADA

Summing the fifth harmonic currents to show the three main


The current in (9) is needed in (11) to calculate the total fifth
components, a comparison can be made between the fifth har-
harmonic current of the feeders without Circuit Breaker A1,
monic injected by the utility (MAINA), the total fifth harmonic
which is the harmonic filters feeder. Circuit Breaker A1 and A2
were added together in the previous intermediate summations. injected by the example substation load (LOADA), and the
fifth harmonic current into the harmonic filter (LOADA1). As
Equation (11) is the sum of all the feeder fifth harmonic
can be seen from Fig. 5, the fifth harmonic current injected by
currents:
the example sub load only partially cancels the fifth harmonic
LOADA LOADA2 LOADA34 LOADA567 current being injected by the Utility 69-kV line.
LOADA (11) As can be seen from the plot in Fig. 6, the major component
of the fifth harmonic which flows into the harmonic filter
injected into the sub (LOADA1) is coming from the utility tie (CBMAINA). The
sum of the injected harmonic currents from the loads in the
ERROR LOADA LOADA1 CBMAINA example sub (LOADA) is small due to cancellation between
(12) the feeder sources.
542 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 3, MAY/JUNE 1998

Fig. 5. The fifth harmonic currents.

Although the apparent intent of IEEE Std. 519 is to regulate time-domain recording which is not present, i.e., half-wave
the pollution of the common electrical carrier by industrial asymmetry.
plants, in this case, the industrial user is being polluted by the Half-wave asymmetry is present in a waveform if the
common electrical carrier. positive half cycle, when shifted 180 , is not the mirror image
of the negative half cycle. In the frequency spectrum of the
VI. ANALYTICAL TOOLS waveform, half-wave asymmetry is indicated by the presence
of even harmonics.
A. Determination of Harmonic Spectrum FFT The most common occurrence of half-wave asymmetry
producing even harmonics in power systems is probably the
The method used by a particular instrument to determine
presence of the second harmonic in transformer magnetizing
the frequency spectrum of a waveform can have a dramatic
current. This harmonic is so prevalent in transformer magnetiz-
effect on the accuracy of the analysis of that waveform. The
ing current that it is used as restraint current for the operation
following example demonstrates the necessity of knowing
what to expect from a certain waveform in the way of of transformer differential relays (87T) to prevent operation of
frequency content by visual inspection of the time-domain these relays during transformer energization.
recording of that waveform. Following the standard rule of thumb which requires a
The recording in Fig. 7 was taken by an instrument which sample rate of twice the highest frequency to be measured,
provides the harmonic spectrum data from an FFT in the form the instrument used in the above measurement has a 7-
of a picture. The recording was made of a drive converter with kHz sample rate, which, in theory, should be sufficient to
low commutation reactance, high firing angle, and low angle measure frequency content up to 3.5 kHz. The stated frequency
of overlap. bandwidth for the FFT is to the fiftieth harmonic, or 3 kHz.
This instrument produced a time-domain recording of the However, the instruments measurement is spread out over
voltage and current and a frequency-domain calculation for eight cycles, rather than one cycle. This measurement tech-
each by utilizing an FFT. Inspection of the frequency-domain nique results in valid frequency content if the signal being
calculation (FFT) for the current waveform in Fig. 7 shows measured does not change appreciably in the eight cycles
that the spectrum which resulted from the calculation does over which the sample is taken. However, due to the duty
not match the time-domain recording. In particular, the large cycle of the drives in this application, the signal does change
values shown for the second, fourth, sixth, and eighth har- dramatically over the eight cycles of the sample, resulting in
monics indicate the presence of a type of asymmetry in the an erroneous FFT.
SIMPSON: POWER QUALITY STUDIES 543

Fig. 6. Sum of the fifth harmonics.

TABLE II
FFT OF WAVEFORM SHOWN IN FIG. 7
1 100 29 0.17
5 52.89 31 0.68
7 23.31 35 0.38
11 7.42 37 0.24
13 7.04 41 0.44
17 1.92 43 0.01
19 3.06 47 0.43
23 0.39 49 0.16
25 1.47

spectrum from [2] was used in the analysis and is shown in


Table II. Notice the great difference between the FFT of the
instrument based on eight cycles of the current waveform and
the FFT [2] based on one cycle.
If there is significant decay in a waveform over the first
few cycles of a recording, an FFT may still be calculated if
the vendors software supplies data points for any waveform
of interest. One vendors software will provide 1024 points for
any captured waveform or any portion of a captured waveform.
The number 1024 is a power of 2 and, therefore, can be used
by a spreadsheet program or a math calculation program to
calculate an FFT.
The current waveform in Fig. 8 was recorded during ener-
gization of a distribution transformer with wye-ground/wye-
ground primarysecondary windings.
Fig. 7. Frequency- and time-domain recordings for a converter with low In Fig. 8, the first 31 cycles of transformer energization
commutation reactance. current is displayed. Note that the current decays from an
amplitude of about 5.45 A at the first cycle (218 A primary),
The correct FFT for this waveform can be found in [2] and to about 2.31 A at 30 cycles (92.6 A primary). The transformer
is shown in Table II. Reference [2] gives a frequency spectrum full-load current rating at the primary voltage is 115 A. The
by FFT for a waveform similar to the recorded waveform. This extraordinarily long duration of the transformer magnetizing
544 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 3, MAY/JUNE 1998

Fig. 8. Transformer magnetizing current.

ground relays as ground-fault current. The component of the


third harmonic current on each conductor will sum in phase at
the neutral to equal 66% of the fundamental. This is the value
seen by ground overcurrent relays.
The pickup of the phase overcurrent relay was set at 240
A primary, which is above the 218 A of fundamental current
seen on transformer magnetizing current. However, the ground
overcurrent relay is set to a pickup of 60 A, well below the
A of third harmonic current circulating
initially in the ground loop. This resulted in a tripout of ground
Fig. 9. Antiferroresonance transformer design with five-leg core. overcurrent relays on transformer energization currents.
The ability to analyze the waveform by taking sample
current is believed to be the result of the relatively low voltage data over one cycle was critical in the analysis and solution
(161-V peak, 113-V rms secondary, or 0.91 pu) and the five- of the problem. The solution was to replace the ground
leg core design of the transformer. overcurrent relays with relays which had a third harmonic
The impedance of the source in this system (a diesel filter to desensitize the relay to third harmonic distortion in
generator) is probably about 10 the impedance of the typical the current waveform.
distribution system in which this transformer is normally
applied. This transformer probably sees a worst case of about
1% voltage drop in its normal application. B. Application of Kirchoffs Current Law
The 9% voltage drop seen here results in magnetizing The following example demonstrates the necessity of ade-
current at about 1.5 transformer rating. The ANSI benchmark quate measurements being taken in order to perform accurate
for transformer magnetizing current for a unit of this size is analysis. In particular, this example demonstrates the need
812 rated current [7]. In addition, the low voltage coupled to determine not only the amplitude and phase angle of
with the large amount of iron in the five-leg core of the the fundamental and all harmonic components of the current
antiferroresonance transformer design, as shown in Fig. 9, waveform, but also the need to take these measurements in all
results in magnetizing currents up to 60 cycles. The ANSI conductors on the same phase of a circuit in some cases.
benchmark is six cycles [7]. A complaint was received from a customer that he believed
Even though the waveform decays significantly over the that the saturable core transformer (SCT) which provided
magnetizing current event shown in Fig. 8, an FFT of the energy to the field converter for his in-house generator was
waveform is still possible. This instruments software allows over heating. The customer believed that the overheating was
the user to obtain 1024 sample points for any waveform or part the result of unbalanced currents in the SCT. Furthermore, the
of a waveform which is stored in the instrument. A sample was customer believed that the unbalance in the SCT currents was
taken over one cycle of the transformer magnetizing current the result of a faulty design.
and is shown in Fig. 10. Then, 1024 points were obtained for The customer had taken measurements of the current in
an FFT calculation. one of the three conductors in each of the three phases
Note in Fig. 11 that the third harmonic component of of the secondary delta winding of the SCT (see Fig. 12).
this waveform is about 22% of the fundamental. This third The customer had taken the measurements with a hand held
harmonic current will circulate in the power system in the ammeter, and the amplitude of the three phase currents was
same way as zero-sequence current and will be seen by substantially different.
SIMPSON: POWER QUALITY STUDIES 545

Fig. 10. One cycle of transformer magnetizing current.

Fig. 11. The current FFT spectrum.


Fig. 12. Measured currents in SCT.

Since the length of the conductors connecting the secondary


windings of the SCT was less than 5 ft, it was assumed that
the current on the unmeasured two conductors of the same
phase would be the same as that on the measured conductor.
It was not believed that 5 ft of conductor was long enough
for unbalances in the geometry of the conductors to produce
substantial negative-sequence components in the currents. This
would seem to be an especially appropriate assumption in light
of the low voltage of the SCT secondary circuit, which was
about 250-V ac.
The initial measurements in the SCT circuit by the power
system engineer utilizing a power quality instrument seemed
to verify the complaint by the customer. The power system
engineer also initially only measured one of the three con-
ductors in each phase of the SCT delta winding. The initial
measurement is shown by the following (see Fig. 13):
150 A at 136 ; Fig. 13. Measured currents on one of three conductors per phase.
104 A at 170 ;
31 A at 231 .
Note that the polarity of has been reversed, since the was the result of uneven saturation of the SCT iron core. Since
polarity of the current probe connection was reversed during the saturable core transformer operates on the principle of
the measurement. saturating the iron to regulate voltage, this seemed reasonable.
Initially, the power system engineer believed that the unbal- In addition, large third harmonic components in the current
ance in the phase currents inside the delta winding of the SCT waveforms confirmed severe saturation.
546 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 3, MAY/JUNE 1998

Fig. 16. Sum of the currents on three conductors of phase C A.


Fig. 14. Sum of the currents on three conductors on phase A B .
of the voltage and current waveform spectrums. Repeated
reconnections of the current and voltage probes finally resulted
in an unchanging spectrum after about 2 h attempting these
measurements.
The second instrument brought to the site on the second visit
succeeded in taking the desired measurements immediately.
The vast difference in ability to analyze the waveforms was
dependent on the way in which the FFT was implemented
by each instruments software or firmware package and the
algorithms which each instrument used to determine whether
it was reading a good signal.
The efficiency and reliability of the second instrument in
obtaining measurements allowed these measurements to be
taken on all three conductors of each phase during the second
site visit. Following are the readings taken on the second visit.
For the leg:

Fig. 15. Sum of the currents on three conductors on phase B C .

However, after consulting with a colleague about this prob-


(see Fig. 14).
lem, it was pointed out that the sum of the fundamental and
all harmonic currents measured in this circuit did not equal
zero, as required by Kirchoffs law. For the leg:
Further investigation into this unique problem resulted in a
different conclusion. The power system engineer went back to
the site with two power quality instruments. In addition to the
instrument which he had on the first visit, he carried a second
instrument which he considered more reliable. (see Fig. 15).
The instrument which was used on the first site visit took
about 2 h to get a reading of the current and voltage waveforms For the leg:
in the three phases. The large amount of harmonic distortion in
these waveforms, plus the large unbalance between the three
phases, resulted in a system measurement which confused the
first instrument.
The first instrument which had been brought to the site on
the first visit would not settle down to a single measurement (see Fig. 16).
SIMPSON: POWER QUALITY STUDIES 547

Fig. 17. Total current in all conductors of the SCT delta inside and outside the delta.

Each of the three current probes was also connected to one of


the three conductors in phase of the SCT secondary circuit,
in order to determine the total current in that leg by performing
the vector sum of the three conductor currents. The measured
currents are as follows:

The total current on phase of the SCT secondary circuit was

Fig. 18. SCT currents.

Each of the three current probes was also connected to one of


A plot of the total current on each of the three phases is shown the three conductors in phase of the SCT secondary circuit,
in Fig. 17 and shown in the proper location in the circuit in order to determine the total current in that leg by performing
graphically in Fig. 18. the vector sum of the three conductor currents. The measured
Each of the three current probes were also connected to currents are as follows:
one of the three conductors in phase of the SCT secondary
circuit outside the delta, in order to determine the total current
in that leg by performing the vector sum of the three conductor
currents. The measured currents are as follows:

The total current on phase of the SCT secondary circuit was

The total current on phase of the SCT secondary circuit was Note that, in all cases, the currents outside the SCT in
the secondary circuit followed the usual assumption that the
magnitude and angle of the current on each of the three
548 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 3, MAY/JUNE 1998

conductors of each phase was approximately equal. The polar REFERENCES


form is
[1] J. F. Witte, F. P. DeCesarno, and S. R. Mendis, Damaging long-
term overvoltages on industrial capacitor banks due to transformer
energization inrush currents, IEEE Trans. Ind. Applicat., vol. 30, pp.
11071115, July/Aug. 1994.
[2] D. Rice, A detailed analysis of six-pulse converter harmonic currents,
of the phasor IEEE Trans. Ind. Applicat., vol. 30, pp. 294304, Mar./Apr. 1994.
[3] D. Roddy and J. Coolen, Electronic Communications, 2nd ed. Reston,
VA: Reston, 1981, pp. 358, 539.
[4] IEEE Recommended Practice for Emergency and Standby Power Systems
for Industrial and Commercial Applications, IEEE Std. 446, 1987.
[5] Recommended Practices and Requirements for Harmonic Control in
Electric Power Systems, IEEE Std. 519, Oct. 1991, sec. 9.5, p. 97.
[6] ANSI Standard for Electric Power Systems and Equipment-Voltage Rat-
ings (60 Hz), ANSI Standard C84.1-1989.
[7] IEEE Recommended Practice for Protection and Coordination of Indus-
trial and Commercial Power Systems, IEEE Std. 242-1986.
[8] IEEE Recommended Practice for Powering and Grounding Sensitive
Electronic Equipment, IEEE Std. 1100-1992.
The total current on all three legs of the delta circuit and [9] IEEE Recommended Practice on Surge Voltages in Low-Voltage AC
all three legs of the secondary circuit of the SCT is plotted in Power Circuits (ANSI), IEEE Std. C62.41-1991.
Fig. 17 and placed in the proper respective location in Fig. 18.
Note that the vector for M is plotted with negative polarity,
due to the measurement being taken with negative polarity.
Inspection of Fig. 17 shows the phase rotation is negative
sequence, indicating that phases and were reversed during Ronald H. Simpson (M83SM90) received the
B.E.E. degree from Georgia Institute of Technology,
the measurements. Atlanta, in 1977.
He was Superintendent of Operations with Lock-
hart Power Company, Lockhart, SC, from March
VII. CONCLUSION 1977 to December 1979. From December 1979 to
The proper choice of instrumentation, measurement tech- January 1982, he was a Power Systems Engineer
with GE Company Installation and Service En-
niques, and analytical tools is vital to the successful implemen- gineering, Charlotte, NC. From January 1982 to
tation of any power quality study. Whether the desired result December 1983, he served as a Project Electrical
is the determination of harmonic distortion levels, a harmonic Engineer with ITE Electrical Products, Tucker, GA.
Since December 1983, he has been a Senior Power Systems Engineer with
filter design, or transient waveform analysis, the proper choice GE Company, Duluth, GA. He is the author of several technical papers which
of instrument, measurement technique, and analytical tools can have been published in journals and conference proceedings.
make the difference between a well-engineered solution to a Mr. Simpson is a Senior Member of the IEEE Industry Applications Society
(IAS) and is presently serving as Treasurer of the Pulp and Paper Industry
complex problem and an expensive failure. Committee. He received the IAS Third Prize Paper Award in 1986. He also
This paper has reviewed the points of consideration for received the Meritorious Service Award from the Pulp and Paper Industry
power quality instrumentation and described appropriate mea- Committee in June 1992. He received the Super Star All Star Award from GE
Installation and Service Engineering in December 1989 and the Professional
surement techniques. In addition, analytical tools have been and Social Activities Award from GE Industrial and Power Systems in
discussed which are appropriate for certain applications. February 1994.

You might also like