Test report
(2007) S.D.Z. No. 1155
I. Commission unit
Xi’an XD High Voltage Apparatus Co., Ltd.
II. Sample description
Name: double-column horizontal retractable outdoor high-voltage AC (alternating current)
isolating switch
Model specification: GW□-550/4000
Manufacturer: Xi’an XD High Voltage Apparatus Co., Ltd.
Sample mode: sample presentation
Wuhan High Voltage Research Institute State Grid Corporation of China
Special seal for test reports (Seal)
III. Standards
GB1985-2004 High-Voltage AC Isolating Switch and Grounding Switch
DL/T593-2006 Common Technical Requirements on High-Voltage Switchgear and Control Gear
GB/T 16927.1 Section I of High –Voltage Test Technique: General Test Requirements
GB/T11604 Test Method about Radio Interference of High-Voltage Switchgear
GW□-550/4000 Technical Assignment on Double-Column Vertical Retractable Outdoor High-
Voltage AC Isolating Switch
GW□-550/4000 Trial-Manufacture Appraisal Outline on Double-Column Vertical Retractable
Outdoor High-Voltage AC Isolating Switch
GW□-550/4000 Technical Specification on Double-Column Vertical Retractable Outdoor High-
Voltage AC Isolating Switch
IV. Test type
Commission Test
V. Test date
From October 15 to 16, 2007
VI. Test conclusion
According to GB1985-2004, DL/T593-2006 and other standards and technical requirements
raised by the commission party, after tests on items raised by the commission party are conducted;
results show that the tests are qualified. (See the report for test items and data in details)
Tested by: Meng Gang
Checked by:
Reviewed by: Chen Yong
Approved by: Post: director
Date: December 3, 2007
http://www.whvri.com/jcbg

(2007) S.D.Z. No. 1155 Wuhan High Voltage Research Institute State Grid Corporation of China

VII. Test items and results

Serial Test items Standard requirements Test results Evaluation


No.
1 1 min power frequency Switch off and to ground: 740KV No flashover or Qualified
withstand voltage test Switch on and to ground: 740KV breakdown
Between open contacts: 740(+315)
KV
There is the shortest distance
between two grounding
switches:635KV
2 Operation impulse withstand Switch off and to ground: ±1300KV No flashover or Qualified
voltage test Switch on and to ground: ±1300KV breakdown

Between open contacts: ±1175


(+450)KV

3 Lightning impulse withstand Switch off and to ground: ±1675KV No flashover or Qualified
voltage test Switch on and to ground: ±1675KV breakdown

Between open contacts: ±1675


(+450)KV

4 Radio interference <500uV Qualified


Under the voltage of ,
measurement
radio interference level is equal or
less than 500 uv.
Attention: the data in the table (voltage values) is modified value at the height of 2000m above sea level.

Appendix A: main parameters of samples

Serial No. Items Technical parameters


1 Rated voltage, KV 550
2 Rated frequency, Hz 50
3 Rated current, A 4000
4 Rated short-time withstand current (effective value), 63
KA
5 Rated short-time withstand time, s 3
6 Rated peak value withstand current (peak value), KA 160
7 Rated short-time power To ground 740
frequency withstand Fracture 740(+315)
voltage (effective value),
KV
8 Rated short-time power To ground 1675
frequency withstand Fracture 1675(+450)
voltage (effective value),
KV
9 Rated short-time power To ground 1300
frequency withstand Fracture 1175(+450)
voltage (effective value),
KV
(2007) S.D.Z. No. 1155 Wuhan High Voltage Research Institute State Grid Corporation of China

Appendix B: main test instruments and apparatus

Serial Name/specificatio Serial Measuring Uncertainty/a Calibration Effective date


No. n of apparatus No. of range ccuracy Institution
apparatus
1 2250KV testing TGY/Y
transformer Q-01
2 250KV testing TGY/Y
transformer Q-028
3 FLUKE AC/DC TGY/Y 0-400V 2.0/0.5 National high voltage June 16, 2008
digital multimeter Q-15 metering station
4 2250KV voltage TGY/Y 2250KV 1.0 National high voltage November 1,
divider Q-02 metering station 2007
5 5400KV impulse TGY/Y 5400KV - - -
voltage generator Q-136
6 5400KV impulse TGY/Y 5400KV 1.0 National high voltage August 5,
voltage generator Q-159 metering station 2009
7 64M peak TGY/Y 0-1600KV 0.5 National high voltage June 29, 2008
voltmeter Q-141 metering station
8 TDS340 TGY/Y - 2 Hubei Measuring& September 12,
Q-149 Testing Technique 2008
Institute
9 TDS210 TGY/Y - 2 Hubei Measuring& September 12,
Q-147 Testing Technique 2008
Institute
10 Electromagnetic TGY/Y 9KHz-30MHz - Wuhan Measuring & July 31, 2008
interference Q-1528 Calibrating Station
measuring receiver under China
ESCI Shipbuilding
Industry Corporation
(CSIC)

(2007) S.D.Z. No. 1155 Wuhan High Voltage Research Institute State Grid Corporation of China

Appendix C: test items


1. Short-time power frequency withstand voltage test
The main measuring apparatus: 2250KV and 4A outdoor power frequency cascaded testing
transformer and measuring system, and overall uncertainty of the measuring system is within 2% ;
250 KV power frequency testing transformer and measuring system, and overall uncertainty of the
measuring system is within 2% ; TDS210 oscillograph.
Atmospheric conditions in testing area :
P=102.68Kpa ; dry-bulb temperature : t=20.5℃ ; wet-bulb temperature : t=20.0℃
Test conditions :
Sample condition Pressuriztion Grounding position 1 min power frequency withstand voltage
position
Voltage (KV) Test result
Switch on (dry Aa F 740 Qualified
sample)
Switch on (wet Aa F 740 Qualified
sample)
Switch off (dry A aF 740 Qualified
sample) a AF 740 Qualified
Switch off (wet A aF 740 Qualified
sample) a AF 740 Qualified
Between open A(+a) F 740(+315) Qualified
contacts (dry a(+A) F 740(+315) Qualified
sample)
Between open A(+a) F 740(+315) Qualified
contacts (wet a(+A) F 740(+315) Qualified
sample)
There is the shortest A aF 635 Qualified
distance between a AF 635
attached grounding
switches
Attentions :
1. A stands for one-side terminal of a tested switch ; a stands for the-other-side terminal of a tested switch ; and F
stands for a switch base ;
2. The data in the table (voltage values) has been calibrated to standard atmosphere condition;
3. The data in the table (voltage values) is modified value at the height of 2000m above sea level.
4. Wet test conditions are as follows :

Artificial rain resistivity:

Rainfall ratio of artificial rain: vertical component: 1.2mm/min


Horizontal component: 1.3mm/min ; temperature of artificial rain: 20℃

(2007) S.D.Z. No. 1155 Wuhan High Voltage Research Institute State Grid Corporation of China

2. Operation impulse withstand voltage test

The main measuring apparatus: 2250KV and 4A outdoor power frequency cascaded testing
transformer and measuring system, and overall uncertainty of the measuring system is within 2% ;
5400KV and 527KJ outdoor impulse voltage generator ; 5400KV outdoor low-resistance cascaded
resistance capacitance divider ; 64M-typed peak voltmeter ; TDS340 oscillograph, and overall
uncertainty of the measuring system is within 1%.
Atmospheric conditions in testing area :
P=102.50Kpa ; dry-bulb temperature : t=21.4℃ ; wet-bulb temperature : t=16.5℃

Test conditions :
Sample Pressurizti Grounding Positive polarity Negative polarity
condition on position ( KV Pressurizati ( KV Pressurizati ( KV Pressurizati
position ) on times ) on times ) on times
Voltage Voltage Voltage
(KV) (KV) (KV)
Switch Aa F 1300 15 0 1300 15 0
on (wet
sample)
Switch A aF 1300 15 0 1300 15 0
off (dry a AF 1300 15 0 1300 15 0
sample)
Switch A aF 1300 15 0 1300 15 0
off (wet a AF 1300 15 0 1300 15 0
sample)
Between a(+A) F 1175(+ 15 0 1175(+450) 15 0
open 450)
contacts A(+a) F 1175(+ 15 0 1175(+450) 15 0
(wet 450)
sample)
Attentions :
1. A stands for one-side terminal of a tested switch ; a stands for the-other-side terminal of a tested switch ; and F
stands for a switch base ;
2. The data in the table (voltage values) has been calibrated to standard atmosphere condition;
3. The data in the table (voltage values) is modified value at the height of 2000m above sea level.

(2007) S.D.Z. No. 1155 Wuhan High Voltage Research Institute State Grid Corporation of China

3 Lightning impulse withstand voltage test

The main measuring apparatus: 2250KV and 4A outdoor power frequency cascaded testing
transformer and measuring system, and overall uncertainty of the measuring system is within 2% ;
5400KV and 527KJ outdoor impulse voltage generator ; 5400KV outdoor low-resistance cascaded
resistance capacitance divider ; 64M-typed peak voltmeter ; TDS340 oscillograph, and overall
uncertainty of the measuring system is within 1%.
Atmospheric conditions in testing area :
P=102.50Kpa ; dry-bulb temperature : t=21.4℃ ; wet-bulb temperature : t=16.5℃
Test conditions :
Sample Pressurizt Groundi Positive polarity Negative polarity
condition ion ng Voltage Pressurizati Breakdo Voltage Pressurizati Breakdo
position position (KV) on times wn times (KV) on times wn times
Switch Aa F 1675 15 0 1675 15 0
on (dry
sample)
Switch A aF 1675 15 0 1675 15 0
off (wet a AF 1675 15 0 1675 15 0
sample)
Between a(+A) F 1675(+45 15 0 1675(+45 15 0
open 0) 0)
contacts A(+a) F 1675(+45 15 0 1675(+45 15 0
(dry 0) 0)
sample)
Attentions :
1. A stands for one-side terminal of a tested switch ; a stands for the-other-side terminal of a tested switch ; and F
stands for a switch base ;
2. The data in the table (voltage values) has been calibrated to standard atmosphere condition;
3. The data in the table (voltage values) is modified value at the height of 2000m above sea level.

4. Radio interference measurement


The main measuring apparatus: 2250KV and 4A outdoor power frequency cascaded testing
transformer and measuring system ; the overall uncertainty of measuring system is within 2% ;
electromagnetic interference measuring receiver ESCI ; and coupling capacity is TRF800-1000.

Serial No. Test items Standard Test results Performance


requirements evaluation
1 Radio interference Under the voltage of Qualified
test ,
radio interference
level is

Test explanation: tests shall be conducted on the extra-high voltage outdoor test ground. Test
samples shall be arranged according to requirements of GB/T 2217.2-2000. Test frequency is
0.5MHz ; and applied AC is .