FIRST FLOOR

Project : Legend Heights (Hotel)


Area Name OFFICE FLOOR FIRST FLOOR Date :- 12-Jul-17
Area(Sq.ft) 665 HEIGHT 11 = 7315 Cu.ft

ITEM Area/Qty. Sun Gain/ Factor Btu/hr


Sqft/Nos. Temp. dif
SUMMAR
SOLAR GAIN - GLASS CONDITIONS DB WB RH
E GLASS 0 * 12 * 0.56 0 OUTSIDE 110 75 20
S GLASS 0 * 12 * 0.56 0 ROOM 75 64 55
W GLASS 0 * 164 * 0.56 0 DIFF. 35
N GLASS 0 * 14 * 0.56 0
NE GLASS 0 * 12 * 0.56 0
NW GLASS 0 * 123 * 0.56 0
SE GLASS 0 * 12 * 0.56 0
SW GLASS 160 * 100 * 0.56 8960
Sky light 0 * 123 * 0.56 0
SOLAR & TRANSMISSION GAIN WALLS & ROOF
E WALL 0 * 35 * 0.38 0 OUTSIDE CFM 110
S WALL 0 * 33 * 0.38 0
W WALL 0 * 29 * 0.38 0
N WALL 0 * 21 * 0.38 0
NE WALL 0 * 27 * 0.38 0 28348 RSH
NW WALL 0 * 23 * 0.38 0 ------------- -------------- =
SE WALL 0 * 35 * 0.38 0 30796 RTH
SWWALL 38 * 31 * 0.38 448
ROOF-SUN 0 * 52 * 0.12 0 Indicated ADP 54 Selected

TRANSMISSION GAIN - EXCEPT WALLS & ROOF Dehumid rise


ALL GLASS 160 * 35 * 1.10 6160
PARTITON 0 * 10 * 0.38 0
PARTITION 0 * 10 * 0.56 0
CEILING 0 * 25 * 0.38 0
FLOOR 0 * 10 * 0.38 0
COIL BYPASS FACTOR
INTERNAL HEAT
PEOPLE 11 * 245 2695
HP 0 * 746 * 3.41 0
LIGHTS 997.5 * 1.25 * 3.41 4252
EQUPT WATT 665 * 1 * 3.41 2268
OUTSIDE AIR 110 * 35 * 0.108 416
FAN WATT 0 * 0.50 * 3.41 0
Room sensible heat sub total 25198
Duct heat gain & losses+ Safety (12.5%) 3150

ROOM SENSIBLE HEAT 28347.68

ROOM LATENT HEAT


PEOPLE 11 * 205 2255
APPLIANCES 0 * 1 * 3.412 0
OUTSIDE AIR 110 * 3 * 0.068 22
Room Latent heat sub total 2277
Duct losses + Safety (7.5%) 171

ROOM LATENT HEAT TOTAL 2448

ROOM TOTAL HEAT 30795.92


OUTSIDE AIR HEAT
SENSIBLE 110 * 35 * 0.97 3742
LATENT 110 * 3 * 0.61 202
GRAND TOTAL HEAT SUB TOTAL 34740
Piping loss (5%) 1737 Dehumid Cfm 1389

cooling load sheet


FIRST FLOOR
TR 3.0
TOTAL 36477

cooling load sheet


FIRST FLOOR

Project : Legend Heights (Hotel)


Area Name : OFFICE FLOOR FIRST FLOOR Date :- 12-Jul-17
Area(Sq.ft) 665 HEIGHT 11 = 7315 Cu.ft

Item Area/Qty. Sun Gain/ Factor Btu/hr


Sqft/Nos. Temp. dif
MONSOON
SOLAR GAIN - GLASS CONDITIONS DB WB RH
E GLASS 0 * 11 * 0.56 0 OUTSIDE 95 83.0 60
S GLASS 0 * 13 * 0.56 0 ROOM 75 64.0 55
W GLASS 0 * 165 * 0.56 0 DIFF. 20 5
N GLASS 0 * 11 * 0.56 0
NE GLASS 0 * 11 * 0.56 0
NW GLASS 0 * 100 * 0.56 0
SE GLASS 0 * 11 * 0.56 0
SW GLASS 160 * 127 * 0.56 11379
Sky light 0 * 107 * 0.56 0
SOLAR & TRANSMISSION GAIN WALLS & ROOF OUTSIDE CFM 110
E WALL 0 * 20 * 0.38 0
S WALL 0 * 18 * 0.38 0
W WALL 0 * 14 * 0.38 0
N WALL 0 * 6 * 0.38 0 27655 RSH
NE WALL 0 * 12 * 0.38 0 ------------- -------------- =
NW WALL 0 * 8 * 0.38 0 30657 RTH
SE WALL 0 * 20 * 0.38 0
SWWALL 38 * 16 * 0.38 231 Indicated ADP 53.5 Selected
ROOF-SUN 0 * 37 * 0.12 0
TRANSMISSION GAIN - EXCEPT WALLS & ROOF Dehumid rise
ALL GLASS 160 * 20 * 1.10 3520
PARTITION 0 * 10 * 0.38 0
PARTITION 0 10 * 0.30 0
CEILING 0 * 15 * 0.38 0
FLOOR 0 * 15 * 0.38 0
INTERNAL HEAT
PEOPLE 11 * 245 2695
HP 0 * 746 * 3.41 0
LIGHTS 997.5 * 1.25 * 3.41 4252
EQUPT WATT 665 * 1 * 3.41 2268
OUTSIDE AIR 110 * 20 * 0.108 238
FAN WATT 0 * 0.50 * 3.41 0
Room sensible heat sub total 24582
Duct heat gain & losses+ Safety (12.5%) 3073

ROOM SENSIBLE HEAT 27655

ROOM LATENT HEAT


PEOPLE 11 * 205 2255
APPLIANCES 0 * 1.00 * 3.41 0
OUTSIDE AIR 110 * 81 * 0.068 604
Room Latent heat sub total 2859
Duct losses + Safety (7.5%) 143

ROOM LATENT HEAT 3002

ROOM TOTAL HEAT 30657

OUTSIDE AIR HEAT


SENSIBLE 110 * 20 * 0.972 642
LATENT 110 * 81 * 0.612 1632
GRAND TOTAL HEAT SUB TOTAL 32931

cooling load sheet


FIRST FLOOR
Piping loss (5%) 988 Dehumid Cfm 1323
TR 2.83
TOTAL 33919

cooling load sheet


FIRST FLOOR

GR/LB
74
71.2
3

0.921

54

18.90

0.1

cooling load sheet


FIRST FLOOR

cooling load sheet


FIRST FLOOR

GR/LB
152
71.2
81

0.90

53.5

19.35

cooling load sheet


FIRST FLOOR

cooling load sheet